HSE Information Sheet. Advice on acceptance criteria for damaged Passive Fire Protection (PFP) Coatings. Offshore Information Sheet No.

Similar documents
HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries

Bituminous Sheet Flat Roofs: Their repair and maintenance

September 1, 2003 CONCRETE MANUAL CONCRETE PAVEMENT REHABILITATION

Atlantic Maintenance Services

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

Successful Approach to the Repair of Reinforced Concrete Support Structures in Delayed Coking Units

Rehabilitation of an Aging Concrete Reservoir Adit Tower

Rehabilitation of corroded pipelines and pipes with FibaRoll

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011

Fire-Damage or Freeze-Thaw of Strengthening Concrete Using Ultra High Performance Concrete

NORSOK STANDARD M-501 Edition 6 (2012)

WATERPROOFING OF WET ROOMS

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

Site Inspection Report

GARDEN CITY SKYWAY SUBSTRUCTURE REHABILITATION

Experimental assessment of concrete damage due to exposure to high temperature and efficacy of the repair system

FIRETEX FX Range. Intumescent protection for steel framed car parks

MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS

Specification for Pipe Coating Repairs Offshore

18 June 2001 GUIDELINES ON FIRE TEST PROCEDURES FOR ACCEPTANCE OF FIRE-RETARDANT MATERIALS FOR THE CONSTRUCTION OF LIFEBOATS

Water Damage & Repair

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

BLACK JACK ALL WEATHER ROOF COATING

IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

A Case of Choice of Passive Fire Protection (PFP) in an Oil & Gas EPC Project

SPREFIX SPRAY INSULATION _ in the marine market.

Carboline Supplement to MP October 2012 MATERIALS PERFORMANCE 1

RECOATING AND RENEWING SPF ROOFING SYSTEMS

Condition assessment and repair of antenna towers concrete foundations

Chartek. Trusted epoxy passive fire protection

NEW ELECTRICAL SUBSTATION Building 300 SECTION ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

Chapter 2 Basis of design and materials

Enclosures DuraSystems Barriers, Inc. The Passive Fire Protection Specialists

Acrylic Coatings: The Perfect Stucco Finish

INDUSTRIAL FLOORING INSTALLATION CHALLENGES. James C. Ziegler, ArmorSeal Product Manager Sherwin Williams Cincinnati, Ohio, USA

Construction. Technology and Concepts for the Repair and Protection of Reinforced Concrete

Repair and Rehabilitation of Nehru Memorial College of K.V.G. Group of Institutions at Mangalore - A Case Study

FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England

Oil and Gas Pipeline Design, Maintenance and Repair

Fire Damage Evaluation. Concrete Garage. Vehicular fires in parking garages are not an

KP3 Offshore maintenance management template. Communication between onshore support staff and offshore maintenance technicians

COATING & WRAPPING OF UNDERGROUND PIPING

09/07/07 GLASSFIBER REINFORCED CEMENT (GRC) C. S. I. Spec Master Spec Page 1

THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY

Colorado State University. Durrell Center Roof Repair

SOLVING SECONDARY CONTAINMENT PROBLEMS

ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

The AQUAFIN Approach to Concrete Repair

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market

Repair of Spalling and Leaking Clay Brick Building Walls

Introduction. Facade Fire Test on PUR External Thermal Insulation Composite System (ETICS)

White rust on galvanized and galvanized pre-painted steel. Technical Information

Winterizing Your Building

WHAT IS INFRARED (IR) THERMOGRAPHY

Pavement Patching Repair for AC and PCC Pavement Surfaces. Vern Thompson

CONCRETE REPAIR GUIDELINES. Concrete repairs can be broken down into four basic types, plus special repairs and planing.

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS

BILL OF QUANTITY FOR THE WORK OF "REPAIRING OF CIVIL & PLUMBING WORKS INSIDE AND OUTSIDE OF THE WORKSHOP"

Asbestos: Notifiable Non-Licensed Work. A Minor Change or a Significant Challenge

PTFE Slide Bearings 04/10 149

Fire Testing of Recycled Materials for Building Applications

Peel & Seal Self-Stick Roofing Solutions

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

Composite Panel Firewall Systems

Additional Information. Paint Application

Asphalt Shingle Application Requirements

H2 Opening Statement Asbestos

Precast Concrete Parking Structures

MSC/Circ June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY

ASBESTOS CONTAINING MATERIALS POLICY

Scotch-Weld TM. DP410 Off-White. Product Data Sheet. Product Description. Key Features Rapid cure at room temperature; cure rate may be accelerated

A. Work on this project shall consist of, but is not limited to, the following:

2. The mold is closed up and held under hydraulic pressure while the rubber material or compound cures.

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

BEST PRACTICE GUIDE. Fibrelime Premixed Universal Plaster and Render

EVALUATION OF THE PERFORMANCE OF THE PROTECTIVE SURFACE COATINGS FOR CONCRETE

Guidance note. Risk Assessment. Core concepts. N GN0165 Revision 4 December 2012

PMCap Local Thin Area Repair and Restoration Component. for Pressure Retaining Items

Underwriters Laboratories Testing Information

PYROSWISS VETROFLAM CONTRAFLAM

Dow Corning PROPRIETARY. Dow Corning. A Thermal Modelling Comparison of Typical Curtain Wall Systems

Chapter 3 Pre-Installation, Foundations and Piers

Ver. 2. Guide to. Inspecting Residential Brick Veneer

Low-slope reroofing guidelines

bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls

3 Masonry and Manufactured Stone (Interior and Exterior)

NAPCA BULLETIN APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE

CONIROOF : Tailor-made Solutions for your Roof CONIROOF

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

Building Owners Guide to a Duro-Last System!

Double Glazing Glass. Energy Saving Solutions. Harris Silicones & Glass (Pvt.) Ltd.

Darchem Thermal Protection

CAUSES, EVALUATION AND REPAIR OF CRACKS IN CONCRETE

Structural Failures Cost Lives and Time

MARTIN TESTING LABORATORIES (MTL) PAINTS AND COATINGS TESTING CAPABILITIES

Transcription:

HSE Information Sheet Advice on acceptance criteria for damaged Passive Fire Protection (PFP) Coatings Offshore Information Sheet No. 12/2007 Introduction...2 Background...2 Additional information...3 PFP fire attack characteristics...3 Establishing criteria for allowable damage to coatings...4 Coating damage, identification and evaluation...5 Brief descriptions of damage, anomalies and maintenance issues...6 Inspection, repairs and risk assessments...8 Relevant legal requirements...8 Further advice...8 References...9 1

Introduction This information sheet provides guidance for duty holders on better practice in understanding how typical anomalies in PFP coatings affect fire resistance performance. Repair of damaged PFP should be based on the assessment of damage in relation to the fire attack conditions. This guidance is based largely on the results of a Joint Industry Project that has examined the performance of cementitious and epoxy intumescent passive fire protection (PFP) coatings that contain anomalies. In this note, the role of fire protection is considered as part of maintaining Installation integrity or emergency response in the event of a fire, and does not include considerations for asset protection. Background Passive fire protection (PFP) is defined as a coating or cladding arrangement or freestanding system which, in the event of fire, will provide thermal protection to restrict the rate at which heat is transmitted to the object or area being protected. The type and amount of PFP needed depends on the fire type and duration and the failure criteria of the item being protected. The coating is a mitigation measure to protect items that have an identified role in maintaining structural integrity or platform emergency response, and will therefore have a Performance Standard associated with them. The coatings fire performance criteria specify survival times and fire type; hydrocarbon jet or pool fire and cellulosic fires. A review of the coating performance will be necessary if there are inherent defects in the application, deterioration through weathering or ageing or the PFP has been damaged. Reappraisal of the PFP will need to consider if: It is still required and, if not, what to do with it? Old material is still sound but the original fire scenario has changed - can it be rerated? A more severe fire scenario has been identified - what are the requirements? Some of the PFP has deteriorated or is damaged - what are the criteria for repair and how can it be repaired? Passive Fire Protection (PFP) coatings are applied to barriers and structural elements of oil and gas installations to mitigate against the effects of fires (Ref 2). As such a Performance Standard (PS) will be associated with the coating. It will specify survival times and is aimed at ensuring an appropriate level of integrity of the protected item is maintained to prevent an event from escalating, or for ensuring that personnel can be evacuated safely during an emergency. The criteria are described by defining: Whether the protected item is a barrier or a load-bearing element. The type of fire/heat flux loading to which it is subjected. The critical temperature that should not be exceeded to ensure integrity and/or insulation requirements are met. The time over which the temperature should remain below this critical temperature. 2

Fire protection has three main aims: To prevent load-bearing structure reaching 400 C, the generally accepted temperature at which steel strength is reduced by half; To protect process vessels; To prevent heat transfer through walls into habitable spaces by limiting the inner wall temperatures (sometimes referred to as the back face) to an average 139 C and 180 C at any location. It is generally assumed in offshore safety case assessments (Ref 1, 2) that PFP material is fit-for-purpose, performs as specified, and therefore Performance Standards are met. However, there is evidence that PFP on some installations is not in acceptable condition, and OSD Inspections over a number of years have highlighted the variable state of PFP on these Installations. Physical damage to PFP occurs constantly, as a matter of course, and in some instances protective coatings have been poorly applied and have degraded more rapidly than expected (Ref 3, 4 5) In recent years, several offshore Installations have changed their use and hence their fire attack profiles. Changes of this type may affect the platforms fire risks that then need to be re-assessed. Additional information Coating materials form the majority of the PFP offshore as they can be applied to any shape. They comprise of three or four different layers, the primer coat (tie coat), the PFP (which will probably include some kind of mechanical retention system), a top sealer coat and / or a decorative topcoat. There are many types of passive fire protection coatings available, Cementitious (Mandolite), Epoxy Intumescent (Chartek IV), Subliming (Thermolag), Phenolic Foam (Firetex M89), Glass Fibre (Vosper Thornycroft GRP) and Elastomer Rubber (Viking Fire Stop) all which can provide the required level of fire protection for different fire types. The epoxy intumescent and subliming materials have the disadvantage that they begin to degrade at temperatures above 80 C and this precludes use on hot surfaces e.g. Separators. However, new dual layer systems have recently become available whereby phenolic foam is bonded directly to the hot surface, providing an insulating layer, and a second layer of material, with char forming components, is bonded to this. There are three fire categories against which PFP coatings are specified: A rating Cellulose fire, H rating - Hydrocarbon fire, and J rating- Jet fire. There is also a time component associated with the coatings fire rating viz. H60 rating provides protection in a hydrocarbon fire for 60 minutes. PFP fire attack characteristics When evaluating damage to PFP it is necessary to consider the fire type and conditions of flame and target interaction. An analysis of fire attack needs to be considered in terms of the thermal load on a component and possible erosive force of a flame. For example, a 3

component fully engulfed in a flame will be subject to a higher heat load than a component only partly in contact with a flame. When dealing with Jet fires, the erosive effect of the flame has to be considered because it can cause significant damage to protective coatings particularly if the coating is not physically intact. Jet fires also have a higher heat flux than pool fires with the radiative and convective heat loads generated in different proportions. Jet fires therefore are more onerous in terms of mitigation than pool fires or a radiation heat load. Establishing criteria for allowable damage to coatings A significant finding of the tests on damaged PFP (Ref 6) is that anomalies in a protective coating are not acceptable. The tests confirmed the (fairly obvious) conclusion that some anomalies are more severe than others and highlighted the issue that some types of damage can cause gross failure of the PFP during a fire. Additionally, that less significant damage, if left unrepaired, will deteriorate with time. The work also highlighted the very limited amount of useable data and information with which to quantify anomalies in PFP. Hence describing damage to PFP coatings is essentially a qualitative process. The Damaged PFP JIP (Ref 6) proposed that Qualitative categorisation is based on 3 severity levels. Severity Level 1 will cause gross failure of PFP, when subjected to a fire threat, leading to a significant element of the protected component becoming exposed to the fire. Remedial action will involve removal and reinstatement of significant amounts of material and should be undertaken immediately. This level of damage includes, Unretained and disbonded material Corrosion or mill scale under an epoxy intumescent Reinforcement exposed and visibly damaged Substrate exposed with reinforcement damaged Major failure of retention system at corners Water at PFP/substrate interface Waterlogged or popped material Modification with PFP not reinstated Addition of attachment with no PFP protection Severity Level 2 provides some protection of substrate but may reduce the fire resistance performance during the fire threat to a level that is unacceptable, or is present in an area of high structural importance, or presents a falling object or integrity hazard, or will lead to significant deterioration of the material. Remedial action will involve a repair requiring reasonable levels of reinstatement within an agreed timescale. This includes, Retained but disbonded material PFP eroded with retention mesh exposed but intact Surface cracks, chips, gouges, scrapes, spalling and topcoat loss with reinforcement unexposed, but found in extreme environmental locations or areas of excessive physical exposure where accelerated 4

damage can occur. Any surface cracks, chips, gouges, scrapes and spalling with reinforcement unexposed but located on edge features of beams and columns. Evidence of inadequate material thickness or poor reinforcement at edge features of load bearing structural elements Any anomaly that is not a Level 1 anomaly but is located at a critical structural integrity location Evidence of chalking through exposure to UV (Intumescent). Evidence of heat damage from welded modifications or operations (Intumescent). Part thickness anomalies at edge features of load bearing structural sections (Intumescent). Evidence of inadequate material thickness or poor reinforcement at edge features of load bearing structural elements (Intumescent). Severity Level 3 minor damage will worsen if not repaired but does not immediately reduce the fire resistance performance. It will lead to deterioration of the material leading to 1 or 2 unless corrected. Remedial action will be minor and will be a maintenance task. This includes, Surface cracks, chips, gouges, scrapes spalling and topcoat loss with reinforcement unexposed and located in protected environmental locations. Surface cracks, chips, gouges, scrapes and spalling with reinforcement unexposed but located in areas of extreme physical exposure. Coating damage, identification and evaluation A methodology for evaluating damage to protective fire coatings has been proposed (Ref 6) and should be used to evaluate the level of damage to a PFP coating in the context of the Fire Hazard it is designed to mitigate. A robust risk assessment of the fire scenario, including escalation potential is therefore essential to assess accurately the PFP s damage severity level. The proposed methodology is repeated in 5 steps below: 1 Identification of components or systems that act as passive fire protection. 2 Determination of the criticality of each PFP component or system in terms of its potential to require production to be halted. 3 Assessment and severity ranking of each anomaly noted in the PFP system. 4 Risk assessment and ranking of the PFP system (from criticality and severity of anomaly). 5 Allocation of urgency rating for remedial works. 5

Brief descriptions of damage, anomalies and maintenance issues Water Ingress This does not occur with epoxy intumescent materials. The majority of damage associated with cementitious materials occurs as a result of water ingress into the material, due to breakdown of the topcoat. It can also move into the coating during curing when the cement shrinks leaving a small gap between the coating and substrate. Once within the material, water can have a number of deleterious effects on the materials ability to perform as a fire protection material. The predicted life of 10-15 years for these materials by the manufacturers is not fully supported by evidence noted offshore where typical problems with cement materials have emerged after 5 years and the materials show significant damage after 8-9 years. Maintenance of a topcoat is critical for continuing integrity Disbondment A coating is bonded to the steel substrate by adhesive forces and a physical retention mechanism (primary retention) provided by a mesh. The mesh will allow the coating to maintain its fire protection capability even if the material has lost its adhesion with the substrate. However excessive moisture within the coating will accelerate the corrosion rate of a steel mesh and its steel support pins. Surface Cracking and Spalling - Cracking is a common form of damage noted in cementitious materials. It occurs through incorrect application leading to cracking during curing, local impact damage, structural flexure leading to damage (both during installation and in-service), or vibration induced damage. The surface cracks extend through the topcoat into the PFP material but frequently do not reach the substrate. Cracks and spalling are accelerated by freeze/thawing causing the cracks to increase in size. Spalling results in uncovering fresh areas of coating. Clearly, water can penetrate the coating though the cracks and areas uncovered after spalling. Chips and Gouges Similar effect to cracks and spalling Erosion - Environmental erosion is particularly noted in cementitious materials where material is exposed to the elements and sees a range of different weathering conditions. Typically these are exposed faces of the platform and at platform extremities where wind speeds are high and rain and saltwater spray is driven. This is particularly noted at wall corners, on the corners of flanges and webs of exposed beams, and on primary structural steelwork. Anomaly and Severity Level Illustrations The following examples are provided for illustrative purposes. These are examples only any specific case must be assessed individually on its own merits, and take account of the fire risks posed by the hazards that could threaten it. 6

Description of anomaly Surface cracks, chips, gouges, scrapes, spalling and topcoat loss with reinforcement unexposed, Severity Level 2 if in area of extreme physical exposure or where accelerated damage can occur OR Severity Level 3 in located in protected environmental locations. Description of anomaly Unretained and disbonded material on supporting webs of fire/blast wall. Severity Level 1 if it will lead to a significant proportion of the protected element becoming exposed to any fire. Description of anomaly PFP eroded with retention mesh exposed but intact Severity Level 2 provides some protection, is present in an area of high structural importance, and will lead to deterioration of material. 7

Inspection, repairs and risk assessments Anomalies in PFP coatings identified by Inspection, should be repaired based on the outcome of a risk assessment specific to the location, and the severity of coatings damage. Generalising repair procedures for particular anomaly types would be too prescriptive if the risks from fire attack are not fully defined. It is more practical to allow the Operator to make decisions on a repair strategy that is appropriate to the Hazard Profile of the Installation. The onus is on having repair procedures that are known to be adequate for the prevailing conditions on that Installation and its Process. It is the Duty Holders responsibility to make decisions on a repair strategy that maintains risk to persons from fires and explosions to be as low as is reasonably practicable (ALARP). If for example, it is intended to operate a platform beyond its original life for a further 25 years then the most cost effective option may be a long-term solution of removing any cementitious material and apply an epoxy intumescent; conversely, if the platform is only required for another 5 years then less expensive repair such as patching damaged areas may be appropriate. It is advised that Duty Holders use repair procedures provided by materials manufacturers for the normal repairs to PFP that typically involve re-instatement of material of the same type. These procedures cover surface preparation, reinforcement, etc. It is also advised that certain procedures undertaken by integrity management contractors that involve non-standard repair procedures are avoided. Relevant legal requirements Health and Safety at Work etc Act 1974 (HSWA), Sections 2 & 3 Offshore Installations (Safety Case) Regulations 2005 (SCR05), Reg 12 Offshore Installations (Prevention of Fire and Explosion, and Emergency Response) Regulations 1995 (PFEER) Reg. 12, 13, 14, and 19. Offshore Installations and Wells (Design and Construction etc) Regs 1996 Reg 8 Further advice Further advice can be obtained from: Health and Safety Executive Hazardous Installations Directorate Offshore Division Lord Cullen House Fraser Place Aberdeen AB25 3UB Tel: 01224 252500 8

References 1 A guide to the Offshore Installations (Safety Case) Regulations 2005 L30 Third edition HSE Books 2005 ISBN 0 7176 6184 9 2 ISO 13702, 1999 Petroleum and Natural Gas Industries Control and Mitigation of fires and explosions Offshore production installations 3 Update of Reviews on Passive Fire Protection (PFP HSL/HSE Report PS/03/12) 4 Fire Test on specimens from the Brent-Bravo accommodation Module for the Offshore Safety Division Report PS/98/04 5 Fire Test on specimens from the Cormorant Alpha accommodation Module for the Offshore Safety Division Report PS/98/05 6 Acceptance Criteria for Damaged Passive Fire Protection Coatings ref MMUO13 P2- R-01 (Joint Industry Project). This information sheet contains notes on good practice which are not compulsory but which you may find helpful in considering what you need to do 9