Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Smoke Extract Fans Keep Your Cool: Smoke Extraction with Systemair systemair
Disclose the secret of fresh air! Since 1974 Systemair cares for the purity of an essential resource. Today Systemair is one of the leading ventilation companies worldwide. A success story, which started in Skinnskatteberg, Sweden, with the invention of the inline duct fan. This invention revolutionised the ventilation world. Since then the company has continuously advanced and now offers a comprehensive range of products for all ventilation requirements. The experts of Systemair know the conditions and see the point whatever you need - the ventilation concept of a shopping centre, domestic ventilation of a single familiy house or the ventilation of tunnels and metro stations. Over 2500 employees in more than 60 subsidiaries and 40 countries are available for the essential proximity to the customers. This brochure presents the wide range of our smoke extract fans used in case of fire to extract smoke gases, and also during normal working conditions for standard ventilation. For further information about our smoke extract fans and all the other Systemair products you can contact our experts in your local Systemair company or you can just visit our online catalogue on www.systemair.com. Green Ventilation Our label Green Ventilation marks all products according to Systemair s High Energy Efficiency Classification. All of these products combine cost effectiveness and energy efficiency. Quality Systemair has been certified according to ISO 9001, ISO 14001 and ATEX. Our R&D centre belongs to one of the most modern facilities in Europe. We test in compliance with the international standards EN, ISO and AMCA. Skinnskatteberg, Sweden Systemair head office The main plant in Skinnskatteberg houses one of the company s distribution centers, the largest production facility and is the Systemair group head office. Systemair AB, the Systemair group head office in Skinnskatteberg, Sweden. The production is virtually fully automated with modern machinery featuring advanced computer support. Also located here is the company s most advanced test installation for measuring technical data. 2 I Smoke Extract Fans
systemair Hässleholm, Sweden Hasselager, Denmark Madrid, Spain VEAB VEAB is the leading European manufacturer of electric duct heaters. Production of heating and cooling coils, electric and water based. Production of air handling units. Production of air handling units. Windischbuch, Germany Headquarters of Systemair Germany and distribution center. Production facility for fans and modular air handling units, specialized on engineered products (e.g. tunnel and jet fans). Dal, Eidsvoll, Norway Production of air handling units for the Norwegian market. Bratislava, Slovakia The factory in Bratislava manufactures air distribution products and EN certified fire and smoke dampers. Maribor, Slovenia Specialized in centrifugal smoke extract fans, EN certified. Kansas City, USA Production of fans for the US market. Ukmerge, Lithuania Production of smaller air handling units with energy recovery systems. Kuala Lumpur, Malaysia Manufacturing of products for the Asian market. Bouctouche, Canada Manufacturing of duct fans and heat exchangers used in residential ventilation for the North American market. Smoke Extract Fans I 3
systemair Smoke extract fans for every requirement Smoke extraction of buildings requires precise planning and customised concepts. the range. Systemair smoke extract fans include the following temperature classes: exhaust air with high temperatures, for parking garages and tunnel ventilation. Systemair s comprehensive range of products offers suitable solutions for every requirement: centrifugal fans and axial fans for roof, duct or wall mounting. Performance range from 500 up to 400.000 m³/h. Systemair smoke extract fans are approved for smoke extraction in case of fire as well as for everyday ventilation. Comprehensive accessories complete F600 600 C/120 min. Tested to EN 12101-3 Systemair smoke extract fans have been tested by Technical University of Munich, LGAI Barcelona or BSRIA Brachnell to ensure that it complies with the European product and testing standard EN 12101-3. The complete range carries the CE Mark in accordance with EN 12101- F400 400 C/120 min. F300 300 C/120 min. Typical areas of application include shopping centres, airports, industrial buildings, cinemas, theatres or similar buildings. Systemair smoke extract fans are also used during process Axial Fans 4 I Smoke Extract Fans Jet Fans
systemair 3:2002-06; continued compliance is monitored by TÜV Süd. The EU Declaration of Conformity is available for you to download at www.systemair.de Mechanical smoke extraction During a fire, smoke and fire gases spread through the entire building. It is therefore essential that buildings are constructed to prevent the expansion of smoke and fire in case of fire. Evacuation routes as well as Wall and Duct Fans firefighting routes for the fire-services have to be kept clear of smoke. Mechanical exhaust systems reduce the risk factors in case of fire. They extract the smoke and heat from the building. In comparison with natural smoke extraction units, they work independently of external conditions and assure the full performance immediately. Mechanical smoke extraction units are especially indispensable to the following application areas. High ceiling rooms without windows Subterranean rooms and passages Buildings which are constantly exposed to wind Huge rooms with high fire load Rooms with sprinkler systems Today, mechanical smoke and heat extraction systems are essential for fire prevention measures. Roof Fans Smoke Extract Fans I 5
Smoke Extract Centrifugal Fans Duct Fan MUB/F F400-400 C/120 min. Versatile installation and assembly variants - Installation either inside or outside the fire zone without additional insulation - Can be installed vertical or horizontal - Suitable for indoor or outdoor installation Choice of exhaust direction; it can be modified on site Backward curved impellers, manufactured from galvanized steel The casing consists of a frame, manufactured from profiled steel, 4 double skin panels from galvanized steel and 20 mm mineral wool insulation inside There is a choice of single-speed or two-speed motors A circular connection spigot is pre-installed as standard DIBt approval has been applied for (status 02/11) Air flow up to 13.770 m³/h Wall Fan WVA / WVI F400-400 C/120 min. F600-600 C/120 min. Backward curved impellers; F400 made of galvanized steel, F600 made of stainless steel, welded Casing manufactured from steel, powder coated RAL 7032 Standard IEC motor; ISO F; IP54; single-speed or two-speed version WVA for installation only outside the building, and outside the fire zone WVI for installation inside the building and inside the fire zone DIBt approval has been applied for (status 02/11) Air flow up to 40.000 m³/h 6 I Smoke Extract Fans
Smoke Extract Centrifugal Fans Roof Fan DVV F400-400 C/120 min. F600-600 C/120 min. Temperature of transported air up to 120 C in continuous operation Backward curved impellers; F400 made of galvanized steel sheet; F600 made of stainless steel Seawater resistant aluminium casing, base plate and inlet nozzle from galvanized steel sheet Encapsulated, insulated motor, placed outside the air flow; ISO class F; enclosure class IP54 Motor cooling via fresh air duct Installation above heated rooms; also applicable above unheated rooms with the use of FSL flaps (accessories) DIBt approval Z-78.11-167, Berlin Air flow up to 54.800 m³/h Roof Fan DVG-V F400-400 C/120 min Temperature of transported air up to 120 C in continuous operation Backward curved impellers; made of galvanized steel sheet Seawater resistant aluminium casing, base plate and inlet nozzle from galvanized steel sheet Encapsulated, insulated motor, placed outside air flow; ISO class F; enclosure class IP54 DIBt approval Z-78.11-188, Berlin Air flow up to 17.700 m³/h Smoke Extract Fans I 7
Smoke Extract Axial Fans AXC...(B) F300-300 C/120 min. Fan size from 315 to 1.600 mm Casing made of hot-dip galvanized steel Aerofoil impeller with adjustable pitch angle for maximum efficiency Terminal box in IP65 mounted at the outside of the casing for easy wiring Motors IP54, insulation class H, in accordance with EN 60034-5/IEC 85 DIBt approval Z-78.11-175, Berlin Air flow up to 212.000 m³/h AXC...(B)-G F300-300 C/120 min. Fan size from 315 to 1.600 mm Casing made of hot-dip galvanized steel Aerofoil impeller with adjustable pitch angle for maximum efficiency Terminal box in IP65 mounted at the outside of the casing for easy wiring Motors IP54, insulation class H, in accordance with EN 60034-5/IEC 85 Two fans in series for higher pressure DIBt approval Z-78.11-175, Berlin Air flow up to 212.000 m³/h 8 I Smoke Extract Fans
Smoke Extract Axial Fans AXC...(F) F400-400 C/120 min. Fan size from 315 to 1.600 mm Casing made of hot-dip galvanized steel Aerofoil impeller with adjustable pitch angle for maximum efficiency Terminal box in IP65 mounted at the outside of the casing for easy wiring Motors IP54, insulation class H, in accordance with EN 60034-5/IEC 85 DIBt approval Z-78.11-190, Berlin Air flow up to 212.000 m³/h AXC...(F)-G F400-400 C/120 min. Fan size from 315 to 1.600 mm Casing made of hot-dip galvanized steel Aerofoil impeller with adjustable pitch angle for maximum efficiency Terminal box in IP65 mounted at the outside of the casing for easy wiring Motors IP54, insulation class H, in accordance with EN 60034-5/IEC 85 Two fans in series for higher pressure DIBt approval Z-78.11-190, Berlin Air flow up to 212.000 m³/h Smoke Extract Fans I 9
Smoke Extract Jet Fans Jet Fans AJR / AJ8...(B) F300-300 C/120 min. Fan size from 315 to 400 mm Aerofoil impeller with adjustable pitch angle for maximum efficiency Casing manufactured from galvanized sheet steel, completely sound insulated Motors IP54, insulation class H (smoke extract); Motors IP55, insulation class F (CO-exhaust), according to EN 60045-5/IEC 85 Terminal box for easy access at the outer fan casing, min. IP66 Fully reversible blade settings available on request Removable fan module also after installation for easy maintenance Two design versions: circular AJR and octagonal AJ8 DIBt approval Z-78.11-182, Berlin Air flow up to 7.700 m³/h Tunnel Jet Fans AJ...(T) F300-300 C/120 min. Tunnel Jet Fans AJ...(F) F400-400 C/120 min. Fan size from 500 to 1.600 mm Thrust performance higher than 40 N/kW Casing manufactured from galvanized or hot dip galvanized steel sheet Aerofoil impeller with adjustable pitch angle for maximum efficiency Impeller for one rotation direction or truly reversible Terminal box mounted at the outside of the casing, minimum IP65 Standard IEC motors according to IEC 34, smoke extract motors with different temperature classes for smoke displacement Motors with frequency 50 Hz and 60 Hz available Permanently lubricated ball bearings; optional relubrication device. Jet Fan IV 50 / IV 85 F300-300 C/120 min. Compact casing, ideal for rooms with low ceilings Appealing design Thrust performance 50 N and 85 N Casing manufactured from galvanized steel sheet Motor execution F300 for 300 C/120 min. or standard temperature Exhaust direction can be variably modified Approved inspection switch optional 10 I Smoke Extract Fans
Special Applications: Wall Mounted Axial Fans AXC...-P (55 C) AXC...(B)-P F300 / EN 12101-3 certified, CE labelled. Monitored by TÜV Süd. HA...(F)-P F400 / EN 12101-3 certified, CE labelled. Monitored by TÜV Süd. Square wall plate with inlet cone manufactured from steel, hot dip galvanised upon completion. With protection guard. IEC- standard or smoke extract motors, single or two speed Terminal box supplied loose Available up to impeller diameter 1.000 mm AXC: Adjustable aluminium impellers HA: Welded steel impellers AXC...-P Axial Roof Fans (exhaust and supply fans) AXC...-D (55 C) AXC...(B)-D F300 Casing manufactured from steel, hot dip galvanised upon completion Delivered with roof cowl and base frame No wind or snow load testing required for this design AXC-D Axial Fan with insulated box Double skin panels manufactured from galvanised steel Panels containing 20 mm thick high-quality mineral wool for sound and thermal insulation Vibration-free mounted fan; mounting feet with vibration isolators and suction and pressure sided elastic joints Reduction of approx 7 db AXC-B Smoke Extract Fans I 11
www.systemair.com Systemair GmbH 02/2011 / E8038