The risk assessment of fire damper installations

Size: px
Start display at page:

Download "The risk assessment of fire damper installations"

Transcription

1 The risk assessment of fire damper installations June 2010 Paul White

2 OVERVIEW OVERVIEW The purpose of this presentation is to highlight that fire dampers form a key part of the passive fire protection within a building, but are at best often overlooked, but at worst not even recognised for the job that they might be called on to do in the event of fire. It seeks to clarify the regulatory requirements and fill in the gaps left by the guides to the RRFSO where fire dampers are installed in a building 2

3 What is this? FIRE DOORS Everyone knows what a fire door is and most people see one every day 3

4 What is this? FIRE DAMPERS This is a fire damper and they are generally hidden above ceilings and mounted in a ductwork run, most people don t know that they exist 4

5 Ad hoc testing to BS476-20/22 FIRE DAMPERS BS476-20/22 This shows a fire damper during the old style of ad hoc testing to BS 476 5

6 Test setup for EN FIRE DAMPERS BS EN The fire damper is subjected to a 300pa pressure difference for the whole of the test and the leakage recorded as a pass failure criteria 6

7 Fire and Leakage Rated Fire Dampers FIRE DAMPERS BS EN Fire damper tests to EN in practice 7

8 Fire Dampers FIRE DAMPERS APPLICATION AND TEST DETAILS Application and test details For use in normal ventilation ducts at fire boundaries to maintain compartmentation in the case of fire Generally tested for Integrity (E), Insulation (I) (if required) and Reduced Leakage (S) (again, if required) Also considered are horizontal, vertical, fire from inside to outside, fire from outside to inside, symmetry etc Units are mounted in a supporting partition, such that would be used in practice. During the test, the damper must close, and is then subjected to a 300Pa pressure differential. E Integrity damper must not leak more than 360 m 3 /hr/m 2 I Insulation thermocouples record temperature rise (140/180 C max) S Leakage rating damper must not leak more than 200 m 3 /hr/m 2, at ambient and during the fire test. The smallest example must also not leak more than 200 m 3 /hr/m 2 8

9 Fire Damper Standards FIRE DAMPERS -2 STANDARDS Product standard EN 15650: 2010 Fire dampers Published (CEN TC156 WG9) Test standard EN :1999: Fire resistance tests for service installations: Fire dampers Published, but under review (CEN TC127 WG2 TG4) Classification standard EN :2005: Fire classification of construction products and building elements - part 3: classification using data from fire resistance tests on components of normal building service installations Published (CEN TC127 WG7) Extended field of application standard pren : Extended applications of test results for fire resistance tests for service installations : Dampers Under development (CEN TC127 WG2 TG4) 9

10 Regulation - ADB APPROVED DOCUMENT B (1) The following slides give a snapshot of the requirements in Approved Document B It is strongly recommended that anyone making risk assessments carefully considers the requirements in this document and does not rely purely on the information given here It is available as a free download from - search on approved documents 10

11 Regulation - ADB APPROVED DOCUMENT B (2) Mechanical ventilation and air-conditioning systems Page Para 2 Where the ductwork system serves more than one part of a sub-divided escape route, a fire damper should be provided where the duct work enters each section of the escape route operated by a smoke detector or suitable fire detection system. The fire dampers should close when smoke is detected 11

12 Regulation - ADB APPROVED DOCUMENT B (3) Mechanical ventilation and air-conditioning systems Page Note Fire dampers activated only by fusible links are not suitable for protecting escape routes. However an ES classified fire and smoke damper which is activated by a suitable fire protection system may be used 12

13 Regulation - ADB APPROVED DOCUMENT B (5) Ventilation ducts, flues etc. Page Where air handling ducts pass through fire separating elements the integrity of those elements should be maintained There are 3 basic methods and these are: Method 1: protection using fire dampers; Method 2: protection using fire resistant enclosures; Method 3: protection using fire-resisting ductwork 13

14 Regulation - ADB APPROVED DOCUMENT B (6) Ventilation ducts, flues etc. Page Method 1 (e.g. Dampers) is not suitable for extract ductwork serving kitchens. This is due to the likely build up of grease which can adversely affect the effectiveness of any dampers. 14

15 Regulation - ADB APPROVED DOCUMENT B (7) Fire dampers Page Fire damper should be situated within the thickness of the fire separating element and be securely fixed. It is also necessary to ensure that, in a fire, expansion of the ductwork would not push the fire damper through the structure. 15

16 Regulation - ADB APPROVED DOCUMENT B (8) Fire dampers Page Adequate means of access should be provided to allow inspection, testing and maintenance of both the fire damper and its actuating mechanism. 16

17 Regulation - ADB APPROVED DOCUMENT B (9) Fire dampers Page Where the use of the building involves sleeping risk, such as an hotel or residential care home, fire dampers should be actuated by smoke detector-controlled automatic release mechanism, in addition to being actuated by thermally actuated devices... (caveats on certain types of alarm systems and abilities of people to leave the area)... 17

18 Regulation - ADB APPROVED DOCUMENT B (12) Fire dampers Page cont. Note: Fire dampers actuated only by fusible links are not suitable for protecting escape routes. However, an ES classified fire and smoke damper which is activated by a suitable fire detection system may be used 18

19 Regulation - ADB APPROVED DOCUMENT B (14) Fire dampers Page Fire dampers should be tested to BS EN :1999 and be classified to BS EN :2005. They should have an E classification equal to, or greater than, 60 minutes. Fire and smoke dampers should also be tested to BS EN :1999 and be classified to BS EN :2005. They should have an ES classification equal to, or greater than, 60 minutes. 19

20 Regulation - ADB APPROVED DOCUMENT B (15) Fire dampers Page Note 1 Note 1: Fire dampers tested using ad-hoc procedures based on BS476 may only be used be appropriate for fanoff situations. In all cases, fire dampers should be installed as tested. PW Note: You cannot get an E or ES classification if you test to BS476, so dampers for sleeping risk areas and escape routes need to be tested to EN

21 Regulation - ADB APPROVED DOCUMENT B (1) ADB refers to a lot of second tier documents and also references other guides. This BS5588 series is referred to and is still apparently valid, although effectively withdrawn. The department for Communities and Local Government (CLG) still says that it contains good and safe information. It is replaced by BS 9999 and this where we get some clear guidance on maintenance requirements (ex BS ) ADB also recommends the use of third party certificated products 21

22 Other publications - ASFP ASFP GREY BOOK ASFP Grey Book About to be published in its second edition Contains details of regulation, standards testing etc Also gives some guidance on project planning and installation It is planned that it will list certificated products with approved installation methods Also has sister documents about fire rated dusts, structural steel protection and fire seals 22

23 Other publications - HVCA HVCA DW144 & DW145 HVCA DW144 and DW145 DW144 is under review for its second edition For dampers this is supported by DW145 which will be referred to for damper installations 23

24 Other publications Dept of Health HTM DEPARTMENT OF HEALTH HTM (1) 24 Written to cover healthcare premises Describes fire dampers in terms of BS EN classified E and ES Fire and smoke dampers classifed ES Transfer grilles should be fitted with fire and smoke dampers Where walls do not pass the ceiling, ducts through the ceiling should be protected with fire dampers

25 Other publications Dept of Health HTM {cont} DEPARTMENT OF HEALTH HTM (2) Fire & Smoke dampers in compartment walls motorised to close on signal Fire & Smoke dampers in sub compartment walls link only PW Note: motorised would probably be better for regular testing Ducting serving fire hazard rooms should be protected with dampers, or if duct is passing through, no dampers, but fire resisting duct 25

26 Other publications Dept of Health HTM {cont} DEPARTMENT OF HEALTH HTM (3) 26 Installation requirements are given, but unfortunately this does not say use manufacturers instructions, rather what not to do, also a requirement for ceilings It requires details of all dampers to be included in the fire strategy and drawings for complex buildings

27 Other publications Dept of C S F BB100 DEPARTMENT OF CHILDREN, SCHOOLS & FAMILIES BB Generally as ADB References the ASFP Grey Book Product certification for property protection fire dampers should also satisfy LPS1162 It requires details of all dampers to be included in the fire strategy and drawings for complex buildings

28 Certification standard - LPCB CERTIFICATION STANDARD 28 The LPCB run a certification scheme for fire dampers. The LPS 1162 document contains all the tests that LPC require the product to undergo, before certification may be offered It also states that to meet it, a company must have full BS EN ISO 9001 accreditation. The LPCB visit the factory at least once a year to confirm by measurement that the certificated products maintain all the tested dimensions, and confirm that the products still comply with any assessments that may have been made

29 Regulatory Reform (Fire Safety) Order - RRFSO RRFSO RRFSO -1- There is a series of published guides to meeting the requirements of the RRFSO Information on fire dampers is vague, but is generally as follows: 1) laundry chutes (smoke and fire dampers) 2) dampers in ducts should be correctly installed 3) the fact that in cooking processes ventilation ducts and dampers should be considered. 29

30 Regulatory Reform (Fire Safety) Order - RRFSO RRFSO However, fire dampers are referred to indirectly as follows: RRFSO ) In a checklist: Are any holes or gaps in walls, ceilings and floors properly sealed, e.g. where services such as ventilation ducts and electrical cables pass through them? 2) Ventilation systems: Where ventilation systems might assist the spread of flames, smoke and hot gases from a fire it will be necessary to take steps to safe guard the means of escape against this hazard.

31 Regulatory Reform (Fire Safety) Order - RRFSO RRFSO RRFSO Unfortunately, fire dampers are not referred to in the maintenance check list section, which is a key area where they should be, or in the frequency of checking section, also key. Therefore we need to turn to BS9999 for further guidance

32 Regulatory Reform (Fire Safety) Order - RRFSO BS9999 BS Annex V (normative): Routine inspection and maintenance of fire safety installations This requires smoke control systems and their components to be tested as often as weekly, however it is not clear what constitute smoke dampers. This could possibly refer to dampers that are used to protect escape routes and areas with sleeping risk. This should be considered by the designer and perhaps the risk assessor.

33 Regulatory Reform (Fire Safety) Order - RRFSO BS9999 BS Annex W (normative): Routine inspection and maintenance of ventilation and air conditioning ductwork This requires simple fire dampers (spring operated so probably curtain fire dampers) to be tested every two years or more often if conditions are such that they get dirty quicker. Both annexes should be looked at in their entirety before drawing any conclusions, and consideration given to the rest of the document

34 Risk assessment Considerations/Key areas RISK ASSESSMENT The positioning of the product The application of the product (fire, or fire and smoke) The supporting construction into which the damper is fitted What testing has been undertaken? What assessment information is available? What maintenance regimes are in place?

35 Risk assessment Positioning of the product RISK ASSESSMENT -2- Is it known where all the fire, and fire and smoke, dampers are installed schedule and drawing Is there clear access, both outside and inside for cleaning and maintenance Are there any gaps around the damper between it and the supporting construction? Is the fire damper mounted within the wall? The last might be allowed if the duct and the joint with the wall are installed using a tested method Application escape route or area with sleeping risk Does the fire damper have an ES classification (or equivalency through assessment) when mounted in the supporting construction being used e.g. masonry, dry wall, batt, other fire stopping etc? Has the damper been installed to the manufacturers instructions or at least to the documented satisfaction of the BCA? Note to get an ES classification, the damper must have been tested (or assessed for equivalency) to BS EN , BS 476 cannot confirm the S low leakage criteria 35

36 Risk assessment Application are the fans immediately turned off in the event of a fire incident RISK ASSESSMENT Dampers tested ad hoc to BS 476 may be acceptable if the fans are turned off. Dampers having an E classification are, however, recommended and must be used if the fans are left on. If the fans are left on, curtain fire dampers are not recommended as they may be held open by residual airflow Does the fire damper have an E classification (or equivalency through assessment) when mounted in the supporting construction being used e.g. masonry, dry wall, batt, other fire stopping etc? Has the damper been installed to the manufacturers instructions or at least to the documented satisfaction of the BCA? Note to get an E classification, the damper must have been tested (or assessed for equivalency) to BS EN

37 Risk assessment Maintenance regime RISK ASSESSMENT Does this exist for the fire dampers? Is the responsible person aware of this requirement? Do adequate records of testing and inspection exist? Do the records note any and all remedial action to the fire damper and to the seal between it and the supporting construction Refer to Annex V and Annex W of BS9999

38 Summary SUMMARY 38 The requirements for the risk assessment of fire dampers are not clear from the RRFSO However, through reference to ADB and BS9999, a clear path can be drawn Additional help is given in the ASFP Grey Book and HVCA DW145 There must be clear records of where dampers are positioned, that they are installed correctly and that they are maintained correctly, including the state of any seal around the damper at the interface between it and the supporting construction

39 WRONG WRONG -1- The damper is not in the plane of the wall and the duct is not protected. Has the damper been tested in association with batt? If fire resisting, is the duct supported around its outside at its joint with the wall 39

40 WRONG WRONG -2- The dampers are not in the plane of the wall, the duct is not protected and it is unlikely that the dampers have been tested passing through a hole in a steel beam 40

41 WRONG WRONG -3-! 41

42 RIGHT RIGHT -1- The damper is within the plane of the wall, the installation is complete and without any damage to the seal around the damper. Note: However, it needs to be checked that damper has been tested in a batt installation, especially for ES requirements 42

43 The risk assessment of fire damper installations THANK YOU FOR LISTENING

Fire Protection Of Ventilation Systems DAMPERS & AIR TRANSFER GRILLES A PRESENTATION BY PHILLIP HORTON OF FIRE ENGINEERING SOLUTIONS

Fire Protection Of Ventilation Systems DAMPERS & AIR TRANSFER GRILLES A PRESENTATION BY PHILLIP HORTON OF FIRE ENGINEERING SOLUTIONS Fire Protection Of Ventilation Systems DAMPERS & AIR TRANSFER GRILLES A PRESENTATION BY PHILLIP HORTON OF FIRE ENGINEERING SOLUTIONS THE AIM OF THE WORKSHOP: Provide assistance in the selection, installation

More information

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market Ian Stewart Passive installer scheme manager September 2011 Introduction to BRE Global Research,

More information

Decree of the Ministry of the Environment on fire safety of ventilation systems

Decree of the Ministry of the Environment on fire safety of ventilation systems THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18

More information

Certification of construction products - Fire dampers. Certification Rules 032

Certification of construction products - Fire dampers. Certification Rules 032 Certification of construction products - Fire dampers Certification Rules 032 1 Contents Contents 1 0 Preface 1 1 Scope and intended application 2 2 Technical requirements 2 2.1 Properties 2 2.1.1 Protection

More information

- 5 - Table1. Maximum Compartment Volumes

- 5 - Table1. Maximum Compartment Volumes - 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,

More information

Fire rated and smoke outlet ductwork

Fire rated and smoke outlet ductwork Fire rated and smoke outlet ductwork An industry guide to design and installation Association House, 99 West Street, Farnham, Surrey GU9 7EN t: 01252 739142 f: 01252 739140 www.asfp.org.uk FR&SODUCTWORK

More information

Passive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection

Passive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking

More information

Australian/New Zealand Standard

Australian/New Zealand Standard Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The

More information

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning NORSOK STANDARD H-001 Rev. 4, Nov. 2001 Heating, ventilation and air-conditioning This NORSOK standard is developed by NTS with broad industry participation. Please note that whilst every effort has been

More information

RC44. for fire risk assessment of catering extract ventilation

RC44. for fire risk assessment of catering extract ventilation Catering extract 17/10/06 15:45 Page 1 RC44 for fire risk assessment of catering extract ventilation IMPORTANT NOTICE This document has been developed through the Insurers Fire Research Strategy scheme

More information

Standard the the Raising

Standard the the Raising Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

Fire Safety Requirements for Child Care Centre

Fire Safety Requirements for Child Care Centre Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,

More information

Fire and Security Products and Services

Fire and Security Products and Services www.redbooklive.com Fire and Security Products and Services Making LPCB Approval work for you Not all fire and security products and services on the market can be trusted in the event of a fire or attempted

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard : ISSUE 3.0 Requirements for the LPCB Approval and Listing of Companies Undertaking the Maintenance and Repair of Doorsets, Shutters, and Active Smoke/Fire Barriers This standard

More information

ASFP Ireland - Fire Safety Certification. Colin Keeley Senior Site Inspector & Training Officer 22 nd September 2011

ASFP Ireland - Fire Safety Certification. Colin Keeley Senior Site Inspector & Training Officer 22 nd September 2011 ASFP Ireland - Fire Safety Certification Colin Keeley Senior Site Inspector & Training Officer 22 nd September 2011 Fires can be devastating with serious consequences Fires in Ireland Irish Fire Service

More information

The terms hazard and risk are often used, which we define as the following:

The terms hazard and risk are often used, which we define as the following: Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information

More information

UPP Residential Services Fire Risk Assessment

UPP Residential Services Fire Risk Assessment UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

Life Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers

Life Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers May 2014 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER APPLICATION

More information

Composite Panel Firewall Systems

Composite Panel Firewall Systems Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial

More information

Fire safety in buildings and implementation of European fire test standards

Fire safety in buildings and implementation of European fire test standards Fire safety in buildings and implementation of European fire test standards Dr Debbie Smith OBE Chair of CEN TC127 Fire Safety BRE Global Ltd, UK 18 th June 2014 Part of the BRE Trust Construction Products

More information

Smoke exhaust systems

Smoke exhaust systems 1 Fire zone, e.g. hall 2 Smoke exhaust zone, separated by smoke curtains Natural and mechanical smoke extraction General information 3 Natural smoke and heat exhaust vent 4 Air inlet opening or wake max.

More information

Fire Stopping and Penetration Seals for the Construction Industry SECOND EDITION

Fire Stopping and Penetration Seals for the Construction Industry SECOND EDITION Fire Stopping and Penetration Seals for the Construction Industry SECOND EDITION Fire Test Study Group 1 INTRODUCTION The (ASFP) was formed in 1976. The objectives of the Association are to encourage,

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

GENERAL FIRE SAFETY TERMS & DEFINITIONS

GENERAL FIRE SAFETY TERMS & DEFINITIONS UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:

More information

The Basics of Commercial Kitchen Exhaust Cleaning

The Basics of Commercial Kitchen Exhaust Cleaning The Basics of Commercial Kitchen Exhaust Cleaning ANSI/IKECA C 10 ANSI/IKECA C 10: Standard for Cleaning of Commercial Exhaust Systems IKECA Introduces the Kitchen Exhaust Cleaning Industry s First American

More information

UDSA - UDSBD unit heater

UDSA - UDSBD unit heater APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

An Industry Guide to the design for the installation of Fire and Smoke Resisting Dampers

An Industry Guide to the design for the installation of Fire and Smoke Resisting Dampers ASFP An Industry Guide to the design for the installation of Fire and Smoke Resisting Dampers Association House, 99 West Street, Farnham, Surrey, GU9 7EN Telephone: 01252 739142 Fax: 01252 739140 ISBN

More information

Services Enclosures and Protected Shafts - Maintaining Compartmentation

Services Enclosures and Protected Shafts - Maintaining Compartmentation Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping

More information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed

More information

Introduction. CE marked construction products

Introduction. CE marked construction products Introduction This Technical Booklet has been prepared by the Department of Finance and Personnel and provides for certain methods and standards of building which, if followed, will satisfy the requirements

More information

Fire Safety Risk Assessment Checklist for Residential Care Premises

Fire Safety Risk Assessment Checklist for Residential Care Premises Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or

More information

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/10/10 Rev Page 1 A new updated version of Approved Document B comes into force from the 6 th April 2007. This revised guidance is split into two separate documents:- Volume 1 Dwelling Houses

More information

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.

More information

Fire and Smoke Dampers: Best Practice Design Tips. An AMCA International White Paper. July 2015

Fire and Smoke Dampers: Best Practice Design Tips. An AMCA International White Paper. July 2015 July 2015 Fire and Smoke Dampers: Best Practice Design Tips An AMCA International White Paper AMCA International 30 West University Dr. Arlington Heights, IL 60004 USA www.amca.org June 2015 This white

More information

Introduction to cable fire stopping

Introduction to cable fire stopping Introduction to cable fire stopping Duncan Alabaster Technical Director of PFC Corofil Effects of major fire damage on businesses 6% are sold or merged 23% fully operational again after one year 43% never

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

1-085 Fire safety performance of materials

1-085 Fire safety performance of materials Transport for London London Underground Category 1 Standard 1-085 Fire safety performance of materials! Please read the Written Notices attached to this standard Issue: A3 MAYOR OF LONDON Contents 1 Purpose

More information

Action required (Please tick) If you answered YES, record Action Points at STEP 4

Action required (Please tick) If you answered YES, record Action Points at STEP 4 RECORD OF FIRE SAFETY RISK ASSESSMENT Building Name & Use: Address: Postcode: Name of person(s) with fire safety duties: Name and contact details of assessor: Date of Assessment: 6 th February 2011 Laurel

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

FIRE RISK ASSESSMENT COMPETENCY COUNCIL

FIRE RISK ASSESSMENT COMPETENCY COUNCIL FIRE RISK ASSESSMENT COMPETENCY COUNCIL Competency Criteria for Fire Risk Assessors Version 1 Published : 21/12/11 Page 1 Foreword Fire safety legislation requires that, for most premises except private

More information

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Page 1 of 7 PURPOSE: This Guidance

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance

CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance CIBSE Guide M: Maintenance engineering and management compliance legislation and guidance Types of System/Plant Action required Frequency by Type of Fire and Smoke Fire extinguishers Discharge (not CO

More information

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery Part 3 Ancillary technologies Chapter CONTENTS SCOPE Clause Page DESIGN Design standards D1 1 Statutory requirements D2 1 System design D3 1 Building integration D4 2 Noise D5 2 Access and controls D6

More information

Greater Manchester Fire and Rescue Service

Greater Manchester Fire and Rescue Service Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY

More information

DUCT SMOKE DETECTOR D4120

DUCT SMOKE DETECTOR D4120 Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity

More information

IFE Level 4 Certificate in Fire Science and Fire Safety (HL)

IFE Level 4 Certificate in Fire Science and Fire Safety (HL) IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

Fire precautions in dwellings. Private sector housing Providing homes building communities

Fire precautions in dwellings. Private sector housing Providing homes building communities Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared

More information

Fire Safety Challenges and Solutions. Claire Guise Health and Safety Manager

Fire Safety Challenges and Solutions. Claire Guise Health and Safety Manager Fire Safety Challenges and Solutions Claire Guise Health and Safety Manager Marie Curie Cancer Care (UK Wide) 9 Palliative Care Hospices (owned) Facilities Manager in place (NEBOSH General Certificate

More information

Call reduction guidance for false alarm/ unwanted fire signals

Call reduction guidance for false alarm/ unwanted fire signals Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately

More information

Fire Risk Assessment Safety Checklist

Fire Risk Assessment Safety Checklist Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory

More information

How To Design A Gas Dryer

How To Design A Gas Dryer Non Domestic Laundry Gas Appliance Installation Code of Practice Introduction This code of practice has been produced with the assistance of all Companies within the OPL sector of SLEAT because of the

More information

Reducing false alarms

Reducing false alarms Toolkit for Reducing false alarms from Automatic Fire Detection Systems Working together to make Cornwall safer Please read the information and guidance in this leaflet, and answer the questions in sections

More information

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13 presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve

More information

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

Contents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4

Contents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 Contents 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 2. Scope and Application 2.1 Scope of the Guide 5 2.2 Premises to which the

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

Housing Act 2004 Regulatory Reform (Fire Safety) Order 2005 Fire Safety in Purpose-Built Flats Have you taken sufficient action?

Housing Act 2004 Regulatory Reform (Fire Safety) Order 2005 Fire Safety in Purpose-Built Flats Have you taken sufficient action? Housing, Culture & Enterprise Private Sector Housing Hove Town Hall (Room 217) Norton Road Hove BN3 3BQ Telephone: (01273) 293156 Fax No: (01273) 292452 Email: psh@brighton-hove.gov.uk D G Prichard QFSM,

More information

CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES

CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES CERTIFICATE OF APPROVAL No CF 5055 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 1 st Industrial Area,

More information

Decree of the Ministry of the Environment on fire safety of buildings

Decree of the Ministry of the Environment on fire safety of buildings E1 THE NATIONAL BUILDING CODE OF FINLAND 1 Fire safety of buildings Regulations and guidelines 2002 Decree of the Ministry of the Environment on fire safety of buildings Adopted in Helsinki, 12 March 2002

More information

Safety Storage Cabinets

Safety Storage Cabinets Safety Storage Cabinets Safe storage of flammables? The workplace without a fire resistant Safety Storage Cabinet Dangers, risks and your disadvantages... STORAGE ROOM Transport/working time - Increased

More information

Tremco Fire Protection Systems Group Technical Bulletin

Tremco Fire Protection Systems Group Technical Bulletin Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,

More information

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER PSUM These technical specifications determinate a range of manufactured sizes and models of fire shutters (further only shutters)

More information

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently (68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please

More information

Fire Alarm system Installation Guide

Fire Alarm system Installation Guide Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

Document No Amendment No Approved By Approval Date Review Date NS200 MAJOR SUBSTATIONS VENTILATION DESIGN STANDARD

Document No Amendment No Approved By Approval Date Review Date NS200 MAJOR SUBSTATIONS VENTILATION DESIGN STANDARD Network Standard NETWORK Document No Amendment No Approved By Approval Date Review Date : : : : : NW000-S0059 1 Chief Engineer 19/01/2016 01/12/2018 NW000-S0059 NS200 MAJOR SUBSTATIONS VENTILATION DESIGN

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

Reducing Injury and Damage Related to Electric Dryer Fires. Fire Containment Tests for the Second Edition of UL 2158

Reducing Injury and Damage Related to Electric Dryer Fires. Fire Containment Tests for the Second Edition of UL 2158 Reducing Injury and Damage Related to Electric Dryer Fires Fire Containment Tests for the Second Edition of UL 2158 Reducing Injury and Damage Related to Electric Dryer Fires: Fire Containment Tests for

More information

ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape

ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape ModuSec Secure and efficient IT room solutions Turnkey Modular Construction Fast clean build to any size or shape Room in room Standalone external build Transportable Modusec SR Options Modusec SR Options

More information

Fire Resistant Systems

Fire Resistant Systems Fire Resistant Systems A R C H I T E C T U R A L A L U M I N I U M G L A Z I N G S Y S T E M S Fire Resistant Systems Introduction Kawneer are pleased to introduce two new comprehensive Fire Resistant

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

Fire safety ONLINE VERSION APPROVED DOCUMENT VOLUME 2 BUILDINGS OTHER THAN DWELLINGHOUSES ONLINE VERSION. The Building Regulations 2010

Fire safety ONLINE VERSION APPROVED DOCUMENT VOLUME 2 BUILDINGS OTHER THAN DWELLINGHOUSES ONLINE VERSION. The Building Regulations 2010 Building Regulations 2010 Published by NBS, part of RIBA Enterprises Ltd, and available to purchase from: RIBA Bookshops Mail Order The Old Post Office, St Nicholas Street, Newcastle Upon Tyne, NE1 1RH

More information

Colorcoat Technical Paper Fire performance of pre-finished steel cladding systems

Colorcoat Technical Paper Fire performance of pre-finished steel cladding systems CI/SfB (4-) Nh2 (A3j) May 2013 CI/SfB (4-) Nh2 (A3j) May 2013 Colorcoat Technical Paper Fire performance of pre-finished steel cladding systems MINIMISING FIRE RISK Tata Steel have a long history of product

More information

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES

More information

How To Write A Fire Risk Assessment

How To Write A Fire Risk Assessment Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes

More information

ONLINE VERSION ONLINE VERSION

ONLINE VERSION ONLINE VERSION The Building Regulations 2000 Fire safety B APPROVED DOCUMENT VOLUME 2 BUILDINGS OTHER THAN DWELLINGHOUSES B1 Means of warning and escape B2 Internal fire spread (linings) B3 Internal fire spread (structure)

More information

Fire Risk Assessment For Simple Premises

Fire Risk Assessment For Simple Premises Fire Risk Assessment For Simple Premises Responsible Person (Employer or other person having control of the relevant premises) Company / Premises Name Address of Premises Postcode Primary Use of Premises

More information

RVH/BCH Data Centres Proposals for Surge Protection and Ventilation

RVH/BCH Data Centres Proposals for Surge Protection and Ventilation REPORT Proposals for Surge Protection and Ventilation BELFAST HEALTH AND SOCIAL CARE TRUST ROYAL GROUP OF HOSPITALS GROSVENOR ROAD BELFAST BT12 6BA Rev. 01 6th September 2013 Table of Contents 1.0 Ventilation

More information

Fire Doors Explained. Presented by - Peter Barker

Fire Doors Explained. Presented by - Peter Barker Fire Doors Explained Presented by - Peter Barker Objectives and Outline 1. The role of fire resisting doors 2. Proving the performance of fire resisting doors 3. Common problems and solutions The Role

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1581: Issue 2.1 Requirements and tests for LPCB approval of nonload This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information

More information

Understanding BS EN 771-3: Aggregate concrete masonry units

Understanding BS EN 771-3: Aggregate concrete masonry units 60 Charles Street, Leicester LE1 1FB Tel: 0116 253 6161 Fax: 0116 251 4568 Email: enquiries@cba-blocks.org.uk Website: www.cba-blocks.org.uk February 2006 Understanding BS EN 771-3: Aggregate concrete

More information

2014 British Columbia Building Code Changes

2014 British Columbia Building Code Changes District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most

More information

Commercial Kitchen Fire Safety

Commercial Kitchen Fire Safety Commercial Kitchen Fire Safety Commercial grade kitchens are a common feature found in many churches today, as religious institutions are providing meals for daycares, soup kitchens, meals on wheels and

More information

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications International Water Mist Conference, London, United Kingdom,23-24 September, 2009 High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications Fire Fighting In Civil Applications

More information