Fire safety in the North/South Line project. Designing measures for fire resistance in infrastructure

Similar documents
SAFIR A software for modelling. to the fire

Frost Damage of Roof Tiles in Relatively Warm Areas in Japan

Quality Assurance Concepts. Outline

THE HONG KONG INSTITUTION OF ENGINEERS 香 港 工 程 師 學 會. Admission Requirements for the Fire Discipline (Normal Route) Item Description Remarks

Annex of the certificate (Page 1/6) Accreditation Scope

1-085 Fire safety performance of materials

Fire testing procedure for concrete tunnel linings

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Composite Panel Firewall Systems

Physically Crosslinked Foam Insulation

STEEL BUILDINGS IN EUROPE. Single-Storey Steel Buildings Part 7: Fire Engineering

Understanding BS EN 771-3: Aggregate concrete masonry units

Introduction. Eurocodes. Specification. Cost

List of Frequently Utilized Storage Tank Standards and Practices

Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces

Reliability of Temperature-Dependent Models for Analysis of Reinforced Concrete Members Subjected to Fire

Introduction. Facade Fire Test on PUR External Thermal Insulation Composite System (ETICS)

Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades

Fire-induced damage in prestressing steels

Investigations of a Long-Distance 1000 MW Heat Transport System with APROS Simulation Software

1.3 Properties of Coal

SPREFIX SPRAY INSULATION _ in the marine market.

Relevant British, European and International standards

fr fire retardant MARMOLEUM

Core Fittings C-Core and CD-Core Fittings

Fire-resistant barriers: background on requirements and determination method. Reading guide for test reports.

CONSTRUCTION MATERIAL TESTING

AdMaS centre Structure of the centre: Development of Advanced Building Materials Development of Advanced Structures and Technologies

Pavement Patching Repair for AC and PCC Pavement Surfaces. Vern Thompson

HSE Information Sheet. Advice on acceptance criteria for damaged Passive Fire Protection (PFP) Coatings. Offshore Information Sheet No.

SÖDERLEDSTUNNEL STOCKHOLM FIRE PROTECTION OF THE WESTERN TUBE A CASE STUDY

Chapter 2 Basis of design and materials

Security of Mass Transportation View of CDV - Transport Research Centre in the Czech Republic. by Karel Pospisil Director of CDV

Structural fire design Eurocode Timber structures

Enclosures DuraSystems Barriers, Inc. The Passive Fire Protection Specialists

Fire safety issues. Solved. efectis. group. The European experts in fire safety

Test report P 7013-E. InoPaz H2O. Pazkar LTD. Alon Tavor Industrial Zone AFULA / Israel. J. Magner Dipl.-Ing. N. Machill.

Safety Storage Cabinets

STADIUM Software Overview. Durability and Service Life of Concrete Structures

BOFIRE A FEM-programm for non-linear analysis of structural members under fire conditions

The International Journal Of Science & Technoledge (ISSN X)

HIGHWAYS DEPARTMENT GUIDANCE NOTES ON THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE DECKS

Microwave absorbing tiles:

to control the heat alongside the boiler to protect the more sensitive metal components against thermal, erosive and corrosive degradation

Using CFD in Platform Design

Study of durability of sprayed concrete

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: TEC-WOOD ( )

Site and Storage Conditions for Class 3.1 Flammable Liquids

Current opportunities of sprayed waterproofing membrane. Frank Clement Technical Manager Sprayable Membranes MEYCO Global Underground Construction

Summary of risks with conductive and nonconductive plastic pipes at retail petrol stations

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011

BETONYP building boards. The modern way of living.

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

High Performance PSA in Sheet Membrane in Water Protection

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN : 2007

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

Fire Security Systems

The European Fire Safety Standard CEN TS Railway Interiorsexpo Amsterdam November 2008

OFFICIAL MASTER DEGREE PROGRAMME "ARCHITECTURAL TECHNOLOGY" Syllabus

Naue GmbH&Co.KG. Quality Control and. Quality Assurance. Manual. For Geomembranes

Loss Prevention Standard

Portable petrol storage containers

Hanson Building Products. precast basement solutions

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments

Commercial Gas Furnace Upflow

WORLD S TALLEST TIMBER BUILDING, BERGEN

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

Numerical modelling of shear connection between concrete slab and sheeting deck

EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS

FIRESTOPPING & SMOKE SEALS

Technical Specification for Model RSK2503 (Z)-06A IR Belt Solar Cell Firing Furnace

INDUSTRIAL ROOFING CASE STUDY: The Advantages of Aluminized Stainless Steel. Roof Installed:

Introduction to cable fire stopping

EcoTouch Insulation with PureFiber Technology

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

Optimal 5zon. Product information - Optimal 5zon 06/11/13. Pressure redistributing foam mattress. Clinical and performance information

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS

The soot and scale problems

VeMet, Utrecht, NL «Solution in Wear Protection» Dipl.-Ing. Wolfgang Leichnitz. Quit

C. Section TESTING LABORATORY SERVICE.

World Tunnel Congress Underground Facilities for Better Environment and Safety - India

THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY

North American Stainless

Fire-Rated Glass and Glazing START

A World Class Manufacturer of Induction Bends

Roof Insulation Building. Energy. Environment friendly e-library

Product Line DUST. The family of hermetic luminaires

Successful Approach to the Repair of Reinforced Concrete Support Structures in Delayed Coking Units

Gas Explosion at a Subway Construction Site

Performance 17 Two-Stage Air Conditioner with Puron Refrigerant

CFD Based Air Flow and Contamination Modeling of Subway Stations

COMMERCIAL BUILDING APPLICATIONS

INTERIM ADVICE NOTE 96 /07 Revision 1 GUIDANCE ON IMPLEMENTING RESULTS OF RESEARCH ON BRIDGE DECK WATERPROOFING

Calculation of Liquefied Natural Gas (LNG) Burning Rates

GCLs USED IN SECONDARY CONTAINMENT

Mass Concrete. Robert Moser CEE8813A Material Science of Concrete. Definitions & Standards, Thermal Cracking, and Temperature Rise

also in this issue Automatic Doors for the People Calculating Roof Insulation R-values Waterproofing and Concrete Balconies

Commonwealth of Pennsylvania PA Test Method No. 632 Department of Transportation October Pages LABORATORY TESTING SECTION. Method of Test for

Transcription:

Fire safety in the North/South Line project Designing measures for fire resistance in infrastructure 15 april 2015

https://www.flickr.com/photos/noordzuidlijn/ Prologue Separate contractors for concrete works and finishing works Safety requirements defined during concrete works Fire protection of stations to be handled in finishing phase

Challenge Handling changing safety requirements Designing fire resistance in finishing phase How? Team of fire safety and structural engineers from client and contractor working together Define approach together and make it SMART Keep authorities informed on approach and progress

Approach definition of station/tunnel Building permit station/tunnel Building permit defines station locations (formal) Bored tunnel is clearly defined Remaining parts: structural characteristics (e.g. dilatations) Example near Rokin station Tunnel (bored) Station Tunnel (other)

Approach thermal load on structure Building permit station/tunnel Definition of starting points Safety strategy: safe haven principle Make sure metro stops at station Stations are safe havens: more robust safety measures Fire scenario based on safety strategy and fire load Metro fire in station/tunnel Compartment with normal fire load Compartment with limited fire load

tunnel station Metro fire Metro fire Low fire load Normal fire load Safe haven NSL curve EUR 120 ISO 90 ISO 120 Approach fire curve Building permit station/tunnel Definition of starting points Determination of thermal load Fire curve from thermal load Station: Metro fire: EUREKA 120 Low fire load: ISO 90 Normal fire load: ISO 120 Tunnel: Metro fire: specific curve NSL (rolling stock based)

Approach demarcation in station (1) Building permit station/tunnel Definition of starting points Determination of thermal load Fire curve from thermal load per station per member Station: low fire load metro fire ISO 90 EUR 120 Direct area of influence?

Approach demarcation in station (2) Building permit station/tunnel Definition of starting points Determination of thermal load Fire curve from thermal load per station per member Direct area of influence External flaming model based on Law/EC model Realistic worst-case scenario based on fully developed metro fire Safety factors applied EUREKA (metro fire) is contact surface of the flame with structure

Approach fire resistance per station per member mixture loading cover Planning Ultimate (accepted) limit state concrete works moisture Proven considerations Interface temperature spalling Requirements: Temperature criteria for concrete and steel (durability) No concrete spalling Conclusion spalling: Spalling behaviour can not be modelled/predicted yet (progressive insight) and concrete structure already exists Assess spalling behaviour using in-situ fire tests Cost Requirements on products (SMART) Efectis

Air + water gas Spalling of concrete Liquid water Spalling: evaporating water volume increase pressure Parameters that affect spalling: Moisture content Mixture composition and strength (permeability & porosity) Mechanical loading Here: moisture, high strength, low permeability, high load

Assess spalling in-situ practical approach Choose worst-case and most representative concrete mixture(s) Choose worst-case loading conditions Assess spalling behaviour (protected structure) Find non-spalling result

Assess spalling in-situ mobile furnace 36 fire tests in 5 underground stations and immersed tunnel below IJ Resulting design interface temperatures from 200 C to 400 C Low temperatures caused by high concrete strength, loading and mixture composition (permeability / not designed for non-spalling) Efectis Efectis

Efectis Assess spalling in-situ Spalling!

Approach final design per station per member Planning Ultimate (accepted) limit state concrete works Proven considerations Cost Requirements on products (SMART) Design mixture loading cover moisture Interface temperature spalling Fire test results With fire test results: SMART requirements for products Passive fire protection product can be chosen Required thickness based on existing (laboratory) fire test data Decision: Spalling in ISO zone omitted in line with Eurocode

Conclusions / recommendations Changing requirements occurred during the construction process Cooperation between client and contractor Was experienced as an exciting and interesting period Keep authorities involved in the process Not only necessary but helpful as well Design/assess fire resistance & spalling behaviour early in the process

Thank you for your attention.... and see you on Friday at the site-visit