1 center for the polyurethanes industry October 2009 Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces One of the largest growing uses of spray polyurethane foam (SPF) insulation is in residential attics and crawl spaces. As with all other foam insulation applications, this use is regulated by building codes to assure that occupants are properly protected from the risk of fire. In order to demonstrate compliance with these requirements, the spray foam supplier typically performs fire tests, the results of which are submitted to an evaluation organization, such as the International Code Councils Evaluation Services (ICC ES), for review. A product s performance is assessed against an Acceptance Criteria meant to clarify code requirements or to provide a technical basis for products or systems that are alternates to what is specified in the code. Through a public hearing process, the ICC-ES developed the Acceptance Criteria for Spray-applied Foam Insulation (AC 377). Recent modifications to the fire testing portion of AC377 were approved by the ICC-ES Committee in June These changes, adopted by stakeholders in a consensus, voluntary standards development process, are explained in this article. The American Chemistry Council's Center for the Polyurethanes Industry (CPI) and the Spray Polyurethane Foam Alliance (SPFA) are working to educate spray foam suppliers, contractors and specifiers regarding these new fire tests and the evaluation reports on this use issued by ICC-ES. The new protocol is based on code-compliant assemblies, and creates a credible standard for flammability performance for SPF installed in attic and crawl space applications. (Note performance in flammability tests does not necessarily predict how a material will perform in an actual fire.) Code Requirements According to the International Building Code (IBC ) and the International Residential Code (IRC R316.4), all foam plastic insulation must be separated from the interior of the building by an approved 15-minute thermal barrier, such as ½-inch gypsum wall board or equivalent material. This thermal barrier may be omitted if certain conditions are met in attics and crawl spaces. Specifically, entry must be restricted to service of utilities AND the foam plastic must be protected from ignition with a code specified material. Section of the IRC prescriptively defines the following six materials as ignition barriers: 1½ mineral fiber insulation ¼ wood structural panels ⅜ particleboard ¼ hardboard ⅜ gypsum wall board 16 mil corrosion resistant steel Note that these materials used as ignition barriers are not necessarily as protective as thermal barriers. Unlike thermal barriers, these materials are not required to limit the average temperature rise on the unexposed surface to less than 250oF after a 15 minute exposure to an ASTM E119 temperature curve, nor is there a requirement for these materials to stay in place for at least 15 minutes when subject to specific fire tests. Special Approvals Allowed by Code The use and implementation of the prescribed ignition barriers over SPF insulation in attics and crawl spaces have proven to be awkward and inefficient. Fortunately, the building codes allow for special fire tests to prove equivalent performance of alternate assemblies. In general, these fire tests must be related to the end-use configuration, and the finished foam plastic assembly must be tested in the maximum thickness and density intended for use. 1
2 Options exist in the building codes to perform testing on the assembly to qualify SPF without a thermal barrier. Passing these tests, with more stringent requirements than tests for ignition barrier equivalence, would allow the assembly to be used in lieu of the thermal barrier. Specific testing includes NFPA 286 (with criteria from IRC R ), UL 1040, UL 1715 or FM Assemblies passing these tests can also be used as an alternate to using code-prescribed ignition barriers. The building codes also allow code-prescriptive ignition barriers to be substituted with an assembly that can show at least equivalent performance. Again, these fire tests must be related to end-use configuration. Typically, the baseline is set based on performance of a prescribed ignition barrier over the SPF in question. The Route to Special Approvals of Alternate Assemblies Although the ICC-ES officially came into being on February 1, 2003, it has a history of over 70 years. The previously existing four building product evaluation services in the US combined their operations into one, the ICC-ES. The ICC-ES evaluates building products for compliance with the code and issues reports on these products free of charge to code officials, contractors, and any others with an interest in the building industry. These reports are only advisory since it is only the code official or other authority having jurisdiction that can grant final approval for product use. The foam plastic industry has worked with the ICC-ES to develop specific Acceptance Criteria (AC) for its products. These ACs are important because they can address products that fall under code provisions that are not sufficiently clear, such as fire testing and approval of alternate assemblies in attics and crawl spaces. These foam plastic specific ACs are: AC12 for Foam Plastic Insulation and AC377 for Spray-Applied Foam Plastic Insulation. Note that these ACs are intended solely for the use in development of the ICC-ES evaluation reports. The ICC-ES has not approved AC usage by other evaluation entities in publishing code-compliance reports or for product certification activities. Complications of Comparative Testing By definition, comparing performance of a test assembly to a baseline assembly requires two fire tests. Selection of an appropriate code complying baseline is important to the credibility of the test. This was the case in the original AC377, where a comparative crawl space test, SwRI 99-02, developed at Southwest Research Institute, was used to eliminate the ignition barrier over foam plastic insulation altogether. In April 2000, the International Conference of Building Officials Evaluation Services (ICBO ES) allowed for testing to qualify an alternate ignition barrier material or system utilizing the comparative crawl space test, SwRI 99-02, with Kraft paper faced fiberglass batts as an ad hoc baseline assembly [1]. Figure 1. The SwRI comparative crawl space test showing a baseline assembly constructed with Kraft paper facing exposed to the flame source. As long as the foam plastic outperformed the fiberglass, the construction was approved for use in attics and crawl spaces. This policy was later adopted by ICC-ES. Although the ICBO mentioned three acceptable protocols for testing, the Kraft faced fiberglass was chosen as the baseline by many companies. Passing performance in this test allowed for omission of the prescribed ignition barrier. One problem with the ICBO-ES, and later ICC-ES 2
3 policy, was that the orientation of the Kraft paper was not specified. Leaving the Kraft paper exposed is a non-compliant construction (IRC R and Exception 1, IBC and 719.3), and it is not a prescriptive ignition barrier. Another complicating factor was that passing the comparative crawl space test also allowed elimination of the ignition barrier in the attic space, despite the differences in crawl space size and geometry compared to an attic space. An Interim Solution The ICC-ES took action in late 2007 by asking SPFA to propose a new approach for fire performance testing of attics and crawl spaces. SPFA formed an Attics and Crawl space Task Force in early 2008 to address this request. Based on a recommendation from SPFA, ICC-ES adopted a fixed time to flame threshold for performance in SwRI in May 2008 thereby eliminating the need for two comparative tests and providing a consistent baseline [2]. This recommendation became known as AC377 Appendix B and was seen by ICC-ES as an interim solution. It allowed SPFA time to develop a more rigorous proposal to meet the intent of the code. All new and renewed evaluation reports issued after May 2008 and before June 2009 were subject to the interim requirements. Appendix B as a fire test option expired in June The SPFA Task Force Protocol The SPFA, with funding from member companies and the Center for the Polyurethanes Industry, initiated a study to find a code compliant solution for testing spray foam for attic and crawl space applications. Other foam plastic insulation industries were consulted during protocol development. Recognizing that the spray foam industry would use the same test baseline, the SPFA embarked on development of a large scale fire test protocol based on a widely-accepted room corner test, a modified NFPA 286. NFPA 286 is a room corner fire test, utilizing an 8 ft high, 8 ft wide by 12 ft long room with a controlled sand gas burner ignition source in the corner. A code approved prescriptive ignition barrier was investigated as the comparative baseline: SPF covered with ¼ inch plywood. Based on an average time for room flash-over from six of these tests, a Pass/Fail time threshold was assigned. Figure 2. The NFPA 286 test assembly Tests were also performed on SPF without the plywood to uncover any testing issues specific to SPF. Because of the uneven surface of SPF, and based on heat-flux mapping of various ignition sources and their distance to the wall, the task force added a requirement for the SPF in the corner above the flame to be within a certain distance from the burner assembly. Another requirement in the protocol is that the product or assembly being tested for approval must be uniform on both the walls and the ceilings. For example, there is no option to apply an intumescent coating to the wall, but not the ceiling of the attic. If a coating is used, it must be uniformly applied to both surfaces. Attics can be made with various slopes in the ceiling. Instead of testing each possible slope for approval, this room corner test is conservative in that it evaluates the extremes of vertical wall and horizontal ceiling, eliminating the need to test each possible slope. 3
4 Currently, some manufacturers have ICC-ES reports that allow approval to cover only the vertical (wall) surface and leave the ceiling foam exposed. In the extreme case, this approval would inadvertently allow exposed foam on the ceiling of the attic to be installed on a slope all the way to the floor of the attic. Figure 3 uses a schematic to explain this point further. Because most attic ceilings are not 8 ft from the floor at their lowest point, like the test configuration, testing only the ceiling in a room corner test does not adequately represent attic use. The requirement in the protocol that any thermally resistive coating be applied uniformly to all surfaces (vertical and horizontal) eliminates the need to limit the approval to a specific configuration. ICC-ES is allowing generic comparative room corner tests until June 2010, but will apply the SPFA test protocol requirements to any new submitted test data. In addition, testing horizontal ceilings will no longer gain approval for sloped under roof decks. Figure 3. Schematic explanation of extension of vertical walls to sloped roof and inappropriate extension of horizontal ceiling to sloped roof Moving Forward: Revisions to Existing Evaluation Reports As the process of creating tests with realistic, code-compliant baselines for attic and crawl space approvals using AC377 has progressed over the past few years, the ICC-ES has given ample notice to report holders of the pending changes. In June 2008, it was announced that by the end of 2009, all spray-applied foam plastic insulation evaluation reports that currently have approval for use in attics and crawl spaces based upon a Kraft-faced fiberglass baseline will have those sections deleted from the evaluation report. These reports were based upon either the ICBO April 2000 letter or on AC377 Appendix B (an expired, interim solution with specific pass/fail times that were based upon non-code compliant construction). Generic Comparative Room Corner Test (A1.2.2) Additional Conditions and Eventual Deletion ICC-ES decided to allow AC377 Appendix A1.2.2 to remain in place until June During this period, any new tests submitted using this generic comparative room corner test will have the following additional criteria applied (based on SPFA recommendations from their development work): Care shall be taken to provide as smooth a surface as possible especially in the wall areas adjacent to, as well as above the flame source For testing on walls, the maximum deviations of distance between the flame source and the foam surface are as described in AC 377 Appendix X, Figure 3 If approval is sought for the underside of roof deck only, approval will be granted only for use on horizontal surfaces at heights equal to or greater than the ceiling height tested If coverings are used over the foam, they shall be applied at the same thickness or minimum coverage rate to all foam surfaces. 4
5 Options Available for Meeting Code Attics The following options are detailed in AC 377 for approved SPF use in attics: Use a code-prescribed ignition barrier (A1.1) Perform a special approval test in lieu of thermal barrier (A1.2.1) Perform a modified-nfpa 286 room corner test (Appendix X) Perform generic comparative room corner tests with ¼ plywood baseline (A1.2.2, expires June 1, 2010) Crawl Spaces The following options are detailed in AC 377 for approved SPF use in crawl spaces: Use a code-prescribed ignition barrier (A2.1) Perform a special approval test in lieu of thermal barrier (A2.2.1) Perform a modified-nfpa 286 room corner test (SPFA Protocol, Appendix X) Perform comparative crawl space tests with ¼ plywood baseline (A2.2.2 and Appendix C) The acceptance of the SPFA Protocol by ICC-ES into the Acceptance Criteria for Spray-applied Foam Insulation (AC377, Appendix X) provides a number of credible options to demonstrate compliance with the code. Furthermore, the testing options apply to a variety of SPF products and systems, including exposed spray foam or spray foam covered by an alternate ignition barrier, such as an intumescent coating. Using the SPFA Protocol (Appendix X) allows an SPF supplier to gain acceptance of both attic and crawl space use from one test. Conclusions The SPF industry worked with code bodies to assure that testing protocols for spray foam insulation installed in attics and crawl spaces meet the intent of the code. The ICC-ES unanimous approval of the SPFA test protocol allows the industry, code officials, home builders and home owners to be confident that a well thought out, thorough and robust test will be used to qualify SPF products for use in attics and crawl spaces. AC 377 (June 2009 Revision): Testing Options for SPF Use in Attics and Crawl Spaces Thermal barrier equivalence, NFPA 286 or UL 1715, or UBC 26-3 [1] Comparative room corner tests plywood baseline, UBC 26-3, UL 1715 or NFPA 286 [2] Comparative crawl space tests plywood baseline, Appendix C [3] Modified NFPA 286 [4] ATTICS Storage Allowed No Storage Permitted [testing allowed only to June 1, 2010, approvals sunset January 1, 2011] NO No Storage Permiitted CRAWL SPACES Storage Allowed NO No Storage Permiitted No Storage Permiitted [1] AC 377 Section 3.3.3, Appendix A 1.2.1, [2] AC 377 Appendix A1.2.2 [3] AC 377 Appendix A2.2.2 [4] AC 377 Appendix X The revised AC377 also means that Evaluation Services Reports are under review by ICC ES. The following table can serve as a guide regarding current ESRs. 5
6 Impact of Revised AC 377 (June 2009 Revisions) on Current Evaluation Services Reports (ESRs) BASIS FOR ESR NFPA 286 or UL 1715, or UBC 26-3 [1] Comparative room corner tests plywood baseline, UBC 26-3, UL 1715 or NFPA 286 [2] Comparative crawl space tests - Kraft faced fiberglass baseline [3] Crawl space test Appendix B-Time threshold (prior to June 2009 Revision) [4] Modified NFPA 286 [5] COMMENTS No need to amend/revise ESR. ESR expires January 1, Revision must be based on applicable test(s) from Testing Options Table. ESR expires January 1, Revision must be based on applicable test(s) from Testing Options Table. ESR expires January 1, Revision must be based on applicable test(s) from Testing Options Table. No need to amend/revise ESR. [1] AC 377 (June 2009 Revisions) Section 3.3.3, Appendix A 1.2.1, [2] AC 377 Appendix A1.2.2 [3] ICBO-ES April 2000 Letter [4] Appendix B, which was deleted from AC 377 (June 2009 Revisions) [5] AC 377 Appendix X References 1. Gerber, B. Recognition of Use of Foam Plastic Insulation in Attics and Crawl Spaces, Subject MISC1-R (MB/RK) (Previously MISC2-0799). International Conference of Building Officials Evaluation Services. 11 April Beaton, M. Proposed Revisions to the ICC-ES Acceptance Criteria for Spray-Applied Foam Plastic insulation, Subject AC R1. ICC-ES Evaluation committee memo, May 19,
THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY
THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY Spray Polyurethane Foam Alliance Copyright 2005 To order copies of this publication, call 800-523-6154 and request SPFA Stock Number AY 126 TECHNICAL
Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
Polyurethane Products
Polyurethane Products ISSUE AX173 JULY 2011 Table of Contents Introduction Overview of U.S. Model Building Code Fire Performance Requirements Use of Amine Catalysts in Polyurethanes Manufacture Polyurethanes
ICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3493 Reissued September 2014 This report is subject to renewal September 2015. A Subsidiary of the International Code Council DIVISION:
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.
0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-1826 Reissued 02/2016 This report is subject to renewal 02/2018. DIVISION: 07 00 00 THERMAL
Fire Testing of Recycled Materials for Building Applications
Fire Testing of Recycled Materials for Building Applications Robert H. White Abstract To gain wide market acceptance of new building products made from recycled materials, fire testing may be necessary.
THE DOW CHEMICAL COMPANY Issued: August 1, 2008 200 LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN 48674 (989) 638-8655 www.dowbuildingmaterials.
ICC EVALUATION SERVICE, INC. EvaluateP InformP Protect Los Angeles Business/Regional OfficeP 5360 Workman Mill RoadP Whittier, CA 90601 (562) 699-0543 phonep (562) 695-4694 fax DIVISION: Section: 6 WOOD
EcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
Underwriters Laboratories Testing Information
Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum
Meeting the Fire Code with Continuous Foam Plastic Insulation
Dow Building Solutions Meeting the Fire Code with Continuous Foam Plastic Insulation The 2012 International Building Code (IBC) specifies the fire tests that must be passed if a foam plastic material is
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION
0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-3758 Reissued 04/2016 This report is subject to renewal 04/2017. DIVISION: 07 00 00 THERMAL
HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663)
HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) Fire-Retardant-Treated Wood Framed Wall Assemblies GENERAL INFORMATION Fire-resistant construction
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003
M E M O R A N D U M To: Partnership for Safer Buildings Date: 21 March 2003 From: Codes Assessment Subcommittee Walter Smittle III, Chairman Re: Building Code Fire Safety Concerns: NFPA 5000, Building
LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION: 06 05 83 SHOP APPLIED WOOD COATINGS SECTION: 06 16 00 SHEATHING REPORT HOLDER:
0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1365 Reissued 04/2016 This report is subject to renewal 04/2017. DIVISION: 06 00 00 WOOD, PLASTICS
LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council RETAINED ON U.S.
ICC-ES Legacy Report ER-5043* Reissued March 2004 www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council Legacy report on the 1997 Uniform Building Code DIVISION: 09
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
If you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in one year.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-900* Reissued March, 20 This report is subject to renewal in one year. A Subsidiary of the International Code Council DIVISION:
In accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council *Revised April 2014
ICC-ES Evaluation Report ESR-1647* Issued July 2013 This report is subject to renewal August 1, 2015. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name:
STATE OF CALIFORNIA RESIDENTIAL ALTERATIONS - RE-ROOF CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name: CALIFORNIA ENERGY COMMISSION CF-1R-ALT-01-E (Page 1 of 2) Date Prepared: A.
Continuous Insulation Using Polyiso Wall Sheathing
PIMA Technical Bulletin #403 Continuous Insulation Using Polyiso Wall Sheathing What it is, what it does, and why you need it About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70%
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in
REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
ICC-ES Evaluation Report Reissued September, 2010 This report is subject to re-examination in one year.
ICC-ES Evaluation Report ESR-2270 Reissued September, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
Executive Summary Inclusion of Current Firewall Requirements in NBCC
Executive Summary Inclusion of Current Firewall Requirements in NBCC This background paper has been prepared on behalf of the Gypsum Manufacturers of Canada by Standing Committee on Fire Safety & Occupancy
The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A
TechSpecs A builder s blueprint for construction technologies January 2013 The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A C B A E D H G F A. Wood Floor Framing - p. 2 B. Foundation
CLOSED-CELL SPRAY FOAM Resisting Wind Uplift in Residential Buildings
CLOSED-CELL SPRAY FOAM Resisting Wind Uplift in Residential Buildings RICHARD S. DUNCAN, Ph.D., P.E. JINHUANG WU, Ph.D. NOTICE: All statements, information and data given herein are believed to be accurate
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations Fire Protection Review for the Fixed Target ES&H Review Committee September 2010 By James Priest PhD DRAFT Overview: When reviewing
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
UL Fire Door Inspection Service. UL Fire Alarm Certification Program. A valuable but misunderstood resource for jurisdictions
2013 Issue 2 2 A Strong Foundation 3 Introducing UL Fire Door Inspection Service 6 Enhanced UL Marks Coming Your Way Soon UL Fire Alarm Certification Program A valuable but misunderstood resource for jurisdictions
FIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Fire-Retardant-Treated (FRT) Plywood
T e c h n i c a l n o t e Fire-Retardant-Treated (FRT) Plywood Number K320 January 2009 Introduction Codes assure fire safety by controlling such things as size and design of the structure and flame-spread
FIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
Wood use in Type I and II (noncombustible) construction
Wood use in Type I and II (noncombustible) construction D.G. Bueche Hoover Treated Wood Products, Thomson, Georgia, USA ABSTRACT: As with many products, the building code regulates the use of wood in construction.
research highlight Highly Energy Efficient Building Envelope Retrofits for Houses
research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with
National Renewable Energy Laboratory
FireRatingsofPVSystems: AGuideforStakeholders Preparedfor: NationalRenewableEnergyLaboratory Golden,Colorado Preparedby: BrooksEngineering 3949JoslinLane Vacaville,CA95688 www.brooksolar.com November2014
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
FIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors
fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors Roxul Safe n Sound Sound Control and Fire Safety From One Batt Insulation Roxul
Solar America Board for Codes and Standards
Impacts on Photovoltaic Installations of Changes to the 2012 International Codes A Solar ABCs White Paper May 2011 Solar America Board for Codes and Standards www.solarabcs.org Solar America Board for
Built to Last. Built for Beauty. Good. Solid. Logix. TM
Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a
Classroom Door Security & Locking Hardware
Classroom Door Security & Locking Hardware The ability to protect students and teachers while in the classroom is a high priority in all educational institutions. Many schools and school districts have
APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET
Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing
Fire-Rated Glass and Glazing START
Fire-Rated Glass and Glazing START www.pilkington.com/fire Fire-Rated Glass and Glazing Pilkington Fire Protection Glass North America 946 Kane Street, Suite A Toledo, OH 43612 Provider Number: J200 Course
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
H-Stud Area Separation Wall System
12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
Product Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail [email protected] Product Guide
FIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
City of Houston, Texas, Ordinance No. 2008-
City of Houston, Texas, Ordinance No. 2008- AN ORDINANCE AMENDING THE CITY OF HOUSTON BUILDING CODE AND ADOPTING ADDITIONAL LOCAL AMENDMENTS TO THE INTERNATIONAL RESIDENTIAL CODE FOR ONE- AND TWO- FAMILY
MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015
MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 **Disclaimer: This document is to serve as informational purposes only. This is not a code book or a final interpretation of the
Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors.
Fire & Soundproofing Insulation Roxul SAFE N SOUND Fire and Soundproofing Insulation for Interior Partition Walls and Floors. Roxul SAFE N SOUND Sound control and fire safety from one batt Insulation.
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER:
0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1900 Reissued 03/2016 This report is subject to renewal 03/2017. DIVISION: 07 00 00 THERMAL
Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise
Baltimore, Maryland NOISE-CON 2010 2010 April 19-21 Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise Scott Harvey
HCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 2013 CALIFORNIA BUILDING CODE 199
CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter for state agency
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
RB271 06/07 R807.1 RB272 06/07 R807.1. Public Hearing: Committee: AS AM D Assembly: ASF AMF DF. Proponent: Rick Davidson, City of Hopkins, MN
3. The use of asphalt shingles and other roof coverings has been successful over these composite insulation panels, so the extra details about vapor retarders, etc. can be eliminated. RB271 06/07 R807.1
Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance
Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements
Lightweight Partition Design for Residential and Commercial Buildings
Lightweight Partition Design for Residential and Commercial Buildings Stanley D. Gatland II, CertainTeed Corporation, Valley Forge, Pennsylvania Guidelines are presented for the design and proper installation
REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012
TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
Fire or Ignition Resistant? Building Materials & Vegetation
Fire or Ignition Resistant? Building Materials & Vegetation Steve Quarles, IBHS & Pat Durland, Stone Creek Fire, LLC 2011 Backyards & Beyond Wildland Fire Education Conference Denver, Colorado October
Class Number 4880. May 2010. 2010 FM Approvals LLC. All rights reserved.
Approval Standard for Class 1 Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish Materials or Coatings and Exterior Wall Systems Class Number 4880 May 2010 2010 FM Approvals
FIRE-RESISTANCE RATINGS WITH STEEL JOISTS
FIRE-RESISTANCE RATINGS WITH STEEL JOISTS The Underwriters Laboratories (U.L.) Fire Resistance Directory lists hundreds of assemblies their fire resistance ratings. The Specifying Professional can choose
2009 IECC Update. Scope. Content. International Energy Conservation Code
2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
03/05/14 REVISOR RSI/JC RD3945
1.1 Department of Commerce 1.2 Proposed Permanent Rules Relating to Commerce; Thermal Insulation Standards; 1.3 Materials and Installation 1.4 7640.0100 AUTHORITY; PURPOSE; INCORPORATIONS BY REFERENCE.
Load Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS. www.r-control.com CONTROL, NOT COMPROMISE.
R-CONTROL s STRUCTURAL INSULATED PANELS Note: Information deemed reliable at time of printing. Please visit www.r-control.com for latest information. June 2012 CONTROL, NOT COMPROMISE. www.r-control.com
NFPA 30-2008: Basic Requirements for Storage Tanks
NFPA 30-2008: Basic Requirements for Storage Tanks New York City Metro Chapter Society of Fire Protection Engineers New York, NY February 22, 2011 NFPA 30, Flammable and Combustible Liquids Code Storage
Code Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
Additions and Alterations
Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal
Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit
R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed
CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...
Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
GreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers
City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.
Composite Panel Firewall Systems
Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.
ATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 09/01/2016 Issued: 09/04/2015 Visit www.ati-es.com for current status Page 1 of 17 UFP Ventures II,
NRCA s steep-slope manual is thoroughly revised for 2013
Photo courtesy of Boone Brothers Roofing, Omaha, Neb. NRCA s steep-slope manual is thoroughly revised for 2013 by Maciek Rupar 38 www.professionalroofing.net MARCH 2013 P ublished in January, The NRCA
The better way to build TM. Installation Manual. EXTERIOR WALL SIPs
The better way to build TM Installation Manual EXTERIOR WALL SIPs July 2015 EXTERIOR WALL SIPs Installation Manual Table of Contents Topics General Requirements................................... 3 Materials..............................................
Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction
T e c h n i c a l n o t e Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction Number J450 February 2009 Controlling against moisture damage in structures depends upon proper system
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
Cost Estimation for Materials and Installation of Hot Water Piping Insulation
Cost Estimation for Materials and Installation of Hot Water Piping Insulation Prepared for Pacific Northwest National Laboratory Under Contract Number: 18O9O2 By Gary Klein, Managing Partner Affiliated