Gas Explosion at a Subway Construction Site
|
|
|
- Sabina Norman
- 10 years ago
- Views:
Transcription
1 Gas Explosion at a Subway Construction Site Apr. 8th, 1970, Osaka city KOBAYASHI, Hideo (Tokyo Institute of Technology) (Summary) On April 8th, 1970, a huge gas explosion occurred at the site of construction for elongation of Osaka city subway line No.2 (Tanimachi line). The gas was leaked out of a detached joint for a drainer on the medium pressure piping, which was under construction for suspension. The gas was filled in the tunnel, ignited, and exploded violently creating a fire pillar of over 10m in height, and causing cover plates over to scatter over an area 200m in length (Figures 1, 2, and 3). The explosion resulted in a terrible accident (so-called Tenroku gas explosion accident), with 79 persons dead, 420 persons injured and 495 houses and buildings burned and destroyed. Almost all of the victims were bystanders having no direct relation to the construction work. The causes of the accident were believed to be a decrease of the joint strength by the weight of passing traffic vehicles together with the influences of the construction work itself. Furthermore, no measures were taken against drawing off the joints. Because most of victims were bystanders, this accident had a large social influence, and it left various precepts as a municipal disaster that was produced by the tremendous boom of municipal development in an age of high economic growth. 1. Event At the site of construction for elongation of Osaka city subway line No.2 (Tanimachi line), the suspending work had been conducted in the underground for the exposed pipes of medium and low pressure gas (Figures 4 and 5). A joint of the drainer for the medium pressure pipe became detached, and that caused gas to blow out, ignite, and then explode violently (Figure 6). Results of fault tree analysis are described below. Figure 7 - Fault tree diagram based on morphology, mechanism, and process of the destruction. The possible causes of the gas leak are considered to be rupture, draw out, crack, or opening of the pipe. Results of investigation after the accident showed that a joint of the drainer for the medium pressure pipe was drawn down, and that was assumed to cause the leak of gas. The same type of the drawn joint had an initial strength that was rated against an inner pressure of about 8 tons, however, the detached joint could not resist an inner pressure of even 1 ton. The cause of this change in the strength of the joint could be one or more of the following; (1) the strength of the joint had decreased, (2) no measure was taken to prevent the drawing off the joints, and (3) the construction work on the day of the accident formed a suspending condition of the pipe. These complex conditions caused the drawing down of the joint of the pipe. Cause (1) of the decrease in strength of the joint was considered to be the result of the following three factors, initial defects, gradual degradation over time by the traffic load, and influences from the construction work of the subway. The possibility of initial defects that were formed when the joint buried 1
2 under the ground, was estimated by considering the working situation and procedure of the burying process as well as the burying conditions at that time. The gradual degradation of the joint strength was considered to be important because of the shallow depth at which he medium pressure gas pipe was buried that caused it to suffer from vibration and subsidence by the passing traffic vehicles prior to the start of the construction work on the subway. After beginning the subway construction work, repeated excavation and burying in the area for the experimental drilling and covering was estimated to exert a larger influence than the traffic loads even though the period was much shorter. The source of the ignition was regarded at first to be an emergency vehicle, which caught fire at the site of the gas leakage. However, because the fire of the emergency vehicle continued for about ten minutes, the concentration of the gas mixture in the upper part of the pit just below the fire was believed to have already exceeded the limit of combustion, so that there was no fear of catching fire. Otherwise, the fire in the emergency vehicle should have occurred at the same time as the ignition of the explosion. The explosion occurred at near the center where the emergency vehicle that had caught fire located. However, the ignition point does not always coincide with the center of explosion because of a phenomenon by which the flame caused by the ignition propagates in the mixed gas before the explosion. From the reasons mentioned above, it is difficult to consider that the emergency vehicle fire was the source of ignition. There were many other potential sources of ignition around the site. The ignition source was considered to be one of those other potential sources except the emergency vehicle. Results of event tree analysis are described below. Figure 8 - Event tree diagram for the explosion and the leak of gas by drawing off the joint. The fastening strength of the gas pipe was decreased by an initial defect that had occurred immediately after the burying work. Furthermore, the joint strength degraded gradually over time from vibration and subsidence caused by the traffic loads, and finally the joint strength decreased rapidly as a result of the influences of the subway construction work. The pipe was exposed in hanging condition during the construction work. The decreased joint strength could not resist the inner pressure because there was no prevention against drawing off. Then the joint was drawn off, and caused the gas leak. The explosion occurred as a result of some unidentified ignition source. 2. Course The medium pressure gas pipe, the joint of which was drawn off in the accident was installed in May The construction work of the subway was conducted by the open-cut method, one of the methods for digging tunnels. The procedure of the open-cut method is as follows. First, steel piles are hammered along both sides to form walls. Then, the steel piles are bridged with H-shaped steel bars, upon which covering plates are placed to minimize the traffic disturbance on the roads. Finally, the area between the walls of steel piles is excavated from the ground surface. In this construction work, a tunnel of 11m in width, 5m in depth, and 225m in length was excavated along the north side of a road of 26m in width, and covered with covering plates (2m in length, 75cm in width, 20cm in thickness, and 380kg by weight) which were made 2
3 of concreted steel frames. The gas pipe, a total of 200 m in length, had two traversing points at both ends forming right angles bends. On the morning of April 8, the soil under the north corner of the traversing point was removed causing the entire length of the medium pressure gas pipe including the traversing points to be suspended, making it easy for pipe to move near the traversing point in a horizontal direction. At about 5:15 pm, 27 workers under suspending work for the exposed pipes escaped from the tunnel to the surface because they noticed the gas that blew out suddenly. At 5:20 pm, a patrol car of the gas company, on the way back to the base by chance, also found the gas leak by chance, and took communications by wireless with an emergency car and a repair car to call out. Fire trucks also arrived by dispatch from stations around the site. At that time, the gas blew out from cracks, 20m in length, between the cover plates. Fire men requested all residents and bystanders in the area to evacuate and avoid using fire. At 5:39 pm, when the emergency car of the gas company started its engine over the cover plates, the car caught fire, and then the gas blowing from the cracks also ignited. The fire gained force gradually, and at 5:47 pm, a huge explosion with a fire pillar of over 10m in height occurred, causing the cover plates to scatter over an area 200m in length. The injured persons and the cover plates fell down to the ground, and the fire pillar expanded to the surrounding houses on both sides. 3. Cause The strength of the joint had decreased by multiple causes including initial defects, gradual degradation with traffic loads, and influences from the construction work for subway. Construction work related personnel should have estimated the decrease of the joint strength, even though the failure may not been anticipated. Therefore, the basic cause of the accident was attributed to the lack of measures taken to prevent the drawing off of the joints. 4. Immediate Action When a large gas leak happens, construction work related personnel must inform not only the gas company, but also the fire station and the police station. Depending on the place and situation of the gas leak, the personnel must announce to persons in a wide area that persons and cars are not to enter the site and they must inform people around the site that the use of fire is prohibited as soon as possible. Furthermore, they must order the neighboring residents to take refuge in a safety area. The victims of this accident included a crowd of curious spectators for the first gas leakage, who did not realize that they were standing on the cover plates. In order to avoid such a tragedy, persons around the site must be ordered to take refuge in a safety area. 5. Countermeasure Taking opportunity of the accident, the Gas Service Act, 77th and 78th articles, "Protection of gas pipe exposed by excavating" was legislated. The act contained the following stipulations. Confirm that sand and soil at both ends of an exposed pipe have no possibility of collapse. 3
4 Take suitable measures to prevent leakage. Take measures to absorb and to disperse the expansion and contraction of the pipe by the change of temperature. Take measures to shut off the gas in an emergency. 6. Knowledge Consider the possibility of defects: This accident occurred because of no one had considered the possibility of a defect causing the decrease of joint strength. Construction work related personnel should take actions based on consideration that old facilities used for a long time might have some number of defects. It should be remarked that routine actions considered to be safe in ordinary circumstances might in fact be quite dangerous unknown to anyone. Recognize the dreadfulness of urban civil engineering works. 7. Sequel In regard to the criminal responsibility of the accident, the accused side, that is, the constructor, Osaka-city, and Osaka Gas Company, was tried with the procurator side in criminal court. The judicial decision, given fourteen years later, judged a responsibility of negligence on the part of the accused side. At that time, a series of judgments of "not guilty" had continued in the criminal trials on urban disasters. This judgment changed the trend of criminal trial and became an epoch-making decision to recognize anew the importance of safety. The judgment concluded that the accident was the joint responsibility of the accused three juridical persons for not applying an appropriate preventive draw off measure that would have been an effective method for preventing the accident. 8. Information Source (1) On the Liaison Office for Accident of Gas Explosion at Osaka, May, 1970, Gas Section, Department of Public Utility service, MITI. (2) Information about Cases of Serious Accidents, The Japan Gas Association. 9. Primary Scenario 01. Poor Value Perception 02. Poor Safety Awareness 03. Lack of Safety Measure 04. Organizational Problems 05. Poor Management 06. Poor Management for Work 07. Production 4
5 08. Hardware Production 09. Construction Work for Subway 10. Open-cut method 11. Suspension of Gas Pipe 12. Regular Operation 13. Nonobservance of Procedure 14. No prevention against Drawing Off 15. Malfunction 16. Poor Hardware 17. Decrease of Joint Strength 18. Failure 19. Fracture/Damage 20. Drawn Off Joint for Drainer 21. Secondary Damage 22. External Damage 23. Leak of Gas 24. Explosion 25. Bodily Harm 26. Death 27. Bodily Harm 28. Injury 29. Damage to Society 30. Social System Failure 31. Burned Down of Houses 5
6 Fig. 1 Spot of gas explosion accident. 6
7 Fig. 2 Appearance of fire by gas explosion. 7
8 Sakaisuji-line Kokubunji-2chome Tenroku-cross Tanimachi-line Tenjinbashi-suji-6chome St. Kokubunji Starting spot of accident Accident spot Miyakojima-dori Kanei-cho Fig. 3 Rough sketch of accident spot. 8
9 Drawing off part Drainer for medium pressure gas Drainer for high pressure gas Hanging bolt Piping for medium pressure gas (300mm in inner diameter) Piping for low pressure gas (500mm in inner diameter) Sleeve Sleeve Cable duct Fig. 4 Appearance of piping for city gas. 9
10 Fig. 5 Imaging sketch of hanging situation. 10
11 Pressing ring Rubber O-ring Lead O-ring Jute Fig. 6 Connecting method for piping. 11
12 Gas explosion or Gate Ignition souse Gas leakage or Gate Others Fired car or Gate Burst Drawing off and Gate Crack, Opening mouth No prevention against drawing off Hanging in space Decrease of joint strength and Gate Initial defect Degradation on time by traffic load Influence by construction work for subway Fig. 7 Fault tree diagram based on morphology, mechanism, and process of the destruction. 12
13 Gas piping Initial defect Degradation on time by traffic load Influence by construction work for subway Hanging in space No prevention against drawing off Yes Ignition souse Yes Result Explosion Yes No Leakage Yes No Decrease of joint strength Yes No Decrease of joint strength Yes No Decrease of joint strength No Decrease of joint strength No Soundness Fig. 8 Event tree diagram for the explosion and the leak of gas by drawing off the joint. 13
Emergency Plan. This emergency plan provides a format of data essential in an emergency situation.
Emergency Plan A. Introduction This emergency plan provides a format of data essential in an emergency situation. B. Definition of Emergency Incident An emergency condition exists when we determine that
AIR-CONDITIONER SPLIT TYPE
FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,
50AI01oe 02/15. Labko GRP cesspools. Instructions for installation, operation and maintenance
02/15 Labko GRP cesspools Instructions for installation, operation and maintenance Reliable solutions Wastewater treatment systems Contents 1 LABKO CESSPOOLS... 3 1.1 GENERAL... 3 1.2 IMPORTANT TO KNOW
How To Safely Dig For Natural Gas
PNG DIAL B4-U-DIG book_final_nu 5/1/05 3:24 PM Page 2 Phoenix Natural Gas,197 Airport Road West, Belfast BT3 9ED. Tel. 08454 55 55 55. www.phoenix-natural-gas.com PNG DIAL B4-U-DIG book_final_nu 5/1/05
Treatment Practice for Controlling Water Damage in the Annular Space of Shaft Freezing Hole
An Interdisciplinary Response to Mine Water Challenges - Sui, Sun & Wang (eds) 2014 China University of Mining and Technology Press, Xuzhou, ISBN 978-7-5646-2437-8 Treatment Practice for Controlling Water
Important Points: Timing: Timing Evaluation Methodology Example Immediate First announcement of building damage
3.3. Evaluation of Building Foundation Damage Basic Terminology: Damage: Destruction, deformation, inclination and settlement of a building foundation caused by an earthquake. Damage grade: Degree of danger
National Transportation Safety Board Washington, DC 20594
National Transportation Safety Board Washington, DC 20594 Safety Recommendation Mr. Jack Requa Interim General Manager and Chief Executive Officer Washington Metropolitan Area Transit Authority 600 5th
Explosion of a gasoline vapour cloud formed in a hydrocarbon loaded effluents storage tank 10 December 1999 Arquata Scrivia Italy
Explosion of a gasoline vapour cloud formed in a hydrocarbon loaded effluents storage tank 10 December 1999 Arquata Scrivia Italy UVCE Storage tank Hydrocarbons Steam coil Corrosion Steam Instrumentation
APPENDIX. The Nagasaki Atomic Bombing
APPENDIX The Nagasaki Atomic Bombing The foremost characteristic of the physical damage caused by the Nagasaki atomic bomb was the tremendous, instantaneous destruction wreaked by the blast wind and the
EMERGENCY PREPAREDNESS
EMERGENCY PREPAREDNESS Page 1 SECTION 11 EMERGENCY PREPAREDNESS CONSIDERATIONS FOR APPROPRIATE EMERGENCY PREPAREDNESS...3 EMERGENCY PREPAREDNESS POLICY Emergency Preparedness Policy - Sample...5 EMERGENCY
1.3.2 Method of construction and restoration of existing water service connections. This shall include:
1.0 GENERAL 1.1 DESCRIPTION: This specification shall cover the rehabilitation of existing water lines using the GRUNDOCRACK PIPE BURSTING SYSTEM. Pipe bursting is a system by which the pneumatic bursting
December Newsletter by Vincent Dunn Backdraft and flashover, what is the difference?
Photo By: Steve Spak December Newsletter by Vincent Dunn Backdraft and flashover, what is the difference? What is a backdraft explosion and how does differ from a flashover? Explosions kill and injure
COMBUSTIBLE DUST EXPLOSIONS
COMBUSTIBLE DUST EXPLOSIONS Most people would not think that dust made up of ordinary materials such as food could explode, but under certain circumstances it can. On 7 February 2008, a violent explosion
The Current Situation and Circumstances Regarding the Great Earthquake Damage
The Current Situation and Circumstances Regarding the Great Earthquake Damage Ishinomaki District Water Supply Authority Junichi Takaki, Deputy Technology Director 116 Shinkaminuma Hebita Ishinomaki-city
VILLAGE OF GRANVILLE SEWER BACK-UP and WATER LEAK POLICIES
VILLAGE OF GRANVILLE SEWER BACK-UP and WATER LEAK POLICIES SEWER BACK-UP POLICY General Sewer back-ups are an unfortunate, but common problem in older communities. A sewer back-up can create a health or
Masahiko Kunishima, Takehumi Sato (note of 1)
Concrete mould timber support collapse accident in the gymnasium construction work in Maritime Self-Defense Force Atsugi air base. [February 14th, 1992 (Fri). The Kanagawa Prefect. Ayase City.] Masahiko
Field Damage Inspection and Static Load Test Analysis of Jiamusi Highway Prestressed Concrete Bridge in China
Advanced Materials Research Vols. 163-167 (2011) pp 1147-1156 Online available since 2010/Dec/06 at www.scientific.net (2011) Trans Tech Publications, Switzerland doi:10.4028/www.scientific.net/amr.163-167.1147
Installation Manual. BYD Wall-mounted AC Charging Box
Installation Manual BYD Wall-mounted AC Charging Box BYD Wall-mounted AC Charging Box Installation Manual Version/Revision: A/0 Dedicated Service Commitment from BYD Auto Dear valuable customers: We are
Eric Six Heath Consultants Incorporated
Eric Six Heath Consultants Incorporated 9030 Monroe Road Houston, TX 77061 www.heathus.com The contents of this manual are proprietary to Heath Consultants (HEATH). Reproduction in whole or in part of
Leakage Detection Using PLUMBOAT
International Journal of Scientific and Research Publications, Volume 4, Issue 10, October 2014 1 Leakage Detection Using PLUMBOAT Pratiksha Kulkarni Electronics & Telecommunication Department, R.A.I.T
Preventing Overheated Boiler Incidents
Preventing Overheated Boiler Incidents PSE&G Appliance Service October 2012 Runaway Boiler Explosion Review Items Hazard Background Past Incidents PSE&G Emergency Response Future Process Improvements What
Meeting the Challenge of Pipeline Emergency Repair
Meeting the Challenge of Pipeline Emergency Repair Michael R. McReynolds, PE, SE 1 Tao Peng, PE, SE 2 ABSTRACTS The Metropolitan Water District of Southern California (MWD) is the nation s largest provider
Final Report on the Study on Safety Management for Construction Work in Japanese ODA Project. Workers Training Materials for Hazard Prediction
Final Report on the Study on Safety Management for Construction Work in Japanese ODA Project Workers Training Materials for Hazard Prediction February 2012 JAPAN INTERNATIONAL COOPERATION AGENCY(JICA)
ALMATEC Series CX CX 10 CX 130
ALMATEC Series CX CX 10 CX 130 Operating and Installation Instructions ought to be studied before installing the pump The ALMATEC Maschinenbau GmbH is certified as a modern, quality-orientated enterprise
Cardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: 0041 22 77 66 051 [email protected]
CARDOK CARLIFT Fast access to underground garages Fast, Silent, Discreet, Design, High-Tech Installation to replace an access ramp on private property Dimensions: (Built to measure, all dimensions can
METHOD OF STATEMENT FOR STATIC LOADING TEST
Compression Test, METHOD OF STATEMENT FOR STATIC LOADING TEST Tension Test and Lateral Test According to the American Standards ASTM D1143 07, ASTM D3689 07, ASTM D3966 07 and Euro Codes EC7 Table of Contents
PROCEDURES PREVENTION OF ACCIDENTAL IGNITION
Page No: 1 of 7 6.0 PURPOSE (192.751) All possible precautions shall be exercised to prevent the accidental escape and ignition of gas. Whenever possible, potential sources of ignition should be eliminated
THE ENVIRONMENTAL CRIMINAL JUSTICE IN CHINA
1 THE ENVIRONMENTAL CRIMINAL JUSTICE IN CHINA WANG, SULI Director, Division of Legislation, Office of Policy and Legislation, the National Environmental Protection Agency of China, No. 115, Xizhimennei
Your Boiler Room: A Time Bomb?
Your Boiler Room: A Time Bomb? Is you boiler room a potential Time Bomb? A few basics you need to know to work safely in the boiler room: Two potentials for explosions in a boiler room: Water/steam side
Maintenance and Management of JR East Civil Engineering Structures
Maintenance and Management of JR East Civil Engineering Structures Tadayoshi Niitsu Introduction Japan s problem of aging population and declining birth-rate has been known for years and the labour force,
After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE
86 :: Certificate in Construction Supervision (CIVIL) 12 ROOF 12.1 INTRODUCTION The structure provided to cover the house surface (floor) is known as roof. For different situation and requirement, it is
FUJI DIGITAL SOUND DETECTOR FSB-8D INSTRUCTION MANUAL
FUJI DIGITAL SOUND DETECTOR FSB-8D INSTRUCTION MANUAL Instruments for the location of underground utilities and water leaks. INDEX Page USE... 3 WARRANTY... 3 FOR SAFE USE... 4 BEFORE USE THE DETECTOR...
BARRIER LIFT SYSTEM 2 BARRIER LIFT SYSTEM
BARRIER LIFT SYSTEM BARRIER LIFT SYSTEM The crash rated elkosta Barrier Lift System BLS offers maximum security for highly sensitive entry or exit points against unauthorised vehicles attempting to break
QUESTIONS AND ANSWERS ON NEW FALL PROTECTION LEGISLATION
QUESTIONS AND ANSWERS ON NEW FALL PROTECTION LEGISLATION 50.4(1) An owner of a place of employment, an employer and a contractor shall each ensure that each component of a fall-protection system is inspected
EMERGENCY MESSAGE TEMPLATES
General Guidelines: EMERGENCY MESSAGE TEMPLATES Text messages may not be longer than 160 characters, including spaces. E-mail and voice mail messages should generally be the same message. There are two
The integrity evaluation of the reactor building at unit4 in the Fukushima Daiichi nuclear power station
The integrity evaluation of the reactor building at unit4 in the Fukushima Daiichi nuclear power station May 2012 Government and TEPCO s Mid-to Long Term Countermeasure Meeting Management Council Outline
The right cover for your individual circumstances
The right cover for your individual circumstances It is not always easy to decide which options you need to insure your vehicle and yourself properly. This guide can help you: you can use it to check at
THE GAS UTILITIES S AND THE JAPAN GAS ASSOCIATION S EFFORTS TO IMPROVE SAFETY
THE GAS UTILITIES S AND THE JAPAN GAS ASSOCIATION S EFFORTS TO IMPROVE SAFETY Kunihiro Hara Assistant Manager of Safety Technology Sec.,Gas Technology Dept., The Japan Gas Association 1. City Gas Safety
Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
Compressed Gas Cylinder Storage and Handling Guide
Overview Compressed gas cylinders are used in many workplaces to store gases that vary from extremely flammable (acetylene) to extremely inert (helium). Many compressed gas cylinders are stored at extremely
Oil and Gas Pipeline Design, Maintenance and Repair
Oil and Gas Pipeline Design, Maintenance and Repair Dr. Abdel-Alim Hashem Professor of Petroleum Engineering Mining, Petroleum & Metallurgical Eng. Dept. Faculty of Engineering Cairo University [email protected]
HAZARD RISK ASSESSMENT
HAZARD RISK ASSESSMENT Mt Grace Batchelor Magnesium Project A hazard risk assessment was undertaken to identify and assess the consequences of unplanned incidents that may pose safety, environmental risks,
Reporting dangerous goods incidents. Guideline (6th edition)
Reporting dangerous goods incidents Guideline (6th edition) Reference The recommended reference for this publication is: Department of Mines and Petroleum, 2011, Reporting dangerous goods incidents guideline
ISO IEC 27002 2005 (17799 2005) INFORMATION SECURITY AUDIT TOOL
9.1 USE SECURITY AREAS TO PROTECT FACILITIES 1 GOAL Do you use physical methods to prevent unauthorized access to your organization s information and premises? 2 GOAL Do you use physical methods to prevent
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN Adopted October 5, 2009 Table of Contents Chapter Description Page 1 Facility Descriptions... 3 1.1 Municipal Power Plant, 1001 Park
Holiday Home Insurance PROPOSAL FORM
Holiday Home Insurance PROPOSAL FORM Holiday Home Insurance Summary of Cover available There are conditions, limitations, exclusions and excesses within the wording a copy of which will be provided on
A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS
A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS What is a groundwater protection plan? A groundwater protection plan identifies the activities being conducted that can pollute groundwater and
Development of Seismic-induced Fire Risk Assessment Method for a Building
Development of Seismic-induced Fire Risk Assessment Method for a Building AI SEKIZAWA National Research Institute of Fire and Disaster 3-14-1, Nakahara, Mitaka, Tokyo 181-8633, Japan [email protected]
Traffic accidents in Hanoi: data collection and analysis
Traffic accidents in Hanoi: data collection and analysis Nguyen Hoang Hai Vietnam, Hanoi Department of Transport, [email protected] 1. Introduction Hanoi, the capital and administrative center of Vietnam,
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
Optimum proportions for the design of suspension bridge
Journal of Civil Engineering (IEB), 34 (1) (26) 1-14 Optimum proportions for the design of suspension bridge Tanvir Manzur and Alamgir Habib Department of Civil Engineering Bangladesh University of Engineering
Motor Vehicle Fatalities Accepted by the Workers Compensation Board
Motor Vehicle Fatalities Accepted by the Workers Compensation Board Year to date, numbers as of January 1, 2008 to December 31, 2008 The fatalities listed represent motor vehicle fatalities that have been
Accidents - how to deal with them
Accidents - how to deal with them Introduction Following an accident on site there seem to be so many things to do. This FactFile Information Sheet aims to provide clear guidance on the steps that should
INCREASE OF DURABILITY AND LIFETIME OF EXISTING BRIDGES. PIARC TC 4.4 EXPERIENCE.
INCREASE OF DURABILITY AND LIFETIME OF EXISTING BRIDGES. PIARC TC 4.4 EXPERIENCE. M.Sc. Gediminas Viršilas Head of Bridge Division, Lithuanian Road Administration Working group 2 of PIARC Technical Committee
AWWA Small Systems Pipe Repair Checklist, as published in July 2008 Opflow Question of the Month
, as published in July 2008 Opflow Question of the Month Thanks to: Mike Grahek, Los Angeles Department of Water, Los Angeles, California Ahmad Havivian, Black & Veatch, Gaithersburg, Maryland David Kroon,
Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A.
Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A. Properties of hydrogen Hydrogen is an odorless, colorless gas. With molecular
HOUSE BUILDING DIGEST
HOUSE BUILDING DIGEST (Construction Specifications-Foundations) Creating Enabling Environment for Affordable Housing for All This is an attempt by BMTPC to provide useful but often ignored information
Earthquake damage in wastewater systems and postearthquake repair methods; limitation and practice
Earthquake damage in wastewater systems and postearthquake repair methods; limitation and practice M. R. Zare 1, S. Wilkinson 2, R. Potangaroa 3 1. PhD candidate, University of Auckland, Auckland, New
hs2 Ground A non-technical guide
hs2 Ground Investigations A non-technical guide Contents HS2 ground investigations 1 Essential Q&A 2 2 In-ground investigation techniques 9 2.1 Cable percussion borehole 10 2.2 Rotary core borehole 12
Fire Safety In High Rise Building
Fire Safety In High Rise Building CLASSIFICATION OF BUILDINGS AS PER NATIONAL BUILDING CODE 1. GROUPING. Group A - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group B Group C - Educational
Chapter 4 Crimes (Review)
Chapter 4 Crimes (Review) On a separate sheet of paper, write down the answer to the following Q s; if you do not know the answer, write down the Q. 1. What is a crime? 2. There are elements of a crime.
NEW YORK STATE BAR ASSOCIATION. LEGALEase. If You Have An Auto Accident SAMPLE
NEW YORK STATE BAR ASSOCIATION LEGALEase If You Have An Auto Accident If You Have An Auto Accident What should you do if you re involved in an automobile accident in New York? STOP! By law, you are required
FLAMMABLE LIQUIDS COMPLIANCE NOTE
Issued by: Heather Rice Page: 1 of 7 COMPLIANCE NOTE INTRODUCTION This document provides additional guidance to support the Arrangement on Flammable Liquids (Ref No. CYC/HS/A27) CONTENTS Section Topic
WATER MAIN CONSTRUCTION TECHNIQUES DEPARTMENT OF PUBLIC WORKS WATER & WASTEWATER DIVISION
WATER MAIN CONSTRUCTION TECHNIQUES Overview Water Main - Materials Specifications Installation Future? Water Main Materials Material Types There are various material types used for water mains, these include:
SECTION 8 Industrial Facilities Field Investigation
SECTION 8 Industrial Facilities Field Investigation Types of Data to Be Collected and Recorded Warehouses, manufacturing facilities, energy-producing facilities, and factories should be inspected for performance
This instruction is valid for all ACD pump models shown on page 2
Screw pumps ACD Maintenance and Service Instruction This instruction is valid for all ACD pump models shown on page 2 Contents Page List of components 2 Exploded view/ordering code 3 Service intervals
GUIDELINES - Gas Inspection Regulations 1. Recommendations for camping site owners
GUIDELINES - Gas Inspection Regulations 1. Recommendations for camping site owners Offer gas tests by recognized experts for camping guests. Keep a record for gas tests. Write down the date and who tested
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
FLA S FIRE SAFETY INITIATIVE
Improving Workers Lives Worldwide FLA S FIRE SAFETY INITIATIVE Preventing fires and saving lives by empowering workers and factory managers SCENARIO 1 OCCURS AT FACTORY ABC, WHICH HAS NOT IMPLEMENTED NECESSARY
APPENDIX J GAS DISTRIBUTION
APPENDIX J GAS DISTRIBUTION Ji Jii APPENDIX J GAS DISTRIBUTION NEIL G. THOMPSON, PH.D. 1 SUMMARY The natural gas distribution system includes 2,785,000 km (1,730,000 mi) of relatively small-diameter, low-pressure
Always. Reliable. Tight. Wall sleeves Versatile solutions for building entries. cablepipebuildingentry+
Always. Reliable. Tight. Wall sleeves Versatile solutions for building entries. cablepipebuildingentry+ The wall sleeve The wall sleeve a largely unnoticed but very important sealing part. Wall sleeves
Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996
CITY OF SAN JOSE BUILDING DIVISION POLICY Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 All new and replacement water heaters installed
Session: HDPE Pipe Test Rafael Ortega, Vice President, Lockwood, Andrews & Newnam
Session: HDPE Pipe Test Rafael Ortega, Vice President, Lockwood, Andrews & Newnam Education Master of Business Administration University of Houston, 1985 Bachelor of Science, Civil Engineering University
GEOTECHNICAL ISSUES OF LANDSLIDES CHARACTERISTICS MECHANISMS PREPARDNESS: BEFORE, DURING AND AFTER A LANDSLIDE QUESTIONS FOR DISCUSSIONS
GEOTECHNICAL ISSUES OF LANDSLIDES CHARACTERISTICS MECHANISMS PREPARDNESS: BEFORE, DURING AND AFTER A LANDSLIDE QUESTIONS FOR DISCUSSIONS Huge landslide Leyte, Phillipines, 1998 2000 casulties Small debris
APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT
APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT City of Swartz Creek 8083 Civic Drive Swartz Creek, MI 48473 810-635-4464 Fee Received: $ Date: / / Receipt No: Demolition Permit (including Right of
WHAT TO DO Immediately After Being Involved in an Auto Accident
WHAT TO DO Immediately After Being Involved in an Auto Accident BY EDDIE E. FARAH & CHARLIE E. FARAH, ATTORNEYS AT LAW If a person is seriously injured, do not move them unless they are in imminent danger.
ABOVE-GROUND STORAGE TANKS
ABOVE-GROUND STORAGE TANKS Above-ground storage tanks in Georgia are regulated by the State Fire Marshall and by the EPA. Above-ground tanks containing 1,100 gallons or less do not require any secondary
Lessons from Offshore Accidents
Lessons from Offshore Accidents Tekna Prosessikkerhet, Bergen 2007-11-27 Jon Erik Pettersvold/DNV Energy With extracts from Petrobras Presentation June 2001 Source: www.petrobras.com.br Lessons from Offshore
Emergency Preparedness Guidelines
DM-PH&SD-P7-TG6 رقم النموذج : I. Introduction This Guideline on supports the national platform for disaster risk reduction. It specifies requirements to enable both the public and private sector to develop
Part of Your Community Important Safety Information. TransCanada - Bison Pipeline
Part of Your Community Important Safety Information TransCanada - Bison Pipeline Public Safety Information Pipeline Safety is Everybody s Business This brochure contains important safety information about
10 Victims and the law 57
10 Victims and the law 57 10: Victims and the law This section gives a summary of the law in relation to victims of crime. Introduction The court may call a victim as a witness in a criminal case. However,
Free piston Stirling engine for rural development
Free piston Stirling engine for rural development R. Krasensky, Intern, Stirling development, [email protected] W. Rijssenbeek, Managing director, [email protected] Abstract: This paper presents
Wafer Check Valve ASAHI AV VALVES. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1
Serial No. H-V066-E-2 Wafer Check Valve User s Manual Contents (1) Be sure to read the following description of our product warranty 1 (2) General operating instructions 2 (3) General instructions for
Workplace Incident Fatalities Accepted by the Workers Compensation Board in 2014
Workplace Incident Fatalities Accepted by the Workers Compensation Board in 2014 Workplace Incident Fatalities Year to date, numbers as of December 31, 2014 Workplace Incident fatalities are cases where
PET-10 INSTRUCTION MANUAL PRESSURE TANK
INSTRUCTION MANUAL PRESSURE TANK PET-10 This manual contains IMPORTANT WARNINGS and INSTRUCTIONS. Equipment in this manual is exclusively for painting purposes. Do not use for other purposes. The operator
FRAME DOOR OPENING, DOOR AND SIDE PANEL OUTER
NUBIRA/LACETTI FRAME DOOR OPENING, DOOR AND SIDE PANEL OUTER 6 1 SECTION 6 FRAME DOOR OPENING, DOOR AND SIDE PANEL OUTER CONTENTS 1. FRAME DOOR OPENING........................................... 6 2 1.1.GENERAL
orlando OWNER S MANUAL
orlando OWNER S MANUAL 2 Assembling & operating manual Orlando 30 mbar - PORTABLE GAS BARBECUE 1. 2. 3. Improper installation, adjustment, alteration, service or maintenance can injury or property damage.
PROPOSAL FOR CONTRACTORS ALL RISKS
PROPOSAL FOR CONTRACTORS ALL RISKS 1. Title of contract (If project consist of several sections, specify section(s) to be insured) 2. Location of site Country/Province/district City/town/village 3. Name
Gas Meter Clearances and Service Installation Requirements
March 2015 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE s Customer Construction Services 1-888-321-7779 or visit PSE.com/CustomerConstruction
ITS specification Jointing chambers and pull pits (ITS-02-02)
ITS specification Jointing chambers and pull pits (ITS-02-02) NZ Transport Agency Effective from September 2011 Copyright information This publication is copyright NZ Transport Agency (NZTA). Material
Resource Piling Large Load Tests using a Reaction System
Resource Piling Large Load Tests using a Reaction System RESOURCE PILING S BACKGROUND Core businesses Bored Piles Reaction System Load Test Secant Piles RESOURCE PILING Contiguous Bored Pile Wall Kentledge
Adjustments for the Active Pneumatic Vibration Isolation Table during Final Installation (File version 6)
Adjustments for the Active Pneumatic Vibration Isolation Table during Final Installation (File version 6) Loosening the valves on the steel base plates of the valve assemblies during the installation procedure
Maintenance and Service Instruction
Screw pumps E4 Maintenance and Service Instruction E4 1 IMO AB This instruction is valid for all E4 pump models shown on page 2 Contents Page List of components 2 Exploded view/ordering code 3 Service
Factors to Consider When Developing an Evacuation Plan
The following should be viewed only as suggestions: Factors to Consider When Developing an Evacuation Plan 1. You must identify your document with a specific title and explanation. Example: Evacuation
R&D on Oil-Burning, Environment-Friendly, High-Efficiency Boiler
[N.2.1.1] R&D on Oil-Burning, Environment-Friendly, High-Efficiency Boiler (Environment-Friendly, High-Efficiency Boiler Group) Takashi Murakawa, Yasuhiro Kotani, Kazuhiro Kamijo, Koichi Tsujimoto, Hiroshi
GATE VALVES ASAHI AV VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1
Serial No. H-V011-E-11 GATE VALVES Type P (Standard: Plug) Type S (Soft Seal) Contents (1) Be sure to read the following warranty clauses of our product 1 User s Manual (2) General operating instructions