MICROGRIDS FOR DATA CENTERS



Similar documents
Energy Systems Integration

CERTS Microgrid Research and Lessons Learned

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply.

Microgrid Technology: Enabling Energy Reliability and Security Opportunities in Campus, Commercial & Industrial Communities

Advanced Protection of Distribution Networks with Distributed Generators

Strategic Microgrid Development for Maximum Value. Allen Freifeld SVP, Law & Public Policy Viridity Energy

Solar Power Plant Design and Interconnection

Microgrid Building block for Smart Cities

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Electrical Grid Continuity in California Port Operations. Making Our Clients Successful

Preparing for Distributed Energy Resources

PV And Storage: Solutions with Potential

Sanjeev Choudhary SunEdison Advanced Solutions

Scope of Restoration Plan

Governor s Two-Storm Panel: Distribution Infrastructure Hardening Options and Recommendations

Design of electrical power system for a 1000MW nuclear power generating station

About Southern California Edison

Distributed Generation: Feeder Hosting Capacity. Dean E. Philips, P.E. FirstEnergy Service Corp Manager, Distribution Planning & Protection

Deep Dive on Microgrid Technologies

Financial Analysis of Solar Photovoltaic Power plant in India

Power Quality. Uninterruptible Power Supply

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC DRAFT V0.

Inverter / Charger Installation General Operations and AC and DC Connections

Transmissão em Corrente Contínua

Minimizing Impact of Electric Utility Outages with Backup Generation

Key Concepts Of Distributed Generation

MAINTAINING SYSTEM BLACKSTART IN COMPETITIVE BULK-POWER MARKETS

AC COUPLED HYBRID SYSTEMS AND MINI GRIDS

Utilities Respond to the Rise of Solar

Addressing the U.S. Department of Defense Mission Assurance Concerns and Renewable Energy Mandates

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems

YSmart Technology Co.,Ltd

Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter System

ALL STAR ELECTRIC COMPANY 10,000 Trumbull SE, Suite #F Albuquerque, NM (505) voice & fax NM License

IEEE Smart Grid Series of Standards IEEE 2030 TM (Interoperability) and IEEE 1547 TM (Interconnection) Status. #GridInterop

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process

Power Management of Cell Sites

Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva

Advanced Inverter Overview

Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer

Design of Battery Energy Storage System for Generation of Solar Power

Office of Electricity Delivery & Energy Reliability. US DOE Microgrid R&D Program

Additional Solar System Information and Resources

Modern Power Systems for Smart Energy Society

Smart Grid: Concepts and Deployment

SCE Experience with PV Integration

SDG&E s - Sustainable Communities Program

Guidelines for Large Photovoltaic System Integration

16 West Coast Regional Plan

QUESTIONS and ANSWERS RFB , Metal Clad Switchgear and Power Control Room

UPS Applications and VRLA Battery Sizing

Designed for uptime. Defining data center availability via a tier classification system

Generic PCSR Sub-chapter 15.4 : Electrical Equipment

Control of Distributed Generation Units in Stand-Alone Industrial Networks

Integrated Distribution Management System in Alabama

Paralleling Switchgear

Isolated-Parallel UPS Configuration

Understand Hybrid Generator Battery Systems

Seize the benefits of green energy and the smart grid

Five Nines and Infrared (IR) Testing at Data Centers

March ComEd Grid Modernization

Making Energy Storage Work for The Pacific Northwest

Underground vs. Overhead Transmission and Distribution

ABSTRACT DCMCCT PROJECT OVERVIEW

Micro-Turbine Combined Heat & Power Generators (CHP) Cold Climate Applications 2014 Polar Technology Conference Richard S.

User Manual of Grid Tie Inverter with Limiter

Coordinated and Optimized Control of Distributed Generation Integration

METERING BILLING/MDM AMERICA

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering

Brochure Introducing HVDC

Enterprise Approach to OSIsoft PI System

Wesleyan University. Electrical Power Study

Operation and Control Microgrid and Distributed Generation. Mohammad Shahidehpour Illinois Institute of Technology

The State of the Electrical Grid in Washington State. Michael Pesin, PMP, P.E. Seattle City Light

ENA Customer Guide to Electricity Supply

Electric Utility Crossroads Includes Renewables and Storage

Overview brochure. Energy Storage Keeping smart grids in balance

Venteea A Smart Grid demonstrator for the DRES integration on the MV distribution networks.

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Renewable and Alternative Energy Outlook

Electric Power in Airplane. Student: Maja Knezev Course ELEN 615, 31 st August 2006

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

DG Modeling Challenges & Results. Jens Schoene

ECE 586b Course Project Report. Auto-Reclosing

Transcription:

MICROGRIDS FOR DATA CENTERS

Table of Contents Summary of Pareto Energy s Microgrid Business Model Understanding the Risks of On-Site Power for Critical Infrastructure The Pareto Energy GridLink Solution 3 10 16 MICROGRIDS FOR DATA CENTERS PAGE 2 OF 20

Microgrids for Data Centers Page 3 of 20 Summary of Pareto Energy s Microgrid Business Model

The Pareto Energy Microgrid Business Model: Patented Non-Synchronous Interconnection Technology Enables An Always Islanded Microgrid with the Ability to Plug and Play Multiple Distributed Energy Resources and to Provide Continuous Power During Utility Grid Power Outages at Below Grid Rates with Governance by the Microgrid Energy Users Microgrids for Data Centers Page 4 of 20

Pareto Energy has Developed Utility Company Support For its Business Model Edison Electric Institute May 6, 2011 Dear Mr. Warner: I am writing to invite you to participate in an EEI project to assess the implications of smart gridenabled distributed resource development. As I'm sure you realize, the marriage of smart grid (SG) technologies with distributed energy resources (DER) has the potential to change fundamentally traditional utility operating paradigms, and the utility business. This has become more pressing as public policy encourages the development of DER owned by customers and third parties. We think it is vital, therefore, to understand the implications of these new technologies and policies. We have identified your project work as among the cutting-edge demonstrations in this area. We believe your perspectives and experience can contribute significantly to building a knowledge base about pilots that demonstrate the integration and interoperability of multiple types of DER at multiple levels and establish frameworks for stakeholder collaboration and participation by new market players. Of particular interest to EEI are your innovative governance structure and your "GridLink" technology that enables a safe connection between a microgrid and a traditional grid. These innovations represent significant sustainable economic development assets. Microgrids for Data Centers Page 5 of 20

The Pareto Energy Business Model for Data Centers Traditional Backup Systems versus a GridLink Non-Synchronous Microgrid Traditional Data Center Power System GridLink Non Synchronous Microgrid Microgrids for Data Centers Page 6 of 20

The Pareto Energy Business Model for Data Centers The Value Proposition for Traditional Backup Systems versus a GridLink Non- Synchronous Microgrid (Page 1 of 3) Traditional Data Center Power System Total Cost for Backup = $2000 / kw Diesel = $300 - $450; Switchgear, relays = $100/kW; UPS: $1,000/kW; engineering, permitting, installation is project specific, can range from $100 to $800 / kw. Costs of CHP Units: there is a need to oversize the generators to enable synchronization and islanding. GridLink Non-Synchronous Microgrid Total Cost for GridLink = $750 / kw Inverters = $200 KW; transformers, switchgear, ehouse packaging and system controls = $200; Softcosts = $150; redundant GridLinks for n+1 = add $200. Costs of CHP units: units can be more optimally sized due to no need for synchronization. Microgrids for Data Centers Page 7 of 20

The Pareto Energy Business Model for Data Centers The Value Proposition for Traditional Backup Systems versus a GridLink Non-Synchronous Microgrid (Page 2 of 3) Traditional Backup System Interconnection Risk: it is not unusual to encounter years of approval for synchronous interconnection and there is a risk of rejection where there are networked grids, fault current limits, or the maximum penetration depth of distributed generation has already been reached for the feeder in question. Construction Risk: systems tend to be oversized to enable islanding and islanding must be tested on-site with significant adjustments of the switch gear systems. Any change to add additional generation modules can require a new interconnection agreement and a recalibration of islanding and synchronization. GridLink Non-Synchronous Microgrid Interconnection Risk: approval is typically gained within months with little chance of rejection because a non-synchronous microgrid is not interconnected to the utility grid and so the utility grid sees it as a resistive load only. Construction Risk: with no need for synchronization, systems can be optimally-sized. GridLink units are tested off-site. Once installed the microgrid is always islanded. Additional generating modules plug and play like loads with no need for new interconnection agreements or recalibration for islanding. Microgrids for Data Centers Page 8 of 20

Traditional Backup System Operating Risks: The Pareto Energy Business Model for Data Centers The Value Proposition for Traditional Backup Systems versus a GridLink Non-Synchronous Microgrid (Page 3 of 3) Island-mode operation depends on battery storage plus UPS to maintain high-quality power. Coordination of multiple load-following generators can be difficult and there can be limited ride-through for voltage sags and other disturbances. Redundant on-site generators are idle or exporting excess power to utility at wholesale rates. GridLink Non-Synchronous Microgrid Operating Risks: The microgrid is always islanded. Grid ride-through even for severe over/under voltage events, unbalanced phases, or poor power quality. Stable on-site generators, no trips, stalls, no load-following oscillations or control issues. High utilization of on-site generators in place of grid power at retail rates with the option to export at retail to neighboring energy users. Microgrids for Data Centers Page 9 of 20

Microgrids for Data Centers Page 10 of 20 Understanding the Risks of On-Site Power for Critical Infrastructure

Existing Synchronous Interconnection Technologies Must Control Multiple Disturbances in Utility AC Voltage that Would Cause the Utility Company to Disconnect the Microgrid Such that it Cannot Provide Continuous Power During Grid Power Outages. This is Technically Feasible but Economically Expensive. Microgrids for Data Centers Page 11 of 20

The Consequences of Delayed Islanding of On-Site Power: Bradley International Airport October 2011 Outage, On-Site CHP Took Many Hours to Island FAA Report on Bradley Outage: 20 inches of snow fell at Bradley International. It caused a widespread commercial power failure, which caused communications problems in the airport. Luggage belts and cargo belts and elevators stopped working. There was difficulty refueling airplanes. There was difficulty de icing aircraft. We all know that when you can t de ice your aircraft in those conditions, you might as well weld your plane to the ramp. You re not going anywhere. Source: http://www.faa.gov/news/speeches/news_story.cfm?newsid=13252 Not the only recent outage at Bradley: A power outage occurred on March 6 on 8:15 p.m. that was caused by a blip on the C L & P grid and a switch that did not operate as it should have at the Airport's cogeneration plant. (Bradley Airport Minutes, March 2011) Microgrids for Data Centers Page 12 of 20

The Consequences of Delayed Islanding of On-Site Power: September 2011 San Diego Outage, UC San Diego Took Many Hours to Island Last year, an unanticipated power outage of most of San Diego was caused by a utility worker s switching error in Arizona. The University of California San Diego s Microgrid: Could not island instantaneously, Required 6 hours for black start, and After utility power was restored, required a second campus black out to resynchronize. Microgrids for Data Centers Page 13 of 20

New York City Case Study: Con Edison Faces Very High Costs to Accommodate Synchronized Microgrids According to a study by Columbia University: The fault current margin will always be linked to the total amount of electricity-generating capacity connected to the grid. As demand continues to increase each year around the city, requiring additional generation to be connected to the grid, the technological 'fixes' called for by the Public Service Commission will work for some time. At some point, however, the upgraded circuit breakers may also reach their higher-rated capacity limit, requiring yet another round of system upgrades. A second technical solution externaltothegridinvolvestheuseofpowerelectronics,whichareamixofdevicesusedto convert, control, and improve power quality. Some manufacturers use two complementary forms of power electronics a rectifier and an inverter to switch from AC to DC and back to AC power in order to produce higher quality power and facilitate interconnection. The duration and complexity of the review is likely to be substantially less than for synchronous interconnection. Microgrids for Data Centers Page 14 of 20

New York City Case Study Con Edison Agrees that No Existing Technology Can Affordably Island a Microgrid to Provide Continuous Power During a Grid Power Outage (Excerpts From the 2010 Report of the NYPSC Distributed Generation Collaborative ) The City proposed a conceptual CHP installation with an electric power generator supplying a portion of the energy requirements at a municipal hospital campus. After its review, Con Edison noted that all the technical interconnection requirements, e.g, transfer trip, short circuit study and fault current mitigation, voltage and stability studies, telemetry, would have to be met, that the customer would be responsible for interconnection costs, including studies and system reinforcement, and that a primary connection for the generator would require that the customer employ personnel trained in high tension switching on site 24 hours a day, seven days a week. Based on those case-specific assumptions, Con Edison advised that it considers this site to be a reasonable candidate for this type of connection. Despite positive qualities of this particular City proposal, and Con Edison s agreement to investigate ways to interconnect DG in this fashion, as a general matter, this type of approach is not the preferred interconnection method for Con Edison and may be cost prohibitive for the customer. Con Edison s concerns are: both planned and unplanned feeder outages require customer interaction with the Company for communications and breaker operations if a feeder is planned to be removed from service, when the customer opens the breaker, Con Edison personnel would need to lockoutandtagthebreakersothatoutageworkmaybeperformed.whenthefeederisreadytobe returned to service, all of these steps must be repeated by the customer and Con Edison personnel in reverse order. Feeder testing coordination could be required, which may require actions by customer personnel. (note that in the same report Con Edison committed to 800 MW of customer-owned generation, but advised that it would take 3 to 5 years to develop interconnection solutions; in 2011. however, they approved Pareto Energy s GridLink solution.) Microgrids for Data Centers Page 15 of 20

Microgrids for Data Centers Page 16 of 20 The Pareto Energy GridLink Solution

Overview of Pareto Energy s GridLink Approach T raditionally, a generator connects to the utility grid by dum ping all its pow er directly onto the m ain pow er line (Synchronous Interconnection). O ne increasingly com m on alternative is to use inverters to regulate the pow er flow s fro m local generation onto the grid back-to-back inverters (as show n) for rotating m achinery such as engines, or single grid -tie inverters for D C sources such as solar or fuel cells. In contrast, in P areto's approach, the m icrogrid takes over the service to a custom er's loads, integrating local sources of pow er w hile still keeping them fully connected to their utility feeds. Once GridLink is cut-andspliced into the distribution line, no pow er ever flow s directly from the utility grid to the loads. U tility feeds are treated equally with any local sources of power, and flow through the m icrogrid's inverters before connecting to customer loads (Non-Synchronous M icrogrid Interconnection). N onetheless, all pow er from the local sources flows onto a distribution feeder, w hether ow ned by the utility or the custom er (N on-synchronous Parallel Interconnection). So utilities still need to be concerned with islanding, fault current contributions, penetration depth, and other issues that can m ake parallel interconnection so difficult. Microgrids for Data Centers Page 17 of 20

Each GridLink ehouse can be customized for a particular load. The standard 6 MVA e-houses use a redundant series of 2MVA blocks for converting the power from AC to DC and back to AC. Each package is the size of a shipping container, including two transformers. They are prepackaged and burned in at the factory for easy installation on-site. Microgrids for Data Centers Page 18 of 20

Adding New Power Generation Once the non-synchronous microgrid is permitted, it can have power fed to it from multiple sources without requiring new utility permits. The energy can come from any source, such as solar, wind, gas engine/turbine, or energy storage. The modular nature allows the new energy to be added in the future, again without additional permitting. This is very good for testing new or experimental forms of power generation or energy storage. A system controller can be programmed to optimize the use of the different energy sources, since each can be optimized independently by the microgrid controller. Microgrids for Data Centers Page 19 of 20

Shalom Flank Microgrid Architect and CTO sflank@paretoenergy.com (202) 797 8820 Contact Information Guy Warner Chairman and CEO gwarner@paretoenergy.com (202) 247 6171 Alan McDonnell Engineering amcdonnell@paretoenergy.com (603) 546 5785 Microgrids for Data Centers Page 20 of 20