NovaTorque Brushless Permanent Magnet Motor Field Test Report

Similar documents
Catalyst RTU Controller Study Report

DIRECT CURRENT GENERATORS

Motor Fundamentals. DC Motor

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Principles of Adjustable Frequency Drives

Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt.

ECM Motors Manufactured By Regal Beloit. Products and Applications- What s an ECM? GEXPRO Regal Beloit s distribution arm for all ECM motor products

Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.

Unit 33 Three-Phase Motors

Induction Motor Theory

Specifying a Variable Frequency Drive s

CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR

Chen. Vibration Motor. Application note

Basics of Electricity

FREQUENCY CONTROLLED AC MOTOR DRIVE

Inductance. Motors. Generators

AC Induction Motor Slip What It Is And How To Minimize It

We will discuss common industrial applications with guides for the proper use of electric motors on these.

Chapter 4.5: Electric Motors, Variable Speed Drives

SYNCHRONOUS MACHINES

Understanding the Alternator

Technical Guide No High Performance Drives -- speed and torque regulation

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

Introduction. Upon completion of Basics of AC Motors you should be able to:

HIGH SPEED PERMANENT MAGNET SYNCHRONOUS MOTOR / GENERATOR DESIGN FOR FLYWHEEL APPLICATIONS

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

8 Speed control of Induction Machines

Torque motors. direct drive technology

1150 hp motor design, electromagnetic and thermal analysis

Application Information

Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA

The Ultimate Truck Stock Motor

A METHOD OF CALIBRATING HELMHOLTZ COILS FOR THE MEASUREMENT OF PERMANENT MAGNETS

Principles and Working of DC and AC machines

Vehicle Design Summit Electric Hub Motor (V2) Eric Conner Harvey Tang Matthew Peddie

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

Simple Analysis for Brushless DC Motors Case Study: Razor Scooter Wheel Motor

EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE

Energy Saving ECM Motors and Fans Ventilation Catalogue

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans

Chapter 22: Electric motors and electromagnetic induction

ECM MOTORS IN FAN POWERED TERMINAL UNITS

Enhancing the Design of Electric Machines through the Interaction of Software Tools. Markus Anders Electric machine sector manager CD-adpaco

Centrifugal Fans and Pumps are sized to meet the maximum

Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters

Features and Benefits. Product Overview. Installation Overview. Sales Strategy Overview FPO

Accurate Air Flow Measurement in Electronics Cooling

AC Motor Speed. n s = synchronous speed (in RPM), f = frequency (in Hz), and p = the number of poles

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

WHITE PAPER. DC Motors Explained. DC Motors Explained: White Paper, Title Page

Application Information Fully Integrated Hall Effect Motor Driver for Brushless DC Vibration Motor Applications

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

1. The diagram below represents magnetic lines of force within a region of space.

Introduction. Motor Types

Heating, Ventilation and Air Conditioning Rebate Catalog Saving energy for a brighter future

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

BRUSHLESS DC MOTORS. BLDC 22mm. BLDC Gearmotor Size 9. nuvodisc 32BF. BLDC Gearmotor Size 5

VAV Laboratory Room Airflow The Lowdown on Turndown

Motors and Generators

Linear DC Motors Magnetic Flux Permanent Bar Magnets

EC medium pressure axial fans. The effi cient system solution.

Lab 14: 3-phase alternator.

Synchronous motor. Type. Non-excited motors

How to Optimize Performance and Minimize Size in High Speed Applications High Performance Brushless DC Motors

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS

Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models

How To Make A High Efficiency Thermostat

The quadrature signals and the index pulse are accessed through five inch square pins located on 0.1 inch centers.

Wound Rotor Induction Motors 4-12 poles, up to 8000 kw, HP

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

13 ELECTRIC MOTORS Basic Relations

PRODUCTS DC MOTORS BLPM MOTORS AC MOTORS CONTROLLERS

Development Of High Efficiency Brushless DC Motor With New Manufacturing Method Of Stator For Compressors

Ampere's Law. Introduction. times the current enclosed in that loop: Ampere's Law states that the line integral of B and dl over a closed path is 0

3. Three phase winding technology

Introduction. Three-phase induction motors are the most common and frequently encountered machines in industry

EVER EFFICIENT. EVER RELIABLE. EVER PROFITABLE.

Documenting Results to Validate Energy Savings Projects: Case Study of Direct Drive Cooling Tower Installations: Before and After

"AC2EC" - Replacement made easy New EC motor design Compact and efficient

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE

Power and Cooling for Ultra-High Density Racks and Blade Servers

Demand Based Static Pressure Reset Control for Laboratories

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

COOLING TECHNOLOGY INSTITUTE

Welcome to this presentation on LED System Design, part of OSRAM Opto Semiconductors LED 101 series.

AC Servo Motors and Servo Rated Gearheads

Fan Applications & System Guide

This slide is hidden. It will not show up during presentation.

Data Center Cooling. The engineer s choice

Power Plant Electrical Distribution Systems

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.

Tips For Selecting DC Motors For Your Mobile Robot

Edmund Li. Where is defined as the mutual inductance between and and has the SI units of Henries (H).

How To Save Energy On A Power Supply

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

Objectives. Capacitors 262 CHAPTER 5 ENERGY

Transcription:

NovaTorque Brushless Permanent Magnet Motor Field Test Report Submitted to: Sacramento Municipal Utility District May 21, 2014 Prepared by: ADM Associates, Inc. 3239 Ramos Circle Sacramento, CA 95827 The information in this report is provided by SMUD as a service to our customers. SMUD does not endorse products or manufacturers. Mention of any particular product or manufacturer in this report should not be construed as an implied endorsement.

TABLE OF CONTENTS 1. Executive Summary...1 2. Introduction...3 3. Methodology...5 4. Results...8 5. Conclusion...11 6. Appendix...12 About the Customer Advanced Technologies Program" SMUD s Customer Advanced Technologies (C.A.T.) program works with customers to encourage the use and evaluation of new or underutilized technologies. The program provides funding for customers in exchange for monitoring rights. Completed demonstration projects include lighting technologies, light emitting diodes (LEDs), indirect/direct evaporative cooling, non-chemical water treatment systems, daylighting and a variety of other technologies. For more program information, please visit: LIST OF FIGURES https://www.smud.org/en/business/save-energy/rebates-incentives-financing/customer-advanced-technologies.htm Sacramento Municipal Utility District i

List of Figures Title Page Figure 1: The NovaTorque PremiumPlus+ Brushless Permanent Magnet Motor and Exploded View... 4 Figure 2: NovaTorque Motor Nameplate Figure 3: Induction Motor Name Plate... 5 Figure 4: Side-by-Side Fans Used for Test, NovaTorque Motor in Background... 6 Figure 5: Motor kw versus VFD Percent Speed for Both Fans... 10 Figure 6: Motor kw versus Airflow Rate for Both Fans... 10 Figure 7: Flow Measurement Area of the Exhaust Fan Air Handler Damper... 16 List of Tables Title Page Table 1: Summary Results... 2 Table 2: Pre and Post Motor Swap Power Averages... 8 Table 3: Weather and Return Air Data... 8 Table 4: Pre and Post Motor Swap VFD and Airflow Rates... 9 Table 5: Normalized Results... 9 Table 6: Air Velocity (ft/min) Measurements: Induction Motor 100% Speed... 12 Table 7: Air Velocity (ft/min) Measurements: Induction Motor 80% Speed... 13 Table 8: Air Velocity (ft/min) Measurements: Induction Motor 60% Speed... 13 Table 9: Air Velocity (ft/min) Measurements: NovaTorque Motor 100% Speed... 13 Table 10: Air Velocity (ft/min) Measurements: NovaTorque Motor 80% Speed... 14 Table 11: Air Velocity (ft/min) Measurements: NovaTorque Motor 60% Speed... 14 Table 12: Air Velocity (ft/min) Measurement Averages... 14 Table 13: Air Flow (cfm) Measurement Averages... 14 Table 14: Air Flow (cfm) Trended from BMS System... 15 Table 15: Percent Differences Between Measured and BMS System Flow Rates... 15 Table 16: Stroboscope Measurements of Motor Speed (RPM)... 16 Sacramento Municipal Utility District ii

1. Executive Summary ADM Associates, Inc., conducted an evaluation of a new high efficiency motor for the Sacramento Municipal Utility District (SMUD). SMUD funded the evaluation through its Customer Advanced Technologies (CAT) program. In this case, the goal was to evaluate the second generation of a brushless permanent magnet motor, conventionally known as an Electronically Commutated Motor (ECM), developed by NovaTorque, Inc. ADM previously performed a bench test study of a NovaTorque 3 horsepower (hp) PremiumPlus+ Motor, while this report presents the methodology and results of a field study of a NovaTorque 5 hp PremiumPlus+ Motor in a variable speed fan application. NovaTorque claims that these new motors save more energy than National Electrical Manufacturers Association (NEMA) Premium Efficiency induction motors, with increased percentage savings in variable-speed and part-load applications. As stated by NovaTorque, the reasons for this energy usage reduction are: 1. Permanent magnets supply the magnetic field in the rotor; energy is not required to create the rotor magnetic field as it is with induction motors. 2. The axial field poles use grain-oriented steel laminations, resulting in low eddy-current energy losses. 3. The motor winding is very compact with no end-turns, resulting in low current induced energy loses. The field study was conducted comparing the NovaTorque motor to a high efficiency induction motor in a side by side field test comparison. The study was organized as follows: two 5 hp motors with variable frequency drives (VFD) served fans operating in parallel in an air handling exhaust application. One of the conventional motors was replaced with a NovaTorque PremiumPlus+ Motor. Power monitoring of each motor VFD combination was conducted in conjunction with the site s Building Energy Management System (BMS) monitoring air flow rates of each fan. The resulting data were normalized to the volume of air flow and used to calculate energy use associated with the two motor systems. After one month of monitoring, the two motors were swapped and monitored for an additional month in order to compensate for any instrumentation accuracy variables operational differences. The NovaTorque motor showed an 8.5 percent reduction in demand (Table 1) when compared directly to the induction motor. The demand normalized to airflow showed a savings of 8.7 percent in average W/cfm. Savings in other applications may vary as the average speed and speed range vary. The estimated annual energy use dropped from 4,104 to 3,754 kwh, an 8.5 percent savings. Airflow measurements were taken, and the BMS airflow monitoring was independently verified. RPM measurements were then taken for comparison with the VFD display readouts; differences between the two readings were negligible. Further discussions of these items are included in the appendix of this report. Sacramento Municipal Utility District 1

Table 1: Summary Results Induction Motor NovaTorque Motor Difference % Reduction Average Demand, kw 1.09 1.00 0.09 8.5% Average airflow rate, cfm 4,355 4,384-30 -0.7% Normalized Demand, W/cfm 0.249 0.227 0.022 8.7% Estimated Annual Energy, kwh 4,104 3,754 350 8.5% As shown by this case study, NovaTorque PremiumPlus+ Motors can save energy and lower demand. The PremiumPlus+ Motors have been tested and verified by NovaTorque to be compatible with selected types of VFDs. Prior to using a NovaTorque motor you should confirm with NovaTorque the compatibility of the VFD that will be used. Sacramento Municipal Utility District 2

2. Introduction 2.1 Background ADM Associates, Inc., conducted an evaluation of a new high efficiency motor for the Sacramento Municipal Utility District (SMUD). SMUD funded the evaluation through its Customer Advanced Technologies (CAT) program. In this case study, the goal was to conduct field testing and evaluate the second generation of a brushless permanent magnet motor (conventionally known as an Electronically Commutated Motor) developed by NovaTorque, Inc. (see Figure 1). The NovaTorque PremiumPlus+ Motor must be paired with a qualified variable frequency drive (VFD) to optimize savings. The NovaTorque PremiumPlus+ motor s performance as an energy efficiency technology was previously evaluated by ADM using laboratory testing, and is currently being analyzed further in this field study. NovaTorque has expanded the range of ECM motors to include 2, 3, 4, 5, 7.5 & 10 hp motors. NovaTorque claims that these new motors save more energy than National Electrical Manufacturers Association (NEMA) Premium Efficiency induction motors, with increased percentage savings in variable-speed and part-load applications. As stated by NovaTorque, the reasons for this energy usage reduction are: 1. Permanent magnets supply the magnetic field in the rotor; energy is not required to create the rotor magnetic field as it is with induction motors. 2. The axial field poles use grain-oriented steel laminations, resulting in low eddy-current energy losses. 3. The motor winding is very compact with no end-turns, resulting in low I²R energy loses. Figure 1 illustrates the motor and its various components, and NovaTorque supplied ADM with the following description of its motor technology: 1 The rotor in the NovaTorque motor design consists of a pair of conical hubs mounted on opposite ends of the motor shaft. The rotor hubs use an interior permanent magnet (IPM) arrangement which provides magnetic flux concentration. An IPM design has both mechanical and adhesive magnet retention, which allows for higher speed motor operation than a surface permanent magnet design. The surface area available for magnetic flux transmission is maximized by giving the motor s stators and rotor hubs matching conical shapes. By making the rotor/stator surface area interface twice with the perpendicular cross-sectional area of the stator field pole, the motor s geometry also concentrates the magnetic flux density. The NovaTorque motor uses an axial flux path which flows straight (parallel to the shaft) through the axially-oriented field poles of the stator. The straight flux path enables the use of grain-oriented steel laminations which significantly lowers eddy-current losses in the steel. The axial orientation of the NovaTorque motor stator field poles allows the use of bobbin-wound coils (which creates a thermal path) as one face of the coils is next 1 The description has been summarized by ADM for this report. Sacramento Municipal Utility District 3

to the external motor case, instead of being inside the lamination stack as is found in an induction motor. The bobbin coil winding has no end-turns, resulting in lowered I²R energy losses. Figure 1: The NovaTorque PremiumPlus+ Brushless Permanent Magnet Motor and Exploded View 2.2 Assessment Objectives The goal of this study was to determine the case specific energy savings associated with the application of a 5 HP NovaTorque ECM motor in place of a standard induction motor in one of SMUD s air handling systems. Savings were evaluated for energy and demand, and were normalized to air volume flow. These findings are presented as a resource that can be used to help inform and shape future energy efficiency programs by understanding efficiency differences between the performances of ECM motors compared to common induction motors. Sacramento Municipal Utility District 4

3. Methodology The energy savings potential of the NovaTorque motor was evaluated using a side by side test of 5 hp air handler motors operated by identical variable frequency drives in a real building application. The test procedure called for four weeks of data collection with the motors in each position. The NovaTorque is a permanent magnet motor (Figure 2), while the comparison motor was an existing premium efficiency induction motor (Figure 2). Figure 2: NovaTorque Motor Nameplate Figure 3: Induction Motor Name Plate The two fans used for this study are located in a SMUD shop building (see Figure 4). These fans run in parallel on the top deck, drawing exhaust air across heat recovery coils into a common chamber and pushing the air into a common duct. Metrics were collected to normalize motor energy use to air flow rates using the Building Energy Management System (BMS). After the first four weeks of data collection, SMUD swapped the positions of the two motors and collected data for another four weeks. The purpose of swapping motor positions was to switch the power and air flow sensors in order to account for any difference in accuracy between the sensor systems or any non-symmetry. Prior to the test the VFD s were replaced by (ABB ACS355) VFDs widely used for control of induction motors and also compatible with NovaTorque motors. Sacramento Municipal Utility District 5

Figure 4: Side-by-Side Fans Used for Test, NovaTorque Motor in Background The following is the list of BMS trend points that were collected at one minute intervals for the analysis: 1. Exhaust Air flow CFM, Fan 1; 2. Exhaust Air flow CFM, Fan 2; 3. Total Exhaust air flow, CFM; 4. Target Exhaust air flow, CFM; 5. Exhaust air temperature in fan chamber; 6. Percent Speed, frequency, or RPM of Fan 1; 7. Percent Speed, frequency, or RPM of Fan 2; 8. Fan power, kw, Fan 1 (reported by VFD); 9. Fan power, kw, Fan 2 (reported by VFD); 10. Drive input voltage, Vac, Fan 1; 11. Drive input voltage, Vac, Fan 2; 12. Drive input current, Amps, Fan 1; and 13. Drive input current, Amps, Fan 2. In addition to the data provided by the BMS, ADM independently monitored and collected power use data. Two WattNode watthour meters (model WNB-3D-480-P) were placed inside the VFD enclosure, one for each fan motor. The WattNode power accuracy rating is ±0.5% at 5% to 100% of full scale. The WattNodes require a current sensor input. High-accuracy split-core current transducers (CTs) were used which have an accuracy of ± 0.5% from 1% to 100% of full scale. The CTs have a 20 amp full scale primary rating. These meters measure three-phase 480 V loads and produce a pulse output that is proportional to the energy the load uses. The pulse output from the WattNode meter was connected to a battery operated Hobo pulse logger (model UX90-001M), and recorded energy use in 1-minute intervals. Sacramento Municipal Utility District 6

Independent air flow measurements were also conducted for the two fans by using a hot wire anemometer to take a matrix of air speed measurements in front of the louvered fan intake. The model used was the TSI VelociCalc Plus with an air speed range from 0 to 9999 feet per minute (ft/min) and an accuracy of ± 3% of reading or ±3 ft/min, depending on whichever is greater; the resolution is 1 ft/min and the instrument has a response time of less than one second. The sensor is on a 40 inch telescoping probe. At the time of the air flow measurement, the SMUD BMS operator set the fans to fixed speed settings for several minutes as air flow measurements were being made. Three fixed fan speeds were used for air flow measurements, 60%, 80%, & 100% speed, which represent the typical range of operation. The airflow results are discussed in the appendix of this report. Temperature and humidity data were also collected in order to identify any relationships between fan operation and weather data, allowing for normalization of monitored savings to a typical year. One time measurements of motor RPM (revolutions per minute) were also taken using a stroboscope. The RPM test results are discussed in the appendix of this report. Sacramento Municipal Utility District 7

4. Results Monitoring occurred during the period from October 30th to February 14th. The motor position was swapped on January 16th, meaning that the monitoring period prior to the motor swap was twice as long as the period after the swap. Issues with trend log consistency suggested that most of the November data would not be used. The post period is the limiting factor when selecting comparable pre and post periods for analysis. Equal weighting for pre motor swap and post motor swap averages was achieved by using an equal number of monitoring days from both periods. The total number of monitoring points varies by day because the system is set up to trend only when the motors are in operation, which roughly follows the work schedule. The pre- and post-motor swap monitoring periods both spanned four weeks. The eight week average motor power draw for the induction motor was 1.09 kw while the NovaTorque average draw was 1.00 kw. The average demand was reduced by 0.09 kw or 8.5 percent. Average demand for the pre- and post- motor swap periods are shown in Table 2. Table 2: Pre and Post Motor Swap Power Averages Induction Motor NovaTorque Motor Difference % Reduction Pre Motor Swap Average, kw 1.02 0.95 0.07 6.8% Post Motor Swap Average, kw 1.16 1.05 0.12 10.0% Average Demand, kw 1.09 1.00 0.09 8.5% The average savings in the two motor positions is an accurate representation of the monitoring period conditions for the two fan motor positions. Next we compared the pre-swap and postswap periods under several conditions in order to demonstrate their similarity to each other. The outside temperature conditions when the fans were running and trend data were available averaged 53 ºF with a range of 32 to 79 ºF as can be seen in Table 3. The average outside temperature during fan operation for the pre-swap period was 51.4 ºF while the post-swap period averaged 54.2 ºF. During the post-swap period, the outside air temperature averaged 2.8 ºF warmer and the return air temperature averaged 2.9 ºF warmer. Table 3: Weather and Return Air Data Pre-Swap Post-Swap Both Periods Average Outside Temperature, ºF 51.4 54.2 52.8 Min. Outside Temperature, ºF 33.0 32.4 32.4 Max. Outside Temperature, ºF 72.4 78.6 78.6 Standard Deviation, ºF 9.8 10.4 10.1 Average Return Air Temp, ºF 54.6 57.5 56.1 Swapping the motors allowed variations in the flow sensors and position symmetry to be averaged out by operating the fan motors for the same amount of time in each position. The BMS is setup so that the VFDs provide equal set speeds for the NovaTorque and the induction Sacramento Municipal Utility District 8

motors. Data comparing the VFD and airflow rate conditions for the pre- and post-motor swap periods are provided in Table 4. The average pre-swap period VFD speed was 68.4 percent while the post-swap period VFD speed was 71.8 percent. The fan speeds were similar across both periods, but averaged 3.4 percent faster during the post-swap period. The airflow rates were also higher for the post-swap period. The airflow rate was used to normalize the motor energy use. The average airflow rate of the NovaTorque driven fan was 0.7% higher than the induction motor driven fan. With the average VFD speed around 70 percent, the amount of motor slip on the induction motor is expected to be less than if the motor is operating at full speed or is more heavily loaded. Table 4: Pre and Post Motor Swap VFD and Airflow Rates Induction Motor NovaTorque Motor Difference % Reduction Pre-Swap airflow rate, cfm 4,344 4,149 195 4.5% Post-Swap airflow rate, cfm 4,365 4,620-255 -5.8% Average airflow rate, cfm 4,355 4,384-30 -0.7% Pre-Swap VFD Speed, % 68.8 68.1 0.7 1.0% Post-Swap VFD Speed, % 72.2 71.5 0.7 1.0% Average VFD Speed, % 70.5 69.8 0.7 1.0% The average power savings during the monitored period was 8.5%, which equates to 0.09 kw. These values were then normalized to the amount of airflow drawn by the fan motors. The normalized results are provided in Table 5 and show that the average normalized savings increased slightly to 8.7 percent. The normalized power per airflow volume was 0.249 W/cfm for the induction motor and 0.227 W/cfm for the NovaTorque motor. The savings are expected to vary, by an unknown amount, during other seasons. The system only runs during the work day, which eliminates a majority of night time and weekend operation. Although savings cannot be reliably annualized without addition seasonal operating data, Table 5 displays a projection as if the conditions are the same throughout the year. This provides a magnitude of the annual energy use and savings. The estimated annual energy use dropped from 4,104 kwh for the induction motor to 3,754 kwh for the NovaTorque motor, an 8.5 percent savings. Table 5: Normalized Results Induction Motor NovaTorque Motor Difference % Reduction Average Demand, kw 1.09 1.00 0.09 8.5% Average airflow rate, cfm 4,355 4,384-30 -0.7% Normalized Demand, W/cfm 0.249 0.227 0.022 8.7% Estimated Annual Energy, kwh 4,104 3,754 350 8.5% Sacramento Municipal Utility District 9

Presentation of the motor fan power curve data for both motors versus VFD percent speed and airflow are provided in Figure 5 and Figure 6 respectively. Eight weeks of pre- and postswapping data are included. 3.0 kw 2.5 2.0 1.5 Induction Motor, kw NovaTorque, kw Power (Induction Motor, kw) Power (NovaTorque, kw) y = 0.00002549x 2.4999 R² = 0.9800 1.0 0.5 y = 0.00001189x 2.657 R² = 0.9819 0.0 0 20 40 60 80 100 VFD % Speed Figure 5: Motor kw versus VFD Percent Speed for Both Fans 3.0 2.5 2.0 Induction Motor, kw NovaTorque, y = 0.0000000191x kw 2.1266874406 R² = 0.9430801508 Power y = (Induction 0.0000000111x Motor, kw) 2.1799298277 R² = 0.9486753664 Power (NovaTorque, kw) kw 1.5 1.0 0.5 0.0 0 1000 2000 3000 4000 5000 6000 7000 CFM Figure 6: Motor kw versus Airflow Rate for Both Fans Sacramento Municipal Utility District 10

5. Conclusion The findings presented in this report indicate that the NovaTorque PremiumPlus+ motor has the potential to save energy in variable speed applications where it supplants a typical NEMA Premium efficiency induction motor. The NovaTorque motor system maintained more efficient operation in a real building, variable speed application than did the NEMA Premium induction motor. When evaluated in an in-situ study, the NovaTorque motor showed 8.5% savings when compared to a Premium Efficiency induction motor, with normalized power demand savings of 8.7%. Sacramento Municipal Utility District 11

6. Appendix Air flow measurements were taken using a TSI VelociCalc Plus flow meter. Initially a 126 measurement point distribution was initiated to calculate the flow profile of the fan. Conducting this test verified that a 24 point distribution would accurately represent the flow profile. Measurements were taken in the 24 point pattern for each fan at 60% flow, 80% flow, and 100% flow. These flow measurements were verified with the systems BMS trending. Velocity measurements were taken in units of feet/minute (ft/min) which were then converted to flow (CFM) by taking the average of the velocity points across the damper and multiplying it by the area of the damper (32.5 inches x 32 inches). Table 6: Air Velocity (ft/min) Measurements: Induction Motor 100% Speed Right Side: Induction Motor 100% Start: 9:36 End 10:18 left side (approx. 1" from the edge) 5 in 10 in middle 20 in 25 in right side (approx. 1" from the edge) 1-line (top) 770 1000 374 600 275 875 920 2-gap 1740 1520 1330 1180 3-line 1260 1050 1080 1100 4-gap 1495 1285 1185 1150 5-line 1290 1030 960 970 6-gap 1420 1180 1060 1260 7-line 1150 940 1150 8-thin gap 1180 935 870 9-bar 1185 885 870 10-thin gap 1220 1050 845 11-line 1080 870 800 12-gap 1130 1010 890 13-line 970 955 830 14-gap 1025 1000 905 15-line 995 775 655 16-gap 995 735 630 17-line 970 600 670 18-gap (bottom) 450 520 750 Sacramento Municipal Utility District 12

Table 7: Air Velocity (ft/min) Measurements: Induction Motor 80% Speed Right Side: Induction Motor 80% Start: 11:28 End 11:35 left side (approx. right side (approx. 1" from the edge) middle 1" from the edge) 1-gap 1160 900 994 2-gap 1020 1040 1010 3-gap 915 915 980 4-bar 770 815 880 5-gap 835 860 830 6-gap 815 650 700 7-gap 600 420 585 8-gap 315 290 520 Table 8: Air Velocity (ft/min) Measurements: Induction Motor 60% Speed Right Side: Induction Motor 60% Start: 11:05 End 11:27 left side (approx. right side (approx. 1" from the edge) middle 1" from the edge) 1-gap 1060 750 445 2-gap 925 715 800 3-gap 760 625 730 4-bar 570 620 600 5-gap 560 610 580 6-gap 482 450 445 7-gap 425 305 250 8-gap 365 175 289 Table 9: Air Velocity (ft/min) Measurements: NovaTorque Motor 100% Speed left side: Nova Torque 100% Start: 10:24 End 11:45 left side (approx. right side (approx. 1" from the edge) middle 1" from the edge) 1-gap 1840 1440 1140 2-gap 1500 1255 1240 3-gap 1325 1140 1120 4-bar 1030 875 830 5-gap 1000 1040 1000 6-gap 1030 955 1000 7-gap 870 750 985 8-gap 945 600 635 Sacramento Municipal Utility District 13

Table 10: Air Velocity (ft/min) Measurements: NovaTorque Motor 80% Speed Left Side: Nova Torque 80% Start: 11:36 End 11:45 left side (approx. 1" from the edge) Middle right side (approx. 1" from the edge) 1-gap 1070 1150 1030 2-gap 985 1020 1080 3-gap 920 880 870 4-bar 770 690 690 5-gap 840 675 800 6-gap 790 630 800 7-gap 595 530 650 8-gap 365 350 375 Table 11: Air Velocity (ft/min) Measurements: NovaTorque Motor 60% Speed Left Side: Nova Torque 60% Start: 10:46 End 11:04 left side (approx. 1" from the edge) middle right side (approx. 1" from the edge) 1-gap 920 825 850 2-gap 900 710 770 3-gap 950 610 675 4-bar 710 500 600 5-gap 760 480 580 6-gap 750 430 503 7-gap 630 340 350 8-gap 200 260 270 Table 12: Air Velocity (ft/min) Measurement Averages Induction NovaTorque 60% 564 607 80% 784 773 100% 1066 1064 The system averages were taken and then multiplied by the damper area to obtain CFM. The results are shown in Table 13. Table 13: Air Flow (cfm) Measurement Averages Induction NovaTorque 60% 3,898 4,195 80% 5,419 5,343 100% 7,368 7,354 Sacramento Municipal Utility District 14

The BMS system flow measurements were trended during the measuring period. The resulting CFM measurements are shown in Table 14. Table 14: Air Flow (cfm) Trended from BMS System Induction NovaTorque 60% 3,756 3,624 80% 5,116 4,886 100% 6,522 6,249 The measurement differences between the one time measurements and the system BMS measurements show a 4% to 18% difference, with all instances showing the one time measurements recording higher flow rates than the BMS recording (Table 15). Table 15: Percent Differences Between Measured and BMS System Flow Rates Induction NovaTorque 60% 104% 116% 80% 106% 109% 100% 113% 118% There are two reasons for these differences. First, there is some variability to the damper area. The measurements were calculated using the length times the width, but there are several damper veins obstructing the flow path and creating a smaller effective area (Figure 7). Additionally, the VelociCalc flow meter has an accuracy of ± 3%. Due to these differences, the BMS measurements are the preferred method of flow metering as they are permanently in place and continually logging airflow data. Sacramento Municipal Utility District 15

Figure 7: Flow Measurement Area of the Exhaust Fan Air Handler Damper Motor Speed measurements were taken in units of RPM and compared to the VFD display readout. Measurements were taken at 50% speed and 100% speed. The goal was to see if any effects from reduced rotational slip of the NovaTorque motor could be picked up by comparing the measured speed with the VFD speed setting. It was hypothesized that when the VFD was set to the 1800 RPM max, the NovaTorque would function at exactly 1800 RPM while the induction motor would show operation at fewer RPMs because of slip. The results (Table 16) showed a scenario similar to the expected, however the difference between the NovaTorque RPM and the Induction Motor RPM shows only a.2% difference at full speed, and even less of a difference at half speed. Table 16: Stroboscope Measurements of Motor Speed (RPM) Pre-swap Post-swap Stroboscope Reading VFD Panel Reading 50% 100% 50% 100% NovaTorque 893 1798 891 1800 Induction 893 1795 891 1800 NovaTorque 893 1798 893 1800 Induction 892 1795 893 1800 Sacramento Municipal Utility District 16