Verifying PowerLogic ION7550 / ION7650 Accuracy

Similar documents
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Digital and Analog I/O

WebMeter Internal Web Server Feature

PowerLogic ION7550 / ION7650

Transmitter Interface Program

Device Support in PowerLogic ION Enterprise 5.6 Service Pack 2

TRANSFORMER LOSS COMPENSATION FOR METERMEN PRESENTED BY: MICHAEL K. BEARDEN

Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples

Polyphase kwh Electricity Meter

ALPHA Meter Installation Information

TIG INVERTER INSTRUCTION MANUAL

VOLTAGE REGULATOR AND PARALLEL OPERATION

PowerLogic Sub Meter Display (SMD and SMDOPN)

PERF10 Rubidium Atomic Clock

FAQ s on Siemens Magmeters

Scan QR Code for more information. SEM 3 - Embedded Micro Metering Module. User Manual. Answers for infrastructure and cities.

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Digi-Motor Installation Guide

User Manual V SDM220MODBUS. Single-Phase Two Module DIN rail Meters

CONTENTS. PAGE Chapter 1 General Information 1. Chapter 2 Setup 4 DP450-VDC 7 DP450-VAC 7 DP450-DCC 7 DP450-F 8 DP450-HACC 9 DP450-HDCC 11 DP450-E 13

Quick Start Guide , Rev DA March Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator

Using the NI 17xx Smart Camera Direct Drive Lighting Controller

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

How to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers.

UPS System Capacity Management Configuration Utility

Configuring security in ION devices using ION Setup

Basic Specifications. Electrical. EPSON Perfection Color EPSON MatrixCCD TM line sensor. device Effective pixels

Modbus and ION Technology

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

User Manual for CH-PFC76810

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

12 Volt 30 Amp Digital Solar Charge Controller

TS1200 Intelligent Lead Free Soldering Station. Operation Manual

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Installation and Operation Back-UPS 1250, 1300, 1500

Manual Ranging MultiMeter

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

Current Monitoring Kit QUICK START GUIDE

Current Monitoring Kit

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision [Version 2.2]

Energy Management Energy Meter Type EM23 DIN

i ChatterBox! Motorcycle Security

Lenovo IdeaCentre Q180 Series

Ameritron ATP-102 Tuning Pulser II

NC-12 Modbus Application

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

Series 6000 Torque measured metal bellow coupling

CM500 High Speed Cable Modem User Manual

Power Meter Series 700

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

Square D Clipsal Two-Channel DIN-Rail DALI Gateway

INSTALLATION & SERVICE MANUAL. Display Panel

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering

Electrical Safety Tester Verification

SYSTEM 4C. C R H Electronics Design

Keysight N4877A Clock Data Recovery and Demultiplexer 1:2

SX460. Generator Automatic Voltage Regulator Operation Manual

Application Technique. Safety Function: Magnetic Door Switch Monitoring

AIR QUALITY SURVEILLANCE BRANCH ACCEPTANCE TEST PROCEDURE (ATP) FOR. Teledyne Advanced Pollution Instruments Model 400 E Ozone Analyzer AQSB ATP 002

By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document

Digital I/O: OUTPUT: Basic, Count, Count+, Smart+

AutoRanging Digital MultiMeter

LOXONE 12 Channel Amplifier

PowerShield SNMP Adaptor

G-100/200 Operation & Installation

A project to optimise quality and energy efficiency must include metering

ADM1TE 5/30A DIN rail single phase two wire energy meter

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011

SA-9600 Surface Area Software Manual

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

PowerLogic ION7550/ION7650 Power and energy meters User guide

Fundamentals of Power

FIRERAY 2000 Installation Guide

Controller Automation, Model II+

Application Technique. Safety Function: Door Monitoring

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

PRO370D 65A Mbus MID DIN rail three phase four wire energy meter. User manual Version 1.03

Lab E1: Introduction to Circuits

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

Sierra S-Series Smart Interface Software User Manual

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

Research RF Sputtering Packages

3500/62 Process Variable Monitor

Allen-Bradley/Rockwell

Introduction. Page 2 / 9

Energy Management Power Analyzer Type WM14-96 Basic Version

CruzPro VAF110. AC Volts, Amps, Frequency, kw Monitor

Safety Precautions WARNINGS

TC-9102 Series Surface Mount Temperature Controllers

CX Zoner Installation & User Guide

Series /16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB.

Transcription:

70072-0190-00 TECHNICAL 03/2009 Verifying PowerLogic ION7550 / ION7650 Accuracy All PowerLogic ION7550 / ION7650 meters are tested and verified at the factory according to IEC (International Electrotechnical Commission) and ANSI (American National Standards Institute) standards; however, before a new revenue meter is installed, it is important to perform a final accuracy verification. ION meters are digital and do not require calibration, only verification of their accuracy. This technical note outlines a procedure for verifying the accuracy of ION7550 / ION7650 meters. In This Document Introduction................................................ 2 Accuracy Standards and Current Ranges................................. 2 Testing Overview...................................................... 3 Test Procedure.............................................. 5 Connecting the Test Harness............................................ 7 Connecting the Control Equipment...................................... 8 Option A: Using the Front Panel Pulser LED........................... 8 Option B: Using the Digital Outputs.................................. 9 Typical Sources of Test Errors.......................................... 10 ION, ION Enterprise, Modbus, Modicon, Power Measurement, PowerLogic, Schneider Electric, Square D, and WebMeter are either trademarks or registered trademarks of Schneider Electric in France, the USA and other countries. All other trademarks are property of their respective owners. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 2009 Schneider Electric. All rights reserved. www.global.powerlogic.com Using Test Mode............................................ 11 Switching to Test mode............................................ 11 Configuring Energy Measurements..................................... 12 Changing the Energy Measurement................................. 12 Changing the Pulse Weight........................................ 13 Test Points........................................................... 14 Additional Information ION7550 / ION7650 Installation Instructions ION7550 / ION7650 User Guide ION Setup Online Help or User Guide ION Reference

Introduction Verifying ION7550/ION7650 Accuracy Introduction The revenue accurate ION7550 / ION7650 meter is digital and therefore needs no servicing. It is tested for accuracy at the factory and remains accurate for the life of the meter. In contrast, electro mechanical meters need mechanical adjustment before installation and periodic calibration thereafter. Calibration testing is unnecessary for digital meters. Digital meters require accuracy testing, or verification, to ensure the meter meets required accuracy specifications. If you know your meter is within required accuracy specifications before installation, errors observed in the field could be attributed to incorrect connections or instrument transformer ratio settings. Accuracy Standards and Current Ranges The meter conforms to the following accuracy standards, depending on the meter s current input order option: Current Input Order Option Standard Accuracy Range Starting Current C E IEC 62053-22 5A 0.2S (formerly IEC 60687 5A 0.2S) ANSI C12.20 current class 20 accuracy class 0.2 IEC 62053-22 1A 0.2S (formerly IEC 60687 1A 0.2S) IEC 62053-22 5A 0.2S (formerly IEC 60687 5A 0.2S) ANSI C12.20 0.2 accuracy specification 50 ma to 20 A 5 ma 150 ma to 20 A 5 ma 10 ma to 10 A 1 ma 50 ma to 10 A 1 ma 15 ma to 10 A 1 ma Current input order options F and G are excluded from this technical note. Page 2 2009 Schneider Electric. All rights reserved.

Verifying ION7550/ION7650 Accuracy Testing Overview Testing Overview The most common method for testing meters is to inject voltage and current from a stable power source and compare the meter energy readings with readings from a reference energy meter or energy standard. In general, it is recommended that a meter s accuracy be verified using a reference meter or an energy standard, rather than only the source of the test signal. Although meter shops use different methods for testing revenue meters, most test equipment requirements are similar. Test harness A test harness is essential for non socket meters. Ensure that the test harness for the meter is wired properly. The current and voltage transformers must be accurately rated and must perform within specifications to provide accurate results. Power source It is important to have a steady power source. Power that energizes the meter must be reliable and must provide: the rated voltage of the meter, unity power factor (1.0) and lagging power factor of 0.0 (for VARh testing) or 0.5. Test loads There are three methods of current loading: customer s load (a meter in service), resistance load (characteristics similar to a lighting load), and phantom loading (a test board). Your test load device or other loading circuit must be set within the current capacity ranges for the meter. The procedure outlined in this document describes verification using a phantom load or test board. The ION7550/ION7650 will maintain its accuracy during signal source variations, but its energy pulsing output needs a stable test signal to produce accurate test pulses. The meter energy pulsing mechanism needs approximately three to four seconds to stabilize after every source adjustment; the meter measurements are accurate during the signal source transitions, but the pulse output should be allowed to stabilize before the start of every test to ensure accuracy. Control equipment Control equipment is required for counting and timing the pulse outputs (revolutions) from the front panel pulser LED or the digital outputs. Most standard test benches have an arm with red light sensors used for this purpose. The optical sensors on the test bench can be disrupted by strong sources of ambient light (such as camera flashes, fluorescent tubes, sunlight reflections, floodlights, etc.) and cause test errors. Use a hood if necessary to block out ambient light. Environment The meter should be tested at the same temperature as the testing equipment. The ideal temperature is about 23 o C (73 o F). Ensure the meter is warmed up sufficiently before testing. 2009 Schneider Electric. All rights reserved. Page 3

Testing Overview Verifying ION7550/ION7650 Accuracy A warm up time of 30 minutes is recommended for ION7550/ION7650 meters before energy accuracy verification testing. At the factory, the meters are warmed up to their typical operating temperature before calibration. This pre calibration warm up ensures that ION7550/ION7650 meters will reach their optimal accuracy at operating temperature. Most high precision electronic equipment requires a warm up time before it reaches its specified performance levels. Both ANSI C12.20 and IEC62053 22 energy meter standards allow the manufacturers to specify meter accuracy derating due to ambient temperature changes and self heating. The ION7550/ ION7650 accuracy de rating specifications exceed the requirements of both the ANSI C12.20 and IEC62053 22. Grounding The ION7550/ION7650 meter s safety ground terminal must be connected to a low impedance grounding system in order to avoid electric shock and to ensure that the meterʹs accuracy remains within specifications. The signal source and the reference meter (or energy standard) should also be grounded if recommended by their respective manufacturers. If the test configuration allows, the meter s neutral voltage terminal should be grounded in any test configuration with unbalanced phase voltages. Reference Meter or Energy Standard To ensure accuracy of the ION7550/ION7650 verification test, it is recommended that a reference meter or a reference energy standard, with a specified accuracy of ±0.025% or better, be used. Before the start of testing, the reference meter or energy standard should be warmed up as recommended by its manufacturer. Verify the accuracy and precision of any measurement equipment you use (i.e., voltmeters, ammeters, power factor meters). Page 4 2009 Schneider Electric. All rights reserved.

Verifying ION7550/ION7650 Accuracy Test Procedure Test Procedure The following are guidelines for testing the meter; your meter shop may have other testing methods. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. Meter accuracy verification (testing) must be performed by qualified electrical personnel. Turn off all power supplying the meter under test and the test equipment before working on it. Always use a properly rated voltage sensing device to ensure power is off. Connect the meter s protective ground (earth) terminal to the installation s protective ground (earth) system before applying power. Failure to follow these instructions will result in death or serious injury. 1. Turn off power to the test harness or other standard measuring device to prevent hazardous voltages on meter terminals and connected equipment. Use a properly rated voltage sensing device to confirm power is off. 2. Place the meter into the test harness or other standard measuring device. Ensure all voltages are in parallel with the meter being tested and all currents are in series (see Connecting the Test Harness on page 7). Ensure the meter s protective ground (earth) is connected to the installation s protective ground (earth). 3. Connect the control equipment used for switching the voltage to the test standard device. 4. Connect the control equipment used for counting the standard output pulses using one of the methods listed: align the red light sensor on the standard test bench armature over the front panel pulser LED. OR connect to the meter s digital outputs (see Connecting the Control Equipment on page 8). 5. Before performing the verification test, let the test equipment power up the meter. Apply voltage for at least 30 seconds. This warm up allows the meter s internal circuity to stabilize. 6. Apply the rated current and voltage to the terminals of the meter. 7. Set the meter s volts mode to 4W WYE. 8. Place the meter in test mode, if desired (see Using Test Mode on page 11). This allows the meter to enter the field with no kwh values in the registers. If you are performing field testing, put the meter in test mode to avoid affecting customer billing data. 2009 Schneider Electric. All rights reserved. Page 5

Test Procedure Verifying ION7550/ION7650 Accuracy 9. Perform testing on the test points (see Test Points on page 14). 10. Run each test point for at least 30 seconds to allow the test bench equipment to read an adequate number of pulses. Allow 10 seconds of dwell time between test points. Page 6 2009 Schneider Electric. All rights reserved.

Verifying ION7550/ION7650 Accuracy Connecting the Test Harness Connecting the Test Harness The following is an example using the WECO model 8CA 1 adapter, which provides an easy means of connecting an ION7550 / ION7650 meter to a WECO test machine. 1. Connect the harness wires to the meter s voltage and current inputs: Test Machine Socket Meter Voltage and Current Inputs 2. Plug the adapter into the WECO test machine s socket. 3. Ensure the meter s ground terminal (earth) and the test set ground (earth) are connected. 4. Set the WECO machine to 9S. Non-specified connections can be left floating (not connected). 2009 Schneider Electric. All rights reserved. Page 7

Connecting the Control Equipment Verifying ION7550/ION7650 Accuracy Connecting the Control Equipment You can use the meter s front panel red pulser LED or the digital outputs for control purposes. For TRAN models, you must use the digital outputs. Option A: Using the Front Panel Pulser LED 1. Carefully position the test machine s optical arm over the meter s front panel pulser LED. 2. Set test machine to adjust optics and ensure that the meter s LED pulses are being read. Front Panel Pulser LED Page 8 2009 Schneider Electric. All rights reserved.

Verifying ION7550/ION7650 Accuracy Connecting the Control Equipment Option B: Using the Digital Outputs Connect the meter s digital outputs to the WECO test machine. These captured wire connectors are found on the rear of the meter. See below for details: Vf = 5-30 VDC If = 3-100 ma +12 VDC from WECO Solid State Input From WECO Solid State Input Resistor External RELAY - SPST +12 to 30 VDC from WECO Solid State Input 2009 Schneider Electric. All rights reserved. Page 9

Typical Sources of Test Errors Verifying ION7550/ION7650 Accuracy Typical Sources of Test Errors If excessive errors are observed during verification testing, the test setup should be examined to eliminate typical sources of measurement errors: Loose connections of voltage or current circuits, often caused by worn out contacts or terminals. Inspect terminals of test equipment, cables, test harness and the meter under test. Meter ambient temperature significantly different than 23 C (73 F). See Environment on page 3 for an explanation. Floating (ungrounded) neutral voltage terminal in any configuration with unbalanced phase voltages. Ambient light interference or sensitivity issues with the optical sensor. Unstable power source causing energy pulsing fluctuations. Incorrect test setup: not all phases connected to the reference meter or the energy standard. All phases connected to the meter under test should also be connected to the reference meter/standard. Moisture (condensing humidity), debris or pollution present in the meter under test. Meter not properly grounded to the test set. Ensure the meter ground (earth) and the test set ground (earth) are connected Page 10 2009 Schneider Electric. All rights reserved.

Verifying ION7550/ION7650 Accuracy Using Test Mode Using Test Mode When the meter is in test mode, it does not accumulate billable quantities. The test measurements collected by the meter are sent to different registers so that the billing quantities are not changed. The ITC (Instrument Transformer Compensation) operation should be disabled during the meter energy accuracy verification (Disable PT and CT compensation by setting the Ratio Correction Type and Phase Correction Type setup registers in all ITC modules to None.) Hardware locked meters must be unlocked before they can enter test mode. See the ION7550 / ION7650 Hardware Lockable product option document for more information on locking and unlocking meters. Switching to Test mode Place the meter into test mode using ION Setup. The meter s front panel displays the Test Mode screen when the meter is in test mode. Entering Test Mode using ION Setup 1. Open ION Setup and connect to the meter using Basic Mode. 2. Click on the Setup Assistant and select the Verification folder. Select the Verification tab. 3. Select Test Mode and click Display. If security is enabled, you are prompted for the meter s password. A dialog box informs you the meter is in test mode. 4. Click OK. The Test Mode window is displayed. Test data is grouped on three tabs: Energy: kwh, kvah, kvarh delivered and received data. Rolling Demand: kw Demand, kw Peak Demand delivered and received, and Test Demand settings (number of sub intervals, sub interval length). Click Peak Reset to reset the test mode demand registers. Volts, Amps and Power: real time values, updated once per second. Click Loss Mode to select single phase or three phase loss mode. Click Test Reset on any tab to reset the test mode registers. 5. Click Close. A dialog box informs you the meter has returned to normal mode. All test mode registers are reset when the meter returns to normal mode. 2009 Schneider Electric. All rights reserved. Page 11

Configuring Energy Measurements Verifying ION7550/ION7650 Accuracy Configuring Energy Measurements Use ION Setup to configure the meter s energy measurement test parameters. Changing the Energy Measurement You can test accuracy over either of the meter s two hardware channels (the front panel pulser LED or the DO4 digital output) by configuring the channel to pulse based on one of the following energy measurements: kwh del+rec (default) kvarh del kvarh rec kwh del kwh rec Using ION Setup to configure the pulse source 1. Open ION Setup and connect to the meter in Advanced Mode. 2. Open the Calibration Pulser Modules folder. 3. Double click the Wh Pulser LED module to edit the front panel pulser LED or the Wh Pulser D4 module to edit the DO4 digital output. If security is enabled on the meter, you are prompted for the meter s password. 4. Select the Inputs tab. 5. Select the Source register and click Edit. The ION Input Selection: Source dialog is displayed. 6. Scroll down to Integrator Modules and double click to view all Integrator Module sources. Select your pulse source from the list and click OK. Your Source input must be in kw (not Watts). Page 12 2009 Schneider Electric. All rights reserved.

Verifying ION7550/ION7650 Accuracy Configuring Energy Measurements 7. Click on the Setup Registers tab. Select CAP Int Mode and click Edit. Select the CAP Int Mode setting that corresponds to your energy measurement and click OK. Energy Measurement kwh del+rec, kvarh del+rec kvarh del, kwh del kvarh rec, kwh rec kwh del-rec, kvarh del-rec CAP INT Mode Setup Value Absolute Forward Reverse Net 8. Click Send to save your changes to the meter. Changing the Pulse Weight Use ION Setup to adjust the number of energy units per pulse. Using ION Setup 1. Open ION Setup and connect to your meter in Advanced Mode. 2. Open the Calibration Pulser Modules folder. 3. Double click the Wh Pulser LED module to edit the front panel pulser LED or the Wh Pulser D4 module to edit the DO4 digital output. If security is enabled on the meter, you are prompted for a password. 4. Select the Setup Registers tab. 5. Select the W Kt register and click Edit. 6. The Enter W Kt dialog box is displayed. Enter the desired pulse weight in Wh/pulse. The pulse rate must be less than 10 Hz for the meter s LED or digital output to operate accurately. 7. Click OK and then Send to save your changes to the meter. 2009 Schneider Electric. All rights reserved. Page 13

Test Points Verifying ION7550/ION7650 Accuracy The Kt value entered defines how much energy the module accumulates before a pulse is sent to the hardware channel. The front panel pulser LED and D4 output are factory set to the same pulse rate. The default Kt value is shown on the label located on the top of the meter, and depends on the meter s form factor and current input option. Current Input Option Default Pulser LED rate Default D4 pulse rate 1 A 0.18 Watt-hours per pulse 0.18 Watt-hours per pulse 5 A 1.8 Watt-hours per pulse 1.8 Watt-hours per pulse Test Points Refer to Configuring Energy Measurements on page 12 for instructions on how to select and configure the energy measurement source. Wh test points It is common practice to test these watt hour test points: Watt-hour Test Point Full Load Light Load Lagging Power Factor Specifications 100% of the rated current, test voltage and rated frequency at unity power factor, or one (1). 10% of the rated current, test voltage and rated frequency at unity power factor, or one (1). 100% of the rated current, test voltage and rated frequency at 0.50 lagging power factor (current lagging voltage by 60 o phase angle). VARh points It is common practice to test these VAR hour test points: VAR-hour Test Point Full Load Light Load Lagging Power Factor Specifications 100% of the rated current, test voltage and rated frequency at zero power factor (current lagging voltage by 90 phase angle). 10% of the rated current, test voltage and rated frequency at zero power factor (current lagging voltage by 90 phase angle). 100% of the rated current, test voltage and rated frequency at 0.87 lagging power factor (current lagging voltage by 30 o phase angle). The rated current is located on the ION7550 / ION7650 serial number label, found on the top of the meter. Page 14 2009 Schneider Electric. All rights reserved.