TRANSFORMER LOSS COMPENSATION FOR METERMEN PRESENTED BY: MICHAEL K. BEARDEN
|
|
|
- Kelly Hart
- 10 years ago
- Views:
Transcription
1 TRANSFORMER LOSS COMPENSATION FOR METERMEN PRESENTED BY: MICHAEL K. BEARDEN
2 WHAT are transformer losses? TRANSFORMER LOSS COMPENSATION THE WHAT, WHEN, WHO, WHERE AND HOW Transformer losses can be viewed as the power consumed (used) by the transformer when performing work. The harder the transformer works, the more power consumed by the transformer and the larger the losses. The transformer losses can be looked at as if the transformer was a variable load connected to the load side of the meter. The load is made up of two parts; the fixed portion, which keeps the transformer alive (no-load losses) and the variable part, which changes with the load (load losses). WHEN are transformer loss calculations performed? Transformer loss calculations are normally performed when the meter is located on the wrong side of the transformer (not at the ownership point or point of delivery). Two of the most common reasons for the meter not to be located at the point of delivery are installation costs and a changing point of delivery or supplier (deregulation). WHO is responsible for the transformer losses? There are two widely accepted practices: 1) the owner of the transformer is responsible for the transformer losses and should pay for the losses. This can be seen in billing rates, which allow customers to receive transformer credits or the energy pricing has been adjusted to compensate for the losses. 2) The supplier of the active power is responsible for the transformer losses. This can be seen at tie points where the power can flow in both directions. This situation is becoming more common with deregulation. WHERE can the losses be calculated? The two most common places for transformer loss calculations to be done are in a computer after the fact or within the meter in real time. Transformer loss calculations are based on voltage and current, not Watt-hours or Var-hours. The after-the-fact calculations method requires the computer not only to have Delivered and Received Watt-hours and Var-hours, but to also have the per-phase voltages and the per-phase currents to accurately calculate the transformer losses. This method would require the system to have up to ten (10) recorder channels for data if the computer calculates the losses after the fact. On the other hand, the PSI Quad 4 meter has all of the per-phase voltage and current values required for the calculation of transformer losses in real time. The meter provides both compensated and uncompensated values at the same time, which allows for easy testing. Property of PSI Rev /28/97
3 HOW, are the losses of a transformer measured? The no-load (iron) losses and the percent exciting current will normally be measured using a voltmeter, ammeter and wattmeter connected per figure 1. The voltage source will be set to the rated voltage and frequency of the transformer (normally the L.V. side), and the H.V. side of the transformer will be open circuited. The no-load (iron) losses will be taken from the wattmeter, and in the case of a three-phase transformer, the algebraic sum of the wattmeter readings will provide the total no-load (iron) losses in watts. The ammeter reading will be used to provide the no-load current, which will be used for the calculation of percent exciting current. The percent exciting current is the applied current expressed as a percent of the full load current. The no-load (iron) loss and percent exciting current tests are normally done on the low voltage side of the transformer because the current readings are larger, and therefore easier to read. Additionally a lower voltage power source will be easier to obtain. The load (copper) losses and the percent impedance can be measured using a voltmeter, ammeter and wattmeter connected per figure 2. The voltage source is normally connected to the H.V. side of the transformer and the L.V. side of the transformer will be shorted (poor shorting links can affect the loss measurement). The voltage will be adjusted until the ammeter reads the full load current rating of the transformer. The load (copper) losses will be taken from the wattmeter, and in the case of a three-phase transformer, the algebraic sum of the wattmeter reading will provide the total load (copper) losses watts loss. The voltmeter readings will be used to provide the impedance voltage, which will be used to calculate the percent impedance. The percent impedance is the applied test voltage expressed as a percent of the normal operating voltage. The load (copper) losses would be the same if they were measured on the low side of the transformer. The high side of the transformer is used because it will require the voltage source to deliver less current. Property of PSI Rev /28/97
4 Note: The above load loss test is normally run on power transformers having low or normal impedance (less than 10%). Because of this, the flux in the core is so small in the short circuit test that the iron losses can be ignored. When testing high impedance power transformers, the no-load losses would be subtracted from the load loss test and the difference would be the load (copper) losses for the transformer. HOW can you calculate transformer losses? ( how the Quad 4 calculates losses) The first requirement will be the transformer data sheet. This sheet will provide you with all of the information required for the calculation of the percent losses within the transformer at different load points. KWH The calculation of no-load (Iron) losses is based on the ratio of the voltages being measured and the rated voltage squared and the results multiplied by the no-load value from the data sheet. The Quad 4 meter has what is referred to as an Iron constant (KWFe). This constant will be multiplied by the voltage squared and the results will equal the KW losses of the transformer due to voltage (No-Load or Iron Losses). The no-load (Iron) losses of a 4160-volt, 3000 KVA, Delta connected transformer with Iron Losses of 9200 watts, Copper Losses of watts, Impedance of 6.25%, exciting current of 1.54% and an actual measured voltage of 4020 volts. The example below shows the no-load (Iron) losses will change only with changes in voltage, not current or power factor. Based on the transformer test sheet, the no-load (Iron) losses of 9200 watts was at rated transformer voltage. Iron Loss calculations at 4160 and 4020 Volts. Example: Calculated 4160 volts (4160/4160)^2 x 9200 = watts Quad volts (4160^2) x 2 x E-7 = KW Number of voltages available within the meter KWHFe constant used by the meter Calculated 4020 volts (4020/4160)^2 x 9200 = watts Quad volts (4020^2) x 2 x E-7 = KW Number of voltages available within the meter KWFe constant used by the meter The calculation of load (Copper) losses are based on the ratio of the current being measured and the rated full load current squared and the results multiplied by load (copper) losses from the data sheet. The Quad 4 meter has what is referred to as a Copper constant (KWCu). This constant will be multiplied by the current squared, and Property of PSI Rev /28/97
5 the results will equal the KW losses of the transformer due to current load (Copper) losses. The examples which follow are based on the following transformer and load data: the load (Copper) losses of a 4160-volt, 3000 KVA, Delta connected transformer with load (Copper) losses of watts, no-load (Iron) losses of 9200 watts, Impedance of 6.25% and 1.54% exciting current. The example below shows the Load (Copper) Losses will change only with changes in current, not voltage or power factor. The first requirement is to calculate the full load transformer current before the Load (Copper) Losses can be calculated. Based on the transformer test sheet, the Load (Copper) Losses are watts at full transformer rated current. The full load line current on the low side of the transformer (4160 volts) is calculated as follows based on the data sheet. 3000Kva x 1000/(4160Volts x 1.732) = Amps. Copper loss calculation at and 200 Amps. Example: Calculated Amps (416.35/416.35)^2 x = watts Quad Amps (416.35^2) x 2 x E-5 = KW Number of currents available within the meter KWHCu constant used by the meter Calculated Amps (200.00/416.35)^2 x = watts Quad Amps (200.00^2) x 2 x E-5 = KW Number of currents available within the meter KWHCu constant used by the meter KVARH The calculation of Vars of Iron Loss is based on the ratio of the voltages being measured and the rated voltage being taken to the fourth power and the results are multiplied by thevars Iron Loss from the data sheet. The Quad 4 meter has what is referred to as an Iron constant (KVFe). This KVFe constant will be multiplied by the voltage to the fourth power and the results will equal the Kvar losses of the transformer due to voltage (Vars of Iron Loss). Property of PSI Rev /28/97
6 The examples which follow are based on the following transformer and load data. The Vars of Iron Loss of a 4160-volt, 3000 KVA, Delta connected transformer with Iron Losses of 9200 watts, Copper Losses of watts, Impedance of 6.25%, exciting current of 1.54% and a actual measured voltage of 4020 volts. The Vars of Iron Losses will change only with changes in voltage, not current or power factor. Based on the transformer test sheet, the Vars of Iron Loss was 45,274 Vars at rated transformer voltage. WHERE did you get 45,274 Vars? Example: Calculation of Vars at rated transformer voltage (4160 Volts). Example: VA = 3000kva x 1000 x.0154 excitation = 46,200 test point) Cos. of Angle = 9200/46200 = , sin of Angle = Vars = 46,200 x = 45,274 vars at 4160 Volts test point) Vars of Iron Losses, 4160 and 4020 Volts. Calculated 4160 Volts (4160/4160)^4 x = Var Quad Volts (4160^4) x 2 x E-14 = KVar Number of voltages available within the meter KVARFe constant used by the meter Calculated 4020 Volts (4020/4160)^4 x = 39,480 Var Quad Volts (4020^4) x 2 x E-14 = KVar Number of voltages available within the meter KVARFe constant used by the meter The calculation of Vars Copper Losses is based on the ratio of the current being measured and the rated full load current squared and the results multiplied by the Vars Copper Losses from the data sheet. The Quad 4 meter has what is referred to as a Copper constant (KVCu). This KVCu constant will be multiplied by the current squared and the results will equal the Vars losses of the transformer due to current (Vars Copper Losses). The examples which follow are based on the following transformer and load data. The Vars Copper Loss of a 4160-volt, 3000 KVA, Delta connected transformer with Copper Losses of 21,720 watts, Iron Losses of 9,200 watts, Impedance of 6.25% and 1.54% exciting current. The Vars copper losses will change only with changes in current, not voltage or power factor. The first requirement is to calculate the full load transformer current before the Vars copper losses can be calculated. Based on the transformer test sheet, the Vars copper loss of 186,237 Vars was at rated full transformer current. WHERE did you get 186,237 Vars? Property of PSI Rev /28/97
7 Example: The full load line current on the low side (metering side) of the transformer (4160 volts). 3000Kva x 1000/(4160Volts x 1.732) = Amps. Example: The calculation of Vars at full rated transformer current ( Amps). VA = 3000kva x 1000 x impedance = 187,500 test point) Cos. of Angle = 21727/ = , sin of Angle = Vars = 187,500 x = 186,237 transformer full load current) Vars of Copper Losses, and 200 Amps. Calculated Amps (416.35/416.35)^2 x 186,237 = 186,237.0 Var Quad Amps (416.35^2) x 2 x 5.371E-4(KVCu) = KVar Number of currents available within the meter Calculated Amps (200/416.35)^2 x 186,237 = 42,974.0 Var Quad Amps (200^2) x 2 x 5.371E-4(KVCu) = KVar Number of currents available within the meter HOW do you enter data into the Quad 4 meter? The Quad 4 meter is programmed using the PSI utility program, Q4COM. The Q4COM program will prompt for the transformer loss data, then calculate the Watts, Iron and Copper Constants and the Vars, Iron and Copper Constants used within the meter and download the constants to the meter. Example of Q4COM download list for transformer loss calculations. Q4COM will check the per-phase power card before calculating the loss constants. Therefore, if you reconfigure the per-phase card after you program TLC, you will need to re-enter the transformer data. The selection affects Delta meters or Wye meters which have or has been wired as a Delta meter and had one of the Delta options (Inscribed Wye, B-Phase Current) turned on. When B-Phase current is selected, the QUAD4 meter will calculate B-Phase and the constants will be adjusted based on the meter providing three current values to the compensation calculation (this will affect the expected series test results, see testing section). The other meter, which will give different losses in the series test set-up, would be the FORM 6A or 36S meters. Loss Calculations... : Transformer and Line Loss (You can select Line Losses Only or With Transformer Losses) Property of PSI Rev /28/97
8 Transformer Connection, Meter Side... : Delta (Select the way the meter sees the transformer) Type of Transformer... : Single 3-Phase Transformer (How is the transformer bank constructed) Delivered Real Power Transformer Loss Sign... : Plus (When you add losses to Delivered they will be subtracted from Received) Connection Resistance, Phase Current... : 0 Ohms (This is the total resistance of the interconnects between transformers in a delta bank) Connection Resistance, Line Current... : 0 Ohms (This is the total series line resistance) Values: Rate Voltage, Meter Side... : 4160 Volts (The Power transformer voltage) Rate KVA... : 3000 KVA (The rated transformer size) Copper Loss... : Watts (Load Losses) Iron Loss... : 9200 Watts (No-load Losses) Exciting Current... : 1.54 % (Percent of rated No-load test) Impedance at operating temp... : 6.25 % (Percent of rated Load Test) CT Primary Current... : 400 Amps (Current Transformer rated size) CT Secondary Current... : 5 Amps (Secondary current at rated primary current) PT Primary Voltage... : 4200 Volts (Primary voltage rating of transformer) PT Secondary Voltage... : 120 Volts (Secondary voltage at rate primary voltage) Use CT * VT Ratio For Line Value Displays... : NO (Select No for secondary readings and Yes for primary or scaled readings) Example of Q4COM download list for transformer loss coefficients. Q4COM will check the per-phase power card before calculating the loss constants. Therefore, if you reconfigure the per-phase card after you program TLC, you will need to re-enter the transformer data. The selection affects Delta meters or Wye meters, which have been wired as a Delta meter and had one of the Delta options (Inscribed Wye, B-Phase Current) turned on. When B-Phase current is selected, the QUAD4 meter will calculate B-Phase and the constants will be adjusted based on the meter providing three current values to the compensation calculation (this well affect the expected series test results, see testing section). The other meter, which will give different losses in the series test set-up, would be the FORM 6A or 36S meters. Transformer Metering Arrangement: 3W Delta, 2 CTs & 2 PTs (True Delta Losses) (This selection wants to know if the percent corrections are referenced to series or three phase values. Remember, losses are based on voltage and current, not power factor or watts. Therefore, Property of PSI Rev /28/97
9 if the losses were watts and the reference was a 3-phase value of 1039 watts, you have a 1.2 % correction. If the reference was a series value of 1200 watts, you have a % correction. Both answers are correct, the losses (12.47 watts) didn t change because they were based on voltage and current, which remained the same, only the value of the reference changed.) Delivered Real Power Transformer Loss Sign... : Plus (When you add losses to Delivered they will be subtracted from Received) Secondary Rate Voltage... : 120 Volts (This should be the meter test voltage or the meter voltage used to calculate the percent losses) Percent Full Load Watts Iron Loss... : % (This value must be based on five (5) Amps and the above voltage.) Percent Full Load Watts Copper Loss... : % (This value must be based on five (5) Amps and the above voltage.) Percent Full Load Vars Iron Loss... : % (This value must be based on five (5) Amps and the above voltage.) Percent Full Load Vars Copper Loss... : % (This value must be based on five (5) Amps and the above voltage.) HOW do you test TLC in the Quad4? The Quad 4 is the easiest meter for testing the accuracy of transformer loss compensation. The main reason behind the ease of testing the Quad 4 meter is that the meter can have both Compensated and Un-compensated values within the meter at the same time. The two most common ways of testing TLC would be; (1) compare instantaneous compensated and un-compensated values, or (2) let the meter calculate the percent accuracy with losses for you ( this is the easiest option). HOW does the meter calculate percent accuracy? The meter can calculate the accuracy by dividing compensated by the uncompensated and multiplying the results by 100. The results are averaged over one minute. WHAT will the tester need to know? The tester will need to know what the expected losses are for each of the test conditions (series or 3-phase testing) and how the meter operates under series and 3-phase conditions. The following three examples will help with the thought process in understanding on how the TLC process works. Find the percent losses of a transformer at a meter test point of 5Amps and 120 volts. The transformer is a 4160-volt, 3000 KVA, Delta connected transformer with load (Copper) losses of watts, Iron Losses of 9200 watts, Impedance of 6.25% and 1.54% exciting current. The meter is connected to the system through 4200/120-volt VTs and 400/5 amp CTs. The example of a delta metering system was chosen because of the effect on series testing which may not be seen in all metering systems and because the perphase card can be configured three (3) different ways when metering delta systems. The configurations of the per-phase card will affect series test results. The other meter, which will give different losses in the series test set-up, would be the FORM 6A or 36S meters. The first suggestion is to select un-compensated watts, compensated watts, per-phase volts and per-phase Amps as display items.. Property of PSI Rev /28/97
10 Circuit Description The losses of the transformer should be calculated for the point at which the test will be run. Using our example, we will test the meter at 120 Volts, 5 Amps and 0.5 Pf, which will be equivalent to 4200 Volts and 400 Amps at the transformer. Testing at a 0.5 Pf will allow you to test the compensation for both Watts and Vars at the same time. The losses at unity and fifty percent power factor will be the same because the current and voltage will be the same for both tests. The percent of losses will be different because the watt load will be different. Example: 1 The first two illustrations are based on the Form 5 meter having no B-phase current available within the meter. Calculated transformer Watts losses. Calculated 4200 Volts (4200/4160)^2 x 9200 = Watts LOAD (Copper) losses Calculated Amps (400.00/416.35)^2 x = Watts Primary Losses = Watts Secondary Losses = /2800 = 10.5 Watts =.0105 Kw Meter Calculation of Watts losses based on the measured voltage and current. Calculated 4200 Volts (4200^2)+(4200^2) x E-4 = Watts LOAD (Copper) losses (3-Phase Test) Calculated loss@ 400 A (400^2)+(400^2) x E- 2= Watts Primary Losses = Watts Secondary Losses = /2800 = 10.5 Watts =.0105 Kw Calculated transformer Vars lose. Calculated 4200 Volts LOAD (Copper) losses Calculated Amps (4200/4160)^4 x = Vars (400.00/416.35)^2 x = Vars Property of PSI Rev /28/97
11 Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR Meter Calculation of Vars losses based on the measured voltage and current. Calculated 4200 Volts (4200^4)+(4200^ 4) x E-11 = Vars LOAD (Copper) losses (3-Phase Test) Calculated 400 A (400^2)+(400^2) x E-1 = Vars Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR The first (1) illustration shows the test results from a meter being 3-phase tested. Calculated Load 5Amps x 120 Volts x x 0.5 Pf =519.6 Watts % TLC = 10.5 Watts / Watts x 100 = 2.02 % Calculated Load 5Amps x 120 Volts x x Pf =899.9 Vars % TLC = Vars / Vars x 100 = 8.68 % Illustration 1 CUSTOMER DISPLAYS UTILITY DISPLAYS PHASES CBA = YNY INST. PHASE A = VLTS INST. DELIVERED = KW INST. PHASE B = VLTS INST. RECEIVED = KW INST. PHASE C = VLTS INST. KW = KW INST. PHASE A = AMPS INST. COMP KW = KW INST. PHASE B = AMPS INST. COMP. DEL. = KW INST. PHASE C = AMPS INST. COMP REC = KW WATTS LOSS CU = KW INST. DEL. Q1 = KVAR WATTS LOSS FE = KW INST. DEL. Q2 = KVAR VARS LOSS CU = KVAR INST. DEL. Q3 = KVAR VARS LOSS FE = KVAR INST. DEL. Q4 = KVAR % KW WITH LOSS = % INST. KVAR = KVAR % KVAR WITH LOSS = % INST.COMP KVAR = KVAR INST.COMP DEL.Q1 = KVAR INST.COMP DEL.Q2 = KVAR INST.COMP DEL.Q3 = KVAR INST.COMP DEL.Q4 = KVAR INST.COMP. Q1+Q2 = KVAR INST.COMP. Q3+Q4 = KVAR Property of PSI Rev /28/97
12 The second (2) illustration shows the test results from a meter being Series tested. The calculated load has changed (in the series test), while the losses have remained the same because the voltage and current are unchanged. Calculated Load 5Amps x 120 Volts x 2 x 0.5Pf = Watts % TLC = 10.5 Watts / Watts x 100 = 1.75 % Calculated Load 5Amps x 120 Volts x Pf = Vars % TLC = Vars / Vars x 100 = 7.52 % Note: The losses are the same in both illustrations 1 and 2. The reason for the difference in % TLC is the actual load on the meter has not remained the same. The reference (load) point (Watts) has changed, while the voltage and current have remained the same for both tests. REMEMBER, losses are based on Voltage and Current, NOT measured Watts. Illustration 2 CUSTOMER DISPLAYS UTILITY DISPLAYS PHASES CBA = YNY INST. PHASE A = VLTS INST. DELIVERED = KW INST. PHASE B = VLTS INST. RECEIVED = KW INST. PHASE C = VLTS INST. KW = KW INST. PHASE A = AMPS INST. COMP KW = KW INST. PHASE B = AMPS INST. COMP. DEL. = KW INST. PHASE C = AMPS INST. COMP REC = KW WATTS LOSS CU = KW INST. DEL. Q1 = KVAR WATTS LOSS FE = KW INST. DEL. Q2 = KVAR VARS LOSS CU = KVAR INST. DEL. Q3 = KVAR VARS LOSS FE = KVAR INST. DEL. Q4 = KVAR % KW WITH LOSS = % INST. KVAR = KVAR % KVAR WITH LOSS = % INST.COMP KVAR = KVAR INST.COMP DEL.Q1 = KVAR INST.COMP DEL.Q2 = KVAR INST.COMP DEL.Q3 = KVAR INST.COMP DEL.Q4 = KVAR INST.COMP. Q1+Q2 = KVAR INST.COMP. Q3+Q4 = KVAR EXAMPLE: 2 Property of PSI Rev /28/97
13 The next two illustrations (3 &4) are based on the form 5 meter having B-phase current turned on. Because this is a vector calculation in the series test set-up, B- phase will be doubled. Calculated transformer Watts Loss. Calculated 4200 Volts (4200/4160)^2 x 9200 = Watts LOAD (Copper) losses Calculated Amps (400.00/416.35)^2 x = Watts Primary Losses = Watts Secondary Losses = /2800 = 10.5 Watts =.0105 Kw Meter Calculation of Watts losses based on the measured voltage and current. Calculated 4200 Volts (4200^2)+(4200^2) x E-4 = Watts LOAD (Copper) losses (3-Phase Test) Calculated 400 A (400^2)+(400^2)+(400^2) x E-2 = Watts Primary Losses = Watts Secondary Losses = /2800 = 10.5 Watts =.0105 Kw Calculated transformer Vars loss. Calculated 4200 Volts (4200/4160)^4 x = Vars LOAD (Copper) losses Calculated Amps (400.00/416.35)^2 x = Vars Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR Meter Calculation of Vars losses based on the measured voltage and current. Calculated 4200 Volts (4200^4)+(4200^4) x E-11 = Vars LOAD (Copper) losses (3-Phase Test) Calculated 400 A (400^2)+(400^2)+(400^2) x E-1 = Vars Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR The third (3) illustration shows the test results from a meter being 3-phase tested with B- phase current turned on. Note: In the 3-phase (normal) operating mode, the results are the same as they were in illustration 1. Property of PSI Rev /28/97
14 Calculated Load 5Amps x 120 Volts x x 0.5 Pf =519.6 Watts % TLC = 10.5 Watts / Watts x 100 = 2.02 % Calculated Load 5Amps x 120 Volts x x Pf =899.9 Vars % TLC = Vars / Vars x 100 = 8.68 % Illustration 3 CUSTOMER DISPLAYS UTILITY DISPLAYS PHASES CBA = YNY INST. PHASE A = VLTS INST. DELIVERED = KW INST. PHASE B = VLTS INST. RECEIVED = KW INST. PHASE C = VLTS INST. KW = KW INST. PHASE A = AMPS INST. COMP KW = KW INST. PHASE B = AMPS INST. COMP. DEL. = KW INST. PHASE C = AMPS INST. COMP REC = KW WATTS LOSS CU = KW INST. DEL. Q1 = KVAR WATTS LOSS FE = KW INST. DEL. Q2 = KVAR VARS LOSS CU = KVAR INST. DEL. Q3 = KVAR VARS LOSS FE = KVAR INST. DEL. Q4 = KVAR % KW WITH LOSS = % INST. KVAR = KVAR % KVAR WITH LOSS = % INST.COMP KVAR = KVAR INST.COMP DEL.Q1 = KVAR INST.COMP DEL.Q2 = KVAR INST.COMP DEL.Q3 = KVAR INST.COMP DEL.Q4 = KVAR INST.COMP. Q1+Q2 = KVAR INST.COMP. Q3+Q4 = KVAR The fourth (4) illustration shows the test results from a meter being Series tested and having B-phase current turned on. The transformer losses measured by the meter will be different because the B-phase current will be doubled. To calculate the % losses in the series test, we will need to re-calculate the losses based on the voltage and current the meter is measuring. Calculated transformer Watts Loss. Calculated 4200 Volts (4200/4160)^2 x 9200 = Watts LOAD (Copper) losses Calculated Amps (400.00/416.35)^2 x = Watts Primary Losses = Watts Secondary Losses = /2800 = 10.5 Watts =.0105 Kw Property of PSI Rev /28/97
15 Meter Calculation of losses based on the measured voltage and current. Calculated 4200 Volts (4200^2)+(4200^ 2) x E-4 = Watts LOAD (Copper) losses Series Test Calculated 400 A (400^2)+(800^2)+(400^2) x E-2= Watts Primary Losses = Watts Secondary Losses = /2800 = Watts = Kw Calculated transformer Vars loss. Calculated 4200 Volts (4200/4160)^4 x = Vars LOAD (Copper) losses Calculated Amps (400.00/416.35)^2 x = Vars Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR Meter Calculation of Vars losses based on the measured voltage and current. Calculated 4200 Volts (4200^4)+(4200^4) x E-11 = Vars LOAD (Copper) losses Series Test Calculated 400 A (400^2)+(800^2)+(400^2) x E-1 = Vars Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR Calculated Load 5Amps x 120 Volts x 2 x 0.5Pf =600.0 Watts % TLC = Watts / 600 Watts x 100 = 2.94 % Calculated Load 5Amps x 120 Volts x 2 x Pf = Vars % TLC = Vars / Vars x 100 = % Illustration 4 CUSTOMER DISPLAYS UTILITY DISPLAYS PHASES CBA = YNY INST. PHASE A = VLTS INST. DELIVERED = KW INST. PHASE B = VLTS INST. RECEIVED = KW INST. PHASE C = VLTS INST. KW = KW INST. PHASE A = AMPS INST. COMP KW = KW INST. PHASE B = AMPS INST. COMP. DEL. = KW INST. PHASE C = AMPS INST. COMP REC = KW WATTS LOSS CU = KW Property of PSI Rev /28/97
16 INST. DEL. Q1 = KVAR WATTS LOSS FE = KW INST. DEL. Q2 = KVAR VARS LOSS CU = KVAR INST. DEL. Q3 = KVAR VARS LOSS FE = KVAR INST. DEL. Q4 = KVAR % KW WITH LOSS = % INST. KVAR = KVAR % KVAR WITH LOSS = % INST.COMP KVAR = KVAR INST.COMP DEL.Q1 = KVAR INST.COMP DEL.Q2 = KVAR INST.COMP DEL.Q3 = KVAR INST.COMP DEL.Q4 = KVAR INST.COMP. Q1+Q2 = KVAR INST.COMP. Q3+Q4 = KVAR Note: The losses are not the same in illustrations 3 and 4. The reason for the difference in losses and % TLC is that the actual load and currents on the meter change from the series and 3-phase set-up. The reference (load) point (Watts) currents have changed, while the voltage remained the same. REMEMBER, losses are based on Voltage and Current, NOT measured Watts. In all three-phase tests (normal operation), the losses and percent correction are the same, and when voltage or current change, the losses change and are correct based on the measured voltages and currents. EXAMPLE: 3 The next two illustrations (5 &6) are based on the form 5 meter having Inscribed Wye turned on. With Inscribed Wye turned on, the meter will now calculate Wye voltages and all three currents. Because this is a vector calculation in the series test set-up, B-phase will be doubled. The fifth (5) illustration shows the test results from a meter being 3-phase tested with Inscribed Wye turned on. Note: In the 3-phase (normal) operating mode, the results are the same as they were in illustration 1 & 3. Calculated transformer Watts Loss. Calculated 4200 Volts (4200/4160)^2 x 9200 = Watts LOAD (Copper) losses Calculated Amps (400.00/416.35)^2 x = Watts Primary Losses = Watts Secondary Losses = /2800 = 10.5 Watts =.0105 Kw Meter Calculation of losses based on the measured voltage and current. Property of PSI Rev /28/97
17 Calculated 4200 V (2425^2)+(2425^2)+(2425^2) x 5.315E-4 = Watts LOAD (Copper) losses 3-Phase Test Calculated 400 A (400^2)+(400^2)+(400^2) x E-2= Watts Primary Losses = Watts Secondary Losses = /2800 = Watts = Kw Calculated transformer Vars loss. Calculated 4200 Volts (4200/4160)^4 x = Vars LOAD (Copper) losses Calculated Amps (400.00/416.35)^2 x = Vars Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR Meter Calculation of Vars losses based on the measured voltage and current. Calculated 4200 V (2425^4)+(2425^4)+(2425^4) x 4.53E-10 = Vars LOAD (Copper) losses (3-Phase Test) Calculated 400 A (400^2)+(400^2)+(400^2) x E-1 = Vars Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR Calculated Load 5Amps x 120 Volts x x 0.5Pf = Watts % TLC = Watts / Watts x 100 = 2.02 % Calculated Load 5Amps x 120 Volts x 1.732x Pf = Vars % TLC = Vars / Vars x 100 = 8.68 % Illustration 5 CUSTOMER DISPLAYS UTILITY DISPLAYS PHASES CBA = YNY INST. PHASE A = VLTS INST. DELIVERED = KW INST. PHASE B = VLTS INST. RECEIVED = KW INST. PHASE C = VLTS INST. KW = KW INST. PHASE A = AMPS INST. COMP KW = KW INST. PHASE B = AMPS INST. COMP. DEL. = KW INST. PHASE C = AMPS INST. COMP REC = KW WATTS LOSS CU = KW INST. DEL. Q1 = KVAR WATTS LOSS FE = KW INST. DEL. Q2 = KVAR VARS LOSS CU = KVAR INST. DEL. Q3 = KVAR VARS LOSS FE = KVAR INST. DEL. Q4 = KVAR % KW WITH LOSS = % Property of PSI Rev /28/97
18 INST. KVAR = KVAR % KVAR WITH LOSS = % INST.COMP KVAR = KVAR INST.COMP DEL.Q1 = KVAR INST.COMP DEL.Q2 = KVAR INST.COMP DEL.Q3 = KVAR INST.COMP DEL.Q4 = KVAR INST.COMP. Q1+Q2 = KVAR INST.COMP. Q3+Q4 = KVAR The sixth (6) illustration shows the test results from a meter being series tested with Inscribed Wye turned on. Note: The voltage and current readings will cause a different amount of losses to be calculated. The answers are correct based on the voltages that have been calculated. Therefore, the results will be correct in normal operation (see illustration 5). Calculated transformer Watts Loss. Calculated 4200 Volts (4200/4160)^2 x 9200 = Watts LOAD (Copper) losses Calculated Amps (400.00/416.35)^2 x = Watts Primary Losses = Watts Secondary Losses = /2800 = 10.5 Watts =.0105 Kw Meter Calculation of losses based on the measured voltage and current. Calculated 4200 V (1406^2)+(2812^2)+(1406^2) x 5.315E-4 = Watts LOAD (Copper) losses (Series Test) Calculated 400 A (400^2)+(800^2)+(400^2) x E-2= Watts Primary Losses = Watts Secondary Losses = /2800 = Watts = Kw Calculated transformer Vars loss. Calculated 4200 Volts (4200/4160)^4 x = Vars LOAD (Copper) losses Calculated Amps (400.00/416.35)^2 x = Vars Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR Meter Calculation of Vars losses based on the measured voltage and current. Property of PSI Rev /28/97
19 Calculated 4200 V (1406^4)+(2812^4)+(1406^4) x 4.53E-10 = Vars LOAD (Copper) losses (3-Phase Test) Calculated 400 A (400^2)+(800^2)+(400^2) x E-1 = Vars Primary Losses = Vars Secondary Losses = /2800 = Vars = KVAR Calculated Load 5Amps x 120 Volts x 2 x 0.5Pf = 600 Watts % TLC = Watts / 600 Watts x 100 = 2.76 % Calculated Load 5Amps x 120 Volts x 2 x Pf = Vars % TLC = Vars / Vars x 100 = % Illustration 6 CUSTOMER DISPLAYS UTILITY DISPLAYS PHASES CBA = YNY INST. PHASE A = VLTS INST. DELIVERED = KW INST. PHASE B = VLTS INST. RECEIVED = KW INST. PHASE C = VLTS INST. KW = KW INST. PHASE A = AMPS INST. COMP KW = KW INST. PHASE B = AMPS INST. COMP. DEL. = KW INST. PHASE C = AMPS INST. COMP REC = KW WATTS LOSS CU = KW INST. DEL. Q1 = KVAR WATTS LOSS FE = KW INST. DEL. Q2 = KVAR VARS LOSS CU = KVAR INST. DEL. Q3 = KVAR VARS LOSS FE = KVAR INST. DEL. Q4 = KVAR % KW WITH LOSS = % INST. KVAR = KVAR % KVAR WITH LOSS = % INST.COMP KVAR = KVAR INST.COMP DEL.Q1 = KVAR INST.COMP DEL.Q2 = KVAR INST.COMP DEL.Q3 = KVAR INST.COMP DEL.Q4 = KVAR INST.COMP. Q1+Q2 = KVAR INST.COMP. Q3+Q4 = KVAR HOW does the Quad4 meter arrive at compensated values? The Quad 4 meter uses internal totalizers to add or subtract the calculated losses from the measured kwh or kvarh every second to arrive at the compensated value. The output of the totalizer will have the compensated value, and the uncompensated value remains Property of PSI Rev /28/97
20 available within the meter allowing for the display of compensated, uncompensated, iron losses, copper losses and percent accuracy with losses. COMPENSATED DELIVERED KWH TOTALIZER When, or if, the results of the one-second total are negative, the one second compensated value of this totalizer will be set to zero. The negative compensated value will be transferred to the compensated received kwh totalizer as a positive value, and the output of the received compensated kwh totalizer will cause compensated received values to increment. When, or if, the result of the one second totalizer is positive, the output of the delivered compensated kwh totalizer will cause compensated delivered values to increment. COMPENSATED RECEIVED KWH TOTALIZER When, or if, the result of the one-second total is negative, the one second compensated value of this totalizer will be set to zero. The negative compensated value will be transferred to the compensated delivered kwh totalizer as a positive value and the output of the delivered compensated kwh totalizer will cause compensated delivered values to increment. When, or if the results of the one-second totalizer are positive, the output of the received compensated kwh totalizer will cause compensated received values to increment. COMPENSATED QUADRANT 1 KVARH TOTALIZER When the uncompensated VARS are in Q4, the VFe and VCu (Delivered Power) inputs are not added in the totalizer. When the one-second total is negative, the output value of the one-second totalizer will be set to zero. The negative value will be transferred to either the Q4 totalizer or Q3 totalizer as a positive value. When the compensated power is Delivered, the results goes to Q4 totalizer, if not, to the Q3 totalizer (Received Power). COMPENSATED QUADRANT 2 KVARH TOTALIZER When the uncompensated VARS are in Q3, the VFe and VCu (Received Power) inputs are not added in the totalizer. When the uncompensated VARS are in Q2, the VFe and VCu (Received Power) are subtracted instead of added (i.e. the sign is reversed). When the one-second total is negative, the output value of the one-second totalizer will be set to zero. The negative value will be transferred to either the Q3 totalizer or Q4 totalizer as a positive value. When the compensated power is Delivered, the results goes to Q4 totalizer, if not, to the Q3 totalizer (Received Power). COMPENSATED QUADRANT 3 KVARH TOTALIZER Property of PSI Rev /28/97
21 When the uncompensated VARS are in Q2, the VFe and VCu (Received Power) inputs are not added in the totalizer. When the one-second total is negative, the output value of the one-second totalizer will be set to zero. The negative value will be transferred to either the Q2 totalizer or Q1 totalizer as a positive value. When the compensated power is Delivered, the results goes to Q1 totalizer, if not, to the Q2 totalizer (Received Power). COMPENSATED QUADRANT 4 KVARH TOTALIZER When the uncompensated VARS are in Q1, the VFe and VCu (Delivered Power) inputs are not added in the totalizer. When the uncompensated VARS are in Q4, the VFe and VCu (Received Power) are subtracted instead of added (i.e. the sign is reversed). When the one-second total is negative, the output value of the one-second totalizer will be set to zero. The negative value will be transferred to either the Q1 totalizer or Q2 totalizer as a positive value. When the compensated power is Delivered, the results goes to Q1 totalizer, if not, to the Q2 totalizer (Received Power). COMPENSATED QUADRANT KVARH TOTALIZER When the uncompensated VARS are in Q4, the VFe and VCu (Delivered Power) inputs are subtracted instead of being added (i.e. the sign is reversed) in the totalizer. When the one-second total is negative, the output value of the one-second totalizer will be added to this totalizer or transferred to the Q2 + Q3 totalizer as a positive value. When the compensated power is Delivered, the results will be added in this totalizer, if not, to the Q2 + Q3 totalizer (Received Power). When the one second total is positive and the power is not delivered, the one second value is transferred to the Q2 + Q3 totalizer (Received Power). COMPENSATED QUADRANT KVARH TOTALIZER When the uncompensated VARS are in Q2, the VFe and VCu (Delivered Power) inputs are subtracted instead of being added (i.e. the sign is reversed) in the totalizer. When the one-second total is negative, the output value of the one-second totalizer will be added to this totalizer or transferred to the Q1 + Q4 totalizer as a positive value. When the compensated power is Delivered, the results will be transferred Q1 + Q4 totalizer, if not, the results will be added to this totalizer (Received Power). When the one second total is positive and the power is not delivered, the one second value is transferred to the Q1 + Q4 totalizer (Delivered Power). COMPENSATED QUADRANT KVARH TOTALIZER When the uncompensated VARS are in Q3 or Q4, the VFe and VCu (Delivered Power) and (Received Power) inputs are not add in the totalizer. When the uncompensated Property of PSI Rev /28/97
22 VARS are in Q2, the VFe and VCu (Received Power) will be subtracted instead of being added (i.e. the sign is reversed). (Note: The VFe and VCu (Delivered Power) are both zero when the VARS are in Q2.) If the one second results are negative, the one second value is transferred to the Q3 + Q4 totalizer as a positive value. COMPENSATED QUADRANT KVARH TOTALIZER When the uncompensated VARS are in Q1 or Q2, the VFe and VCu (Delivered Power) and (Received Power) inputs are not added in the totalizer. When the uncompensated VARS are in Q4, the VFe and VCu (Delivered Power) will be subtracted instead of being added (i.e. the sign is reversed). (Note: The VFe and VCu (Received Power) are both zero when the VARS are in Q4.) If the one second results are negative, the one second value is transferred to the Q1 + Q2 totalizer as a positive value. When negative values are transferred to another totalizer as a positive value, they are only done so when the negative value is more negative than two units of the meter Ke value multiplied by the transformer ratio. This is to allow for the quantizing of the meter. Losses can accumulate for one second without a power (or VAR) pulse in that second, but in subsequent second, power pulses can arrive to offset the loss. The losses can yield a short term negative value which should not be shifted to another totalizer. These short-term negative values are remembered. Due to this memory, very, very small values can be time shifted (delayed) but these delayed values will always be less than two units of the meters Ke (compensated for the transformer ratio). If there are VARHs accumulated in the totalizers before there are two (2) units of Ke power Delivered or Received, the VARHs may be put in the wrong totalizer, as the previous power flow is incorrect. This small error would only occur on startup. TOTALIZER SET-UP To get Compensated: totalizer inputs: (Input numbers) (See notes below) Deliv'd PWR + Watts Del + WFEd + WCUd (2,20,21) (2,63,64) Receiv'd PWR + Watts Rec + WFEr + WCUr (1,22,23) (1,65,66) Q1 Vars + Q1 + VFEd + VCUd (6,24,25) (6,67,68) Q2 Vars + Q2 + VFEr + VCUr (4,26,27) (4,69,70) Q3 Vars + Q3 + VFEr + VCUr (3,26,27) Property of PSI Rev /28/97
23 (3,69,70) Q4 Vars + Q4 + VFEd + VCUd (5,24,25) (5,67,68) Q1 + Q4 Vars + Q1 + Q4 + VFEd + VCUd (6,5,24,25) (6,5,67,68) Q2 + Q3 Vars + Q2 + Q3 + VFEr + VCUr (4,3,26,27) (4,3,69,70) Q1 + Q2 Vars + Q1 + Q2 + VFEd + VCUd + VFEr + VCUr (6,4,24,25,26,27) (6,4,67,68,69,70) Q3 + Q4 Vars + Q3 + Q4 + VFEd + VCUd + VFEr + VCUr (3,5,24,25,26,27) (3,5,67,68,69,70) NOTES: 1.THESE ARE THE ONLY VALID TLC TOTALIZERS SUPPORTED BY THE METER. 2.THERE CAN BE ONLY ONE EACH OF THE ABOVE TLC TOTALIZERS DEFINED IN A METER. 3.THE TOP SET OF INPUT NUMBERS FOR METERS WITH 39 METER INPUTS; THE BOTTOM SET OF INPUT NUMBERS FOR METERS WITH 85 METER INPUTS. The following are "normal" totalizer functions and no special action is taken. They can be considered as "NET VARs". They are only listed here for reference. These could have a negative value and thus can not be used as inputs to recorder channels and not be routed to output relays. Q1 - Q4 Vars + Q1 - Q4 + VFEd + VCUd (6,11,24,25) Q3 - Q2 Vars + Q3 - Q2 + VFEr + VCUr (3,10,26,27) THIS IS THE LIST OF TOTALIZERS USED FOR TLC TESTING Firmware Version: 2737 Max Meter Inputs: 85 Max izations: 16 TOTALIZATION CONTROL DEFINITIONS (table10) =========================================================== TOTALIZER: 1 COMPENSATED KVARH QUADRANT ONE Meter Input: 6 ( 3 Kilovar hours ) Meter Input: 67 ( 3 Kilovar hours ) Property of PSI Rev /28/97
24 Meter Input: 68 ( 3 Kilovar hours ) Negate Output = NO TOTALIZER: 2 COMPENSATED KVARH QUADRANT TWO Meter Input: 4 ( 3 Kilovar hours ) Meter Input: 69 ( 3 Kilovar hours ) Meter Input: 70 ( 3 Kilovar hours ) Negate Output = NO TOTALIZER: 3 COMPENSATED KVARH QUADRANT THREE Meter Input: 3 ( 3 Kilovar hours ) Meter Input: 69 ( 3 Kilovar hours ) Meter Input: 70 ( 3 Kilovar hours ) Negate Output = NO TOTALIZER: 4 COMPENSATED KVARH QUADRANT FOUR Meter Input: 5 ( 3 Kilovar hours ) Meter Input: 67 ( 3 Kilovar hours ) Meter Input: 68 ( 3 Kilovar hours ) Negate Output = NO TOTALIZER: 5 COMPENSATED KVARH QUADRANTS ONE + TWO ( DELIVERED ) Meter Input: 4 ( 3 Kilovar hours ) Meter Input: 6 ( 3 Kilovar hours ) Meter Input: 67 ( 3 Kilovar hours ) Meter Input: 68 ( 3 Kilovar hours ) Meter Input: 69 ( 3 Kilovar hours ) Meter Input: 70 ( 3 Kilovar hours ) Property of PSI Rev /28/97
25 Negate Output = NO TOTALIZER: 6 COMPENSATED KVARH QUADRANTS THREE + FOUR WITH NEGATIVE SIGN ( RECEIVED ) Meter Input: 3 ( 3 Kilovar hours ) Meter Input: 5 ( 3 Kilovar hours ) Meter Input: 67 ( 3 Kilovar hours ) Meter Input: 68 ( 3 Kilovar hours ) Meter Input: 69 ( 3 Kilovar hours ) Meter Input: 70 ( 3 Kilovar hours ) Negate Output = YES TOTALIZER: 7 KVARH QUADRANTS ONE + TWO ( DELIVERED ) Meter Input: 4 ( 3 Kilovar hours ) Meter Input: 6 ( 3 Kilovar hours ) Negate Output = NO TOTALIZER: 8 COMPENSATED KWH ( DELIVERED ) Meter Input: 2 ( 1 Kilowatt hours ) Meter Input: 63 ( 1 Kilowatt hours ) Meter Input: 64 ( 1 Kilowatt hours ) Negate Output = NO TOTALIZER: 9 COMPENSATED KWH ( RECEIVED ) WITH NEGATIVE SIGN Meter Input: 1 ( 1 Kilowatt hours ) Meter Input: 65 ( 1 Kilowatt hours ) Meter Input: 66 ( 1 Kilowatt hours ) Absolute Value = YES Negate Output = YES Property of PSI Rev /28/97
26 TOTALIZER: 10 KVARK QUADRANTS THREE + FOUR ( RECEIVED ) Meter Input: 3 ( 3 Kilovar hours ) Meter Input: 5 ( 3 Kilovar hours ) Negate Output = NO TOTALIZER: 11 KWH COPPER LOSS Meter Input: 64 ( 1 Kilowatt hours ) Meter Input: 66 ( 1 Kilowatt hours ) Negate Output = NO TOTALIZER: 12 KWH IRON LOSS Meter Input: 63 ( 1 Kilowatt hours ) Meter Input: 65 ( 1 Kilowatt hours ) Negate Output = NO TOTALIZER: 13 KVARH QUADRANTS ONE,TWO,THREE & FOUR WITH SIGN Meter Input: 4 ( 3 Kilovar hours ) Meter Input: 6 ( 3 Kilovar hours ) Meter Input: 9 ( 3 Kilovar hours ) Meter Input: 11 ( 3 Kilovar hours ) Negate Output = NO TOTALIZER: 14 KWH ( DELIVERED - RECEIVED ) WITH SIGN Meter Input: 2 ( 1 Kilowatt hours ) Meter Input: 7 ( 1 Kilowatt hours ) Property of PSI Rev /28/97
27 Negate Output = NO TOTALIZER: 15 KVARH COPPER LOSS Meter Input: 68 ( 3 Kilovar hours ) Meter Input: 70 ( 3 Kilovar hours ) Negate Output = NO TOTALIZER: 16 KVARH IRON LOSS Meter Input: 67 ( 3 Kilovar hours ) Meter Input: 69 ( 3 Kilovar hours ) Negate Output = NO THIS IS THE LIST OF TRANSFORMATIONS USED FOR TLC TESTING Firmware Version: 2737 Max Meter Inputs: 85 Max Transformations: 16 TRANSFORMATION CONTROL DEFINITIONS (table10) ========================================================== TRANSFORMATION: 1 COMPENSATED KVARH DELIVERED AND RECEIVED WITH SIGN Unit of Measure: 113 sumation xform Source 1: izer #5 ( 3 Kilovar hours ) Source 2: izer #6 ( 3 Kilovar hours ) Transform Interval Length: 5 ( Subint * Num of Subint) Subinterval Length: 5 Number of Subintervals per Demand Interval: 1 Add Transform Interval Length: TRANSFORMATION: 2 COMPENSATED KWH DELIVERED AND RECEIVED WITH SIGN Unit of Measure: 113 sumation xform Source 1: izer #8 ( 1 Kilowatt hours ) Source 2: izer #9 ( 1 Kilowatt hours ) Transform Interval Length: 5 ( Subint * Num of Subint) Subinterval Length: 5 Property of PSI Rev /28/97
28 Number of Subintervals per Demand Interval: 1 Add Transform Interval Length: TRANSFORMATION: 3 USED FOR % KVAR WITH LOSSES Unit of Measure: 97 Percent Ratio [ A/B ] * 100 Source 1: Transform #1 (Compensated KVARH) Source 2: izer #13 (Uncompensated KVARH) Transform Interval Length: 5 ( Subint * Num of Subint) Subinterval Length: 5 Number of Subintervals per Demand Interval: 1 Add Transform Interval Length: TRANSFORMATION: 4 USED FOR % KW WITH LOSSES Unit of Measure: 97 Percent Ratio [ A/B ] * 100 Source 1: Transform #2 (Compensated KWH) Source 2: izer #14 (Uncompensated KWH) Transform Interval Length: 5 ( Subint * Num of Subint) Subinterval Length: 5 Number of Subintervals per Demand Interval: 1 Add Transform Interval Length: 1 Property of PSI Rev /28/97
Chapter 24. Three-Phase Voltage Generation
Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal
Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications
Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications By Michael Bearden Introduction In 1982 Raymond Ray Stevens published a paper Power Flow Direction Definitions for
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)
Lab 4: 3-phase circuits. Objective: to study voltage-current relationships in 3-phase circuits; to learn to make delta and Y connections; to calculate and measure real, apparent, and reactive powers. Equipment:
How To Wire A Three Phase, Single Phase, Wye Transformer
Three-Phase Transformers When more power is needed - three transformers can be tied together. This is called three-phase. Here s a simple way of comparing single-phase to threephase power. Single-Phase
3-Phase AC Calculations Revisited
AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who
UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE. Department of Electrical and Computer Engineering
UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering Experiment No. 10 - Balanced Three-Phase Networks Overview: Three-phase networks can be connected either in a
Power Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4
Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore Lecture - 33 3 phase System 4 Hello everybody. So, in the last class we have been
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only
ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering
TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering Introduction This application note will assist the user to set up 3-phase metering to monitor Watt, VAR and VA power
Definition AC Power Distribution
COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
USE OF A SINGLE ELEMENT WATTMETER OR WATT TRANSDUCER ON A BALANCED THREE-PHASE THREE-WIRE LOAD WILL NOT WORK. HERE'S WHY.
USE OF A SINGLE ELEMENT WATTMETER OR WATT TRANSDUCER ON A BALANCED THREE-PHASE THREE-WIRE LOAD WILL NOT WORK. HERE'S WHY. INTRODUCTION Frequently customers wish to save money by monitoring a three-phase,
FIT TIER 2 Application
FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:
THREE PHASE CIRCUITS
THREE PHASE CIRCUITS A. PREPARATION 1. Three Phase Voltages and Systems 2. The Determination of Phase Sequence 3. Blondel's Theorem and Its Consequences 4. References B. EXPERIMENT 1. Equipment List 2.
Lecture Notes ELE A6
ecture Notes EE A6 Ramadan El-Shatshat Three Phase circuits 9/12/2006 EE A6 Three-phase Circuits 1 Three-phase Circuits 9/12/2006 EE A6 Three-phase Circuits 2 Advantages of Three-phase Circuits Smooth
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
AC Power. by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department
by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department EE 209 Fundamentals of Electrical and Electronics Engineering, Prof. Dr. O. SEVAİOĞLU, Page 1 Voltage Waveform Consider the
Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6
Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of
11. MEASUREMENT OF POWER CONSUMPTION OF THE NONBALANCED THREE-PHASE LOAD
. MEASEMENT OF OE CONSMTION OF THE NONBALANCED THEE-HASE LOAD Task of the measurement. Measure the active power and the reactive power of the nonsymmetrical -phase load in Y-connection. Do not connect
Measurement of Power in single and 3-Phase Circuits. by : N.K.Bhati
Measurement of Power in single and 3-Phase Circuits by : N.K.Bhati A specifically designed programme for Da Afghanistan Breshna Sherkat (DABS) Afghanistan 1 Areas Covered Under this Module 1. Power in
GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits
PHYSCS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits This experiment is designed to investigate the relationship between current and potential in simple series
PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP
PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection
Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1
Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
7. Reactive energy compensation
593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical
How To Understand And Understand The Electrical Power System
DOE-HDBK-1011/4-92 JUNE 1992 DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 4 of 4 U.S. Department of Energy Washington, D.C. 20585 FSC-6910 Distribution Statement A. Approved for public release;
BSNL TTA Question Paper-Instruments and Measurement Specialization 2007
BSNL TTA Question Paper-Instruments and Measurement Specialization 2007 (1) Instrument is a device for determining (a) the magnitude of a quantity (b) the physics of a variable (c) either of the above
EEL303: Power Engineering I - Tutorial 4
1. Determine the voltage at the generating station and the efficiency of the following system (Figure 1): Both transformers have ratio of 2kV/11kV. The resistance on LV side of both Figure 1: transformers
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (See ARSD chapter 20:10:36 for the requirements for a Tier 2, Tier 3, or Tier 4 Interconnection.) Applicant/Interconnection
ECE 431. Experiment #1. Three-Phase ac Measurements. PERFORMED: 26 January 2005 WRITTEN: 28 January 2005. Jason Wells
ECE 41 Experiment #1 Three- ac Measurements PERFORMED: 6 January 005 WRTTEN: 8 January 005 Jason Wells LEADER: Jason Wells RECORDER: Nathaniel Hakes 1 ntroduction The primary objectives of the experiment
JEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual
JEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual Revised on February 15, 2012 Table of Contents I. Introduction... 2 II. Choosing the Proper Transformer... 2 III. Rapid Selector Charts...
Physical Address: City: State: Zip Code:
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (For Small Generator Facilities with Electric Nameplate Capacities of 10 MW and less) Applicant Contact
User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters
SDM220MODBUS Single-Phase Two Module DIN rail Meters Measures kwh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc. Di-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting 36mm
POWERLOGIC Circuit Monitor Series 2000
Class POWERLOGIC Circuit Monitor Series 2000 Features True rms metering Certified ANSI C2.6 revenue accuracy High accuracy 0.2% current and voltage Power quality readings THD, k-factor, crest factor Over
PowerLogic ION7550 / ION7650
70002-0248-06 02/2009 PowerLogic ION7550 / ION7650 Energy and power quality meter User Guide 7 Third-party Protocols This chapter explains how third party protocols Modbus, DNP 3.0 and SNMP are implemented
Polyphase kwh Electricity Meter
Polyphase kwh Electricity Meter Model Type: 5192B USER MANUAL Issue 1.0 E & O E AMPY Automation Ltd. July 2003 doc. ref. CSD 093 Contents 1 Introduction 2 1.1 Purpose 2 2 Definitions 2 2.1 References 2
THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.
THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
Energy Saving systems for Induction motors.
Energy Saving systems for Induction motors. Are they a sham? Do they work? There seems to be a resurgence in interest in the Nola energy saving algorithm for induction motors, with a number of manufacturers
Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993
R Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993 CONTENTS I. How to Use This Guide II. Common Problems for 3-Wire and 4-Wire Systems III.
TRANSFORMER: THREE PHASE
CONTENTS Transformer : Three Phase 1211 C H A P T E R 33 Learning Objectives Three-phase Transformers Three-phase Transformer Connections Star/Star or Y/Y Connection Delta-Delta or Connection Wye/Delta
ACCURACY OF POTENTIALTRANSFORMERS
8 VOLTAGE TRANSFORMERS Two types of voltage transformer are used for protective-relaying purposes, as follows: (1) the "instrument potential transformer," hereafter to be called simply "potential transformer,"
SmartBlock Power and Energy Monitor With Rogowski Coil (di/dt) Support HE579ACM302
MA0961-02 25 ovember 2013 PAGE 1 SmartBlock Power and Energy Monitor With Rogowski oil (di/dt) Support The SmartBlock AM302 is a Power and Energy Monitor designed to interface with Rogowski oil and OT
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
UNDERSTANDING YOUR UTILITY BILL A GUIDE FOR BUSINESSES IN OHIO
UNDERSTANDING YOUR UTILITY BILL A GUIDE FOR BUSINESSES IN OHIO TABLE OF CONTENTS INTRODUCTION Introduction... 3 Basic Billing Concepts... 4 Customer Choice Programs... 4 Gas Consumption and Charges...
Three-phase AC circuits
Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
AC Generators. Basic Generator
AC Generators Basic Generator A basic generator consists of a magnetic field, an armature, slip rings, brushes and a resistive load. The magnetic field is usually an electromagnet. An armature is any number
Applications. diris_826_a_1_gb_cat
Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered
Radial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
Chapter 16. Current Transformer Design. Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.
Chapter 16 Current Transformer Design Table of Contents 1. Introduction 2. Analysis of the Input Current Component 3. Unique to a Current Transformer 4. Current Transformer Circuit Applications 5. Current
AN_6521_035 APRIL 2009
71M6521 Energy Meter IC A Maxim Integrated Products Brand APPLICATION NOTE AN_6521_035 APRIL 2009 This document describes how to use software to compensate the real time clock (RTC) in Teridian meter chips.
Panel Meters and Controllers Modular Panel Meter Type EDM 35
Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming
Power Factor The Basics
Power Factor The Basics OK. I ve heard a lot about this power factor stuff. What exactly is it? We hope to give you an easy explanation of what power factor is, and to answer the following most asked questions:
Series and Parallel Circuits
Series and Parallel Circuits Components in a circuit can be connected in series or parallel. A series arrangement of components is where they are inline with each other, i.e. connected end-to-end. A parallel
Energy Management Energy Meter Type EM23 DIN
Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy
STATEMENT OF CHARGING METHODOLOGY FOR USE OF ELECTRICITY NORTH WEST LIMITED S ELECTRICITY DISTRIBUTION NETWORK
STATEMENT OF CHARGING METHODOLOGY FOR USE OF ELECTRICITY NORTH WEST LIMITED S ELECTRICITY DISTRIBUTION NETWORK This statement is effective from 1 April 2010 This statement is approved by the Gas and Electricity
SolarEdge Export Limitation Guide
SolarEdge Export Limitation Guide Europe and APAC Version 2.0 Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in
Instruction Manual. EPM 6010 Multi-function Power Metering System. Chapter 1: *1601-0215-A1* GE Energy ISO 9001 LISTED
GE Energy EPM 6010 Multi-function Power Metering System Chapter 1: Instruction Manual Software Revision: 1.17 Manual P/N: 1601-0038-A1 Manual Order Code: GEK-113637 Copyright 2012 GE Digital Energy GE
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
Transformer circuit calculations
Transformer circuit calculations This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
SCHUYLER DEPARTMENT OF UTILITIES SCHUYLER, NEBRASKA ELECTRIC RATES
SCHUYLER DEPARTMENT OF UTILITIES SCHUYLER, NEBRASKA ELECTRIC RATES TABLE OF CONTENTS SECTION I SECTION II SECTION III SECTION IV SECTION V SECTION VI SECTION VII SECTION VIII SECTION IX SECTION X SECTION
NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR
INDEX NO. : M-142 TECHNICAL MANUAL FOR NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2000 Certified Company) 212/1, Mansarover Civil
Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E
SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant
Alternating current three-phase circuits
Unit. C HEE-PHE CCU lternating current three-phase circuits Unit. C HEE-PHE CCU COE: hree-phase systems characteristics Generation of three-phase voltages hree-phase loads -Y and Y- transformation nstantaneous
Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49
Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems by Reza Tajali, P.E. Square D Company, Power Systems Engineering Group 295 Tech Park Drive LaVergne, Tennessee 37086
CURRENT TRANSFORMERS INSTALLATION GUIDE
CURRENT TRANSFORMERS INSTALLATION GUIDE Information contained within this document is subject to change without notice and does not represent a commitment on the part of PRI Ltd or its agents. E&OE. Copyright
Current transformer selection guide
The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary
Impedance 50 (75 connectors via adapters)
VECTOR NETWORK ANALYZER PLANAR TR1300/1 DATA SHEET Frequency range: 300 khz to 1.3 GHz Measured parameters: S11, S21 Dynamic range of transmission measurement magnitude: 130 db Measurement time per point:
Chapter 10. AC Inductor Design. Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.
Chapter 10 AC Inductor Design Table of Contents 1. Introduction 2. Requirements 3. Relationship of, A p, to the Inductor Volt-Amp Capability 4. Relationship of, K g, to the Inductor Volt-Amp Capability
(3 )Three Phase Alternating Voltage and Current
EEE 2015 EECTRCS (3) Monophase 1 Three phase Three phase electric power is a common method of alternating current electric power generation, transmission, and distribution. t is a type of polyphase system
Model 8220. POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter
Special product features '''' ENERGY METER ''' MEASURES RPM POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter Model A measurement tool for electrical parameters and distribution network disturbances
Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1
Current Transformers Bonneville Power Administration Steve Laslo For the Hands On Relay School (3-12) Revision 1.1 February 21, 2012 1 Basic Theory: CT as a Voltage Transformer February 21, 2012 2 CT as
UNDERSTANDING YOUR UTILITY BILL A GUIDE FOR BUSINESSES IN INDIANA
UNDERSTANDING YOUR UTILITY BILL A GUIDE FOR BUSINESSES IN INDIANA TABLE OF CONTENTS Introduction... 5 Basic Billing Concepts... 6 Electric Energy and Demand... 6 Electric Consumption and Charges... 7
Southern California Edison Revised Cal. PUC Sheet No. 59134-E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No.
Southern California Edison Revised Cal. PUC Sheet No. 59134-E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No. 58300-E Schedule TOU-8-RBU Sheet 1 APPLICABILITY Applicable to the additional
Metering Devices IQ Analyzer 6400/6600 Series
Metering Devices IQ Analyzer 6400/6600 Series Technical Data Supersedes TD.17.02A.T.E pages 1-8 dated May 2000 Description Page General Description............................................. 2 Applications....................................................
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
Experiment #5, Series and Parallel Circuits, Kirchhoff s Laws
Physics 182 Summer 2013 Experiment #5 1 Experiment #5, Series and Parallel Circuits, Kirchhoff s Laws 1 Purpose Our purpose is to explore and validate Kirchhoff s laws as a way to better understanding
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
Full representation of the real transformer
TRASFORMERS EQVALET CRCT OF TWO-WDG TRASFORMER TR- Dots show the points of higher potential. There are applied following conventions of arrow directions: -for primary circuit -the passive sign convention
DRIVING LOOOONG CABLES
DRIVING LOOOONG CABLES INTRODUCTION Microphone or line level cables may appear to be foolproof compared to loudspeaker cables. However, they are not. In particular you can easily encounter high frequency
Shark 200-S. Installation & Operation Manual Revision 1.02. Electronic Submeter with WIFI Ethernet Capability and Datalogging
Shark 200-S Electronic Submeter with WIFI Ethernet Capability and Datalogging Installation & Operation Manual Revision 1.02 June 5, 2009 Doc #: E149721 V1.02 e Electro Industries/GaugeTech 1800 Shames
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 by Pamela Ackerman Prepared to partially fulfill the requirements for EE401 Department of Electrical and Computer Engineering
Dual AC Power Monitor
User Manual for the HE200ACM500 Dual AC Power Monitor Page 1 of 28 PAGE 2 Page 2 of 28 PAGE 3 PREFACE This manual explains how to use the Dual AC Power Monitor. Copyright (C) 2008 Horner APG, LLC., 59
SDI Multi Sensor Module with Charger Enclosure Station Support
Description The purpose of the is to provide a low power temperature compensated battery charge controller and a general-purpose interface for analog sensors. Sensor and charge controller data are acquired
Dale Pennington, Managing Director, Utiliworks Consulting LLC, New York, USA
Dale Pennington, Managing Director, Utiliworks Consulting LLC, New York, USA Meter Data from Cradle to Grave, do you know where your Data is? Getting Started Create your project team such that all critical
Using Current Transformers with the 78M661x
A Maxim Integrated Products Brand Using Current Transformers with the 78M661x APPLICATION NOTE AN_661x_021 April 2010 Introduction This application note describes using current transformers (CT) with the
Induced voltages and Inductance Faraday s Law
Induced voltages and Inductance Faraday s Law concept #1, 4, 5, 8, 13 Problem # 1, 3, 4, 5, 6, 9, 10, 13, 15, 24, 23, 25, 31, 32a, 34, 37, 41, 43, 51, 61 Last chapter we saw that a current produces a magnetic
The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.
Three Phase Electricity Supplies and Systems The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system. This consists of 3 separate phase conductors along