Absorption Heat Transfer Performance of Ammonia-Water Mixture in 116 Tube Mini- Channel Heat Exchanger

Similar documents
Experimental Evaluation Of The Frost Formation

Experimental Analysis of an Automotive Air Conditioning System With Two-Phase Flow Measurements

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

ME Heat Transfer Laboratory. Experiment No. 7 ANALYSIS OF ENHANCED CONCENTRIC TUBE AND SHELL AND TUBE HEAT EXCHANGERS

Testing methods applicable to refrigeration components and systems

International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No , March-April 2015

Research on the Air Conditioning Water Heater System

An Experimenatl Study on Heat Transfer Behaviors of A Welded - Aluminum Minichannel Heat Exchanger

Waste Heat Recovery through Air Conditioning System

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

AN EXPERIMENTAL STUDY OF EXERGY IN A CORRUGATED PLATE HEAT EXCHANGER

A LAMINAR FLOW ELEMENT WITH A LINEAR PRESSURE DROP VERSUS VOLUMETRIC FLOW ASME Fluids Engineering Division Summer Meeting

Sizing of triple concentric pipe heat exchanger

CASL-U

High Pressure Ammonia Systems New Opportunities

DEVELOPMENT OF HIGH SPEED RESPONSE LAMINAR FLOW METER FOR AIR CONDITIONING

5.2. Vaporizers - Types and Usage

RESULTS OF ICARUS 9 EXPERIMENTS RUN AT IMRA EUROPE

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Theoretical and Experimental Investigation of Heat Transfer Characteristics through a Rectangular Microchannel Heat Sink

16. Heat Pipes in Electronics Cooling (2)

FEDSM Flow Boiling Heat Transfer Enhancement in Subcooled and Saturated Refrigerants in Minichannel Heat Sinks

Heat Transfer Prof. Dr. Ale Kumar Ghosal Department of Chemical Engineering Indian Institute of Technology, Guwahati

8. Evaporators */ A. Introduction

Saeid Rahimi. Effect of Different Parameters on Depressuring Calculation Results. 01-Nov Introduction. Depressuring parameters

Heat and Mass Transfer Calculation of the Intercooler With Spraying Water for Air Compressor

Understanding Plastics Engineering Calculations

Comparison of Heat Transfer between a Helical and Straight Tube Heat Exchanger

Learning Module 4 - Thermal Fluid Analysis Note: LM4 is still in progress. This version contains only 3 tutorials.

Flow distribution and turbulent heat transfer in a hexagonal rod bundle experiment

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications

cmn_lecture.2 CAD OF DOUBLE PIPE HEAT EXCHANGERS

Analysis of Ammonia Water (NH3-H2O) Vapor Absorption Refrigeration System based on First Law of Thermodynamics

UNIT 2 REFRIGERATION CYCLE

The Effect of Mass Flow Rate on the Enhanced Heat Transfer Charactristics in A Corrugated Plate Type Heat Exchanger

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

MATLAB AS A PROTOTYPING TOOL FOR HYDRONIC NETWORKS BALANCING

CFD Simulation of Subcooled Flow Boiling using OpenFOAM

1. A belt pulley is 3 ft. in diameter and rotates at 250 rpm. The belt which is 5 ins. wide makes an angle of contact of 190 over the pulley.

Refrigerant Charge and Ambient Temperature Effects on the Refrigeration Cycle of a Small Capacity Food Freezer

Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems

Comparison of fin-and-tube interlaced and face split evaporators with flow maldistribution

Module 1 : Conduction. Lecture 5 : 1D conduction example problems. 2D conduction

Water hammering in fire fighting installation

Swissmetro travels at high speeds through a tunnel at low pressure. It will therefore undergo friction that can be due to:

Differential Relations for Fluid Flow. Acceleration field of a fluid. The differential equation of mass conservation

HEAT TRANSFER AUGMENTATION THROUGH DIFFERENT PASSIVE INTENSIFIER METHODS

Chapter 3.4: HVAC & Refrigeration System

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

Physical Chemistry Laboratory I CHEM 445 Experiment 6 Vapor Pressure of a Pure Liquid (Revised, 01/09/06)

Characteristics of Evaporators

Experiment 12E LIQUID-VAPOR EQUILIBRIUM OF WATER 1

Correlations for Convective Heat Transfer

Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior

FLOW MEASUREMENT 2001 INTERNATIONAL CONFERENCE DERIVATION OF AN EXPANSIBILITY FACTOR FOR THE V-CONE METER

Performance Test of Solar Assisted Solid Desiccant Dryer

RESPONSE TIME INDEX OF SPRINKLERS

Test Report issued under the responsibility of:

Natural Convection. Buoyancy force

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Mathematical Modelling and Design of an Advanced Once-Through Heat Recovery Steam Generator

Everest. Leaders in Vacuum Booster Technology

2. CHRONOLOGICAL REVIEW ABOUT THE CONVECTIVE HEAT TRANSFER COEFFICIENT

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids

Precision Mass Flow Metering For CVD Applications.

Department of Chemical Engineering, National Institute of Technology, Tiruchirappalli , Tamil Nadu, India

SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS

A software for calculation of optimum conditions for cotton, viscose, polyester and wool based yarn bobbins in a hot-air bobbin dryer

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Experiment 3 Pipe Friction

DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE

Injection molding equipment

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi

Production of R-134a

A MTR FUEL ELEMENT FLOW DISTRIBUTION MEASUREMENT PRELIMINARY RESULTS

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 NUCLEAR MAGNETIC RESONANCE

Experiment # 3: Pipe Flow

TABLE OF CONTENT

Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions

Exergy Analysis of a Water Heat Storage Tank

Laboratory scale electrical resistivity measurements to monitor the heat propagation within porous media for low enthalpy geothermal applications

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

FLUID FLOW Introduction General Description

Battery Thermal Management System Design Modeling

Thermostatic valve Type AVTA

Validation of a vapour compression refrigeration system design model

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

COMPARISON INVESTIGATION ON THE HEAT TRANSFER CHARACTERISTICS FOR SUPERCRITICAL CO 2 FLUID AND CONVENTIONAL REFRIGERANTS ABSTRACT 1.

A TEST RIG FOR TESTING HIGH PRESSURE CENTRIFUGAL COMPRESSORS MODEL STAGES AT HIGH REYNOLDS NUMBER

Design of heat exchangers

BASIC UNDERSTANDING OF FLOW CALCULATIONS AND ESTIMATES MAKES SIZING VALVES SIMPLER

Grant Agreement No SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window

EXPERIMENTAL STUDIES ON PRESSURE DROP IN A SINUSOIDAL PLATE HEAT EXCHANGER: EFFECT OF CORRUGATION ANGLE

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Absorption Heat Transfer Performance of Ammonia-Water Mixture in 116 Tube Mini- Channel Heat Exchanger Dennis Marijn van de Bor TU Delft, Netherlands, The, d.m.vandebor@tudelft.nl Carlos A. Infante Ferreira TU Delft, Netherlands, The, C.A.InfanteFerreira@tudelft.nl Follow this and additional works at: http://docs.lib.purdue.edu/iracc van de Bor, Dennis Marijn and Infante Ferreira, Carlos A., "Absorption Heat Transfer Performance of Ammonia-Water Mixture in 116 Tube Mini-Channel Heat Exchanger" (2014). International Refrigeration and Air Conditioning Conference. Paper 1489. http://docs.lib.purdue.edu/iracc/1489 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2445, Page 1 Absorption Heat Transfer Performance of Ammonia-Water Mixture in 116 Tubes Mini- Channel Heat Exchanger Dennis Marijn VAN DE BOR 1 *, Carlos INFANTE FERREIRA 1 1 Delft University of Technology, Process & Energy Department, Leeghwaterstraat 39, 2628 CB Delft, The Netherlands +31152784894, d.m.vandebor@tudelft.nl * Corresponding Author ABSTRACT It is known that decreasing the channel size in heat exchangers increases its heat and mass transfer performance. Using such heat exchangers offers the opportunity to reduce the size and cost of industrial heat pumps, what should lead to better market acceptance. In the past, many experiments have been done for air/water mixtures (adiabatic) and refrigerants like CO 2, R134a and water (diabatic). A variety of models predicting heat transfer coefficients for these refrigerants are available in literature, but for certain systems they are not in agreement with each other. Currently data for ammonia/water mixtures, a fluid used in absorption and compression-resorption heat pumps is missing. A novel mini channel shell and tube heat exchanger with 116 tubes with an inner diameter of 0.5 mm, an outer diameter of 1.0 mm and a length of 0.655 m has been developed to increase the heat transfer performance in industrial compression-resorption heat pumps working with ammonia-water as refrigerant. In the current research the tube side heat transfer performance is investigated using the ammonia-water mixture, while water is used in the shell side of the heat exchanger. The influence of mass flow rate, heat load and vapor quality on the heat transfer performance and pressure drop are investigated. The heat load was varied between 200 and 1800 W, with the refrigerant mass flux varied between 20 and 75 kg m -2 s -1 with the average vapor quality ranging between 0.2 and 0.6 kg kg -1 and operating pressures between 5 and 13 bar. Overall heat transfer coefficients, based on the outer diameter of the tubes, between 70 and 700 W m -2 s -1 have been obtained. The approach temperature at the absorber inlet, after calibrating the PT-100 elements, ranged between 0.3 and 4 K and the average temperature driving force is determined to be between 8 and 25 K. The measured pressure drop ranges between 0.02 and 0.2 bar. Trends show an increasing pressure drop and heat transfer coefficient with increasing mass flux and vapor quality. The heat transfer coefficient on the shell side appears to be the limiting factor at higher measured mass fluxes. The heat load was limited by the maximum flow of the water pumps on the shell side as well as the maximum available heating power of 3.5 kw. 1. INTRODUCTION In order to reduce the amount of material used in a heat exchanger, and therefore possibly allowing for cost reduction of heat transfer equipment, brazed plate and mini-channel heat exchangers are investigated for pure fluids and mixtures. They are also of interest for sorption equipment (Cerezo et al., 2009, 2010, Taboas et al., 2010, 2012, van de Bor, 2014) In this study the heat transfer performance of a novel mini-channel heat exchanger is investigated when an ammonia-water mixture flows through the tubes of a shell and tube heat exchanger at low flow rates. The results are compared with a slug flow model and empirical correlations for absorption in an annulus obtained from an earlier study (van de Bor, 2014).

2445, Page 2 2. EXPERIMENTAL SET-UP A heat exchanger has been designed to be applied as the absorber of a compression resorption heat pump. It consists of 116 tubes with an internal diameter of 0.5 mm mounted within a shell with internal diameter of 21 mm. The heat exchanger has a vertical orientation and has a length of 0.655 m. The internal heat exchanging area is 0.119 m 2 while the external heat exchanging area is 0.239 m 2. Fractal distributors have been used to proportionally subdivide the main flow through the 116 tubes and guarantee pure countercurrent flow of tube and shell sides. Details of the fractal distributors and shell design can be viewed in Nefs et al. (2014). Figure 1 shows the experimental set-up that has been used to determine the performance of the heat exchanger. It consists of two independent loops each used to create the required operating conditions in the tube side (left) and in the shell side (right) of the heat exchanger which is positioned centrally. Each loop includes a plate heat exchanger to create sub cooled conditions at the inlet of the circulating magnetically driven gear pumps. A coriolis flow meter allows for both measuring the flow and the density of the flow from which the ammonia-water concentration can be derived. A thermostatic bath brings the flow to the desired temperature level. To compensate for temperature losses before the inlet of the test section a thermostatically controlled tracing coil is used in the feed line. Since the experiments are intended to reproduce process operating conditions, the flows operate at temperature levels in the range 100 to 180 C. Figure 1: Schematic of the experimental set-up. The left side shows the ammonia-water absorption loop which corresponds to the tube side of the multi-tube mini-channel heat exchanger. The right side shows the cooling water loop which corresponds to the shell side of the heat exchanger.

2445, Page 3 In the here reported experiments absorption is taking place inside the tubes. The average ammonia concentration in the tube side loop is 35% (mass). In most of the here reported experiments water is heated up by the absorption process. In some experiments the water has been substituted by an ammonia-water flow with a slightly higher concentration. In these cases the ammonia-water desorption process taking place in the shell side represents the desorption of the process fluid. Table 1: Geometrical data of the 116 tubes mini-channel heat exchanger Position Values Units Length heat exchanger 0.655 m Number of tubes 116 Inner diameter of tubes 0.5 mm External diameter of tubes 1.0 mm Inner diameter shell 21 mm External diameter shell 25 mm Hydraulic diameter shell side 1.8 mm Table 1 summarizes the geometrical data of the heat exchanger. Figure 2 shows a cross section of the heat exchanger. The central area of the heat exchanger is filled with a massive rod which is used to fix the tube sheets. The tube arrangement is also visualized. Figure 2: Cross section of the 116 tubes mini-channel heat exchanger. The internal diameter is 0.5 mm; the shell side hydraulic diameter is 1.8 mm. During the experiments the average circulating concentration of ammonia in the solution was maintained constant at 35% mass. The inlet temperature has been maintained constant at both absorption and cooling water sides. The experimental conditions are summarized in Table 2. During the experiments the water was pressurized so that boiling could not occur in the shell side of the heat exchanger. The mass flow has been varied both on shell and tube sides. The absolute pressure was measured on both sides making use of Sitrans P DS III pressure sensors with an accuracy of 0.13 bar. The pressure drop was measured on both sides making use of Sitrans P DS III differential pressure sensors with an accuracy of 5.3 mbar. The in and outlet temperatures were measured with PT-100 sensors. Table 2: Operating conditions Experimental sets Tube side Shell side Set 1: temperature [ C] 140 100 Set 2: temperature [ C] 160 100 3. EXPERIMENTAL RESULTS

2445, Page 4 3.1 Energy balance The test section is insulated to prevent heat losses to the environment. Nevertheless it can be expected that the energy balance on the shell side gives a smaller heat load than the energy balance based on the tube side. The deviation between the heat loads calculated in both sides is an indication of the accuracy of the experiments. Figure 3 shows for 38 experiments how the two heat loads compare. As the figure shows some of the experiments have been discarded. These were the experiments for which the shell side balance indicated a higher heat load, what is not possible. Figure 3: Comparison between the heat load based on tube side and shell sides. Experiments 4, 8, 11 and 12 showed difficulties with the data reduction and therefore are left out of the figure. Figure 4: Tube side heat load as a function of shell side mass flux. The absorber (tube) side mass flow is also given. Since the operating conditions (inlet vapor fraction) varied during the experiments, a trend can not be recognized for the tube side. Notice that, for the conditions of the experiments, the heat load varies from ca. 0.2 kw (1.7 kw/m 2 ) to 1.8 kw (15.1 kw/m 2 ). Higher heat loads were not feasible in the current set-up. Figure 4 shows the heat load as a function of the shell side mass flux with the mass flow in the tube side as a parameter. Due to small variations in temperature and pressure during the different tests it is possible that, against expectations, lower flow rates produces higher heat loads.

2445, Page 5 3.2 Pressure drop Figure 5 shows the experimental pressure drop. It is clear that the pressure drop is quite low on both sides of the heat exchanger but that specifically in the shell side the pressure drop is extremely low. Figure 5: Experimental pressure in both tube side (mass flows have only been varied up to 6 kg/h due to limitations of the experimental set-up) in which absorption of ammonia in ammonia water solution is taking place and shell side in which water is flowing (mass flows are up to 20 kg/h). 3.3 Overall heat transfer coefficient The overall heat transfer coefficient is derived from the experimental data making use of Equation (1). with U S Q o T,exp AT T,exp (1) and Q m ( h h ) (2) T,exp T,exp T,exp, out T,exp, in ( T T )( T, T, P, P ) n T, i, in S, i, out T S T S TT,exp (3) i1 n Figure 6 shows the values of obtained for the different experiments. Finally the heat exchanging area is T T,exp obtained from Equation (4). The resulting overall heat transfer coefficient is given in Figure 7. A N d L (4) o T o, T T

2445, Page 6 Figure 7: Temperature driving force for the different experiments shown as a function of the shell side mass flux. 800 700 600 500 400 300 200 100 0 0 5 10 15 20 25 30 Figure 8: Overall heat transfer coefficient during the absorption experiments with ammonia-water in the tube side of the heat exchanger and water in the shell side. The lines represent the equation proposed by van de Bor (2014) for the average heat flux across the heat exchanger surface. Although both shell and tube side mass fluxes are quite small, the overall heat transfer coefficient can reach up to 0.7 kw m -2 K -1 as presented in Figure 8. Again, small variations in temperature and pressure during the different tests it is possible that, against expectations, lower flow rates produces higher heat loads. This in turn has its effect on the heat transfer coefficient presented in Figure 8.

2445, Page 7 4. DISCUSSION 4.1 Expected temperature profiles Considering the heat transfer performance of single tube experiments (van de Bor, 2014) it can be expected that significantly higher performance should be attained. A model of the processes in the heat exchanger assuming an annular flow in the tubes indicates however that the temperature differences along the heat exchanger length are not constant for the operating conditions of the heat exchanger. This is illustrated in Figure 9 where the temperature profiles in the heat exchanger are indicated. Figure 9: Numerically predicted temperature profiles along the heat exchanger length. The water flow appears to heat up very quickly so that the temperature driving force becomes very small for 50% of the heat exchanger area. The model assumes annular flow so that heat transfer takes place from liquid film to water. In the present simulation the water flow enters with 84 C and leaves with 159.9 C. With a shell side flow of 10.1 kg/m 2 s, the mass flow is 2.78 g/s so that 898 W are exchanged. In the tube side ammonia is being absorbed. The flow is 4 kg/h so that, at 15 bar operating pressure, the temperature would drop from 160 C to 124 C when liquid and vapor would be in equilibrium. The model expects the liquid film to cool down to 110 C while the vapor phase remains at 147 C. At the outlet there is still 12.5% vapor left, explaining why the assumption of equilibrium leads to higher temperatures. In reality the temperature driving force is close to 0 for about 50% of the area of the heat exchanger. The assumption of equilibrium in the absorption side leads to an average temperature driving force of 24.6 K. The model indicates an average temperature driving force between liquid film and water flow of 9.1 K. This indicates that the overall heat transfer coefficient is 2.7 times larger than indicated in Figure 7. 4.2 Expected temperature profiles In van de Bor (2014) an empirical correlation was proposed for the absorption side heat transfer coefficient in minichannel annuli. Adjusting this equation for absorption inside tubes by changing the surface area to the inner tube area results in equation 5. The shell-side heat transfer coefficient has been obtained from Nefs et al. (2014).

Pred. tube side pressure drop / bar 2445, Page 8 abs Q 0.0079 Ai 1.29 (5) Although the empirical correlations proposed by van de Bor (2014) were derived to obtain the absorption side heat transfer coefficient in an annulus at higher velocities, the function derived at low absorption side inlet temperatures (and consequently low heat loads) is capable of predicting the heat transfer coefficient of most of the experiments within the margin of error of the experiments. This is illustrated in Figure 7 in which the correlation derived by van de Bor (2014) has been applied for the tube side experiments. From van de Bor (2014) it appears that significantly higher absorption heat transfer coefficients can also be attained for heat flux above 50 kw m -2 K -1 while in these experiments the heat flux remains below 15 kw m -2 K -1 4.3 Pressure drop The results for the pressure drop have been compared with the gas-liquid pressure drop equation proposed by Zhang et al. (2010). This model over predicts the tube side pressure drop at low measured values, the prediction is better at higher pressure drop values. Similar results were obtained in van de Bor (2014), see Fig. 10. 0.25 0.2 0.15 0.1 0.05 0 0 0.05 0.1 0.15 0.2 0.25 Exp. tube side pressure drop / bar Figure 10: The pressure drop model by Zhang et al. (2010) tends to slightly overpredict the tube side pressure drop. The lines indicate the +25%/0/-25% error band 6. CONCLUSIONS The heat transfer coefficient increases with increasing heat load Tested flow rates are too low to obtain maximum heat transfer performance Pressure drop increases with increasing flow rate and vapor quality The annular flow model predicts larger heat transfer coefficients than obtained from the measurements assuming equilibrium conditions and constant heat flux along the tube Annular flow might not occur at low flow rates, additional resistances might exist that were not modeled or the heat exchanger loading is too low. NOMENCLATURE A area (m 2 )

2445, Page 9 d diameter (m) h enthalpy (J kg -1 ) L length (m) m mass flux (kg s -1 ) n number of control volumes (-) N number of tubes (-) P pressure (Pa) Q heat load (W) T temperature (C) U overall heat transfer coefficient (W m -2 K -1 ) α Heat transfer coefficient (W m -2 K -1 ) Subscript Abs exp i in o out S T absorption experimental inside inlet outside outlet shell side tube side, total REFERENCES Van de Bor, D.M., 2014, Mini-channel heat exchangers for industrial distillation processes. PhD thesis. Delft University of Technology, Delft, the Netherlands. Cerezo, J., Bourouis M., Vallès M., Coronas A., Best R., 2009, Experimental study of an ammonia water bubble absorber using a plate heat exchanger for absorption refrigeration machines, Appl Therm Eng., vol 29, p. 1005-1011. Cerezo, J., Best R., Bourouis M., Coronas, A., 2010, Comparison of numerical and experimental performance criteria of an ammonia water bubble absorber using plate heat exchangers, Int. J. Heat Mass Trans., vol 53, no. 17-18: p. 3379 3386. Nefs, C.W.M., Van de Bor, D.M., Infante Ferreira, C.A., 2014, Laminar single phase flow distribution in a multitube mini-channel exchanger using fractal distribution, Chem. Eng. Process., available online april 8, 2014 Táboas, F., Vallès, M., Bourouis M., Coronas, A., 2010, Flow boiling heat transfer of ammonia/water mixture in a plate heat exchanger, Int. J. Refrig., vol. 33, no. 4: p. 695-705. Táboas, F., Vallès, M., Bourouis M., Coronas, A., 2012, Assessment of boiling heat transfer and pressure drop correlations of ammonia/water mixture in a plate heat exchanger, Int. J. Refrig., vol. 35, no. 3: p. 633-644. Zhang, W., Hibiki, T., Mishima, K., 2010, Correlations of two-phase frictional pressure drop and void fraction in mini-channel, Int. J. Heat Mass Trans., vol. 53, no. 1-3: p. 453 465. ACKNOWLEDGEMENT The authors want to acknowledge Florijn de Graaf, Hilde Koopmans, Pascal Smulders and Stijn ten Pas for their efforts in collecting the experimental data reported in this paper. This is an ISPT (=Institute for Sustainable Process Technology) project.