LN Series LN-VSTAT and LN-PSTAT Sensors

Similar documents
GSM-EXT Cable Assembly Installation Guide

HMI display Installation Guide

AXIS T81B22 DC 30W Midspan

Power Supply Guide Version 1.0 for D-Show

ENCL-MZ800-WAL ENCL-MX800-PAN MNL TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application.

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT

Installation & Operation Manual

ScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system

Power Over Ethernet Adapters POE101

Installer Guide smart connect

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE

T7560A,B,C Digital Wall Module

FortiFone QuickStart Guide for FON-670i and FON-675i

About the HotWire Slot Standalone Shelf

T0118 T2118 T3118. Instruction Manual

MCR1900 Media Converter 19-Slot Chassis

Installation Instructions. Wireless Adapter/Repeater. Introduction Rev C

Antenna Splitter ASA 1. Instruction manual

5-Port Switch 10/100/1000 Mbps Gigabit Ethernet GS105

About the BitStorm 6051 POTS Splitter

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

NFC Communication Tray Model: HHX-IT3-Z

Wireless Alarm System. Panic Button. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

4-Port Switch. 10/100/1000 Mbps Gigabit Ethernet GS104. Installation Guide

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

WARNING CANADIAN D.O.C. WARNING

LIEBERT VNSA Installation Sheet

UniStream CPU-for-Panel

InnoMedia ESBC B. Quick Install Guide. 1

KVM - DVI, USB 2.0, Cat 5 Extender

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

SNQ-60x0-320 Series Data Center Switch. Quick Installation Guide

InnoMedia ESBC B. Quick Install Guide. 1

MGL Avionics CAN bus interface for Trig Avionics TT21/TT22 transponders

FortiFone QuickStart Guide for FON-370i

WIRELESS STATUS MONITOR

Sense Components. Sense monitor. Antenna assembly. External mounting kit Current sensors. Download the Sense app. Go to sense.com/app.

USB Rover port USB m Cat 5 Extender. User Guide

Dialog Telephone Interface Module Installation Sheet

Wireless Alarm System. Wireless Keypad. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location

Wireless Indoor/ Outdoor Thermometer

High PoE Midspans NPD-6001A NPD-9501A. en Installation Manual

FriendlyNet Hub 5-Port or 8-Port Ethernet Hub User s Manual

omega.com ΩOMEGA RS232 Multi-Drop FMA1600-MDB Multi-Drop Box

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

IMMS-CCC. IMMS-CCC Hardwire Central Interface. Installation Instructions

VOIP-500 Series Phone Quick Installation Guide

=============================== WARNING

ADSL Modem Installation Guide. Model # 36R515 Part # Rev. D Revision Date 12/2000. ADSL Modem Installation Guide

5800 Temperature Sensor Cable Assembly

BODi rs BD004 Series Bandwidth-on-Demand Internet with Reliability and Survivability. Quick Start Guide NOTES

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

MIC-BP4 Bi-Phase Converter Card For the MIC400 series camera

HLWLAN b/g/n Transceiver Kit

SolarEdge. RS485 Expansion Kit Installation Guide. Version 1.0

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

User s Manual VTECH Printed in China

Comm5 Wiring Installation

C24-CAMANL Video Server/Encoder

Duct Humidity Transmitter

LED Security Spotlight User Manual

Compaq Presario Desktop Products. Upgrading and Servicing Guide

Jabra BIZ 2400 USB USER MANUAL

FTP-1000 Touchpad/Display. Installation Manual. Stay. Away. Disarm. Quick Exit

Replacing the Gateway M320 Keyboard

LevelOne IFE Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual

HP-1000E v2. User s Manual. Powerline Ethernet Adapter. HP1000E v2 User s Manual

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

LED MOTION ACTIVATED FLOOD LIGHT

Energy Smart Electric Water Heater Controller

Direct AC Wiring Option Installation Guide

Replacing the Gateway M675 Keyboard

QLINK User Manual Stereo Audio Transmitter

AI120 AIswitch Series 120 Chassis

Table of Contents. 1 - Specifications Installation Wiring User controls...7

PUSH CV. Vi säljer och konsulterar Ledbelysning. Utebelysning Innebelysning Led-strip RGB Drivdon. SÄLJKONTOR Torstensviksvägen Frillesås

Installation Guide. Wyse VX0L and VX0LE Thin Clients 1-GB RAM Upgrade Option Kit. Issue: PN: L Rev. A

UPGRADING AND SERVICING GUIDE

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

TRANSFORMER HD-HAMPTON HAMPTONBAY.COM

RC8021 Indoor Camera Installation Guide

Technical Support. Support Information

MNL-10Rxx Series MNL-15Rxx Series MNL-20Rxx Series

EPSON USB/Parallel Adapter User s Guide

Fire Fighter Phone System Installation Instructions

PrintPAD CN3/4/3e/4e. User Guide

PSACH v.1.0 PSACH 24VAC/6A/1x6A HERMETIC AC power supply for CCTV

HP UPS R1500 Generation 3

16-port Gigabit Switch 10/100/1000 Mbps GS116. Installation Guide

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

OC810 Outdoor Camera Setup Guide

DS A 07/99 MN MI I/A SERIES MICRONET INTERFACE APPLICATION SPECIFICATION

BLACK BOX. T1/E1 Link Extenders OCTOBER 2007 MT195A-T1 MT196A-E1

ANT1750F Multi-Directional Slim Digital Antenna / Antena multidireccional plana para interiores / Antenne numérique mince multidirectionnelle

Wireless Optical Mouse

Wireless Base Station Single and Multiple Headsets

Pad. Quick Start Guide

PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V

Transcription:

LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions LN-VSTAT-1, LN-PSTAT-1 Code No. LIT-12011302 Issued April 24, 2014 Supersedes November 9, 2007 Applications The LN Series LN-VSTAT and LN-PSTAT sensors are specifically designed to connect to the SMRT ports of the Johnson Controls LN Series controllers. The LN-VSTAT-1 works with the LN-VAVFLFS-1 and LN-VVTLFS-1 controllers. The LN PSTAT-1 works with the LN-PFCU-1 and LN-PFCUA-1 controllers. The SMRT ports supply power and serial communications to the LN-VSTAT and LN-PSTAT sensors. The device provides precision local temperature sensing and it allows occupants to adjust the local setpoint and view the occupancy status, local space temperature, and outside air temperature. North American Emissions Compliance United States Compliance Statement (Part 15.19) This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation. Warning (Part 15.21) Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment. To comply with FCC RF exposure requirements for mobile transmitting devices, this transmitter should only be used or installed at locations where there is at least 20cm separation distance between the antenna and all persons. Allow for proper clearance of device casing and wiring terminals for easy access, hardware configuration, and maintenance. The sensor is designed to operate under the following conditions: Ambient temperature between 32º to 158ºF (Oº to 70ºC) Relative humidity from 0% to 95%, non-condensing Ensure proper ventilation of devices and avoid areas where corroding, deteriorating, or explosive vapors, fumes, or gasses may be present. IMPORTANT: Work in a static-free area. Discharge static electricity by touching a known, securely grounded object. Do not handle the controller without proper protection against static discharge. Use a wrist strap when handling the controller. Secure the wrist strap clamp to earth ground. Canada Industry Canada Statement This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Le terme «IC» précédant le numéro de d'accréditation/ inscription signifie simplement que le produit est conforme aux spécifications techniques d'industry Canada. Installation For proper installation and subsequent operation of the LN-VSTAT and LN-PSTAT sensors, follow these recommendations: 1

Dimensions Figure 1: LN-VAVLF, LN-VAVCF, and LN-VVTLF Controller Dimensions Mounting Location Considerations The LN-VAV/VVT controllers are designed for easy installation. However, certain conditions apply when choosing a location for the device: The LN-VSTAT and LN-PSTAT sensors should not be installed on an outside wall Install the sensor away from any heat source Install the sensor away from discharge air grills Install the sensor away from areas where it can be affected by the sun Install the sensor in an area that provides proper device ventilation. Ensure nothing restrains air circulation to the sensor. Note: The LN-VSTAT and LN-PSTAT sensors are not designed for outdoor use. 2

Installation 1. Unscrew the security screw on the bottom of the casing (Figure 2). 11. Flip the printed circuit board back into place. 12..Flip down the front cover verify it clips tightly into place. 13. Install the security screw (Figure 3). FIG:mntng_bs Figure 2: Mounting the LN-VSTAT and LN-PSTAT sensors 2. Open the cover by pulling the bottom side of the casing outwards. Flip printed circuit board to access mounting hole. 3. Pull cables 6 in. out of the wall and insert them in the central hole of the base. 4. Align the base and mark the location of the two mounting holes on the wall. Ensure the correct side of the base is facing upwards. 5. Remove the device and drill holes, if necessary. 6. Install anchors into the wall, if necessary. 7. Ensure the mounting surface is flat and clean. 8. Insert screws in mounting holes of the base. Do not overtighten the screws. 9. Strip each wire 1/4 in. 10. Gently push excess wiring back into the wall. Figure 3: LN-VSTAT and LN-PSTAT Sensors Security Screw 3

Wiring IMPORTANT: Make all wiring connections in accordance with the National Electrical Code and all local regulations. Use Copper conductors only. Do not exceed the control s electrical rating. The LN-VSTAT and LN-PSTAT sensors draw power and communicate with the associated controller over the SMRT wiring using a serial communication protocol. Figure 4 shows the terminal wiring details.)! CAUTION: Risk of Electric Shock. Disconnect power supply before making electrical connections to avoid shock. MISE EN GARDE : Risque de décharge électrique. Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique. SMRT+ SMRT- LON (Optional) LON (Optional) 1/8" Com. Jack 1 2 3 4 Figure 4: LN-VSTAT and LN-PSTAT Sensors Terminal Wiring Details Wiring the LN-VSTAT and LN-PSTAT Sensors to a Controller The LN-VSTAT and LN-PSTAT sensors use a serial communication protocol and are designed to connect to the serial inputs labelled SMRT+ and SMRT- on the LN-VAVLF and LN-VVTLF controller. Note: The LN-VAVCF controller does not support the LN-VSTAT and LN-PSTAT sensors. To wire a wall mounted LN-VAV/VVT controller: 1. Remove the faceplate. 2. Use a screwdriver to press down the tabs located on the bottom of the sensor to remove the cover. 4

3. Connect the SMRT+ and SMRT- output terminals of the LN-VSTAT to the SMRT+ and SMRT- input terminals on the LN-VAV/VVT controller (Figure 6). To connect the LN-VSTAT sensors to an LN-Sensor using an 1/8 in. mono or stereo audio cable: 1. Use the taps on the bottom of the sensor to remove the sensor face plate. 2. Connect the SMRT+ and SMRT- output terminals of the LN-VSTAT sensors to two wires that terminate in the 1/8 in. audio plug (Figure 7). LN-VAV LN-VSTAT Figure 6: LN-VSTAT and LN-PSTAT Sensors - Wired to Controller Using the LN-VSTAT as a Portable Device You can use the LN-VSTAT sensors as a portable device to perform VAV balancing. If an LN-Sensor is already connected to the VAV that you intend to balance, directly connect the LN-VSTAT to the communication jack within the LN Series Sensor. Note: Terminals 1 and 2 of the right most terminal block within the LN Sensor must be connected to the SMRT+ and SMRT- inputs of the VAV controller before you can use the communication jack. Typically, these connections should have been made when the VAV controller and LN Sensor were first installed. Figure 7: SMRT+ and SMRT- Output Terminals with Audio Plug 3. Remove the LN Sensor faceplate and insert the 1/8 in. audio plug into the communication jack. Ensure the two output terminals on the right side of the LN-Sensor are wired to the SMRT+ and SMRTterminals of the LN-Sensor (Figure 8). 5

LN-VAV LN Sensor LN-VSTAT Figure 9: LN-VSTAT and LN-PSTAT sensors Wired to LN Sensor Using an Audio Plug Connect 1/8 in. Audio Plug from LN-VSTAT Sensor Figure 8: LN Sensor Wiring 6

INPUT+ COM TO SMRT+ TO SMRT- INPUT+ OUTPUT+ (0-10 VDC or 24 VAC) OUTPUT- 1 2 3 4 5 6 + - - + + - Com.1 Com.2 SMRT+ SMRT- Communications Wiring LN-- SENSOR Figure 10: LN-Sensor to an LN-PSTAT Sensor Wiring Details You can optionally wire Terminals 3 and 4 of the LN-VSTAT and LN-PSTAT sensors to the LON terminals of the controller. Before you insert multiple wires into any of the terminals on the controller, ensure you properly twist the wires together. You can access the LON network with a laptop by plugging into the communications jack on the LN-VSTAT with a 1/8 in. audio plug. Approved cable types for LON communication is Level IV 22 AWG (0.65 mm), UNSHIELDED. You can use both one pair and two pair wires. The LON communication wire is not polarity sensitive and can be laid out in a bus, star, loop, or free topology network configuration. For loop topology, polarity is important, take special care when connecting the LON network to avoid a short circuit. LN- PSTAT Note: The LN-VSTAT and LN-PSTAT sensors do not have an effect on the network topology for LON networks. Note: The Bus topology network configuration allow for easy network troubleshooting for LON communication wiring. Topology Wiring Choices If the distance between the sensor and the controller (stub length) is less than 3 meters a bus topology must be used (Figure 11). If the stub length is greater than 3 meters, a free topology in a daisy-chain manner must be used (Figure 12). Note: In Figure 11 and Figure 12, the wire runs from the two communication terminals of the LN-VSTAT and LN-PSTAT sensors to the LON/NET terminals of a controller. When you insert multiple wires into the terminals, ensure you properly twist the wires together prior to inserting them into the terminal connectors. 7

Figure 11 shows a bus topology (wired in a daisy chain) with stub length of less than 3 meters. Bus Topology Terminator Bus Topology Terminator CONTROLLER CONTROLLER CONTROLLER Stub Length < 3 m Figure 12 shows free topology (with stub) wired in daisy chain manner. Figure 11: Bus Topology, Stub < 3m Free Topology Terminator CONTROLLER CONTROLLER CONTROLLER Stub Length > 3 m Figure 12: Free Topology, Stub > 3m The wiring scheme in figure is almost identical to a bus topology network, but since the stub length exceeds 3 meters, it becomes a free topology network which requires a free topology terminator. 8

For additional information and detailed explanations on network topology and wire length restrictions, refer to Echelon Corporation s Junction Box and Wiring Guideline for Twisted Pair LONWORKS Networks (Part # 005-0023-01). Note: Use proper network terminators depending on the type of network topology used. Failure to do so may result in communication errors between controllers. Do not use multiple gauges of cable on the same communication bus, as this may also result in communication errors. Troubleshooting Table 1: Troubleshooting Problem Possible Cause Solution Temperature is not read properly Wrong connection Verify that every connection is properly wired. Temperature setpoint is not read properly Wrong connection Software configuration Verify that every connection is properly wired. Verify that the setpoint is configured correctly according to the selected sensor model. Controls Group 507 E. Michigan Street Milwaukee, WI 53202 Metasys is a registered trademark of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. 2014 Johnson Controls, Inc. 9 Published in U.S.A. www.johnsoncontrols.com