1-2 Zone & 2-6 Zone Fire Panel

Similar documents
BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

FIREDEX Conventional Fire Panels

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

CB200W Water Leak Detection Panel Application Guide

ACTIVE 5 ENGINEERING MANUAL

conventional system operation

3. MOUNTING THE FIRE ALARM PANEL PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February FA-300 SERIES Fire Alarm Control Panel

Conventional Fire Detection and Extinguishant Control System Specification

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions

Surveyor Excel-K. Fire Alarm Control Equipment. Installation, Commissioning and Operating Manual

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

GST301. (Single Protection Zone) Operation Manual

LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU Rev 1

CFP 2/4/8 ZONE ECONOMY FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU Rev 1

Fire Alarm Control Panel. Family. Operating Manual

TS510 & TS500. Installation & User Guide. Compatible Equipment

21. Power supply Maintenance... 22

9452/9453 Installation and User Guide

RP1r. Extinguishing Control Panel. User Manual (Software version 3.x) 3 zone control panel to protect 1 extinguishing risk

500r+ Installation and User Guide

INSTALLATION MANUAL CONTENTS

A.1. a Division of Pittway Corporation. Documento: M MGAS-ENG. Edizione: 01/1997 Rev.:

AC-115 Compact Networked Single Door Controller. Installation and User Manual

SFC-200 SERIES LCD FIRE ALARM PANEL

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

INSTALLATION MANUAL PC2525. Version 1.1

SECURIT 800L+ CONTROL PANEL

Digital Keypad Use s Manual

User s Information Guide R1A

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

VEGA Analogue Addressable Control Panels

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

Repeaters and Mimics Data Sheet

Control/Communicator Installation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

Installation and Operation Manual

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

AlarmSense 2-wire detection and alarm system. Product Guide

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU Rev 1

Syncro. Multi Loop Analogue Addressable Fire Control Panel. Product Manual. Man-1055 Issue 21 September 2010

9448 Installation and User Guide

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

TABLE OF CONTENTS FEATURES

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

Using your LED Plus keypad

Syncro. Multi Loop Analogue Addressable Fire Control Panel. Product Manual Man-1055 Issue 26 May 2016

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

Syncro AS. Analogue Addressable Fire Control Panel. Product Manual Man-1096 Issue 14 May 2016

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Secure Keypads for access control

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

HM-W536 Install Guide

LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual

SPR-5 FOUR SECTOR COMPOS I TE CONTROL UN I T.

TABLE OF CONTENTS FEATURES 2 SPECIFICATIONS 2

(68.52) X. June 2000 Supercedes February xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we business differently

D200+ Auto-Dialler Installation/Operators Manual

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6

Operating Instructions

TMS TANK MANAGEMENT SYSTEM

Emergency Voice Communication Systems EVCS Network 8 Data Sheet

Premier M Plus & Infinity 8

Accenta/Optima. Engineer s Manual. Honeywell Security. 8SP399A - Accenta mini panel with remote LCD keypad and communicator outputs.

Model 201 Wiegand Touchpad Reader Installation Guide

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

POINTS POSITION INDICATOR PPI4

Points Position Indicator (PPI1) for Points Motors with Common Ground

JUNIOR V3. Fire Alarm Control Panel INSTALLATION & COMMISSIONING MANUAL GLOBAL REVISION 2.3 FIRE EQUIPMENT QUEUE REVIEW STATUS ZONES

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

MSL1000 Monitored Serial Link Interface Manual V1.01

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

How To Set A Timer On A Gg System

Gen4 Intruder Alarm Panels SIMPLY SECURE. For Residential & Small Commercial Applications

CONTENTS 4. HOW TO UNSET THE PANEL...7

User Manual. Before installation and use, please read the user manual carefully.


SECTION DETECTION AND ALARM

2 4PI175 issue 1_6/01. How to unset system in alarm. Programs 1, 2 and 3. Access codes. How to operate Personal Attack

SmartLine. Conventional Fire Detection Control Panel. Extinguishant system Control Panel. User's Manual. GameOver

THANK YOU FOR VOTING TEXECOM INSTALLATION MANUAL. Security Control Panels. Issue 12

XR1. Intruder alarm system Operating Instructions. Unset system indications. Set System indication

The Child Reminder System Installation Manual

PAC1 Door Access Controller

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access

OPERATING INSTRUCTIONS

Technical Overview Add-on Sensors - Smoke Alarm. Get yours direct at:

BATTERY BOX INSTALLATION WARNING WARNING CAUTION ATTENTION AVERTISSEMENT ADVERTENCIA PRECAUCIÓN SOLBBOX12V CARTON INVENTORY COMPLETED OVERVIEW

Intruder alarm system Engineering Information

SPECIFICATIONS. Remote Keypad Specifications (PC2550RK) Output Voltage Specification. Digital Communicator Specifications

Discovery 1-4 Loop Analogue Addressable Control Panel Application Guide

CR Band Auto Set Dual Alarm Clock Radio ROBERTS. Sound for Generations. Please read this manual before use

PUSH BUTTON START INSTALLATION MANUAL

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Combi B Alarm box. Mounting instructions

Transcription:

1-2 Zone & 2-6 Zone Fire Panel User & Installation Manual IMPORTANT This manual should be left with the panel after installation. We reserve the right to change product specifications without prior notice.

2 Introduction The information provided in this manual covers the 1-2 zone range and the 2-6 zone range of fire alarm control panels. Both ranges are designed to meet the requirements of EN54 Parts 2 & 4. This product should be installed, commissioned and maintained by suitably qualified service personnel with reference to IEE regulations and any statutory requirements. General Description The 1-2 zone and 2-6 zone range of fire alarm control panels are microprocessor controlled and are available with either 1, 2, 4 or 6 sense zones (detector zones) dependent on the model. Both panels in the 1-2 zone range have 2 alarm zones (bell zones), zone disable facility, fault output and one set of volt free changeover contacts which operate on fire. The 2-6 zone range has all the above features plus one man test, class change input, non-latching facility, an extra set of volt free changeover contacts and a 28V output that is energised on fire. Installation Procedure Before proceeding with the installation, please read the section Panel Operation. Installation of the panel should be carried out by qualified personnel. Using the metal box as a template, mark the position of the fixing holes on the wall. Drill and plug the wall, then screw the panel to the wall. Ensure the panel is free from knockout discs, swarf and other debris. Do not remove any end of line resistors from the panel until after the following test is performed. With all end of line resistors fitted inside the panel, connect the panel mains supply to an exclusive 240V AC fused supply. Switch the mains supply on. The internal buzzer will sound. Connect two sealed lead acid batteries to the panel - they should be connected in series providing a 24V DC supply. With both the mains and battery supplies connected, the panel should be silent and in its normal operating mode (power lamp on, alarms & buzzer silent). If a fault is indicated, refer to the fault finding section before proceeding. Disconnect the batteries and switch off the mains supply.

Remove the 3k3 end of line resistor from sense zone 1. Terminate sense zone 1 circuit wiring in the panel observing correct polarity and fit the end of line resistor at the very end of the circuit. Check that all the detectors and call points are correctly wired. With sense zone 1 connected and all other end of line resistors fitted inside the panel, connect the mains and battery supplies. If the panel indicates a fault, refer to the fault finding section before proceeding. Do not megger cables connected to either the panel or any field devices. If no faults are indicated then power down the panel and follow the same procedure with the additional sense zones and then the alarm zones. Adding the zones one at a time makes fault finding and commissioning much simpler. Make sure that no bare wires come into contact with the panel circuit boards during installation. Detector Head Removal The 1-2 zone range and the 2-6 zone range support head removal. The basic principle of head removal is to ensure that all call points will function even if a detector head has been removed. Head removal requires either zener clamp bases or schottky diode bases with the appropriate end of line device to be fitted. When a detector head is removed, the panel will show a fault, but the sense zone circuit will remain intact. Consult the table on page 10 for further information. 3

4 Panel Operation Enabling the front panel buttons. To enable the front panel buttons, the key switch in the top left of the panel must be turned to the On position. Performing a lamp test. If the panel is in its normal condition, pressing the Reset button will cause the panel to perform a lamp test. Resetting the panel after a fire is detected. To reset the panel after a fire event, press the Silence button followed by the Reset button. Resetting the panel. If any of the panel functions have been activated, pressing the Reset button will return the panel to its normal condition. Silencing/resounding the alarms. If a fire is detected, the panel will automatically activate the alarm circuits. To silence the alarms, press the Silence button once. To resound the alarms, press the Silence button again. Silencing the internal buzzer. If a fault is detected by the panel, the internal buzzer will sound. To silence the buzzer press the Silence button. Using the one man test function (2-6 zone range only). To enter test mode, press the Test button. The test LED will be lit and zone 1 fault LED will be flashing. To place zone 1 into test mode, press the Silence button. Press the Test button again and now zone 2 fault LED will be flashing with zone 1 fault LED on steady if it is in test mode. To select further zones, press the Test button to cycle through the zones and use the Silence button to toggle the status of the selected zone. Placing too many zones into test mode at the same time may leave the building with inadequate protection. When a zone in test mode detects a fire event, the alarms will ring for a few seconds before resetting. If the panel is left in test mode and no events occur for approximately 10 minutes, the panel will automatically exit test mode and resume normal operation.

5 If a fire is detected on a zone not in test, then the panel will enter the fire condition and exit test mode. To exit test mode and return the panel to normal operation, press the Reset button. Using the disable function. The panel allows the user to selectively disable the sense zones and the alarm zones. The selection process is very similar to that used in the test function. To enter disable mode, press the Disable button. The disable LED will be lit and zone 1 disable LED will be flashing. Pressing the Silence button will toggle the status of the selected zone and pressing the Disable button will cycle through the available zones. Once the required zones have been selected, press the Reset button. If any zones were disabled, the disable LED and the relevant zone disable LED(s) will remain lit. All incoming signals from disabled sense zones will be ignored. If the alarm zones are disabled, then the alarms will not be activated even if the panel detects a fire event on an active sense zone. Selecting a zone as non-latching (2-6 zone range only). In some situations, such as interlinking fire alarm panels, it is necessary to set a sense zone as non-latching. When a fire event is detected on a nonlatching zone, the panel will go into fire as usual but will automatically reset as soon as the device signalling fire is reset. To enter the non-latching selection mode, press and hold down the Test button. While still holding the Test button, momentarily press the CPU RESET button inside the panel, followed by the WATCHDOG RESET (W/D) button. Keep the Test button held down until the disable and general fault LEDs light, then release the Test button. Zone 1 fault and disable LEDs will be flashing. Pressing the Silence button will toggle the status of the selected zone and pressing the Test button will cycle through the available zones. After the relevant zones have been selected, press the Reset button.

6 Fault Finding Front panel buttons not working. To activate the front panel buttons, turn the keyswitch in the top left of the panel to the ON position. Fault LED and sense zone fault LED flashing, buzzer sounding. Faults monitored are: Open circuit on the sense zone wiring. Short circuit on the sense zone wiring. Detector head removal. Check all detectors and call points on the sense zone indicated. Check wiring is as in example diagrams and ensure the end of line monitor is a 3k3 resistor or an active end of line device. Fault LED and alarm zone fault LED flashing, buzzer sounding. Faults monitored are: Open circuit on the alarm zone wiring. Short circuit on the alarm zone wiring. Blown alarm fuse(s) - Note that on the 2-6 zone range, drawing excessive current from the 28V Aux supply will blow the fuse in Alarm Zone 2. Check alarm zone wiring is as in example diagrams and ensure that the 10k end of line resistor is fitted. Check alarm zone fuses. Fault LED and PSU Fault LED flashing, buzzer sounding. Faults monitored are: Battery supply not present. Batteries damaged or not fully charged. Blown battery fuse. Mains supply not present. Blown mains fuse. Check relevant fuses. Ensure batteries are connected correctly and battery leads are secure. Fault LED and Earth Fault LED flashing, buzzer sounding. The panel has detected an earth fault. The only earth connection to the panel terminals should be to the mains input terminal block. Check that no other earth connections are present.

Fault LED and CPU fault LED lit. Processor fault detected. If no other problems are found then reset the processor. Inside the panel are two push buttons marked CPU RESET and WATCHDOG RESET (W/D). Press CPU RESET followed by WATCHDOG RESET (W/D). Panel does not indicate fire when a call point or detector is tested. Either a faulty call point/detector or wiring not as shown in diagrams. Check the firing resistance of the device is 510 ± 200 ohms and ensure that the correct end of line device is fitted. Head removal not working. Check compatible base is being used and is wired correctly. Either a zener clamp base with a 3k3 end of line resistor, or a schottky diode base with an active end of line device must be used. Power LED blinks intermittently This is perfectly normal and indicates that the processor is running an internal memory check. Fuse ratings. Mains fuse...1a A/S Alarm fuses...200ma A/S (1-2 zone range) 300mA A/S (2-6 zone range) Battery fuse...1a A/S (1-2 zone range) 2A A/S (2-6 zone range) Fault output. The auxiliary fault output, marked AF on the PCB, is an open collector output that is normally pulled low. When the panel detects a fault, the AF output is switched into its high impedance state. Refer to the wiring diagram on page 13 for example connection details. Other faults. For any other faults, perform a CPU reset. Inside the panel are two push buttons marked CPU RESET and WATCHDOG RESET (W/D). Press CPU RESET followed by WATCHDOG RESET (W/D). This will restart the processor, but all configuration information (disable, non-latching) will have to be re-entered. 7

8 Panel Specifications 1-2 Zone Range 1 Zone 2 Zone Mains Voltage (V AC) 240 240 System Voltage (V DC) 28. 4 28. 4 Quiescent Current (ma) 65 65 Quiescent Current, Unsilenced Fault (ma) 75 75 Minimum Battery Size 2 x 12V Required (Ah) 2. 2 2. 2 Detector Voltage (V DC) 20 20 Number of Sense Zones 1 2 Maximum Number of Detectors per Zone 30 30 Firing Resistance (Ohms) 510 ± 200 510 ± 200 Sense Zone End of Line (Ohms) 3k3 3k3 Alarm Voltage (V DC) 28. 4 28. 4 Number of Alarm Zones 2 2 Maximum Alarm Current per Zone (ma) 200 200 Maximum Number of Sounders per Zone 10 10 Alarm Zone End of Line (Ohms) 10k 10k Max. Auxiliary Supply Current in Fire (ma) - - Panel Weight Including Batteries (kg) 4. 5 4. 5 Panel Dimensions (mm) 234 x 225 x 85 234 x 225 x 85

2-6 Zone Range 2 Zone 4 Zone 6 Zone 9 240 240 240 28.4 28. 4 28. 4 95 95 95 99 99 99 3 3 3 20 20 20 2 4 6 30 30 30 510 ± 200 510 ± 200 510 ± 200 3k3 3k3 3k3 28.4 28. 4 28. 4 2 2 2 300 300 300 16 16 16 10k 10k 10k 50 50 50 5 5 5 285 x 230 x 85 285 x 230 x 85 285 x 230 x 85 The 28V Aux supply is derived from Alarm Zone 2. This must be taken into account when calculating the alarm current.

10 Detector Base and Call Point Wiring Information Part Number Nittan STB-4SDR Hochiki YBK-R/5ZD Hochiki YBN-R/4 Apollo S60 Diode Base Apollo S60 Common Base KAC Call Point Fulleon Call Point Resettable Call Point Positive In 4 L1 2 L1 I N L1 I N 1 470 Ohm s + I N Positive Out 4 L2 1 L1 OU T L1 OU T 1 470 Ohm s + OU T Negative In 1 C5 5 L2 L2 2 COMMO N - I N Negative Out 6 C6 6 L2 L2 2 COMMO N - OU T Remote Indicator Positive 4 L1 N/ A L1 I N 1 I N L A N/ N/ A N/ A Remote Indicator Negative 5 S3 N/ A -R -R N/ A N/ A N/ A End of Line Device Active End of Line 3k3 Resistor 3k3 Resisto r Active End of Line 3k3 Resistor To Suit Detector Base To Suit Detector Base To Suit Detector Base Head Removal Supported Yes Ye s No Ye s N o

11 Sense Zone Wiring Diagrams Find the detector bases you will be using in the table on page 10 and check to see which end of line device is required - either a 3k3 resistor or an active end of line unit. The 3k3 resistor should be used if a zone is comprised entirely of call points. Sense zone with a 3k3 end of line resistor. Sense Zone + + in + out + in + out 3k3 EOL Sense Zone - - in - out - in - out orange orange red gold The colour bars on a 3k3 resistor are Sense zone with an active end of line. Sense Zone + Sense Zone - + in + out + in + out - in - out - in - out red Active EOL black The panel is supplied with 3k3 end of line resistors as standard. Active end of line units are available separately. Remote indicator connection details are shown in the table on page 10.

12 Alarm Zone Wiring Diagram The alarm zones are wired as in the diagram below. A 10k end of line resistor must be fitted at the end of the circuit. Motorised fire bells may be used, but solenoid bells MUST NOT be connected to the panel. Alarm Zone + + in/out + in/out 10k EOL Alarm Zone - - in/out - in/out brown black orange gold The colour bars on a 10k resistor are Attaching a relay to an alarm zone. Alarm Zone + Alarm Zone - NO1 NC1 NO2 NC2 A relay may be connected anywhere on the alarm zone wiring provided that two diodes (1N4001 or equivalent) are fitted as shown in the diagram. The end of line resistor is not shown, but must be connected at the end of the alarm zone wiring. The relay must have a 24V DC coil. C1 C2 Alternatively (2-6 zone range only), a relay can be connected to the Aux 28V terminals, however a diode must still be connected across the coil.

13 Additional Wiring Information Connecting a relay to the auxiliary fault (AF) output. A fault relay can be connected to the panel as shown. The diode (1N4001 or equivalent) must be fitted. The relay must have a 24V DC coil. The relay will normally be energised, dropping out if the panel signals a fault condition. The 0V of the external 28V supply must be connected to the 0V terminal (1-2 zone range), or the Aux 28V - terminal (2-6 zone range). NC1 NO2 28V+ Supply Auxiliary Fault AF C1 C2 NO1 NC2 Ringing the alarms remotely (2-6 zone range only). The class change (CC) facility allows a remote source to sound the alarms. When the CC terminal is connected to the Aux 28V - terminal, the alarms will sound. Class Change (CC) Remote C/NO Contacts Aux 28V -

14 Signalling fire to another panel. By connecting two panels as shown below, when panel B closes its auxiliary contacts, panel A will go into fire. If the zone on panel A is set to non-latching it will automatically reset when panel B opens its auxiliary contacts. If both panels need to signal fire to each other, simply duplicate the circuit substituting panel A for panel B and vice versa. Sense Zone + 510R Resistor Panel A 3k3 EOL C/NO Contacts in Panel B Sense Zone - Connecting magnetic door holders. Low voltage magnetic door holders can be switched using a set of auxiliary contacts in the panel. When the panel goes into fire, power to the door holders is removed allowing the doors to close. Care must be taken to ensure that the auxiliary contacts rating of 24V / 1A is not exceeded. Mains voltages MUST NOT be switched directly from the auxiliary contacts - instead, fit a heavy duty relay operated from the auxiliary contacts. 24V Door Holder Power Supply + Panel Auxiliary Contacts C NO Door Holder Door Holder Door Holder -

15 System Log All events should be properly recorded in this log book. An event should include fire alarms (whether real or false), faults, tests, temporary disconnections and the dates of installing or servicing engineer s visits with a brief note of work carried out and outstanding. Name and address... of installation............ Person responsible... Date... for log book... Date...... Date...... Date... System installed by... and is maintained under contract by... Tel.... Notes:

16 Date Time Zone Event Action Required Date Completed Initials