From 48 V direct to Intel VR12.0: Saving Big Data $500,000 per data center, per year



Similar documents
VICOR WHITE PAPER. The Sine Amplitude Converter Topology Provides Superior Efficiency and Power Density in Intermediate Bus Architecture Applications

High-voltage DC distribution is key to increased system efficiency and renewable-energy opportunities

Application Note AN:005. FPA Printed Circuit Board Layout Guidelines. Introduction Contents. The Importance of Board Layout

Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs

3-Phase Synchronous PWM Controller IC Provides an Integrated Solution for Intel VRM 9.0 Design Guidelines

Output Ripple and Noise Measurement Methods for Ericsson Power Modules

400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications

AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family

White Paper: Pervasive Power: Integrated Energy Storage for POL Delivery

Developments in Point of Load Regulation

Understanding Delta Conversion Online "Power Regulation" - Part 2

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

Intel architecture. Platform Basics. White Paper Todd Langley Systems Engineer/ Architect Intel Corporation. September 2010

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Bi-directional Power System for Laptop Computers

Technical Article. Multi-phase DC-DC PMIC: the efficient, space-saving choice for today s application processors. Peter Kammerlander

Fairchild On-Line Design Tool: Power Supply WebDesigner Step-by-Step Guide

SL Series AC and DC Electronic Loads

Laboratory 4: Feedback and Compensation

W a d i a D i g i t a l

Programmable Single-/Dual-/Triple- Tone Gong SAE 800

Power supplies. EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E

Considering the effects of UPS operation with leading power factor loads

SSPI-APPN OTES: PARALLEL C ONNECTIONS

High Performance ZVS Buck Regulator Removes Barriers To Increased Power Throughput In Wide Input Range Point-Of-Load Applications

High Efficiency Battery Charger using Power Components [1]

Development of High Frequency Link Direct DC to AC Converters for Solid Oxide Fuel Cells (SOFC)

Power supply output voltages are dropping with each

Accurate Measurement of the Mains Electricity Frequency

ABB Drives. User s Manual HTL Encoder Interface FEN-31

Bourns Resistive Products

Powering Integrated Circuits (ICs), and managing ripple voltage as it relates

GENERAL POWER SYSTEM WIRING PRACTICES APPLIED TO TECNADYNE DC BRUSHLESS MOTORS

LDO03C/LDO06C/LDO10C

GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS

Design of an Auxiliary Power Distribution Network for an Electric Vehicle

Qualitative Analysis of Power Distribution Configurations for Data Centers

Tamura Closed Loop Hall Effect Current Sensors

DDX 7000 & Digital Partial Discharge Detectors FEATURES APPLICATIONS

The Motherboard Chapter #5

7-41 POWER FACTOR CORRECTION

FREQUENCY RESPONSE ANALYZERS

1+1 PROTECTION WITHOUT RELAYS USING IDT82V2044/48/48L & IDT82V2054/58/58L HITLESS PROTECTION SWITCHING

Input and Output Capacitor Selection

Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions

SYSTEM 45. C R H Electronics Design

Study Guide for the Electronics Technician Pre-Employment Examination

FFT Frequency Detection on the dspic

electronics fundamentals

Application Note. PCIEC-85 PCI Express Jumper. High Speed Designs in PCI Express Applications Generation GT/s

Impedance 50 (75 connectors via adapters)

SERIES-PARALLEL DC CIRCUITS

AC vs DC for Data Centers and Network Rooms

See Horenstein 4.3 and 4.4

Server Technology, Inc.

DC-DC high gain converter applied to renewable energy with new proposed to MPPT search

Power Management of Cell Sites

Application Note 58 Crystal Considerations with Dallas Real Time Clocks

POWER FORUM, BOLOGNA

Experiment 7: Familiarization with the Network Analyzer

nanoetxexpress Specification Revision 1.0 Figure 1 nanoetxexpress board nanoetxexpress Specification Rev 1.

X. Dealing with Signature Differences

Figure 1. Core Voltage Reduction Due to Process Scaling

Lab 3: Introduction to Data Acquisition Cards

ε: Voltage output of Signal Generator (also called the Source voltage or Applied

Power Electronic Circuits

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

DDX 7000 & Digital Partial Discharge Detectors FEATURES APPLICATIONS

Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015

RF Network Analyzer Basics

Constant Current Control for DC-DC Converters

Considerations When Specifying a DC Power Supply

MATERIALS. Multisim screen shots sent to TA.

Evaluating AC Current Sensor Options for Power Delivery Systems

98% Efficient Single-Stage AC/DC Converter Topologies

When the Power Fails: Designing for a Smart Meter s Last Gasp

Use and Application of Output Limiting Amplifiers (HFA1115, HFA1130, HFA1135)

Op-Amp Simulation EE/CS 5720/6720. Read Chapter 5 in Johns & Martin before you begin this assignment.

Control Development and Modeling for Flexible DC Grids in Modelica

Hands On ECG. Sean Hubber and Crystal Lu

SYSTEM 4C. C R H Electronics Design

S-Band Low Noise Amplifier Using the ATF Application Note G004

Fundamentals of Signature Analysis

DC/DC power modules basics

Application Note, Rev.1.0, September 2008 TLE8366. Application Information. Automotive Power

Current and Temperature Ratings

Create Colorful and Bright LED Light with an LED Matrix Dimmer

Signal Types and Terminations

DIGITAL LOGIC CURRENT FLOW

White Paper. Innovate Telecom Services with NFV and SDN

Solar Energy Conversion using MIAC. by Tharowat Mohamed Ali, May 2011

Hybrid Power System with A Two-Input Power Converter

Configure Inverter output for two utility settings, (1)120V/60Hz, (2)220V/50Hz

USB 3.1 Channel Loss Budgets

Quick Start Guide for High Voltage Solar Inverter DC-AC Board EVM. Version 1.3

Rapid Audio Prototyping

National Semiconductor Power Products - Seminar 3 (LED Lighting)

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet

Experiment # (4) AM Demodulator

Transcription:

WHITE PAPER From 48 V direct to Intel VR12.0: Saving Big Data $500,000 per data center, per year Written by: Stephen Oliver Vice President, VI Chip Product Line July 2012 Abstract The exponential rise in Big Data generation, processing and storage, from sources such as intensive industrial simulations, medical research and social media sites highlights the growing demand for data center and cloud computing power worldwide. The subsequent task is to maximize energy efficiency, thus saving money and natural energy resources, minimizing pollution and meeting the US Department of Energy s Exascale challenge; perform an ExaFLOP (1 x 10^18 floating point operations per second) of compute workload using only 20 MW of power. For the power semiconductor industry, the challenge is to provide efficient and high quality power conversion from 480 V 3-phase AC power entering the data center, all the way to 1 V, 100 A+ processors. Here, high quality means providing the optimum voltage and current as dynamically demanded by the processor to operate at peak performance. This paper describes how Vicor s Factorized Power Architecture (FPA ) enables the world s first Intel VR12.0 compliant solution to operate directly from 48 V distribution systems, saving $500,000 per data center in annual running costs. Introduction High-volume data processing and data communication tasks require large-scale dedicated, optimized hardware installations i.e. data centers designed and operated by companies such as IBM, Amazon, Cisco, Hewlett-Packard, Google, Cray and others. Within the data center infrastructure, classical physics principles dictate that power should be channeled to data processing locations at a high voltage to reduce current and so minimize distribution loss [a]. Compute density (related to the number of processors, memory, input / output functionality) and subsequent power draw is also a key issue. As power per rack increases above 10 kw, loss in traditional 12 V rack distribution becomes excessive, with additional financial- and size-related costs such as larger, more expensive copper bus bars, connectors, etc. For applications approaching 20 kw and above per rack, efficient 48 V distribution is required. An example is the POWER7-based IBM Blue Gene /Q, which uses 48 V distribution, 80 kw per rack and is the world s highest performance [b] and most efficient [c] supercomputer, achieving 20,132 TFLOPs and 2,026 MFLOPs/W. In addition, high reliability or high uptime servers require an energy storage system (typically lead-acid batteries) to provide backup power in the event of a main AC-feed interruption. Historically, processing tasks such as switching and routing in the telecommunications industry were performed by small 30 40 W application-specific integrated circuits (ASICs). With the rise of tripleplay (voice, video, internet) usage on mobile phones and tablets, voice-only telecom equipment has become datacom, with the use of standard computing processors. These systems typically use a 48 V rail but in Central Office equipment, the battery back-up voltage may be much wider, requiring wider input-range converters, further reducing the system efficiency. Energy storage is also related to voltage, so 48 V is again the optimum choice [d]. [a] Power = voltage x current. So for the same power, as voltage increases, current decreases. Distribution loss = current^2 x distribution rail resistance. So, distribution at 48 V is 16 x more efficient than at 12 V. [b] Top500 list June 2012, http://www.top500.org/list/2012/06/100 [c] Green500 list November 2011, http://www.green500.org/lists/2011/11/top/list.php [d] In battery and capacitor technologies, energy storage is related to voltage^2. vicorpower.com Applications Engineering: 800 927.9474 Page 1

Regulation Compute workload varies with time. As demand increases, each processor requires more power to maintain performance (MFLOPs). As workload is reduced, the processor may throttle back, moving to idle or sleep states to conserve power. In anticipation of a change in power requirement, the processor sends a serial Identification (VID) code to the power delivery system. During all steady-state and transient periods, the voltage delivered to the processor must remain within tight, pre-defined limits to maximize performance and minimize the chance of a system crash. Power requirements for Intel processors are identified in Regulator (VR) specifications. For the Sandy Bridge and Ivy Bridge processor chip-sets, compliance to the VR12.0 specification is required. Traditional 12 V Limitations As power per rack increases with a 48 V rack distribution requirement, traditional 12 V-VR12.0 solutions must be prefaced by a separate 48 V 12 V conversion stage, as shown in Figure 1, below. Figure 1. Traditional high power server architecture showing two stage 48 12 1 V approach, showing the wide server range 48 V (38 60 V) with back-up energy storage at 48 V. The 96% represents the loss in the motherboard due to the VRM being large and unable to be located adjacent to the processor socket. 48 V (38 60 V) + 48 V Back-up DC-DC Converter (1/4 brick, Regulated, 94.5%) 12 V Regulator Module (VRM) (91.5%) 96% ~1 V V CORE VR12.0 Processor It is critical to consider the power scheme in its entirety. Headline specification claims for DC-DC converters and VRMs ignore losses related to distribution loss on the motherboard and any connector losses. A true approach requires a measurement from the 48 V rail all the way to the processor socket itself, thus taking into account all potential loss elements. Optimized 48 V Solutions: Factorized Power Architecture (FPA ) Factorized Power Architecture (FPA) [e] employs a different approach to power conversion, taking the regulation, isolation and voltage transformation functions of a typical DC-DC converter and separating or factorizing them into individual elements. These individual components (small, high-efficiency regulators and transformer / isolators known as VI Chips ) are then arranged in the optimal power architecture. Figure 2: In traditional IBA, functions are duplicated thus increasing losses. FPA eliminates the duplication, increasing efficiency. Intermediate Bus Architecture (IBA) Input DC-DC Converter Regulation Conversion Isolation Regulator Regulation Conversion Output Factorized Power Architecture (FPA) Input PRM Regulator VTM Transformer Output Regulation Conversion Isolation [e] For additional information, please refer to white paper FPA 101 available at www.vicorpower.com vicorpower.com Applications Engineering: 800 927.9474 Page 2

VI Chip PRM regulators use a non-isolated buck-boost topology. The PRM accepts a varying DC input and creates a tightly regulated, adjustable DC output (the factorized bus (V F )) which feeds into a downstream VTM transformer. The VTM is a fixed-ratio DC-DC transformer using a Sine Amplitude Converter (SAC ), which down-converts V F directly to the processor's core voltage V CORE. Thanks to zero-voltage (ZVS) and zero-current (ZCS) MHz-switching techniques, high-efficiency and high-power densities are achieved, with the PRM [f] up to 97% peak and more than 1,000 W/in 3, and the VTM more than 94% peak and over 100 A/in 2. Figure 3. VI Chip PRM and VTM power components used in FPA With FPA, the power system is architected to maintain high efficiency 48 V distribution along the entire path to the motherboard and to use the PRM and VTM VI Chips adjacent to the processor socket. The result is a highly efficient, small power system with a proven record in high performance systems including the 48 1 V Blue Gene/Q system referenced earlier. World s First 48 V-VR12.0 Solution For Intel processor systems, the VI Chips form a pure powertrain which is accompanied by a separate VID controller, which acts as a translator between the digital processor VID and the FPA powertrain, which, in turn uses the optimal fast analog control loop to provide accurate processor core voltage (V CORE ). Figure 4. Information from the processor (VID instructions) and feedback on current and voltage are fed to the VID control IC. The IC sends a control signal to the PRM regulator which controls the powertrain. 48 V (38 60 V) + 48 V Back-up PRM Regulator (97% peak) V F VTM Transformer (94% peak) ~1 V V CORE 99% Processor Control Current Feedback Feedback Serial VID VID Controller [f] VI Chip components used in the VR12.0 example are PRM48DH480T250A03 and VTM48EF012T130A01, available from www.vicorpower.com vicorpower.com Applications Engineering: 800 927.9474 Page 3

To demonstrate VR12.0 compliance, a Regulator Test Board (VTRB) was created as shown in Figure 5 and configured to support a 145 W, socket R processor. Figure 5. VTRB with close-up showing PRM and VTM modules adjacent to processor socket. No separate 48 12 V converter is required for V CORE. Note also that no bulky electrolytic capacitors are present in the FPA design. A Test Tool (VTT) is inserted into the processor socket which emulates processor behavior to characterize the performance of the powertrain. The performance is recorded and compared to the VR12.0 specifications using an automated spreadsheet. A typical Load Line result, in which V CORE must remain within tight limits while processor current increases, is shown in Figure 6. Figure 6: As processor current demand increases; power cannot be instantly increased, so the core voltage is allowed to droop in relation to the load. This is known as a load line and the core voltage must be maintained within tight limits to ensure processor stability and performance. The FPA result (blue line) is shown in the load increase from zero to 165 A. Output (V) 1.25 1.2 1.15 1.1 1.05 VID1 Loadline VccMAX VccMin 1 0 20 40 60 80 100 120 140 160 180 Load Current (A) Figures 7 and 8 show examples of voltage and current oscilloscope traces during power state transitions. vicorpower.com Applications Engineering: 800 927.9474 Page 4

Figure 7. Load transient waveforms (Power State 1 to Power State 0 transition (16 to 147 A) shown at two different time scales. The FPA system has a clean, stable response within 5 µs. In the scope images, yellow = current step, magenta = load voltage measured in VTT with only SMT ceramic caps. The FPA system does not use traditional large, unreliable electrolytic capacitors. Figure 8: Shows the core voltage response to a VID instruction (Dvid_ps0_121A_up (1.05 V to 1.07 V)). The magenta trace = V CORE (output voltage), cyan = CSO (chip select), green = alert. The results show a stable response in only 2 µs. Additionally, more stringent tests, using sweeps of processor frequency, load power and VID commands are also performed. 3D Matrix plots are created, with an example in Figure 9. Figure 9: 3D Matrix result at Intel Dupont. Chart axes are: X = load (processor) switching frequency (khz), y = Load switching duty cycle (%), Z axis is maximum excursion above set point. vicorpower.com Applications Engineering: 800 927.9474 Page 5

Savings A complete evaluation of the powertrains showed significant size and efficiency savings for FPA vs. the traditional IBA system. Server motherboard real estate (PCB area) is expensive. A reduction in powertrain size means an increase in space available for more compute functionality (processors, memory, input / output functions). The FPA solution uses 50% less motherboard than IBA, while in addition, eliminates the off-board DC-DC converter; in total, a 3 x reduction in size. In power terms, the FPA solution is >5% points more efficient from 60% to 100% processor load as shown in Figure. 10. This is a significant improvement in VR12.0 systems, representing a 10 W or 30% reduction in power loss per processor. Figure 10. 48 V to VR12.0 socket efficiency (accounts for conversion and distribution losses). Efficiency (%) (48V to VR12.0 Processor Socket) 90% 85% 80% 75% Vicor FPA Solu on Tradi onal Solu on 70% 65% 60% 0 20 40 60 80 100 120 140 Processor Load (A) Adjusting for duty cycle / usage rate (85%) and air-conditioning costs (+70%), the final value per processor is 14.5 W saved. A new-build data center typically uses 30,000 processors. Using a $0.13/kWhr price for electricity, 14.5 W quickly becomes $500,000 reduction per year in data center running costs (equivalent to 2,300 imported barrels of oil). The annual saving means that in less than three years, the VI Chip VR12.0 powertrain completely pays for itself. The Power Behind Performance Rev 1.0 07/12 vicorpower.com Applications Engineering: 800 927.9474 Page 6