HANGERS AND SUPPORTS FOR HVAC AND PLUMBING PIPING

Similar documents
SECTION PIPE HANGERS AND SUPPORTS

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the

PART 1 GENERAL 1.1 SECTION INCLUDES

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

SECTION ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS

GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS

4 Installation Requirements

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION FACILITY STORM DRAINAGE PIPING

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

INSTALLING SEISMIC RESTRAINTS FOR MECHANICAL EQUIPMENT

FINAL December 2012 SECTION DUCTWORK

SECTION COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

Ecoflex Wall Penetration Systems: An efficient, sustainable solution for penetrating concrete or block walls

SECTION UNDERGROUND ELECTRIC SERVICE

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS

800 Communications Circuits

James M. Pleasants Company

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

STANDARD SPECIFICATIONS SECTION METAL FABRICATIONS

INSTALLATION OF A BAY WINDOW

SECTION WINDOW WASHING SYSTEMS

SECTION COLD-FORMED METAL DECK FRAMING Elevations Steel Deck Framing by Trex

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN Fax: Re-Roofing: Asphalt Shingles

Embedded Parts Introduction - Anchors

The minimum reinforcement for the stem wall is the placement of:

A. The shade structure contractor shall be responsible for the design, engineering, fabrication, and supply of the work specified herein.

PIPE HANGERS AND SUPPORTS PRICE LIST AND CONDENSED CATALOG

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

WHI 90-Minute Rated Veneered Door Frame Installation Instructions

Services Enclosures and Protected Shafts - Maintaining Compartmentation

Hanson Building Products. precast basement solutions

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

Residential Deck Safety, Construction, and Repair

SECTION FREIGHT & PARKING GARAGE ELEVATORS PART I - GENERAL

SECTION CHAIN LINK FENCES AND GATES

SECTION SOIL AND WASTE SYSTEMS

City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures

ROOF DRAINS TABLE OF CONTENTS

HOW TO ESTIMATE THE COST OF T-BAR

SECTION HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section

Preformed Metal Roofing and Siding

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

Section SEWER PIPE INSTALLATION AND TESTING

Chapter 3 Pre-Installation, Foundations and Piers

GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS PHILLIP STREET, SYDNEY

PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE

Mechanical Services Standard Specification Compressed Air Systems. May For ROYAL HOLLOWAY UNIVERSITY OF LONDON

Mark Cramer Inspection Services, Inc.

FIX TURE CARRI ERS. 140(a) MPB-2011-USA

Excerpts from the Canadian National Building Code (NBC)

AIRPORT SECURITY FENCING. A. American Society for Testing and Materials (ASTM):

FORM DESIGN. easy to work with, and generally available.

METHOD STATEMENT FOR INSTALLATION OF CABLE TRAY/TRUNKING/LADDER

2010 Residential Water Heater Replacement Check List

A. This Section includes the following for soil, waste, and vent piping inside the building:

Standard Practice for Installation of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Subject to Earthquake Ground Motions 1

EAST LYME HIGH SCHOOL

Cat. No. Finishes & Materials. Standard Finish: Electrogalvanized. Change suffix to SS6(C).

Materials. Estimating Steel. Players. Materials. Shop Drawings. Detailing Process. Standard shapes. Fabricated members, Built-up sections

Chapter 36 - STRAW BALE CONSTRUCTION SECTION PURPOSE. SECTION SCOPE. SECTION DEFINITIONS.

Reticulation sewers in basements Technical guidelines

B. Types of mechanical insulation specified in this section include the following:

SECTION GENERAL PROVISIONS FOR HVAC WORK

MRI RF SHIELDING DESIGN

Pipe Clamps and Accessories

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

COMMONLY USED RESIDENTIAL BUILDING CODES

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

DESIGN CLARIFICATION (DC)

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED.

SECTION 22 LIGHTNING PROTECTION SYSTEM

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

Syphonic Roof Drainage

Summit Anchor Company, Inc.

Superform Products Ltd.

I BEAM TRACK INSTALLATION

Wisconsin Building Products Evaluation

SECTION CONDUITS, RACEWAYS, FITTINGS AND CABLE TRAYS

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design

One-third of all fatalities in the U.S. construction

CHAIN-LINK FENCES BID SPECIFICATIONS DESCRIPTION

PROPOSED SPECIFICATION FOR ALUCOBOND PLUS Aluminium Composite Panel Cladding System Fixed Watertight Cassette Panel System - 4mm thick

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

SECTION CABLE TRAYS. A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system.

CITY OF SELMA, TEXAS Inspection Checklist: Commercial

OPEN ITEMS LIST - CONSTRUCTION Project Name: East Central Middle School - Jackson County CLA#: 11003

Sports and High Mast Lighting Poles Phone: (866) Fax: (817)

POWERS Controls No. 4 Pneumatic Damper Actuator

PERIMETER FLASHING. Table of Contents

Transcription:

15090 - HANGERS AND SUPPORTS FOR HVAC AND PLUMBING PIPING PART I DESIGN REQUIREMENTS 1. Prior to beginning design, the Engineer should review building design and construction and design suitable building attachment and pipe support and anchoring system, verifying that the existing building structure can support new piping loads. 2. The Engineer should include the following in piping designs: a. Pipe hanger details, including components, hanger spacing. b. Pipe hanger systems that account for thermal expansion of piping. c. Details of building attachments, including clarifying when support of piping from concrete slab using expansion anchors is acceptable. d. For large piping or where the design otherwise impacts the integrity of the building structure, indicate locations of all pipe hangers. e. Indicate locations and details of pipe anchors, guides and expansion joints or bends. 3. Large piping and equipment should be independently supported from building structure, not from roof decks, etc. All piping should be directly supported from the building, not from other piping, ductwork or equipment. 4. The Engineer should review Contractor s hanger support shop drawings and details to verify that unacceptable pipe movement during all phases of operation of the system (start-up, sudden gpm changes, or shutdown) will not occur. 5. Where several pipes rest on a common trapeze, the hanger rod diameter will be increased and the hanger spacing will be decreased in accordance with maximum and minimum pipe sizes respectively. 6. Select and size pipe hangers and supports for fire protection systems in compliance with the applicable requirements in the latest edition of NFPA No. 13, Chapter 3-15 and NFPA No. 14, Chapter 7-6. 7. The specifications will state that the plumbing contractor should provide supplemental channels and steel to support all plumbing piping and that cut ends of support steel shall be ground smooth free from burrs and sprayed with a galvanized coating. PART II CONSTRUCTION REQUIREMENTS A. General 1. Provide shop drawings and product data for each pipe size and pipe service to include: a. Type and model for all manufactured pipe support components, including building attachments, hangers, insulation saddles and shields, expansion joints, anchors. b. Locations of anchors, expansion bends and joints. 15090-1 May 2009

c. Locations of building attachments where deemed necessary by the Engineer. d. Details and supporting calculation of additional supports. 2. Provide all necessary hangers and supports of approved design to keep piping in proper alignment and prevent transmission of injurious thrusts and vibrations. In all cases where hangers, brackets, etc., are supported from concrete construction, care shall be taken not to weaken concrete or penetrate waterproofing. 3. Install hangers and supports to allow controlled thermal movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units. 4. Load Distribution: Install hangers and supports so that piping live and dead loads and stresses from movement will not be transmitted to connected equipment. 5. Do not hang piping from other piping, ductwork, conduits, or ceiling grids. 6 Piping subject to lateral or vertical movement should be provided with spring hanger type support. 7. Hangers for piping that lacks rigidity, such as Whiteline polypropylene pipe, shall be spaced as recommended by the manufacturer (as a minimum) or preferably with a continuous support. Since the spacing is typically much closer than for other piping materials, the designer must pay close attention to the implications on his design. 8. Hangers, rods, inserts and pipe rolls, exposed to weather, shall be hot-dipped galvanized or primed steel; other hangers and supports shall be dipped in zinc chromate primer before installation. Underground hangers shall be painted with two (2) coats of black asphaltum paint. 9. All piping 8 inches and larger either carrying water or tested with water must be supported directly from steel beams or by means of auxiliary steel furnished and installed by the HVAC Contractor. I-beam clamps should not be used. 10. All other piping may be supported by inserts or beam clamps with sufficient holding capacity to support twice the calculated dead load. The use of expansion bolts should be avoided in new construction. B. Hanger Installation 1. Hangers are to have a maximum of 10 feet spacing between hangers, regardless of service. 2. Horizontal piping should be supported with adjustable clevis type hangers. 3. Multiple sets of piping may be supported on trapeze hangers. Lightly loaded trapeze may use channel support system. Other applications require heavy duty steel trapeze constructed of two (2) channels with threaded rods at each end. The channels and rods should be properly sized to support the weight of the pipes and fluid. Double nuts on the rods should be provided. 4. Vertical Piping: 15090-2 May 2009

a. Vertical piping should be supported by heavy wrought iron or steel clamps securely bolted or welded to the piping, and expansion bolted to the wall. b. Vertical piping for cold piping shall utilize pre-insulated riser clamps with inherent vapor barriers. Alternatives will be considered for use by the University. c. In general, use one clamp for each two floors and one clamp at each floor for copper tubing. Where pipes are in open shafts, provide forged steel bar brackets fixed to wall. 5. Clamping pipe 2½ inches and smaller on channel support systems. a. Use straps specifically designed for pipe material used and size to match outside diameter of pipe or tubing. b. Insulated pipes without vapor barrier can be clamped to horizontal channel supports with straps specifically designed to match outside diameter of insulated pipe and accommodate shield to be installed between insulated pipe and channel. c. Use pipe insulated pipe clamps when clamping insulated pipe with vapor barrier. d. Where piping is run above the floor, and is not hung from the ceiling construction or not supported from the floor, such piping shall be supported from the wall with channel support systems with hangers that cradle pipe. If clamping is required, it shall meet requirements as outlined herein before. 6. Hot Water Piping 3 Inches and Larger. a. Hot water piping 3 inches and larger, and chilled water lines with straight runs longer than 150 feet should be supported on roller hangers. For insulated pipe 8 inches and larger and uninsulated pipe 12 inches and larger, provide individual trapeze hangers. b. Wherever hangers using pipe rolls are used, provide approved steel pipe protection saddles, spot welded to the piping at each hanger location. On cold piping, vapor barrier jackets to cover saddle. The void between the saddle and pipe should be filled with insulation in order to prevent sweating. 7. Provide approved roller support, floor stands, wall brackets, etc. for all lines running near the floor or near walls, which can be properly supported or suspended by the floors or walls. Pipelines near walls may also be hung by hangers carried from approved wall brackets at a level higher than the pipe. 8. Piping subject to lateral or vertical movement should be provided with spring hanger type supports. C. Pipe Slopes and Adjustments 1. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and so maximum pipe deflections allowed by ASME B31.9, Building Services Piping, is not exceeded. 2. Adjust hangers to distribute loads evenly on attachments and to achieve indicated slope of pipe. 15090-3 May 2009

3. All hangers and supports shall be capable of screw adjustment after piping is erected with a locking nut provided to prevent loss of adjustment due to pipe vibration. Hangers supporting piping expansion loops, bends and offsets shall be secured to the building structure in such a manner that horizontal adjustment perpendicular to the run of piping supported may be made to accommodate displacement due to expansion. All such hangers shall be finally adjusted, both in the vertical and horizontal direction, when the supported piping is hot. 4. Inserts a. Furnish, locate and set such inserts and make sure that such inserts are in place when the concrete is poured. Construct inserts of malleable iron or pressed steel with space for rods of all sizes. They shall permit adjustment of bolt in one (1) horizontal direction and shall, when installed in properly cured concrete, develop full strength of bolt. Inserts shall be galvanized. b. Set inserts in position in advance of concrete work. Provide reinforcement rod in concrete for inserts carrying pipe over 4 inches in diameter or ducts over 60 inches wide. c. In areas where the concrete slab is exposed, inserts shall be installed flush with slab surface. 4. If any pipe is to be hung in a space where no inserts have been provided, drill holes in the slab (subject to the Structural Consultant s approval) and provide rods and hanger attached to an approved fishplate or install double expansion shields connected by a 2 x 2 angle, from which the hanger rod is to be suspended. For pipe size 2 inches and under, use single shields but the hanger spacing defined hereinbefore to be reduced to 5-0. The carrying capacity and size of each shield to be calculated on the basis of the spacing indicated above but the minimum size to be 3/8. Shields may be used in concrete slabs only. Shield attachments to existing steel deck to be limited to loads of 500 lbs. Heavier loads to be supported by supplementary structural steel connected to structural beams. Provide all required supplementary steel. 5. Hangers may be directly attached to steel beams of building construction, where they occur, if approved by Structural Engineer. Smaller pipes may be suspended from crosspieces of pipe or steel angles which, in turn, are to be securely fastened to building beams or hung from building concrete construction by means of rods and inserts. The intention is to provide supports which, in each case, will be amply strong and rigid for the load, but which will not weaken or unduly stress the building. D. Anchors 1. Anchor piping where shown on Drawings and as required to localize expansion or to prevent undue strain on piping and branches. Anchors to be entirely separate from hangers. All anchor designs to be submitted for approval and to include piping reactions which respective anchors are capable of supporting. Provide all indicated or required expansion loops. E. Sleeves 1. Provide pipe sleeves for all floor and wall penetrations. 2. Sleeves shall have an internal diameter of at least 1 inch larger than the outside pipe 15090-4 May 2009

size diameter including insulation of the pipe passing through them. Sleeves shall extend at least 1 inch above finish floor elevation. 3. Sleeves for all piping passing through concrete walls or floor slabs shall be 18 gauge galvanized iron. Sleeves shall be set before concrete is poured and before masonry construction is finished. 4. Where pipes pass through sleeves in exterior walls, the space between piping and sleeves shall be completely closed with approved oakum and sealed with mastic, extending at least one (1) inch into sleeve. 5. Where pipes pass through sleeves in foundation walls, a link-seal type waterproof sleeve shall be used similar to link-seal sleeve Model CR. Sleeves shall be set with ends flush with all faces. 6. Provide for exposed piping, both bare and covered, approved-type escutcheons where they pass through wall, partition, floor or ceiling; on bare pipes, held in place by setscrews. Provide special deep-type escutcheons for sleeves, hubs or fittings that project from wall, partition, floor or ceiling. Escutcheons in finished areas shall be chrome-plated. 7. Where pipes pass through construction required to have a fire-resistance rating, they shall be provided with a fireproof system for the specific pipe material, pipe size, insulation and wall of floor material. Provide appropriate BSA number in shop drawing submittals. END OF SECTION 15090-5 May 2009