Mechanical Services Standard Specification Compressed Air Systems. May For ROYAL HOLLOWAY UNIVERSITY OF LONDON

Size: px
Start display at page:

Download "Mechanical Services Standard Specification 5.0 - Compressed Air Systems. May 2010. For ROYAL HOLLOWAY UNIVERSITY OF LONDON"

Transcription

1 Mechanical Services Standard Specification Compressed Air Systems May 2010 For ROYAL HOLLOWAY UNIVERSITY OF LONDON

2 Prepared For The Estates Division By: Hulley & Kirkwood Consulting Engineers Ltd Castle House, Horizon Centre Upper High Street Epsom Surrey KT17 4RS (t): (f): (e): (w): Author: Checked: Approved: David Bantock/Andrew Wakelam Wayne Shipley Wayne Shipley Page 2

3 AMENDMENTS Author Date/Rev Description D Bantock / A Wakelam January 2010 Draft Issue W Shipley May 2010 Comments incorporated after meeting with RHUL Page 3

4 Index: 5.1 INTRODUCTION PIPEWORK General Pipework Preparation Fittings Dezincification Inaccessible Services Minimum Clearances Pipes Passing Through Walls Sleeve / Pipe Clearance Fire Rated Sleeves Wall Clearance Supports Suspended Pipework Wall Mounted Pipework Spacing Expansion Devices Electrical Continuity (Expansion Devices) Care and Storage of Pipework Care of Pipes Gaskets and Fittings Open Ends Connectors Plant Items Draining, Venting and Isolating Requirements Drain Cocks Pipework and Fittings Steel Pipework and Joints Steel Fittings Copper Pipework Joints and Fittings Plastic Pipework and Fittings Compressed Air System Components...12 Page 4

5 5.1 INTRODUCTION This specification covers the requirements for providing compressed air pipework systems associated with general usage. It does not include specialist application associated with medical research, etc. Specialist installers fully conversant and experienced with medical gas systems would normally be engaged to undertake this work. Installers undertaking compressed air systems should be fully qualified and experienced in the supply, installation and commissioning of these systems at the various working pressures. The use and application of material covered in this specification shall be in accordance with the system working pressure and application as identified by Royal Holloway University of London. ALL WORKS ARE TO BE INSPECTED BY THE TENDERING CONTRACTOR PRIOR TO PRICING HEALTH AND SAFETY STATEMENT Health and Safety precautions are required to be taken during the process of undertaking works within buildings cannot be underestimated. Reference shall be made to Royal Holloway University Health and Safety Policy and Contractors Guidance documents available from Royal Holloway University of London Estates Office. The Health and Safety Executive (HSE) publish a series of guidance documents regarding all many different methods of protecting the workforce and people in general when working with hazardous chemicals (COSH) and undertaking potential dangerous work activities. Installers engaged in any work shall be registered with the Construction Skills Certificate Scheme (CSCS) and be in possession of a valid skills card. Page 5

6 5.2 PIPEWORK General The Installers shall allow for installing services in a coordinated manner setting round obstructions to circumvent site difficulties which may not be obvious from the drawings as applicable issued with the works package. All pipework unless specifically identified shall be concealed and installed within false ceilings and architecturally designed service ducts. Pipework in visually exposed conditions shall be installed to have the neatest practicable finish. Pipes generally shall follow the contour of walls etc. Vertical pipes shall be plumb, without off-sets and be set close to local projections in order to follow their lines. No joints shall be made inside the thickness of walls, partitions, floors or ceilings. No pipework shall be concealed withing walls or buried in floors Pipework Preparation Dependent upon the materials being used pipework shall be prepared in strict accordance with the manufacturers recommendations with any lubrication liquids being cleaned off to the manufacturers standards Fittings Pipe fittings shall be installed in such a manner that air or condensate cannot be trapped and pipes can be drained. Care shall be taken to avoid the defacing of fittings. Spanners of the correct size shall be used on all hexagons. Fittings shall be rejected if badly marked and the Installer shall replace such at his own expense Dezincification All fittings, valves, cocks, etc. except where otherwise specified (e.g. cast iron), shall be manufactured from copper, gunmetal, bronze or other agreed materials to prevent dezincification Inaccessible Services All steel pipework runs located within inaccessible areas (e.g. above plaster ceilings, obstructed by ductwork etc.), shall be welded, and all copper pipework shall be brazed. Screwed, compression and flanged joints shall not be permitted in inaccessible locations. The emphasis shall be to avoid joints wherever possible. All pipework tube in contact with the soil or building fabric shall be protected by being twice wrapped in Denso tape or similar and equally agreed. Page 6

7 Minimum Clearances Pipes shall be installed so as to give the following minimum clearances between the pipe and adjacent surfaces, as follows; Walls 25mm Ceilings 100mm Finished Floors 165mm Adjacent Pipes 150mm Pipes to adjacent conduit or trunking 100mm Pipes adjacent to electrical cables not in conduit or trunking 150mm Pipes Passing Through Walls All pipes passing through walls, floor, ceilings, partitions etc. shall be inserted through sleeves of similar material to the pipe provided as part of the installation works. In exposed to view areas eschutcheon plates shall be provided to conceal the sleeves Sleeve / Pipe Clearance Sleeves shall be free from internal burrs and shall have an internal diameter sufficient to allow the pipe to be fixed clear of the sleeve at all points, with at least 3mm gap between sleeve and pipe at all points Fire Rated Sleeves Pipes passing through internal walls, floors or partitions, which are fire barriers, shall have a fire sleeve that complies with the current Building Regulations and tested to BS 476 for a minimum of 2 hours Wall Clearance Sleeves shall be of sufficient length to clear the face of finished wall or ceiling by at least 3mm Supports The Installer shall supply, fix and accurately set out all supports, bolts etc. necessary to suit the runs of pipework. The supports shall be suitable for the duty required and the areas in which the pipe is run. The type of support shall be dependant on location, type and size of the pipework Suspended Pipework Brackets shall consist of ball hanger assemblies comprising split pipe gland or one piece pipe clip, drop rod, locknut and male ball hanger. Page 7

8 For copper pipework, brackets, clips and glands shall be manufactured from gunmetal or brass, for mild steel and galvanised steel pipework, they shall be of a similar material to the pipe. For plastic pipework the selected manufacturers products and recommendations or equal shall be applied. The Installer shall make his own fixings to the structure and prior to any works being undertaken the Installer shall agree the method of fixing to comply with the structural limitations and the requirements of Royal Holloway University of London Wall Mounted Pipework Brackets for vertical pipework shall be of the rigid type to guide the pipework and shall comprise a two piece pipe gland, locknut and screwed rod. For copper pipework, brackets, clips and glands shall be manufactured from gunmetal or brass, for mild steel and galvanised steel pipework, they shall be of a similar material to the pipe. Supports for pipework to be chrome plated shall be of similar finish but the support assembly shall comprise split pipe ring, extended nipple and back plate securely fixed to the structure. All brackets and hangers shall be installed with special attention to freedom for lengthways expansion, either in horizontal or vertical plane and to levels for air elimination and drainage. Supports for rise and drop pipes shall be arranged to allow freedom for expansion movement or horizontal runs. Pipes shall be adequately supported at bends, tees and where changes of direction occur. Vertical risers shall be supported at the base to withstand total weight. Branches from risers shall not be used as means of support for the riser. Valves 76mm and above shall be individually supported. Where it is not practicable to use standard type brackets the Contractor shall supply and fix suitable purpose made supports to suit the position. All pipelines shall be separately supported and pipes slung from other pipes shall not be allowed. "Double" type hangers shall not be used due to the differential in expansion and contraction of the two pipelines and the difficulty of doing work on one pipeline without disturbing the other. All necessary metal supports, tees, angle or channel sections, screws, bolts etc. shall be provided and fixed by the Installer who shall be responsible for the accurate setting of same. For plastic pipework the Installer shall follow the manufacturers materials recommendations for compatibility with the pipework being used. Page 8

9 Spacing The spacings between pipe supports shall not exceed the following values: Note: Additional bracketry should also be considered where directional changes occur. Pipe Material Mild Steel Pipe Nominal Bore Intervals for Horizontal Runs mm m m Intervals for Vertical Runs Light Gauge Copper and above Plastic 16mm 20mm 25mm 32mm 40mm 50mm 67mm 75mm 90mm The support distances shall also be subject to the selected manufacturers recommendations and materials used. Horizontal and vertical pipe fixings and supports shall be arranged at intervals not greater than those shown in the above table for plastic pipework. They shall also be subject to the selected manufacturers recommendations and materials used Expansion Devices The Installer shall be responsible for the design of expansion systems that may be required. For plastic pipework the selected pipework manufacturers should provide all relevant technical data. Expansion of pipework where possible shall be taken up by natural off-sets and changes of direction of pipe runs. Where this cannot be achieved, the Installer shall provide expansion loops, angular expansion compensators, and axial expansion compensators to suit. Page 9

10 Adequate provision shall also be made at all connections to equipment and appliances to avoid stress due to contraction and expansion Electrical Continuity (Expansion Devices) The pipework installations shall be electrically continuous up to and including the plant and equipment. The Installer shall provide and install earth bonding across all flexible joints including those on plant and equipment as necessary. If a mixture of steel, copper and plastic pipework is installed earth bonding of plant and all components shall be provided. 5. Care and Storage of Pipework It is imperative that a high standard of cleanliness is maintained to a standard in order that the cleanliness test as described in ASTM B Clause 12 can be maintained. The Installer shall at all times, using the accepted correct lifting tackle, take great care in offloading and handling pipes and fittings of all types so as to avoid damage to the material and any protective coatings or coverings. Suitable storage areas on site shall be agreed with the client and proper supports to carry pipework clear of the ground shall be used, particularly in damp areas and outdoors. The Installer shall provide suitable protection and/or covers for pipes stored outdoors in order to protect them from the weather and in the case of plastic pipework from solar degradation. Royal Holloway University of London shall reserve the right to reject or have rectified at the Installer's expense any damaged materials Care of Pipes Gaskets and Fittings The Installer shall at all times observe the installation and storage procedure as recommended by the Manufacturers. Gaskets shall be carefully stored to prevent damage. RHUL reserve the right to require any damaged materials to be removed from site Open Ends Care shall be exercised during the erection of pipework to ensure that foreign matter is not allowed to remain on or enter the pipes. When any portion of the installation is left open for any purpose whatsoever, the open end shall be temporarily sealed with purpose made plugs or blanking caps manufactured from sound wooden, metal or plastic materials. Rags, paper or similar substances shall not be used under any circumstances. A valve fitted at the end of a disconnected pipe shall not be considered satisfactory to prevent the ingress of foreign matter. All open ended pipework shall be permanently capped upon completion. Failure to comply with this instruction shall mean that Royal Holloway University of London shall have the right to instruct the Installer that pipework is left uncovered shall be dismantled and the pipework blown-through and/or cleaned at no expense to Royal Holloway University of London. Page 10

11 5.2.5 Connectors Unless otherwise specified, pipelines up to and including 50mm connectors shall be unions, or couplings (Cu) of materials suitable for the service. In pipelines 65mm, 67mm(Cu) and above, connectors shall consist of flanges made of an appropriate material and specification to BS Standards. Sockets and backnuts shall not be used under any circumstances Plant Items All connections to plant and equipment requiring internal inspection and maintenance shall be made using compatible coupling/flanges and positioned as to enable such inspections and maintenance readily and conveniently to be undertaken with the minimum disturbance of pipework and thermal insulation Draining, Venting and Isolating Requirements All pipework shall be installed with sufficient gradient to ensure adequate venting and draining. The Installer shall be responsible for providing such draining and air release arrangements in the form of drain cocks or air vents, type as are specified and as are required to ensure that all sections and subsidiary sections of the installation can be completely drained. Fittings for draining and venting shall be suitable for the working pressure of the systems to which they are connected Drain Cocks Drain cocks shall be positioned as necessary to completely drain the installation and sections as required during operation. Drain cocks installed above floor level shall be fixed as unobtrusively as possible. Drain cocks shall be finished to match the pipework to which they are connected Pipework and Fittings The section of pipework and fittings for extensions or modifications to existing systems shall generally be of the same materials and generally traditional metal pipework. Where the Installer wishes to offer a different material, agreement shall be obtained from Royal Holloway University of London. All jointing methods and compounds shall be fully compatible with the materials being used. Completely new systems shall be reviewed for the best choice of materials, be compatible with the building usage, and system operating requirements. The materials currently available include steel, copper and plastic selected to suit the operating temperatures, pressures and application. Jointing methods include, screwed, welded, grooved, press fit, solvent welded, fusion welded, soldered, brazed and compression. Page 11

12 Steel Pipework and Joints Steel pipework and joints shall be mild steel galvanised or black medium weight or heavy weight manufactured in accordance with BS EN 10255: Joints shall be screwed or welded up to and including 50mm dia. Above this pipework shall be welded with flanged joints to be provided in accordance with BS EN Bolting of steel flanges shall be in accordance with BS EN Steel Fittings Steel fittings shall be in accordance with BS :2000 and 1256:2000 for malleable cast iron and copper alloy. Steel welded fittings shall be in accordance with BS EN :1999. Threaded fittings shall also be in accordance with BS Copper Pipework Joints and Fittings Copper pipework shall be light gauge in accordance with BS EN The following fittings and jointing methods may be applied to suit the application. (a) Capillary soldered fittings to BS EN 1254 Part 1 (b) Compression fittings to BS EN 1254 Part 2 (c) Push fit fittings (copper and plastic) to BS EN 1057 Suitable manufacturers shall be as Pegler/Yorkshire range, including Tectite, Kuterlite, Prestex and XPress Plastic Pipework and Fittings Durapipe manufacture Air-Line Xtra which is a specially formulated blend of ABS as is suitable for a continuous operation at 12.5 bar at 20 o C with a 30 year design life. Durapipe provide all fittings and valves and if used subject to agreement by Royal Holloway University of London, installation shall be carried out in strict adherence to the manufacturers instruction. The size range is from 16mm to 110mm. Alternative manufacturers may be considered but shall be equal and agreed to the satisfaction of Royal Holloway University of London Compressed Air System Components This section of the specification provides guidance as to the type and quality of components that would be acceptable to Royal Holloway University of London for use on compressed air systems. Spirax Sarco Ltd are a major manufacturer and specialist for compressed air components and the following products are available for selection and use on Royal Holloway University of London projects as required. Page 12

13 a) Spirax - Monnier Ultra Clean Compressed Air Filters b) Spirax - Monnier Compressed Air Regulators c) Spirax - Monnier Air Lubricants d) Spirax - Monnier Compressed Air Filter/Regulators e) Spirax - Airodyn Compressed Air Drain Trap f) Spirax - Air and Gas Trap g) Spirax Dri-line MK2 Compressed Air Drain Trap h) Spirax - Monnier Automatic Drain Valve i) Spirax - Monnier Venting and Non-Venting Ball Valve Page 13

Mechanical Services Standard Specification 9.0 - Above Ground Soil, Waste and Ventilation Pipes

Mechanical Services Standard Specification 9.0 - Above Ground Soil, Waste and Ventilation Pipes Mechanical Services Standard Specification 9.0 - Above Ground Soil, Waste and Ventilation Pipes May 2010 For ROYAL HOLLOWAY UNIVERSITY OF LONDON Prepared For The Estates Division By: Hulley & Kirkwood

More information

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant

More information

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant). Fittings for CO 2 Pipe Threads Pipe thread references quoted in this catalogue conform with the requirements specified in the latest issue and amendments of the following ISO Standards: ISO 7-1 (BS21)

More information

PBX Series Quick Fit Connector Bimetallic Steam Traps

PBX Series Quick Fit Connector Bimetallic Steam Traps 6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2 STANDARD for Plumbing, Heating, Hot Water, Cold Water & Electrical work undertaken by owners within the building known as Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers

More information

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose: PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

ASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.

ASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16. ASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.4-1998 - Cast Iron Threaded Fittings ASME/ANSI B16.5-1996 - Pipe

More information

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC) APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines

More information

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED.

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED. CAST IRON THE BASICS 1. DO NOT LIFT ON YOUR OWN. 2. ONLY LIFT THE RADIATOR VERTICALLY. 3. DO NOT LIFT MORE THAN 8/10 SECTIONS AT ANY ONE TIME. 4. POSITION THE RADIATOR BEFORE FINAL ASSEMBLY. 5. THIS PRODUCT

More information

This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink.

This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. 1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. The unit will start automatically. Please pay particular

More information

SECTION 15140 - PIPE HANGERS AND SUPPORTS

SECTION 15140 - PIPE HANGERS AND SUPPORTS Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the

More information

SAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE

SAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE 1 Which tool is used to correct internal hi-low when preparing a 4-in. steel pipe for welding? A. 4-in. grinder with cutting disc. B. Mini-grinder with flapper disc. C. Pencil grinder with cone stone.

More information

building engineering services association specification for: Domestic Heating www.thebesa.com

building engineering services association specification for: Domestic Heating www.thebesa.com building engineering services association specification for: Domestic central Heating installation www.thebesa.com building engineering services association acknowledgments Guide to good practice: Domestic

More information

FIX TURE CARRI ERS. 140(a) MPB-2011-USA

FIX TURE CARRI ERS. 140(a) MPB-2011-USA FIXTURE CARRIERS STRUCTURAL FEET The feet are heavy duty cast ductile iron and invertible. No distinction is necessary between right and left hand. Each foot wraps around the specially formed edge of the

More information

1. Description. 2. List of Accessories included A B C F G H

1. Description. 2. List of Accessories included A B C F G H 1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin. The unit will start automatically. Please pay particular attention to the following: Possible danger to

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION THOMAS - G-FLEX GFLEX TECH SPEC CONNECTING INNOVATION JOHANNESBURG TEL: +27 11 794 7594 CAPE TOWN TEL: +27 21 556 5258 POLOKWANE TEL: 015 298 9142 DESIGNER, MANUFACTURER AND DISTRIBUTOR OF PIPE CONNECTION,

More information

REPLACEMENT AIR CONDITIONING UNITS FOR BRITISH EMBASSY RESIDENCE

REPLACEMENT AIR CONDITIONING UNITS FOR BRITISH EMBASSY RESIDENCE REPLACEMENT AIR CONDITIONING UNITS FOR BRITISH EMBASSY RESIDENCE FOREIGN & COMMENWEALTH OFFICE BE BAHRAIN TEL: MAY 2014 EMAIL: TENDER ISSUE: 002/2014 1. GENERAL REQUIREMENTS 1.01 LOCATION OF SITE The British

More information

RMF Engineering 23 05 23

RMF Engineering 23 05 23 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15062 STEAM AND CONDENSATE PIPING PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Comply with the provisions of the following: 1.2 DESIGN CRITERIA 1. ASME B 31.9 Building Services Piping : for

More information

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap 1263050/6 IM-P126-07 ST Issue 6 BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation

More information

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition. DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which

More information

Select Radiators Installation Guide

Select Radiators Installation Guide Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall

More information

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment

More information

Qualification Guide. BPEC 601/2514/7 - Level 1 Diploma in Plumbing Foundation. BPEC 600/9432/1 - Level 2 Diploma in Plumbing Foundation

Qualification Guide. BPEC 601/2514/7 - Level 1 Diploma in Plumbing Foundation. BPEC 600/9432/1 - Level 2 Diploma in Plumbing Foundation Qualification Guide BPEC 601/2514/7 - Level 1 Diploma in Plumbing Foundation BPEC 600/9432/1 - Level 2 Diploma in Plumbing Foundation BPEC 600/5270/3 - Level 2 NVQ Diploma in Plumbing and Heating BPEC

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

3, 4, 6 & 8 Model H Series Alarm Check Valve Installation and Maintenance Guide ", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such

More information

CEILING CASSETTE FAN COIL UNIT

CEILING CASSETTE FAN COIL UNIT CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and

More information

GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS

GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS 13.1 13.2 2006 Edition SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS GENERAL

More information

Syphonic Roof Drainage

Syphonic Roof Drainage Page 1 T E C H N O L O G Y 2:39 pm Syphonic Roof Drainage P L U M B I N G 23/5/03 A D V A N C E D Prod & Price Gd.for PDF Product Guide SYPHONICS Advanced Roof Drainage Technology Geberit Syphonics Geberit

More information

Acumen Enterprises, Inc.

Acumen Enterprises, Inc. Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter

More information

Pipe Clamps and Accessories

Pipe Clamps and Accessories Products 4.0 Products 4.1 Connection options to pipe clamps with Triple-Thread Connector NT 3G (M16, M10, M8) 4.2 Connection options to pipe clamps with Triple-Thread Connector NT 3G (3/8", M12, M10) 4.3

More information

SECTION 02630 STORM DRAINAGE SYSTEM

SECTION 02630 STORM DRAINAGE SYSTEM SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE

More information

The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs:

The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs: RFQ number PR4877728 The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs: A- Supplying and installing 30 high wall A/C split unit 3HP- 24,000

More information

Wastewater Capital Projects Management Standard Construction Specification

Wastewater Capital Projects Management Standard Construction Specification CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,

More information

What to Expect From the Examination. How to Study the Plumbing Codes

What to Expect From the Examination. How to Study the Plumbing Codes Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.

More information

Colonnade Security Pipe

Colonnade Security Pipe Description: Round & Square downpipe formed from extruded 6060 T4 aluminium in various sizes (Ø83mm, Ø108mm, 83x83 mm & 108x108mm*) & supplied with a complete range of accessories i.e. Offsets, bends,

More information

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes CANTEX INC. 301 Commerce Ste 2700 Fort Worth, Texas 76102 817-215-7000 Fax: 817-215-7001 Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes YOUR FULL

More information

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Installation, Operating and Maintenance Instructions 90/4.5.5 Rev. 0 Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Table of Contents SECTION I... 2 INSTALLATION...

More information

Refrigeration Installation 101

Refrigeration Installation 101 Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly

More information

Mechanical Installation

Mechanical Installation Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

How To Design A Gas Dryer

How To Design A Gas Dryer Non Domestic Laundry Gas Appliance Installation Code of Practice Introduction This code of practice has been produced with the assistance of all Companies within the OPL sector of SLEAT because of the

More information

plumbing products guide

plumbing products guide plumbing products guide radiator pipe guide & seals A significant development in the drive to reduce air leakage and heat loss. Installations such as that shown are all too common. The detail is poorly

More information

CATHODIC PROTECTION SYSTEM DESIGN

CATHODIC PROTECTION SYSTEM DESIGN CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of

More information

SIMPLAIR PIPING. www.irtools.com 1-800-376-TOOL

SIMPLAIR PIPING. www.irtools.com 1-800-376-TOOL SIMPLAIR PIPING INGERSOLL-RAND SIMPLAIR PIPING With push-in fittings and lightweight anodized aluminum pipe, a SimplAir system provides ideal connection throughout your entire air distribution system.

More information

Copper and Copper Alloy Tube, Pipe and Fittings

Copper and Copper Alloy Tube, Pipe and Fittings Copper and Copper Alloy Tube, Pipe and Fittings COPPER and COPPER ALLOY TUBE and PIPE Seamless Copper Pipe: Copper pipe is almost pure copper manufactured to the requirements of ASTM B 42 - Standard Specification

More information

SECTION 221413 FACILITY STORM DRAINAGE PIPING

SECTION 221413 FACILITY STORM DRAINAGE PIPING SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

Hose Clamps & Fittings

Hose Clamps & Fittings All Stainless Steel Marine or Underground Hose Clamps 5/16 HEX HEAD SCREW 60000 SERIES Highly corrosion resistant Use for marine or underground applications Stainless Steel Band, Housing Plated Steel Screw

More information

Cylinder head gasket, replacement

Cylinder head gasket, replacement "VCC065612 EN 20110604" 1(7) Cylinder head gasket, replacement Special tools: 999 5098 Disconnect battery earth lead Drain coolant Remove heat shield over exhaust manifold. (Only the two bottom bolts on

More information

ATTENTION This is a general warning that failure to follow instructions could result in poor functioning of the unit.

ATTENTION This is a general warning that failure to follow instructions could result in poor functioning of the unit. 1. Description The macerating system of this unit is installed in a case, specifically designed for horizontal outlet spigots. This macerator is manufactured in a factory which is quality certified to

More information

Engineering Specifications

Engineering Specifications PUREFLOW PEX PRODUCTS PART 1 GENERAL 1.1 SUMMARY 1.1.1 This specification covers Branch & Main, Parallel Water Distribution Systems (MANABLOC), Cross-linked Polyethylene tubing and fittings using PEX Press

More information

Coolflo Safe Touch Shower Mixing Valve ST20015CP

Coolflo Safe Touch Shower Mixing Valve ST20015CP Coolflo Safe Touch Shower Mixing Valve ST20015CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept

More information

GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY

GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY July 2008 1.0 SCOPE These guidelines describe the way in which air conditioning units shall be installed or replaced

More information

When Should Examination Preparation Begin?

When Should Examination Preparation Begin? Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing

More information

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II 1 For your safety Table of Contents 1 For your safety... 3 1.1 About this manual... 3 1.2 Designated use... 3 1.3 Qualification

More information

Maintenance and Service Instruction

Maintenance and Service Instruction Screw pumps E4 Maintenance and Service Instruction E4 1 IMO AB This instruction is valid for all E4 pump models shown on page 2 Contents Page List of components 2 Exploded view/ordering code 3 Service

More information

LS 2540 SEWER LATERALS AND INSPECTION TEES

LS 2540 SEWER LATERALS AND INSPECTION TEES LS 2540 SEWER LATERALS AND INSPECTION TEES A. Summary B. Submittals C. Site Information D. Sewer Pipe and Fittings E. Lateral Locations F. Lateral Installation G. Inspection Tee Installation H. Removal

More information

SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS

SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS PART 1: GENERAL 1.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of AW facilities. Closely coordinate construction work

More information

SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS

SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. The requirements for pipe material and installation in sewer and drainage collection systems. All materials

More information

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions 4057250/8 IM-P405-16 AB Issue 8 ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Operation

More information

08003-1 WATER SERVICE 2

08003-1 WATER SERVICE 2 08003_Mar08_2011.pdf Page 1 of 7 INDEX Page 08003-1 WATER SERVICE 2 1.1 Pipe 2 1.1.1 Copper 2 1.1.2 Polyethylene 2 1.2 Valves and Fittings 2 1.2.1 Main Stops 3 1.2.2 Curb Stops 3 1.2.3 Curb Box 3 1.2.4

More information

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications Page 1 of 12 TI-S21-07 CH Issue 1 Cert. No. LRQ 0963008 ISO 9001 2-Port Self-acting Temperature Control Valve Selection How to select a system Valve selection: 1. Is the application for heating or cooling?

More information

James M. Pleasants Company

James M. Pleasants Company James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:

More information

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible

More information

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

Ergo-Pro Single Line Solar Station Installation and Operating Instructions Rp 3/4 Ergo-Pro Single Line Solar Station Installation and Operating Instructions Item No Pump type 677.21.70 WILO ST 15/6 13 2 4 11 Technical Specifications Max. operating pressure: 6 bar Max. operating

More information

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table

More information

GENERAL MECHANICAL SPECIFICATIONS

GENERAL MECHANICAL SPECIFICATIONS PROPOSED INFRASTRUCTURE DEVELOPMENT FOR KENYA MEDICAL TRAINING COLLEGE AT OL-KALOU (CLASSROOMS' BLOCK - PHASE I ) - FOR THE DEPARTMENT OF HEALTH SERVICES - NYANDARUA COUNTY GENERAL MECHANICAL SPECIFICATIONS

More information

THE PUSH-FIT SOLUTION FOR PLUMBING AND HEATING SYSTEMS

THE PUSH-FIT SOLUTION FOR PLUMBING AND HEATING SYSTEMS THE PUSH-FIT SOLUTION FOR PLUMBING AND HEATING SYSTEMS Speedfit Fittings are suitable for use with copper pipe. Included in this leaflet: Product Guide Trade Tips How Speedfit Works Making a Good Connection

More information

VAD Variable Area Desuperheaters

VAD Variable Area Desuperheaters Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Metal Pressfitting Pipe Systems

Metal Pressfitting Pipe Systems VdS Guidelines for water extinguishing systems VdS 2100-26-3en Requirements and test methods Part 3: Additional provisions for Pipe Systems made of galvanized steel VdS 2100-26-3en : 2012-04 (01) Publishing

More information

VOYAGER 570G. 744A Sprayer Control

VOYAGER 570G. 744A Sprayer Control VOYAGER 570G 744A Sprayer Control U S E R M A N U A L U S E R M A N U A L Table of Contents CHAPTER 1 - INTRODUCTION...1 SYSTEM CONFIGURATIONS...1 KIT CONTENTS...3 CONTROL HOUSING ASSEMBLY...5 CHAPTER

More information

Direct steam injection humidifiers

Direct steam injection humidifiers Direct steam injection humidifiers Direct steam injection gives quality control of air humidity. Research and development in separation, the use of lightweight stainless steel combined a constant temperature

More information

How To Install An Evaporator Coil

How To Install An Evaporator Coil EVAPORATOR COIL INSTALLATION INSTRUCTIONS EVAPORATOR COIL SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... System Requirements... Location Requirements... Drain Requirements... INSTALLATION INSTRUCTIONS...

More information

Installation Instructions 4508 4508S

Installation Instructions 4508 4508S SYMPHONY Spread Lavatory Faucet with Speed Connect Drain Congratulations on purchasing your American Standard faucet with Speed Connect drain, a feature found only on American Standard faucets. Speed Connect

More information

60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING

60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING 60.1 D-O-L FxE expansion couplings are a bolted, split-sleeve design that provides for expansion and contraction at the coupled joint. These couplings are furnished with restraint rings that, when affixed

More information

GPD Rubber Press Seals

GPD Rubber Press Seals GPD Rubber Press Seals Leading in in ideas SYSTEM-TECHNIK GPD Rubber Press Seals Design Available with a rubber thickness of 30 mm for sealing against non-pressing water and a rubber thickness of 60 mm

More information

GEET Fuel Processor Plans

GEET Fuel Processor Plans GEET Fuel Processor Plans This is a greatly simplified Proof of Concept version of the GEET Fuel Processor that just about anyone can build from parts from a local Hardware store in a weekend for very

More information

Building Services Engineering Technician

Building Services Engineering Technician Building Services Engineering Technician A competent Building Services Engineering Technician is expected to be able to demonstrate the following skills and competences: Systems design in the building

More information

SECTION 15105 DUCTILE IRON PIPE AND FITTINGS

SECTION 15105 DUCTILE IRON PIPE AND FITTINGS SECTION 15105 DUCTILE IRON PIPE AND FITTINGS PART 1 GENERAL.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of Owner facilities. Closely coordinate construction work and connections

More information

Installation instruction CASAFLEX - Connecting piece DN 100

Installation instruction CASAFLEX - Connecting piece DN 100 1 CASAFLEX - 11 10 114,3 x 4,5 3 5 2 4 1 7 6 8 12 9 Do not begin work until you have read the installation instruction carefully. 1 internal backing sleeve 2 graphite packing 3 connecting piece 4 thrust

More information

A. This Section includes the following for soil, waste, and vent piping inside the building:

A. This Section includes the following for soil, waste, and vent piping inside the building: June 2014, Draft 01 22 1316 Sanitary and Waste Vent Piping PART 1. GENERAL 1.01 Summary A. This Section includes the following for soil, waste, and vent piping inside the building: 1. Pipe, tube, and fittings.

More information

Operating Instructions

Operating Instructions Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4

More information

Grade Level Spill Containment Manholes

Grade Level Spill Containment Manholes Grade Level Spill Containment Manholes Installation Instructions 705-5 Gallon 715-15 Gallon 725-25 Gallon Manual # Revision Date Changes from Previous Revision F-1307 7 Mar. 2012 Removed reference to pipe

More information

Maintenance and Instruction Manual. December 2011 Rev. 01 Page 1 of 12

Maintenance and Instruction Manual. December 2011 Rev. 01 Page 1 of 12 Maintenance and Instruction Manual December 2011 Rev. 01 Page 1 of 12 Table of Contents 1. Description of product and function 1.1 The NOREVA non-return valve range 1.2 Correct use 1.3 Transport and storage

More information

Stainless Steel Pipe Fabrication

Stainless Steel Pipe Fabrication Stainless Steel Pipe Fabrication Dr M J Fletcher, Delta Consultants, Rutland UK We are now all too familiar with demands to reduce manufacturing costs. Fabrication of stainless steel poses particular problems.

More information

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk 1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance

More information

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION 1. SCOPE Pipe subsoil drains shall be constructed in accordance with this specification and in conformity with the lines, grades and cross-sections shown

More information

This instruction is valid for all ACD pump models shown on page 2

This instruction is valid for all ACD pump models shown on page 2 Screw pumps ACD Maintenance and Service Instruction This instruction is valid for all ACD pump models shown on page 2 Contents Page List of components 2 Exploded view/ordering code 3 Service intervals

More information

FLEXWELL Safety Pipe. Pipe systems for installations Technical details

FLEXWELL Safety Pipe. Pipe systems for installations Technical details Pipe systems for installations Technical details Notes 08.04.2013 T page 2 Contents 4.0 4.0 Contents 4.1 System description 4.100 System description FLEXWELL Safety Pipe 4.105 System description FLEXWELL

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

Chapter 7 Plumbing Connections

Chapter 7 Plumbing Connections Chapter 7 Plumbing Connections 7-1 General All plumbing equipment and installations must be designed, constructed, and installed in accordance with this code and where not specific, to the applicable provisions

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS

SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS 1 SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

Standard terms and conditions

Standard terms and conditions Standard terms and conditions INTRODUCTION For the provision of a water service (Water Supply, Wastewater and Drainage) Under Section 73(2)(a) of the Water Services Act 2012, landowners may be entitled

More information

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The

More information