SECTION HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section
|
|
- Domenic Reynold King
- 8 years ago
- Views:
Transcription
1 SECTION HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section B. All insulation products shall meet ASTM E 84 requirements for flame spread rating of 25 or less and smoke developed rating of 50 or less. All accessories such as adhesives, mastics, cements, tapes, and cloth shall have individual component and installed composite assembly flame spread and smoke developed ratings not exceeding those stated above. Treatment of jackets or facings required to provide minimum ratings shall be permanent. The use of water soluble treatment is prohibited. All products or their shipping containers shall bear a label indicating that flame and smoke ratings do not exceed above requirements. C. Staples alone shall not be used for securing insulation. All insulation shall be installed in accordance with the insulation manufacturer's recommendations and the NIA/MICA manual. Insulation shall be continuous through wall, ceiling, floor and roof openings and sleeves, except at fire/smoke dampers. All manufacturers recommendations for securing insulation, including maximum spacing of fasteners, shall be strictly adhered to. D. Supports for insulated piping shall be outside the insulation. E. Minimum duct and piping insulation thermal characteristics shall comply with the 2000 International Energy Conservation Code with Georgia State Supplements and Amendments ACCEPTABLE MANUFACTURERS A. Insulation trade names referred to hereinafter are intended to set minimum requirements for insulation including type, density, "K" factor, thickness and finish. Approved manufacturers are: 1. Duct Internal Lining- Certainteed 2. Duct Liner Adhesives Childers Foster Miracle Mon-Eco 3. Duct Blanket Insulation (External Wrap)- Certainteed 4. Preformed Fiberglass Pipe Insulation Southern Crescent Technical College
2 Certainteed 5. PVC Pipe Insulation Jackets Ceel-co Proto P.I.C. Plastics Zeston 6. Closed-cell Foam or Polyolefin Pipe Insulation Armstrong Imcoa Nomaco Rubatex B. Where the product of one manufacturer is specified by name, the equivalent products of the other manufacturers listed above will be acceptable SUBMITTALS A. Prior to ordering any products, the contractor shall submit the following minimum information about the items intended to be used for the project: 1. Intended Service (duct liner, refrigerant piping, hot water piping, etc.) 2. Brand of products 3. Thickness and density of insulation 4. External and/or internal facing composition 5. Maximum and minimum temperature ratings 6. Flame spread and smoke developed ratings 7. Thermal Conductivity 8. Facing type and permeability rating 9. Microbial growth resistance capabilities of insulation exposed to airstreams 10. Duct liner adhesive 11. Pipe insulation jacketing and fitting covers 12. Description of adhesives, cements, and tapes 13. Description of mechanical fastening systems 14. Description of finishing and flashing materials and methods 15. Installation instructions B. Information shall be submitted in the form of published data from the manufacturer of each product. A narrative detailing accessories to be used (adhesives, jacketing, etc.) shall be submitted by the contractor in type-written form on the contractor s letterhead. Submittal of the above items of information does not exempt the contractor from supplying additional information to the engineer as required to clearly convey the intended usage and application of products to the project. The burden of proving acceptability of a proposed product rests on the party submitting the request for approval. PART 2 - PRODUCTS 2.01 DUCT INTERNAL LINING Southern Crescent Technical College
3 A. All supply & return ductwork a min. of 10 feet from unit or greater as indicated on floor plans shall be insulated internally with 1" thick, 3.0 lb. / cu. ft. density acoustical duct liner with an acrylic coating on the air stream side that will not support or promote fungal or bacterial growth as rated in accordance with ASTM C 1071, G21 & G22. Acrylic coating shall be treated with an EPA registered anti-microbial agent. Insulation conductivity, or K value, shall not exceed 0.25 BTU/In. sq. ft. per degree F per hour at 75 degrees F per ASTM C 158. The lining noise reduction coefficient shall be a min. of 0.70 based on Type A mounting as tested in accordance with ASTM C 423. Insulation shall be rated for a minimum velocity to prevent surface fiber erosion of 4,000 FPM. All supply and return ductwork shall be lined with 2-1/2" insulation liner, which shall have a minimum R value of 6. B. All exterior supply and return ductwork shall be lined with 2-1/2" insulation liner, which shall have a minimum R value of DUCT BLANKET INSULATION (EXTERNAL WRAP) A. All ducts not internally lined, serving exhaust systems, nor noted on plans as uninsulated shall be insulated on the outside with 2" thick, 0.75 lb. / cu. ft. density fiber glass duct wrap insulation. All duct associated with energy recovery units shall be insulated. Insulation shall have a factory applied vapor barrier facing, F.S.K., consisting of aluminum foil reinforced with fiberglass yarn and laminated to fireresistant kraft. The insulation shall have an installed thermal conductivity not to exceed.26 BTU/In. sq. ft. per degree F per hour at a mean temperature of 75 degrees F per ASTM C 553, Type III. Insulation shall be rated for minimum service temperature of 250 degrees F. B. All outdoor air ductwork, supply air ductwork, and return air ductwork shall be insulated FIBERGLASS PIPE INSULATION A. Insulate all hot water pipe and all condensate pipe inside the building with fiberglass preformed pipe insulation with all service jacket. Insulation shall have a maximum K of 0.23 BTU/Hr., per degree F., per inch per sq. ft., at a mean temperature of 70 degrees F per ASTM C 547, Class 2. Minimum service temperature shall be 600 degrees F. Insulation thicknesses shall be as follows: Hot Water Pipe: ½" to 3" pipe size 1" thick 4" and larger 1-1/2" thick B. Insulation shall be dual-purpose glass fiber type, pre-molded into hollow cylinders having inside diameters which provide close fit over standard pipe and tubing sizes. Standard lengths shall be 3 to 4 feet. C. The factory applied standard jacket shall be all service jacket (ASJ), with a vapor barrier with maximum 0.02 permeability rating, and supplied with self-sealing longitudinal and butt lap (protected with removable paper strip) CELLULAR GLASS PIPE INSULATION A. Cooling tower exterior water piping shall be insulated with 1-1/2" thick cellular glass pipe insulation certified to conform to the requirements of ASTM C 552. Insulation shall be constructed of cellular glass with a minimum density of 8.0 pounds per cubic foot, permeability of 0.00, and with a thermal conductivity factor (K) of 0.33 at 75 degrees F in accordance with ASTM C 177 and C 518. Average compressive strength at breaking point, per ASTM C165, C240, and C552 is 100 psig. Insulation shall be completely non-combustible per ASTM E136. Maximum linear coefficient of thermal expansion per ASTM E228 shall be / degree F. Insulation shall be composed of closed cell glass. Material shall not be constructed with a binding agent. Southern Crescent Technical College
4 B. Insulation vapor barrier treatment shall include white mastic with fabric reinforcement. Mastic and fabric reinforcement material shall be produced and provided by the cellular glass manufacturer. Piping insulation assembly shall be protected with a minimum 0.016" aluminum jacket CLOSED-CELL FOAM OR POLYOLEFIN PIPE INSULATION A. Refrigerant suction piping between evaporator coils and condensing units of split direct-expansion systems shall be insulated with preformed closed-cell elastomeric, engineered polymer foam or polyolefin insulation. Each refrigerant line in systems containing the expansion valve in the outdoor unit shall be insulated. Insulation shall be 1" thick with a minimum density of 1.5 pounds per cubic foot, maximum permeability of 0.10 per ASTM E 96, and with a thermal conductivity factor (K) of 0.29 at 75 degrees F in accordance with ASTM C 177 and C518. Insulation minimum service temperature range shall be between -40 degrees F to 180 degrees F. Longitudinal seams shall be pre-cut with adhesive coatings on each mating surface. Adhesive coatings shall be protected with plastic liner prior to application. Condensate Pipe: All pipe sizes 1" thick PART 3 - EXECUTION 3.01 EXAMINATION AND PREPARATION A. Ductwork and piping shall be tested for leakage prior to applying insulation materials. Duct leakage shall be measured at less than 5% prior to installation of external insulation INSTALLATION A. Insulation shall be installed in complete conformance with the manufacturer's recommendations and the Contract Documents. B. Duct Internal Lining 1. Insulation shall be adhered to the duct with a coverage of fire retardant adhesive tested in accordance with ASTM C-916 with all edges sealed. Edges of duct exposed to the air stream, such as at fan connections, shall be protected by sheet metal nosing. Installation shall be as recommended in SMACNA Duct Construction Standards - Metal and Flexible. Duct sizes shown on plans are clear inside dimensions. Increase actual duct size as required to allow for internal lining thickness. 2. Internal insulation shall be further fastened with Graham welded pins, Tuff Weld nylon hangers or Sticclips on maximum 16" centers on top section where width exceeds 24" and on side section where height exceeds 24". Before installing the insulation, caulk the edges that will butt with a heavy coat of mastic. All surfaces shall be thoroughly cleaned prior to applying adhesive. Insulation applied to top surface of horizontal duct shall overlap the side pieces to provide maximum support. 3. Any abrasions or tears in the acrylic coating shall be repaired per manufacturer s recommendation. Patching adhesive shall meet ASTM C916. No voids on insulation interior sections will be permitted. Insulation shall be true at ends and shall extend 1/8" past return bend of drive side. Insulation on slip side shall be even with drive. No humps will be permitted where sections join. C. Duct Blanket Insulation (External Wrap) Southern Crescent Technical College
5 1. Insulation shall be held in place with staples and U.L. listed pressure sensitive tape. Additional #18 gauge stainless steel wire on 4 foot centers, shall be installed for all ductwork with dimnesions greater than 12" to prevent sagging. All punctures in vapor barrier shall be sealed. All joints shall be lapped and wired. Staples and tape alone for ductwork with dimensions greater than 12" will not be acceptable. Where service access is required, bevel and seal ends of insulation. For insulated ductwork exposed in mechanical rooms and located less than 8'-0" above finished floor, cover with 24 Ga. aluminum jacket. 2. All punctures in vapor barrier facing shall be sealed with SMACNA tape meeting ASTM Standard C-1136, and shall be UL classified FSK tape, minimum 2 mil thickness aluminum. Manufacturers: Shur-Tape, McGill, or Certainteed. 3. All flexible connectors between water source heat pumps and internally insulated ductwork shall be insulated with duct blanket insulation. The external wrap shall extend a minimum 6" passed the flexible connector on both sides. D. Fiberglass Pipe Insulation 1. Locate insulation and cover seams at locations least visible from finished floor. 2. Neatly finish and seal insulation at all supports, protrusions, and interruptions. 3. Secure insulation seams and protective covers with self-sealing laps. Bevel and seal ends of insulation at equipment, flanges, and unions. 4. Provide same thickness wood block and/or cellular glass inserts between metal support shield and piping on piping 1-1/2" in diameter and larger. Inserts shall not be less than the following lengths: 1-1/2" to 2-1/2" pipe size 10" long 3" to 6" pipe size 12" long 8" to 10" pipe size 16" long 5. Pipe exposed in finished spaces, shall be covered with PVC or aluminum jacket. E. Cellular Glass Pipe Insulation 1. The insulation sections shall be bonded together with black asphalt mastic or adhesive manufactured and provided by the insulation manufacturer. 2. Over the insulation, apply a min. 1/16" thick coating of waterproof white mastic, a coating of open mesh synthetic reinforcing fabric, then a second 1/16" coating of waterproof white mastic, applied in such a manner as to insure complete coverage. 3. All insulation located on the exterior of a building shall be protected with a minimum 0.016" aluminum jacket. Jacketing shall be installed so that longitudinal seams are located on bottom side of horizontal piping runs. Jacketing shall be permanently fastened with aluminum bands provided by the jacketing manufacturer at 2'-0" o.c. F. Closed-cell Foam or Polyolefin Pipe Insulation 1. The insulation longitudinal seams shall be bonded together with factory applied adhesive on each mating surface. Butt joints shall be adhered using the insulation manufacturer s recommended bonding adhesive. Insulation shall not be applied in a compressed or stretched condition. Insulation shall not be installed at ambient temperatures below 40 degrees F. 2. Insulation located on the exterior of the building shall be coated with a minimum of two layers of water-proof mastic or other water repelling coating as manufactured or recommended by the insulation manufacturer. Piping shall then be covered with an aluminum jacket entire length. END OF SECTION Southern Crescent Technical College
B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationB. Types of mechanical insulation specified in this section include the following:
SECTION 23 0700 HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Extent of mechanical insulation required by this section is indicated on drawings and schedules, and by requirements of this section. B.
More informationPipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems
Pipe and Equipment Insulations Zeston PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Zeston PVC Insulated Fitting Covers Installation Instructions for Hot,
More informationFiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationDIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION
SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
More informationGuide Specification SECTION 23 07 00 - HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY
SECTION 23 07 00 - HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. HVAC piping insulation, jackets and accessories. 2. HVAC ductwork insulation, jackets, and accessories. 3. Equipment
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 15250 MECHANICAL INSULATION
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Minimum insulation thicknesses shall comply with ASHRAE Standard 90A. B. Provide saddles and shields under pipe hangers. C. If more than one type
More informationDARTMOUTH COLLEGE DESIGN November 15, 2007 &CONSTRUCTION GUIDELINES
SECTION 15250 MECHANICAL INSULATION PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of mechanical insulation products, of types and
More informationSUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES
SUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES 4121 N.W. 37 th Street, Lincoln, NE 68524 Telephone (402) 470-2627 Fax (404) 470-2410 www.gtexhaust.com
More information4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
More informationSTAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
More information07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
More informationCHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
More informationSECTION 23 0700 HVAC INSULATION
PART 1 GENERAL 1.01 QUALITY ASSURANCE SECTION 23 0700 HVAC INSULATION A. FIRE-TEST-RESPONSE CHARACTERISTICS: FLAME-SPREAD INDEX OF 25, AND SMOKE- DEVELOPED INDEX OF 50 FOR INSULATION INSTALLED INDOORS
More informationEcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationAir-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
More informationSECTION 23 07 00 HVAC AND PLUMBING INSULATION
SECTION 23 07 00 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. HVAC and plumbing piping insulation, jackets and accessories. 2. HVAC and plumbing equipment insulation, jackets and accessories. 3.
More informationProduct Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail ri@reefindustries.com Product Guide
More informationSECTION 07 21 16 - PRE-ENGINEERED BUILDING BLANKET INSULATION
PROJECT ARCHITECT RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationGreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
More informationRefrigeration Installation 101
Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly
More informationFINAL December 2012 SECTION 233100 DUCTWORK
SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insula tion shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation
More informationComponents HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
More informationTremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
More informationFire Barrier Duct Wrap 15A
3 Fire Barrier Duct Wrap 15A Commerical Kitchen Grease Duct Fire Protection System Product Data and Installation Instructions Compliance 1998 Edition Complies with International Mechanical Code Complies
More informationHVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA
HVAC Air Duct Leakage Eli P. Howard, III Group Director Technical Resources SMACNA Key Variables that Affect the Amount of Leakage Static Pressure Amount of Duct Openings in the Duct Surface Seams, Joints,
More informationPeel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
More informationDUCT SYSTEMS CHAPTER 6
CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter
More informationDESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
More informationState of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
More informationSECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.
SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More information2.1 DEFINITION OF INSULATION 1 2.2 GENERIC TYPES AND FORMS OF INSULATION 1 2.3 PROPERTIES OF INSULATION 2 2.4 MAJOR INSULATION MATERIALS 4
SECTION 2: 2.1 DEFINITION OF INSULATION 1 2.2 GENERIC TYPES AND FORMS OF INSULATION 1 2.3 PROPERTIES OF INSULATION 2 2.4 MAJOR INSULATION MATERIALS 4 2.5 PROTECTIVE COVERINGS AND FINISHES 5 2.6 PROPERTIES
More informationAll work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
More informationCITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More information1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
More informationCERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
More informationSECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
More informationEXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationFinal inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
More informationVA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
More informationAUTHORIZATION TO MARK
AUTHORIZATION TO MARK This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set
More informationPIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant
More informationAsphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
More informationComment Form on Proposed Gut Rehabilitation Alternatives
Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to energystarhomes@energystar.gov by October 10 th, 2012 with the subject line
More informationCODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping
BUILDING TECHNOLOGIES PROGRAM Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping The intent of the pipe insulation requirements is to reduce temperature changes
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationPreformed Metal Roofing and Siding
Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision
More informationThis permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).
CITY OF MILPITAS Building & Safety Department 455 E. Calaveras Blvd. Milpitas, CA 95035 408-586-3240 www.ci.milpitas.ca.gov RESIDENTIAL AIR CONDITIONING, REPLACEMENT 1. PERMIT INFORMATION: The replacement
More informationRESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
More informationNCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
More informationROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
More informationSECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 230529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.
More informationHVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings
SUCCESS WITH 2012 IECC DELAWARE Recommended Practices for Optimized Energy Savings for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 CHECKLIST: JOB READY 1. 2.
More informationHVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades
Success with 2015 IECC Northeast & Mid-Atlantic Checklist for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED TEMPLATE 2015.1.0 PAGE 1 CHECKLIST: JOB READY 1. 2. 3. 4. 5. 6. 7. 8.
More informationFRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS
Perry Fiberglass Products, Inc. FRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS PERRY FIBERGLASS Perry Fiberglass Products, Inc. is a leading manufacturer of high
More informationColorado State University. Durrell Center Roof Repair
Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon
More informationAcumen Enterprises, Inc.
Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter
More informationWESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC
More informationHoliday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated.
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standing-seam metal roofing, custom fabricated. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: Show installation
More informationSECTION 072100 FIBERGLASS INSULATION
This Specification Section is provided in CSI format for engineers and architects specifying fiberglass insulation manufactured by Knauf Insulation GmbH. in Shelbyville, Indiana. Delete insulation types
More informationBILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad
BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad PLEASE MARK TICK ON LEFT BOX WHICH EQUIPMENT YOU HAVE QUOTED PROPOSAL BASED ON CHINESE EQUIPMENT
More informationSelf-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
More informationDuct Construction Standards. Code Reference: 2013 Title 24, Part 6 Standards 150.0(m)1. UL Ratings
DUCTS - CONSTRUCTION DO YOU HAVE A PHOTO OF THIS? PLEASE SEND IT TO US! installation.feedback@ energycodeace.com R-H-DS1 Duct Construction Standards All air-distribution system ducts and plenums shall
More informationfoot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
More informationRe-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
More informationFLEX-WRAP Foam Pipe Wrap
FLEX-WRAP Foam Pipe Wrap Flex-wrap Inexpensive Used to wrap all pipes in a concrete pour Satisfies UPC Code Sec.315.7 Provides true expansion space between pipe and a concrete pour Product # Dimesions
More informationA. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
More informationSECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
More informationCondensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION
Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION The Condensation Process Condensation occurs when warmer moist air comes in contact with cold surfaces such as framing members, windows
More informationBuilding Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings
BUILDING ENVELOPE DESIGN BY ROXUL Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB Exterior
More information2015 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY
MINNESOTA ENERGY CODE COMPLIANCE COLLABORATIVE 2015 Minnesota Residential Energy Code (MR 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY (July 15, 2015 Update) Note: The following information contains
More informationFSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS
3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS FSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS 11/2 HOUR UL555 RATED UL555S LEAKAGE RATED
More informationSECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
More informationPlease read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
More informationDIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
More informationSECTION 098400 ACOUSTICAL WALL TREATMENT. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.
SECTION 098400 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting
More informationHOW TO INSULATE A CRAWLSPACE
HOW TO INSULATE A CRAWLSPACE Many homes throughout the United States have what are commonly referred to as crawlspaces. Crawlspaces are open spaces underneath a portion of a home. They are very common
More informationCHAPTER 6 DUCT SYSTEMS
CHAPTER 6 DUCT SYSTEMS SECTION MC 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this
More informationENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES
ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES PART 1 - GENERAL 1.1 SCOPE OF WORK SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS PULTRUDED SQUARE TUBE LADDER
More informationCold Room & Refrigeration System (Casserole Assembly) No of units: 1
Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency
More information- - - - Steel Panel Frame. Exterior Steel Sheeting. Optional Rigid Insulation. Optional Steel Insulation Liner
The Kelly Klosure pre-framed modular panel has 4 components that are factory finished to create an easy and versatile bolt-together system in the field. Steel Panel Frame Exterior Steel Sheeting Optional
More informationITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
More informationInstallation Manual CLIFC Fan & Coil Variable Speed
Installation Manual CLIFC Fan & Coil Variable Speed General Description GENERAL DESCRIPTION FANS EQUIPMENT Totally Factory assembled within the unit all piping, wiring, and required controls for operation
More informationROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016
Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.
More informationCOMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
More informationSub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders
INTRODUCTORY INFORMATION TABLE OF CONTENTS 00 0101 PROJECT TITLE PAGE PROCUREMENT REQUIREMENTS (PROJECT MANUAL) Tab A - Invitation for Bids Tab B - Instructions to Bidders Tab C Bid Form for General Bids
More informationPIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta
PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification Number: 3503-11.2.610 Rev. 2 Rubber Lined Steel Pipe and Fittings Mechanically Coupled Plain End Type System Issued Revised Approved
More informationThermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.
Thermwire Freeze Protection Heating Cable Selection Guide Pipe Freeze Protection Heating Cable Pre-Assembled Pipe Freeze Protection Heating Cable with Attached Cord & Plug Thermwire-Comp Refrigeration
More informationGuidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
More informationGUIDELINE SPECIFICATIONS
GUIDELINE SPECIFICATIONS GORDON SOFFIT-SHIELD - An Exterior Metal Soffit System DIVISION 05 5800 or DIVISION 07 7700 Note To Specifier: SOFFIT-SHIELD should be installed by tradesmen that are experienced
More information2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
More informationSECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
More informationBuilding Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings
Building Envelope Design using ROXUL Building Envelope Design using ROXUL (BEDR ) FIREWALL and ROXUL PLUS MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB
More informationH-Stud Area Separation Wall System
12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic
More informationPhone: 1-800-852-8352 FAX: 937-866-4174 website: www.midwestfasteners.com GUIDE TO INSULATION FASTENING
Phone: 1-800-852-8352 FAX: 937-866-4174 website: GUIDE TO INSULATION FASTENING APPLICATION OF WELD PINS 1. WELD PINS IN PLACE. 2. INSTALL INSULATION ON PINS. 3. PRESS WASHERS ON PINS TO 4. EITHER CLIP
More informationBuilt to Last. Built for Beauty. Good. Solid. Logix. TM
Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a
More informationTundra Series Windows January 2016
Tundra Series Windows January 2016 New Construction Installation Instructions Nail Fin, J-Fin and Brickmold Aplications product. ATTENTION! Read and understand all installation instructions before installing
More information