FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager



Similar documents
Excerpts from the Canadian National Building Code (NBC)

CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements

Errata NFPA 70. Proposed 2014 Edition

WHITE PAPER Fire & safety performance standards

800 Communications Circuits

Fire Performance Standard

FIRE-FIGHTING DESIGN BRIEF REPORT

Terms and Definitions In Canada

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

CAN/ULC-S Installation of Fire Alarm Systems Amendment 1. Canadian Fire Alarm Association (CFAA) D. GOODYEAR FIRE CONSULTING

Limited Combustible: The New Standard for Fire Safety

Fire Alarm System Plans Review Checklist Property location Date of Review

University Design Standard. Fire Alarm Systems

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

DTW Works Master Specification Version 2006

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

Building Code Clarifications - 7. Fire Resistance

OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Click here to see a video example of cable being burned outside the controlled lab environment. UL-910 Test for Flame-Propagation and Smoke Density

Fire Alarm System Monitoring - CAN/ULC-S561-03

Fire Alarm Engineering Best Practices. CFAA NCA Technical Seminar 2014

The most important matter is to select the right product based on the environment in which it will be installed and on its use or application.

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

Sprinkler and Fire Alarm Systems for the Building Official

New Ontario Building Code Highlights

How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System

PLAN REVIEW GUIDE FOR FIRE ALARM

Services Enclosures and Protected Shafts - Maintaining Compartmentation

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

SECTION FIRE ALARM AND DETECTION SYSTEM

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

Design Standards Fire Alarm Systems Division (1995 CMS); (2004 CMS) Amended Feb 2015

Lifeline Fire Protection Cable Systems. Cables

Winnipeg Fire Department Fire Prevention Branch

Decree of the Ministry of the Environment on fire safety of ventilation systems

FIRE CODE INTERPRETATION

Overview of Hotel Fire Safety Requirements

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

D A T A C O M M U N I C A T I O N S C O M P E T E N C E C E N T E R

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Fire Barriers & Fire Stopping

St. John s University

How To Build A Two Hour Firewall In Calgary

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

OPEN ITEMS LIST - CONSTRUCTION Project Name: East Central Middle School - Jackson County CLA#: 11003

FIRE-RESISTANCE-RATED CONSTRUCTION

CHAPTER 9 FIRE PROTECTION SYSTEMS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

FIRE-RESISTANCE-RATED CONSTRUCTION

Building Permit Application

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

- 5 - Table1. Maximum Compartment Volumes

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

How To Build A Basement House

Tremco Fire Protection Systems Group Technical Bulletin

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

Fire Alarm Trainee Log Book

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.

MULTI-FAMILY, COMMERCIAL, INDUSTRIAL, AS GOVERNED BY THE BC BUILDING CODE PART 3

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

Ontario s 2012 Building Code Division B, Part 9 (Ontario Regulation 332/12)

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

City of Bettendorf Fire Alarm System Requirements

PARTICIPATION HOUSE 9 BUTTERNUT LANE, MARKHAM

CITY OF FAIRFAX CODE ADMINISTRATION / FAX

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.

Bold items are particular to the City of Euless

Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012

Decree of the Ministry of the Environment. on fire safety of garages

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Fire Life Safety ORC Review Guidelines for PPD Experimental Installations

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

Manual. October 2014 FIRE SAFETY. for existing RMG buildings

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

BUILDING DESIGN STANDARDS UNIVERSITY SERVICES ELECTRONIC SAFETY AND SECURITY - DIVISION 28 Fire Alarm Systems

C. Conform to requirements of Americans with Disabilities Act (ADA).

4 Installation Requirements

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW OVERVIEW OF CODE REQUIREMENTS

FIRE DETECTION AND ALARM

Transcription:

FIRE RATED WIRING What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager

INTRODUCTION OBC requirements for emergency power OBC requirements for emergency power for fire alarm systems and other building services Requirements for protection of electrical conductors Confusion with fire rating duration: one or two hours FT 1, 4, 6, circuit integrity cables, FAS rated wiring

RELEVANT EXPERIENCE Paul Latreille has provided fire protection and life safety services as designer, project manager and branch manager on over design 500 projects in his 27 year career including : Place De Ville Ottawa s largest office complex Every shopping centre in Ottawa The Peace Tower and Centre Block Headquarters for: Nortel, RCMP, PWGSC, Bank of Canada, CSIS, NRCAN, Canadian Space Agency, Mitel, Newbridge, JDS Uniphase

Emergency Power Requirements 3.2.7.8 Fire alarm systems including those with voice require emergency power supplied from a generator, or batteries or a combination of the two Duration: 24 hours of supervisory power followed by full load power for: o 2 hours for buildings falling under 3.2.6 high buildings

Emergency Power Requirements What is a high building you ask? Group A, D, E or F occupancy over 36m in height (grade to floor level of top storey), Group A, D, E, or F occupancy over 18m in height where the cumulative or total occupant load on or above any storey above grader other than the first storey, divided by 1.8 times the width in meters of all exit stairs at that storey exceeds 300, Containing a group B occupancy in which the floor level of the highest storey of that occupancy exceeds 18 m, Containing a floor area or part of a floor area above the third storey designed or intended for a Group B Division 2 or 3 occupancy, and A Group C building over 18 m

Emergency Power Requirements for Fire Alarm Systems Back to emergency power requirements: o 1 hour for a Group B occupancy that is not within the scope of 3.2.6 o 5 minutes for a building not required to have an annunciator, and o 30 minutes for all other buildings.

Emergency Power Requirements for Building Services 3.2.7.9. An emergency power supply has to be capable of operating under a full load for not less than 2 hours and be provided by an emergency generator for: Elevators serving storeys above the first storey in buildings over 36 m high; All fire fighter s elevators Water supply for fire fighting (fire pumps) if dependent upon electrical power for operation and if under 3.2.6 Fans and other electrical equipment for pressurization systems and exit stair protection Fans for smoke venting

Emergency Power Requirements for Building Services (continued) 30 minutes for water supply for firefighting if dependent upon electrical power for operation and if NOT under 3.2.6 No fire rating of wiring required for standpipe only fire pumps that are located in buildings that are not under 3.2.6

Protection of Electrical Conductors 3.2.7.10 Conductors are required to be protected if they fall under in 3.2.6 and if they serve: Fire alarm systems Emergency equipment identified and required under 3.2.6 (fans for smoke movement, venting fans, exhaust fans, elevators, CACF etc) Fire pumps Mechanical systems related to compartments in hospitals, contained use areas, mezzanines and smoke control Emergency lighting

Protection of Electrical Conductors (continued) 3.2.7.10 (continued) Cables to conform to ULC-S139 Fire Test for the Evaluation of Integrity of Electrical Cables and hose stream application and have a circuit integrity rating of not less than 1 hour. OR Circuit integrity refers to the ability of a power or control cable to maintain voltage and current to the load or the ability of a data and optical fibre cable to maintain error free data transfer and retrieval. (from the new S- 139)

Protection of Electrical Conductors (continued) 3.2.7.10 (continued) Cables to be located in a service space that is separated from the remainer of the building by a fire separation that has a fire resistance rating of not less than 1 hour. OR A service space is a space provided in a building to facilitate or conceal the installation of building service facilities such as chutes, ducts, pipes, shafts or wires. Services spaces shall not contain any combustible material other than the electrical conductors being protected. The fire resistance rating of a service space is never waived even if the building is sprinklered. A service room means a room provided in a building to contain equipment associated with building services.

Protection of Electrical Conductors (continued) 3.2.7.10 (continued) Electrical conductors associated with mechanical equipment are to conform to the following: Cables to conform to ULC-S139 Fire Test for the Evaluation of Integrity of Electrical Cables and hose application and have a circuit integrity rating of not less than 2 hours. OR Cables to be located in a service space that is separated from the remained of the building by a fire separation that has a fire resistance rating of not less than 2 hours.

Other Solutions for Protecting Cabling? Conduit encased in concrete (protection of conventional wiring). In these types of systems, 2 inches of concrete is considered adequate for 1-hour fire resistance. Approximately 4 inches of concrete is required to protect conductors for 2 hours. These systems are very cost effective if proper coverage can be achieved throughout the entire circuit. However it is easier to fire rate conduits up to 1 1/2 inches. It is harder to guarantee 2 to 4 inches. Also, non fire-rated junction and pull boxes compromise the system

What Fire Alarm Wiring Do You Have to Protect? If a fire alarm transponder or annunciator located in one fire compartment is connected to a central processing unit or another transponder located in a different fire compartment, the electrical conductors connecting them shall be protected for 1 hour.

What Fire Alarm Wiring Do You Have to Protect? 3.2.7.10(7): Fire alarm system branch circuits within a storey that connect transponders and individual devices need not conform to sentence 2 (ie. 1 hour rating). APPENDIX NOTE:. A level of protection is required for those conductors protecting the major elements of the fire alarm system. 3.2.7.10(7) permits the protection of electrical conductors to be waived for portions connecting a transponder or fault isolation device to the fire alarm input devices ( fire detectors, manual stations etc) or a voice communication transponder to a fire alarm audible signaling device, provided all circuits or portions of the circuits are contained within the same storey

What Fire Alarm Wiring Do You Have to Protect? Did you read that right? What does that mean? This is a critical interpretation. Hardwired systems require all wiring in the riser to be fire rated. Distributed systems would require all wiring between control units stacked vertically to be fire rated and all circuits that supply multiple floors to be likewise fire rated. Signaling circuits (a strobe circuit for example) that serves multiple floors will now be required to be fire rated.

What Fire Alarm Wiring Do You Have to Protect?.

So, one or two hour rated cable? This is an easy one to answer. Its got to be 2 hours. Anyone know why? Pentair (Pyrotenax) only make a 2 hour rated cable. Pentair is the ONLY manufacturer in the world that has a ULC listing for circuit integrity and a fire rating of 2 hours.

Circuit Integrity and Fire Rated Cables an update ULC de-listed all previous CI cables including mineral insulated cables (2012) Pentair re-tested their cables to the revised ULC standard and ULC re-listed their cables as fire rated cables and circuit integrity cables. (2013) NO OTHER CABLES AT ALL ARE ULC LISTED. PERIOD. Draka Life Line - Only UL listed and only for horizontal installation (2014) and only for one specific manufacturers EMT type conduit Radix CI Only UL listed and vertical restrictions of max 28 ft. (2014) RSCC Only UL listed and 480 Volts Max.(2014)

Circuit Integrity vs FT rated cable This is circuit integrity fire rated cables:

Circuit Integrity vs FT rated cable This is FT rated and FAS cables:

FT Ratings and FAS Type Cables An FT rated cable is not rated or tested to endure fire for any duration. It is simply tested to determine its smoke development classification (how much smoke it will produce) and its flame spread rating (how quickly flame will spread along the cable) Can get only FT-1, FT-4, and FT-6 rated cables. An FAS rated cable is one classified and specifically designed for fire alarm and voice communication use and stands for Fire Alarm Signal (FAS). FAS is a cable type. FT is a smoke development and flame propagation rating system An FAS type cable will be FT rated.

FT Ratings Explained FT1 Vertical Flame Test per C.S.A. C22.2 No. 0.3-92 Para 4.11.1 A finished cable shall not propagate a flame or continue to burn for more than one (1) minute after five (5) fifteen (15) second applications of the test flame. There is an interval of fifteen (15) seconds between flame applications. The flame test shall be performed in accordance with Para 4.11.1 of Canadian Standards Association (CSA) Standard C22.2 No. 0.3. In addition, if more than 25% of the indicator flag is burned, the test cable fails. FT1 Cables can be used in Combustible buildings.

FT Ratings Explained FT4 Vertical Flame Test Cables in Cable Trays per C.S.A. C22.2 No. 0.3-92 Para 4.11.4 The FT4 Vertical Flame Test Cables in Cable Trays is similar to the UL-1685 Vertical Tray Flame Test, but is more severe. The FT4 test has its burner mounted at 20 from the horizontal with the burner ports facing up. The UL-1685 Vertical Tray has its burner at 0 from the horizontal. The FT4 samples must be larger than 13mm (.512 ) in diameter. If not, then the cable samples are grouped in units of at least three (3) to obtain a grouped overall diameter of 13mm. The UL-1581 Vertical Tray does not distinguish on cable size. The FT4 has a maximum char height of 1.5 m (59 ) measured from the lower edge of the burner face. The UL- 1685 has a flame height allowable up to approximately 78 measured from the burner. FT4 Cables can be used in Non-Combustible building

FT Ratings Explained FT6 Horizontal Flame & Smoke Test per C.S.A. C22.2 No. 0.3-92 Appendix B Products passing the FT6 Horizontal Flame and Smoke Test are designated FT6 in the column where the trade number appears. This test is for cables which must pass a Horizontal Flame and Smoke Test in accordance with ANSI/NFPA Standard 262-1985 (UL-910). The maximum flame spread shall be 1.50 meters (4.92 ft.). The smoke density shall be 0.5 at peak optical density and 0.15 at maximum average optical density.

Combustible/Non-Combustible Construction Combustible Construction Means that type of construction that does not meet the requirement for noncombustible construction. Combustible means that a material fails to meet the acceptance criteria of CAN/ULC S114, (Standard Method of test for determination of non-combustibility in Building Materials) (ref: NBC Part 1 Section 1.1.3.2). Noncombustible Construction Means that type of construction in which a degree of fire safety is attained by the use of noncombustible materials for structural members and other building assemblies. Non-Combustible means that a material meets the acceptance criteria of CAN/ULC S114, (Standard Method of test for determination of noncombustibility in Building Materials) (ref: NBC Part 1.1.3.2).

When are FT Rated Cables required? 3.1.4. Combustible Construction and 3.1.4.3 Wires and Cables 3.1.5. Noncombustible Construction, 3.1.5.18 Wires and Cables, 3.1.5.21 Wires in Computer Room Floors, 3.6.4.3 Plenum Requirements FT1 rated cables are permitted in buildings of combustible construction and in computer room sub-floors but NOT in ceiling plenums. Alternative (combustible construction only): located in totally enclosed non-combustible raceway, concealed spaces in walls or concrete slabs

When are FT Rated Cables required? FT4 rated cables are permitted in non-combustible construction, anywhere in the building including computer room subfloors. Alternatives (combustible and non-combustible): Located in totally enclosed noncombustible raceway, concealed spaces in walls, concrete slabs, or 1 hour fire separated service room FT-6 rated cables are permitted in combustible and non-combustible construction and can be used in concealed spaces between the ceiling and the floor or the ceiling and the roof used as a plenum.. Alternatives (combustible and non-combustible): FT4 for single conductor electrical wire and cables. Located in totally enclosed noncombustible raceway.

But... FT classified cables are but one of the permitted classifications of cables. Alternatives are: FT1 Alternatives: FT4, FT6, MPP and CMP (plenum rated cables), MPR, CMR, MPG, CMP, MP, CM, CMX, CMH FT4 Alternatives: FT6, MP, CMP (plenum rated cable), MPR, CMR, MPG, CMG FT6 Alternatives: MPP, CMP (plenum rated cable Check with you local AHJ ad refer to the Ontario Electrical Safety Code (table 19)

Summary Emergency power requirements do not dictate cable circuit integrity ratings (1 hour versus 2 hours) Only one cable is ULC listed for circuit integrity and it only comes in a 2 hour rating An FT rating is required for cables in a building but this has nothing to do with circuit integrity or fire rating of cables There are alternatives to FT ratings Caution is to be used if you choose to build a non-combustible enclosure (but please don t do it)

Thank You! www.lrifire.com info@lrifire.com