SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND
|
|
|
- Cornelius Parsons
- 10 years ago
- Views:
Transcription
1 Belden Electronics Division P.O. Box 1980 Richmond, Indiana U.S. Highway 27 South Richmond, Indiana Telephone: Facsimile: SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND BELDEN has put this information together to inform the market of the modifications to the 2002 NEC concerning 300 volt marking on PLTC type cables. Why isn t 300 volts printed on PLTC cable anymore? The 2002 NEC modified the printing requirements that were allowed on the jacket of PLTC type cables. The use of 300 volts or 300 v in the print legend was disallowed because the voltage marking on the cable may be misinterpreted to suggest that the cable may be suitable for Class 1 electric light and power applications. See NEC clause (H) Marking below. PLTC type cables will still have the same applications use as before. PLTC cables are still rated 300 volts but cannot be so marked after May 25, On February 25, 2003 UL issued revisions to UL 13, Standard for Power-Limited Circuit Cables, which governs the listing and marking requirements of PLTC cable. One of those revisions was the removal of the 300 volts or 300 v marking on the cable in accordance with the 2002 NEC. This removal becomes effective May 25, 2003 for all cable manufacturers. Any existing cable that is in stock or anywhere in the industry pipeline which has the 300 volts or 300 v marking will still be an acceptable cable for use. On May 25, 2003 and after cable manufacturers will not be allowed to mark the 300 volts or 300 v marking on PLTC cable or on any label attached to the product. The NEC does allow an exception to allow voltage markings for cables with multiple listings where a voltage marking for one or more listings is required. See NEC clause (H) Exception. KEY POINTS The use of 300 volts or 300 v in the print legend of PLTC type cables is disallowed by the NEC for all cable manufacturers. The effective date for the discontinued use of the 300 volts or 300 v in the jacket print legend or on any label attached to the product is May 25, All cables produced with 300 volts or 300 v markings before May 25, 2003 are acceptable. This covers all inventories in the industry pipeline including manufacturers, distributors, installers, and end users. There is no change in the use application of these cables. A voltage marking exception is permitted on multiple listed cables when required by the other listing. National Electrical Code and NEC are Registered Trademarks of the National Fire Protection Association, Inc., Quincy, MA.
2 Listing and Marking of Class 2, Class 3, and Type PLTC Cables. Class 2, Class 3, and Type PLTC cables installed as wiring within buildings shall be listed as being resistant to the spread of fire and other criteria in accordance with (A) through (G) and shall be marked in accordance with (H). (A) Types CL2P and CL3P. Types CL2P and CL3P plenum cables shall be listed as being suitable for use in ducts, plenums, and other space used for environmental air and shall also be listed as having adequate fire-resistant and low smoke-producing characteristics. FPN: One method of defining low smoke-producing cable is by establishing an acceptable value of the smoke produced when tested in accordance with NFPA , Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces, to a maximum peak optical density of 0.5 and a maximum average optical density of Similarly, one method of defining fire-resistant cables is by establishing a maximum allowable flame travel distance of 1.52 m (5 ft) when tested in accordance with the same test. (B) Types CL2R and CL3R. Types CL2R and CL3R riser cables shall be listed as being suitable for use in a vertical run in a shaft or from floor to floor and shall also be listed as having fire-resistant characteristics capable of preventing the carrying of fire from floor to floor. FPN: One method of defining fire-resistant characteristics capable of preventing the carrying of fire from floor to floor is that the cables pass the requirements of ANSI/UL , Test for Flame Propagation Height of Electrical and Optical-Fiber Cable Installed Vertically in Shafts. (C) Types CL2 and CL3. Types CL2 and CL3 cables shall be listed as being suitable for general-purpose use, with the exception of risers, ducts, plenums, and other space used for environmental air and shall also be listed as being resistant to the spread of fire. the CSA vertical flame test for cables in cable trays, as described in CSA
3 (D) Types CL2X and CL3X. Types CL2X and CL3X limited-use cables shall be listed as being suitable for use in dwellings and for use in raceway and shall also be listed as being resistant to flame spread. FPN: One method of determining that cable is resistant to flame spread is by testing the cable to the VW-1 (vertical-wire) flame test in ANSI/UL , Reference Standard for Electrical Wires, Cables and Flexible Cords. (E) Type PLTC. Type PLTC nonmetallic-sheathed, power-limited tray cable shall be listed as being suitable for cable trays and shall consist of a factory assembly of two or more insulated conductors under a nonmetallic jacket. The insulated conductors shall be 22 AWG through 12 AWG. The conductor material shall be copper (solid or stranded). Insulation on conductors shall be suitable for 300 volts. The cable core shall be either (1) two or more parallel conductors, (2) one or more group assemblies of twisted or parallel conductors, or (3) a combination thereof. A metallic shield or a metallized foil shield with drain wire(s) shall be permitted to be applied either over the cable core, over groups of conductors, or both. The cable shall be listed as being resistant to the spread of fire. The outer jacket shall be a sunlight- and moisture-resistant nonmetallic material. Exception No. 1: Where a smooth metallic sheath, continuous corrugated metallic sheath, or interlocking tape armor is applied over the nonmetallic jacket, an overall nonmetallic jacket shall not be required. On metallicsheathed cable without an overall nonmetallic jacket, the information required in shall be located on the nonmetallic jacket under the sheath. Exception No. 2: Conductors in PLTC cables used for Class 2 thermocouple circuits shall be permitted to be any of the materials used for thermocouple extension wire. the CSA vertical flame test for cables in cable trays, as described in CSA
4 (F) Class 2 and Class 3 Cable Voltage Ratings. Class 2 cables shall have a voltage rating of not less than 150 volts. Class 3 cables shall have a voltage rating of not less than 300 volts. (G) Class 3 Single Conductors. Class 3 single conductors used as other wiring within buildings shall not be smaller than 18 AWG and shall be Type CL3. Conductor types described in (B) that are also listed as Type CL3 shall be permitted. the CSA vertical flame test for cables in cable trays as described in CSA (H) Marking. Cables shall be marked in accordance with (A)(2), (3), (4), and (5) and Table Voltage ratings shall not be marked on the cables. FPN: Voltage markings on cables may be misinterpreted to suggest that the cables may be suitable for Class 1 electric light and power applications. Exception: Voltage markings shall be permitted where the cable has multiple listings and a voltage marking is required for one or more of the listings. FPN: Class 2 and Class 3 cable types are listed in descending order of fire resistance rating, and Class 3 cables are listed above Class 2 cables, because Class 3 cables can substitute for Class 2 cables. Table Cable Markings Cable Marking Type Listing References CL3P Class 3 plenum cable (A), (F), and (H) CL2P Class 2 plenum cable (A) and (H) CL3R Class 3 riser cable (B), (F), and (H) CL2R Class 2 riser cable (B) and (H) PLTC Power-limited tray cable (E) and (H) CL3 Class 3 cable (C), (F), and (H) CL2 Class 2 cable (C), (F), and (H) CL3X Class 3 cable, limited use (D), (F), and (H) CL2X Class 2 cable, limited use (D), (F), and (H)
5 The following is copied from the UL 13 standard, Second Edition, Copyright 2003, Underwriters Laboratories Inc., 1285 Walt Whitman Road, Melville, NY This reprinted material is not the complete and official position of the Underwriters Laboratories Inc. on the referenced subject which is represented only by the standard in its entirety. February 25, 2003 Superseded requirements for the Standard for Power-Limited Circuit Cables UL 13, Second Edition The requirements shown are the current requirements that have been superseded by requirements in revisions issued for this Standard. To retain the current requirements, do not discard the following requirements until the future effective dates are reached. 1.2 (1.2) Type PLTC cable is rated for 300 volts and is so marked. Cables for Class 3 circuits are rated for 300 volts but are not so marked. Cables for Class 2 circuits do not have a voltage rating. See 40.1 (h). 1.2 effective until May 25, 2003 ************************************************************************************** Here is the new wording that becomes effective May 25, Cables for Class 3 circuits are rated for 300 volts but are not so marked. Cables for Class 2 circuits do not have a voltage rating. See 40.1 (h). Revised 1.2 effective May 25, 2003 Sincerely, Gerald Lee Dorna Gerald Lee Dorna [email protected] [email protected] Technical Relations Manager & Product Liability Manager Belden Electronics Division 2200 U. S. Highway 27 South Richmond, IN PH: FAX: April 15, 2003
WHITE PAPER Fire & safety performance standards
WHITE PAPER Fire & safety performance standards Terminologies describing Fire Performance Terminologies describing Fire Performance often present a challenge to understand as how they apply to a cable
Errata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System July 28, 2003 We are pleased to provide the following joint statement by CII,
HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)
Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
AWG: Cat5e: Cat6: Cat6A:
Some of the terms used in the cable business can be vexing to even the most seasoned folks in the industry. If any of this terminology has ever made you scratch your head, you are certainly not alone.
2012 CATALOG AEROSPACE VVIRE & CABLE INC. aerospacewire.com
* 2012 CATALOG AEROSPACE VVIRE & CABLE INC. A VV aerospacewire.com W e p r o u d l y m a n u f a c t u r e h i - t e m p w i r e & c a b l e. PLENUM CABLE. INDUSTRIAL CABLE. TRAY CABLE. MILITARY WIRE.
UNDERSTANDING. C&M Corporation 51 South Walnut Street, Wauregan, CT 06387 Phone: 860.774.4812 Fax: 860.774.7330 www.cmcorporation.
UNDERSTANDING UNDERSTANDING NFPA 79 By Ned Lloyd and Mike Levesque NFPA-79 is the electrical standard that has been developed by the National Fire Protection Association (NFPA) and is intended to minimize
2011 National Electrical Code
2011 National Electrical Code Changes of Interest to Data/Comm Cabling Contractors, Users and Code Enforcement Officials The National Electrical Code is published by the National Fire Protection Association
Specification SFTP CAT6 Network Cable 23AWG CU
Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)
Safety & Performance in the Wire and Cable Industry
Safety & Performance in the Listed vs. Verified: Marks, Logos and Programs Written by: Antoine Pelletier, Team Leader, Global Cabling Products Larry Todd, Chief Engineer Intertek [email protected] 1-800-WORLDLAB
RoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables
RoHS DATA, COAXIAL AND ELECTRONIC D A TA, C O A X I A L, A N D EL E CTRON I C Cables Index SOLID MULTI-CONDUCTOR CABLES STRANDED MULTI-CONDUCTOR CABLES SPEAKER/ZIP WIRE THERMOSTAT CABLE FIRE ALARM CABLE
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
AN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY. (The following code explanations are to be used with a copy of the 2011 NEC.
AN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY (The following code explanations are to be used with a copy of the 2011 NEC.) To obtain a copy of the NEC contact: National Fire Protection Association
Security & Control Cables
Security & Control Cables Our multi-conductor cables are manufactured in a wide variety of gage sizes, shielding configurations and jacketing materials including plenum, riser and general purpose. Applications
3200 West 22nd Street Erie, PA 16506 ph 814.835.2900 fax 814.835.2904 www.premierconduit.com
200 West 22nd Street Erie, PA 16506 ph 814.85.2900 fax 814.85.2904 www.premierconduit.com Premier-Plenum Duct Premier Plenum Duct is a flexible, non-metallic, corrugated raceway used for effective interior
How To Buy Honeywell Genesis Series Fire Alarm Cables
Fire Wire Genesis Series Cables for Fire-Lite Alarms We've Got a Cable for That! Genesis Series Cables for Firelite DIRECTORY ANN-BUS... 2 Signaling Line Circuits (SLC)... 3 Conventional 2&4 Wire Initiating
Electrical Code (NEC) Snake Tray Cable Management Solutions
Cable Pathway Use and Selection and the National Electrical Code (NEC) By Eric J. Sadler, BSME MIT Snake Tray Cable Management Solutions References: All references to the NEC in this presentation are taken
Cable Substitution Chart
Cable Substitution Chart Per 2005 NEC FIRE-RESISTANCE LEVEL Test Requirements 800 725 760 820 NEC ARTICLES 770 830 PLENUM 4 (Highest) CMP MULTI-CONDUCTOR COAX NFP A 262 (UL-910 Steiner Tunnel) CL3P CL2P
Fire Performance Standard
Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED
Unarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
Code Compliance for Spring Steel Fasteners Based on the 2005 NEC
Code Compliance for Spring Steel Fasteners Based on the 2005 NEC B-Line has recognized the need for a reference source, detailing the National Electrical Code requirements for Spring Steel Fasteners. The
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations Fire Protection Review for the Fixed Target ES&H Review Committee September 2010 By James Priest PhD DRAFT Overview: When reviewing
FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager
FIRE RATED WIRING What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager INTRODUCTION OBC requirements for emergency power OBC requirements for emergency power for fire alarm systems and other building
The most important matter is to select the right product based on the environment in which it will be installed and on its use or application.
Communication cables and burning behaviour international regulations Different regulations and standards apply depending on the geographic location. Europe is normally governed by CENELEC (EN), but in
Copper Cabling Infrastructure Offering
Copper Cabling Infrastructure Offering High-Speed Copper Cabling Systems The deployment of high speed cabling systems has been increasing rapidly as data centers enable their physical infrastructure with
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
MANUFACTURER S CERTIFICATE OF COMPLIANCE
s Type AC (Armored Clad) aluminum and steel interlocked metal clad 600-volt cable is produced 100% in the United States of America using accepted practices and quality assurance procedures to comply with
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
CABLE TRAY MANUAL Based on the 2011 National Electrical Code
2011 CABLE TRAY MANUAL Based on the 2011 National Electrical Code MAN-1 Table of Contents Page No. Introduction... MAN-3 Why Cable Tray? Safety... MAN-4 Dependability... MAN-4 MAN-5 Space Savings... MAN-5
LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m
FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2
Cable Products HONEYWELL SECURITY & CUSTOM ELECTRONICS. Honeywell's Genesis Series provides a full range
HONEYWELL SECURITY & CUSTOM ELECTRONICS Cable Products Honeywell's Genesis Series provides a full range of low voltage cables for security, fire, sound, voice and data, video, structured cabling and other
Report. Analysis of Cablofil Cable Tray for Power Circuits. Reference: RP10002
AC Z Kimball Power Electronics 503 Mustang Drive Mahomet, IL 61853 Report Reference: Issue: 003 Status: Issued Author: Jonathan Kimball Created: 13 June, 2004 Copyright Jonathan Kimball 2004. All Rights
The Instrumentation Cable Experts
1 The Instrumentation Cable Experts Facilities Head office & factory 1300 Industrial Boulevard Mt Pleasant, Texas 75455, USA www.dekoroncable.com Stocking Centres USA Mt Pleasant and Houston Singapore
Outside Telephone Cable
Outside Telephone Cable Filled Core. Moisture Barrier. Description Soft copper wires insulated with high density polyethylene, foam skin or solid. Filled core, conformed by groups of pairs or by unit of
EcoFlex Cable. Smaller. Lighter. Tougher. 100% Recyclable.
EcoFlex Cable Smaller. Lighter. Tougher. 100% Recyclable. Total Performance, Completely Recyclable EcoFlex cable is Alpha Wire s newest innovation in control cabling. A true engineering breakthrough, EcoFlex
Building Cables and Wires
Building Cables and Wires 4 Introduction alfanar is equipped with state-of-the-art manufacturing facilities such as latest machineries, instrumentation, quality control and testing laboratory, etc., for
Lifeline Fire Protection Cable Systems. Cables
Lifeline Fire Protection Cable Systems Cables Lifeline - Superior Innovation in Fire Protection Cable Systems Leadership in two-hour cables Introduced by Draka Engineered Specialties, Lifeline two hour
Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks
Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Introduction This document presents the fundamental aspects of cable and conductor selection for connecting pad mounted shunt
Serial Data Grade Cables
VGA INPUT MONITOR OUT VGA INPUT MONITOR OUT 3.5mm STEREO MINI 3.5mm STEREO MINI L R Audio L R Audio AUDIO INPUTS + - + - AUDIO INPUTS + - + - AMPLIFIED OUTPUT 4/8 ohm COM 70V 100V AMPLIFIED OUTPUT 4/8
Limited Combustible: The New Standard for Fire Safety
Limited Combustible: The New Standard for Fire Safety Written by Daniel Kennefick Limited Combustible Product Business Manager Berk-Tek, A Nexans Company Since the advent of client server computing in
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
INTRODUCTION TO CHAPTER 3 WIRING METHODS AND MATERIALS
CHAPTER 3 WIRING METHODS AND MATERIALS INTRODUCTION TO CHAPTER 3 WIRING METHODS AND MATERIALS Chapter 2 provided the general rules for wiring and protection of conductors, and was primarily concerned with
Requirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
STABILOY BRAND FeeDeR SOLuTIONS
STABILOY BRAND Feeder Solutions DATA CENTER Introduction General Cable understands that data centers depend heavily on a steady, reliable and scalable source of power. That is why our STABILOY Brand aluminum
STABILOY BRAND FeeDeR SOLuTIONS
STABILOY BRAND Feeder Solutions DATA CENTER Introduction General Cable understands that data centers depend heavily on a steady, reliable and scalable source of power. That is why our STABILOY Brand aluminum
WHY CABLE TRAY? BECAUSE A CABLE TRAY WIRING SYSTEM PROVIDES SAFE AND DEPENDABLE WAYS TO SAVE NOW AND LATER
Large numbers of electrical engineers have limited detail knowledge concerning wiring systems. There is the tendency by engineers to avoid becoming involved in the details of wiring systems, leaving the
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
Hook-Up and Lead Wire
3.1 Hook-Up and Lead Wire 3 Table of Contents Hook-Up & Lead Wire Page Introduction: UL Style & CSA Type Listings 3.2 PVC 3.3 3.8 300V, 80 C 3.3 300V, 105 C 3.4 600V, 105 C 3.5 (Type MW) MIL-W-76C-PVC:
Click here to see a video example of cable being burned outside the controlled lab environment. UL-910 Test for Flame-Propagation and Smoke Density
Plenum (CMP) Rated Cable Often found on building material lists, the Plenum rating (CMP) signifies cable that has passed stringent burn testing and is suitable for installation into Air Plenum spaces.
KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
rpsa FIRE PROTECTION ENGINEERS
R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Sample Fire Alarm System Calculations 1. A fire alarm manufacturer specifies
Communication and Control Cable 1-3 6. Fire Alarm Cable 4 7-6 0. Coaxial Cable ( CAT V / M ATV & CCTV Cables) 6 1-7 8
West Penn Wire Cables Communication and Control Cable 1-3 6 A q u a s e a l C a b l e & Process Control Cables (600 Volt) 37-46 Fire Alarm Cable 4 7-6 0 Coaxial Cable ( CAT V / M ATV & CCTV Cables) 6 1-7
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
West Penn Wire. Access Control Systems and Cables WEST PENN WIRE CABLE WITH CONFIDENCE
West Penn Wire Access Control Systems and Cables Access Control Cables AWG Size CARD READER CABLES # of Cond. CMR Shielded CMP Shielded CMR Unshielded CMP Unshielded 22 4 3241 253241B 241 25241B 22 6 3270
100% EMI Emission Containment
100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive
A quick product finder for commercial applications JUDD WIRE INC. A member of the Sumitomo Electric Industries group of companies
A quick product finder for commercial applications JUDD WIRE INC. A member of the Sumitomo Electric Industries group of companies Select, Customize, Order & Receive Products with Ease This catalog contains
CCW Continuously Corrugated Welded Cable A RMORED CAB LE FO R HAZAR D O U S LOCATI O N S
CCW Continuously Corrugated Welded Cable A RMORED CAB LE FO R HAZAR D O U S LOCATI O N S OCTOBER 2014 CCW Servicing Industrial and Specialty Applications This catalog contains in-depth information on the
KNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
Exane 125 Drilling Rig and Commercial Marine Cable
Exane 125 Drilling Rig and Commercial Marine Cable Over 20 Years of Superior Perfomance On Oil Rigs Around The World Engineered Wire & Cable for Demanding Applications Certified as Type P per IEEE-45 STD
MHR-2 Cable. MHR-5/6 Cable. MHRHF-5 Cable. M59-3/5/6 Cable. RG59-3MHR-3 Cable. RG6 Cable. MHR-5STP-2 Cable. MHRVGA Cable.
MHR-2 Two Conductor Mini High Resolution S-Video Cable Plenum Rated Version Available MHR-5/6 Five/Six Conductor Mini High Resolution Cable Plenum Rated Version Available MHR-2 Cable MHRHF-5 Five Conductor
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*
Gexol CIR Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL n Available in Standard and Arctic Grade Jackets n Highly
Section 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.
NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating
Sound, Alarm & Security Cable 7
Electronics Sound, Alarm & Security Cable 7 Index Page The sound and security industry in the United States has grown from a simple and unsophisticated business, begun some 45 years ago, to one which has
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
Screened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
STABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES
STABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES Introduction General Cable understands that assisted living facilities require complex building designs that must address a wide range of systems
Why FOUNDATION Fieldbus?
Product Bulletin PB 244-R3 Fieldbus Cables Fieldbus Tye A cables rovide installation flexibility in many different environments, including outdoors and where multile or extended cable runs are required.
WIRE & CABLE PRODUCTS
WIRE & CABLE PRODUCTS Parallel Speaker Wire 1 leg printed for polarity, ETL or UL Listed CM 77001 UZ1802-9B5 White 18/2 conductor (7/26) parallel speaker wire, 1 leg printed "UL NEC 800 or ETL listed"
New Cable Tie Type Classifications
1 New Cable Tie Type Classifications UL 62275 United States CSA C22.2 No. 62275 Canada NMX-J-623-ANCE Mexico Technically Equivalent to IEC 62275 All cable ties are not created equal!!! With an increasing
Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments
Gexol Gexol World Class World Class Designed for safe, reliable performance in the harshest oil and gas operating environments Power Control Instrument VFD The Global Cable Solutions Company Gexol World
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute Cable Tray Wiring Systems Have Many Cost Advantages Cost is usually a major consideration in the selection of a wiring system.
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES KSR-SK-DB The following installation procedures are suggested guidelines for the installation of in-line cable splices. They
SECTION 18370 SIGNAL WIRE AND CABLE
SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
B. NICET: National Institute for Certification in Engineering Technologies.
PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
The proof is here!! Ron Goethals, Philadelphia; June 18, 2014
The proof is here!! The proof is here!! The proof is here!! The proof is here!! The proof is here!! The proof is here!! Highly flame-retarded non-halogen bedding compounds show remarkable effects on: BURNING
SOUND/SECURITY FIRE ALARM/LIFE SAFETY TEMPERATURE CONTROLS COAXIAL DATACOM HARDWARE FIBER OPTIC SPECIAL APPLICATION C ATALOG, VOL.
C ATALOG, VOL. 11 SOUND/SECURITY FIRE ALARM/LIFE SAFETY TEMPERATURE CONTROLS COAXIAL DATACOM HARDWARE WAREHOUSE / BRANCH LOCATIONS Anaheim, CA Atlanta, GA Boston, MA Phoenix, AZ Portland, OR Seattle, WA
with coloured cores and overall copper screen UL/CSA... 17
CONTENT Cable Track Cables y SD 200 extremely flexible TPE/PUR data cable with coloured cores for continuous movement..... 6 y S 200 extremely flexible TPE/PUR control cable with numbered cores for continuous
Heating Cable. Construction
Mineral Insulated High Temperature A C Constant Wattage Series Resistance Heating Cable Sets Process Temperature Maintenance to F (593 C) Maximum Exposure Temperature 4 F (76 C) (Power Off) Corrosion Resistant
Terms and Definitions In Canada
Terms and Definitions In Canada Most of the following terms and definitions are taken directly from the National Building Code and referenced Test Methods. Learning these terms will provide an important
Tri-Rated Flexible PVC Equipment Wire
Application: High temperature, flame retardant wire designed for use in the switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
Residential Electrical System Aging Research Project. Dave Dini Sr. Research Engineer Underwriters Laboratories
Residential Electrical System Aging Research Project Dave Dini Sr. Research Engineer Underwriters Laboratories Aging Residential Electrical Systems Research Project Sponsors Fire Protection Research Foundation
PROFIBUS cable. PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications
Data Sheet 10/63-6.47-EN Rev. D PROFIBUS cable PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications PROFIBUS PA cables Non-Ex (Hazardous) applications Ex (Hazardous) applications
108-93018 05 APR 2016 Rev M
Product Specification 108-93018 05 APR 2016 Rev M Copper LAN Cable 1. SCOPE 1.1. Content This specification describes the general requirements for CommScope copper LAN cable. 2. APPLICABLE DOCUMENTS The
Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
600V Power Cable 600V SOOW SOW
600V Power Cable Type SOOW UL/CSA 90 C 600V Part AWG No of Insulation Jacket Nominal Wieght/Mft Number Stranding conductors Thickness Thickness O.D. Nom. 18 2 SOOW 18 AWG 2.30 71 18 3 SOOW 16/.010 3.030