1 CAN/ULC-S Installation of Fire Alarm Systems Amendment 1 Canadian Fire Alarm Association (CFAA)
2
3 CAN/ULC-S524 AMENDMENT 1 PUBLISHED February 2011
4 WHY Clarifications New requirements (Technology changes) Minor Corrections
5 SCOPE Voluntary Installations Clarification Installation of Fire Alarm Systems APPLIES
6 SCOPE Voluntary Installations Scope note This standard is intended to apply to both required and voluntary fire alarm installations.
7 POWER BUSSES A very significant change Concern is system survivability Keeps with the philosophy of As significant as Fault Isolators on Data Communication Links
8 POWER BUSSES Is this a BIG change? YES
9 POWER BUSSES A fault including a fault caused by fire, on a power buss could result in loss of that function on more than one fire zone. APPLIES TO MANY SITUATIONS INCLUDING: POWER TO DISTRIBUTED AMPLIFIERS, POWER TO 4- WIRE SMOKE DETECTORS, POWER FROM ADDER POWER SUPPLIES TO STROBES.
10 POWER BUSSES Where a Power Buss Circuit serves more than 1 Floor A fault on one zone (open, short or ground) Shall not prevent normal operation of input or output field devices in more than one fire alarm zone. A class A circuit with fault isolation modules or equivalent shall be used.
11 FIBRE OPTICS Fibre Optics
12 FIBRE OPTICS Fibre Optics Cables shall be provided with mechanical protection similar to electrical conduit as in CEC Section 32
13 FIBRE OPTICS Fibre Optics Cables shall be DEDICATED to fire alarm Each junction access enclosure marked FIRE ALARM
14 FIBRE OPTICS EXCEPTION: Where multiple strand Fibre Optics Cables are not dedicated to fire alarm, the fire alarm system shall continue to function despite any impairment of other systems that share the cable.
15 SMOKE CONTROL SYSTEMS Interface to or programming of smoke control systems cannot be checked or confirmed if the Smoke Control operation is not known. Documentation MUST be provided at the time of fire alarm installation.
16 SMOKE CONTROL SYSTEMS Sequence of smoke control operation. Diagram of type and location of all smoke control equipment (fans, dampers, etc.) Identify building areas smoke control serves. Documentation to be maintained on site.
17 SMOKE CONTROL PLANS
18 STAND ALONE SYSTEMS DELETED Requirement to maintain SYNCRONIZATION in the stand alone.
19 CONTROL OF VISIBLE SIGNALS When should Visible signals (strobes) turn off?
20 CONTROL OF VISIBLE SIGNALS Visible signals (strobes) are intended to supplement audible signals. Visible signals MUST turn off when Signal Silence occurs. Visible signals such as Fire Do Not Enter turn off at Reset.
21 NOT AN OPTION Signals Must ALARM + SIGNAL SILENCE +
22 DUCT SMOKE DETECTORS Duct smoke detector sampling tubes MAY be mounted vertically in the duct at the top.
23 DUCT SMOKE DETECTORS Duct smoke detector sampling tubes MAY be mounted vertically in the duct at the top.
24 CONNECTION TO A MONITORING SYSTEM Connections to a Fire Receiving Centre transmitter must be at a DEMARKATION TERMINAL BOX. The Demarcation Terminal Box must have a minimum of 12 terminals, must be located in the same room as the fire alarm control unit, must be labelled FIRE ALARM DEMARKATION
25 DEMARKATION TERMINAL BOX.
26 DEMARKATION TERMINAL BOX
27 CORRECTIONS TABLE 7 Corridor Spacing Allocation for Ceiling or Wall-Mounted Light Output for Wall-Mounted Visible Signal Devices CHANGED REFERENCE TO CLAUSE TABLE 6 Light Output for Ceiling-Mounted Visible Signal Devices for Various Room Sizes CHANGED REFERENCE TO CLAUSE
28 CORRECTIONS TABLE 5 Light Output for Wall-Mounted Visible Signal Devices for Various Room Sizes ADDED REFERENCE TO CLAUSE AND DELETED WORD DETECTOR FROM TITLE. FIGURE 3 Room Spacing for Wall-Mounted Visible Signal Devices CHANGED REFERENCE TO CLAUSE ADDED REF TO
29 SPOT TYPE FIRE DETECTOR SPACING FIGURE 9
30 SPOT TYPE FIRE DETECTOR SPACING FIGURE 9 RATED SPACING 9.1 m Area of coverage Radius 0.7 x 9.1= 6.4m In irregular shaped rooms all areas must be within 6.4m Narrow rectangular areas must fit within the circle but if 3.1 m wide could have a spacing of 12.5m
31 SPOT TYPE FIRE DETECTOR SPACING FIGURE 9
32 Dave Goodyear
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationFIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager
FIRE RATED WIRING What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager INTRODUCTION OBC requirements for emergency power OBC requirements for emergency power for fire alarm systems and other building
More informationNC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
More informationCLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
More informationPLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
More informationFire Alarm Engineering Best Practices. CFAA NCA Technical Seminar 2014
Fire Alarm Engineering Best Practices CFAA NCA Technical Seminar 2014 2 Overview Code Compliance Equipment Selection and Layout Drawings, Specifications Commissioning and Acceptance Miscellaneous Goals
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
More informationOBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group Course Title: Rev Date Agenda Introduction to Underwriters Laboratories
More informationDTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
More informationAVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839
AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What
More informationFire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
More informationNFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.
NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating
More information25 Years of Manufacturing Excellence INFINITY. The Intelligent 2 Wire Fire Detection System for Professionals
INFINITY The Intelligent 2 Wire Fire Detection System for Professionals Infinity ID 2 The intelligent 2 wire fire detection system for professionals In a nutshell Zeta Alarm Systems is proud to introduce
More informationnr 28 nr 68 nr 4 nr 1
SEEB INTERNATIONAL BILL OF QUANTITIES AIRPORT ELECTRICAL WORKS NEW TERMINAL PIER ITEM ITEM DESCRIPTION UNIT QUANTITY BILL PART SECTION No. VOLUME 3 4 UNIT RATE (R.O.) (in words) (in figures) SECTION R:
More informationFIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION
Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationFire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
More informationCHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
More informationCFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements
CFAA NCR CHAPTER ANNUAL SENINAR Commonly Overlooked Fire Alarm Requirements Introduction of Who I Am And My Experience (aka: only legitimate chance to catch a quick nap) Definitions ( if you nap during
More informationFire Alarm Trainee Log Book
Fire Alarm Trainee Log Book this page is intentionally left blank canadian fire alarm association l association canadienne d alarme incendie PREFACE This training record document was developed by the Canadian
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationM 75 FACU FIRE ALARM SYSTEM NOTES ALL DEVICES WILL BE MOUNTED ON JUNCTION BOXES IAW THEIR DATA SHEETS, MANUFACTURERS' RECOMMENDATIONS AND STANDARD INDUSTRY RACTICES, EXCET WHERE NOTED ON THIS DRAWING ALL
More informationC. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
More informationDesign and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS
More informationFire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
More informationSECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
More informationBS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
More informationNFPA 91 1999 Edition. 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations:
NFPA 91 1999 Edition 2.1.9 Fire dampers shall be permitted to be installed in exhaust systems in the following situations: 1) Where ducts pass through fire barriers (2) Where a collection system installed
More informationBELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
More informationCBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
More informationSolar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
More informationRecommended Practice for Installation of Transit Vehicle Fire Protection Systems
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October
More informationNATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
More informationSECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM
KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as
More information1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.
GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems
More informationFireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance
More informationC. NICET: National Institute for Certification in Engineering Technologies. D. Definitions in NFPA 72 apply to fire alarm terms used in this Section.
SECTION 283100 - FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEM
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
More informationModule 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
More informationAVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard
Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!
More informationFIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationFLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
More informationDesign Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015
Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 13860 (283100) FIRE ALARM SYSTEM The following standard shall be followed for the design of University
More informationConventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
More informationThe Benefits of ADDRESSABLE Fire Alarm Technology
The Benefits of ADDRESSABLE Fire Alarm Technology NOTICE: If you were born after 1990 or if you lived through the 60 s and can t remember what happened since, you may be surprised to learn that fire alarm
More informationInvitation to Bid FIRE ALARM & DETECTION SYSTEM
Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationSECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled
More informationFIRE DETECTION AND ALARM
Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program
More informationFIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
More informationSARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
More informationAttachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply
FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's
More informationStandard the the Raising
Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction
More informationProposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed
More informationHONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT
More informationSECTION 16760 - PLANT INTERCOMMUNICATION SYSTEM. City of San Diego, CWP Guidelines
PART 1 - GENERAL SECTION 16760-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing plant intercommunication systems with power supplies, signal amplifiers,
More informationFinance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application
PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the
More informationC1. FIRE ALARM SYSTEM VERIFICATION REPORT (Reference: Clause 4.1.6, 4.1.7, 4.2.2)
N/UL S537-04 (MN OR N/UL-S524-06) PPNIX ( INORMTIV) IR LRM SYSTM (S) VRIITION RPORTS (Reference: Subsection 4.1-Note, lause 4.2.1, 4.2.2) 1. IR LRM SYSTM VRIITION RPORT (Reference: lause 4.1.6, 4.1.7,
More informationDesign Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)
Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) 1. In addition to the information scheduled below, the pre-tender designer is responsible for: (i)
More informationFire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
More informationSECTION 16721 MULTI-FIRE ALARM SYSTEM
PART 1. GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification Sections, apply to this Section.
More informationFIRE ALARM SYSTEM. reliable fire detection and alarm signalling system
FIRE ALARM SYSTEM reliable fire detection and alarm signalling system Satel fire alarm devices allow to implement reliable and modern systems responsible for fire safety. A combination of 20-year experience
More information4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES
4-Wire Air Duct Smoke Detector Models DH-60 F-70.05 FEATURES Approvals/Listing UL 268A Listed File S1064 Factory Mutual Approved CSFM Listed #3240-1076:121 NYC MEA Listed #134-95-E City of Los Angeles
More informationHERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
More informationENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000
AMHERST COLLEGE ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 Michael Zlogar April 11, 2001 Assistant Fire Chief Amherst Fire Department 68 North Pleasant St. Amherst, MA 01004 FIRE ALARM
More informationFIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
More informationFire Alarm Systems Permit Packet. City of Greer Fire Department
Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting
More informationUSER INSTRUCTIONS CONTENTS
CONTENTS Full Set [1]...2 Part Set [2]...2 Night Set [3]...3 Unsetting...3 Unsetting after or during an alarm...3 Testing the system [5]...3 Isolating zones [6]...4 Reprogramming codes [8]...4 Chime facility
More informationFIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
More informationSECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM
SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Fire alarm system requirements B. Fire alarm equipment C. Fire alarm peripheral devices 1.02 RELATED SECTIONS
More informationPLC BASED FIRE DETECTION & ALARM SYSTEM
PLC BASED FIRE DETECTION & ALARM SYSTEM 1. SCOPE OF WORK 1.1. Design, Engineering, Manufacturing and supply of PLC based Fire alarm detection system for Multi Storied Building of VSSC with SCADA based
More informationHeating and Hot Water Services Controls General Technical Specification
Construction Services Heating and Hot Water Services Controls General Technical Specification Version 1.0 Environment Heating and Hot Water Services Controls General Technical Specification Contents 1.
More informationconventional system operation
conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than
More informationFIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
More informationLife Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
More informationFire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
More informationSPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
More informationABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems
ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems Content Introduction Preventing unauthorized access by perimeter surveillance Monitoring unauthorized access by indoor surveillance
More information5. Central Control and Monitoring System. 6. Gas Detection Systems (future) 7. Mass Notification Systems (future) 8. Smoke Control Systems.
PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for Fire Detection and Alarm. B. The design guidelines contained
More informationDELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
More informationDUCT SMOKE DETECTOR D4120
Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity
More informationManual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
More informationFire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
More informationFIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
More informationFIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
More informationCity of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.
More informationFire Pump Controllers Remote Alarm Panels
Fire Pump Controllers Remote Alarm Panels Remote Alarm Panels 1.8 Remote Alarm Panels FDAP-M Electric... DFDAP-M Diesel... Product Specifications... 2 6 9 Features 1-1 DFDAP-M / FDAP-M Remote Alarm Panel
More informationFIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
More informationFIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
More informationErrata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
More informationA. This Standard outlines the requirements for an addressable fire detection and alarm system.
1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and
More informationFIRE ALARM PERFORMANCE GUIDELINES
FIRE ALARM PERFORMANCE GUIDELINES 2010 Design Guidelines 1 P a g e TABLE OF CONTENTS PART 1 GENERAL.3 1.1 RELATED DOCUMENTS...3 1.2 SCOPE.....3 1.3 QUALITY ASSURANCE....3 1.4 SUBMITTALS.. 5 PART 2 PRODUCTS..6
More informationSPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
More information2301.1 Scope: Communications and Electronic Systems addressed in this section include:
Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and
More informationProject No. 4 Analysis of Active Fire Alarm Systems in WTC 1 & 2. Robert J. Keough Rolf Jensen & Associates Raymond A. Grill, P.E.
Project No. 4 Analysis of Active Fire Alarm Systems in WTC 1 & 2 Robert J. Keough Rolf Jensen & Associates Raymond A. Grill, P.E., FSFPE Arup Fire Objectives Document the design and installation of the
More information