CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS



Similar documents
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION

HERNANDO COUNTY FIRE ALARM GUIDELINES

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM

City of Bettendorf Fire Alarm System Requirements

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

Module 4, Lesson 12 Fire Alarm Systems

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

AETNA FIRE ALARM SERVICE CO., INC.

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Bold items are particular to the City of Euless

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

PLAN REVIEW GUIDE FOR FIRE ALARM

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

FIRE ALARM APPLICATION

Fire Alarm System Plans Review Checklist Property location Date of Review

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) Fire Alarm Permit Application

University Design Standard. Fire Alarm Systems

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

INSPECTION AND TESTING FORM

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc

Michael Catalano 24 Nassau Avenue, Islip NY Phone (631) Chief Fire Marshal Fax (631)

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Original Document 10/16/07 Revised 01/30/09 2 nd Revision rd Revision- 12/18/14

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

1.0 General. Inspection, Testing, and Maintenance 1 of 8

SECTION FIRE ALARM AND DETECTION SYSTEMS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

EXHIBIT A SCOPE OF WORK

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

FIRE DETECTION AND ALARM

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

Module 5. Fire and Emergency Alarm System Part I- Basics

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET

FVSU REPAIR & UPGRADE FIBER OPTIC SECTION FIRE ALARM SYSTEM CONNECTIVITY

Life Safety Code Enabling References

STATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE. Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO***

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.

City of Columbus Department of Building and Zoning Services

SECTION FIRE ALARM AND DETECTION SYSTEM

BASIC FIRE ALARM TRAINING

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

SECTION FIRE ALARM AND DETECTION SYSTEM

NATIONAL FIRE ALARM AND SIGNALING CODE

COMMISSIONING OF FIRE ALARM SYSTEMS

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA

CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE

SECTION FIRE ALARM AND DETECTION SYSTEM

DTW Works Master Specification Version 2006

BUILDING DESIGN STANDARDS UNIVERSITY SERVICES ELECTRONIC SAFETY AND SECURITY - DIVISION 28 Fire Alarm Systems

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)

Winnipeg Fire Department Fire Prevention Branch

Fire Alarm Systems Permit Packet. City of Greer Fire Department

2007 ICC FINAL ACTION AGENDA

The Mission Critical Fire Protection Experts

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CBD-233. Fire Alarm and Detection Systems

Fire Alarm Submittal Requirements and Acceptance Testing

A. This Standard outlines the requirements for an addressable fire detection and alarm system.

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

Sprinkler and Fire Alarm Systems for the Building Official

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS

Project No. 4 Analysis of Active Fire Alarm Systems in WTC 1 & 2. Robert J. Keough Rolf Jensen & Associates Raymond A. Grill, P.E.

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM

Fire Alarm System Monitoring - CAN/ULC-S561-03

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE

Design Standards Fire Alarm Systems Division (1995 CMS); (2004 CMS) Amended Feb 2015

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

FIRE CODE INTERPRETATION

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

FIRE DEPARTMENT CITY OF NEW YORK

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM

SECTION ZONED (DC LOOP) FIREALARM SYSTEM

Transcription:

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL CERTIFICATIONS MUST BE KEPT ON SITE FOR A PERIOD OF THREE YEARS A. OWNER'S SECTION: (TO BE COMPLETED BY THE PROPERTY OWNER OR AGENT) EXPLAIN ALL NO ANSWERS, EXCEPT AS NOTED 1. Is the building occupied? Y N 2. Has the building occupancy or hazard or floor layout changed since the last inspection? (If yes, explain) Y N 3. Are all systems kept in service? Y N 4. Are the test results kept on file? Y N 5. Have there been any modifications to the system since the last certification? (If yes, explain) Y N 6. Was there any action of alarm since the last certification? (If yes, explain) Y N 7. Does this certification cover all fire alarm systems in the building? Y N OWNER/AGENT SIGNATURE PRINT NAME NOTIFY THE PHILADELPHIA FIRE DEPARTMENT AT 215-922-6000 BEFORE TESTS - OUT OF SERVICE OPERATOR# IN SERVICE OPERATOR# CERTIFICATE HOLDERS SECTION: (ALL TESTS SHALL BE IN ACCORDANCE WITH THE PHILADELPHIA FIRE CODE AND NFPA 72, CHAPTER 10) B.CONTROL EQUIPMENT 8. Was the fire alarm Control Panel in an accessible location Y N (In main entrance or unlocked room)? 9. Was the battery charging circuit in the Control Panel Y N operating correctly and at the proper voltage? 10. Was Ground Fault Monitoring tested satisfactorily? Y N 11. Was the test of lamps and LED's in the Control Panel Y N satisfactory? 14. Were trouble signal silence switches and alarm silence Y N switches in the Control Panel tested satisfactorily? 15. Was the off-premises transmission test satisfactory? Y N 16. Did the remote annunciator test satisfactorily? Y N 17. Was the Control Panel supervision test Y N 12. Was the test of interface equipment satisfactory? Y N 13. Were audible and visible trouble and alarm signals in the Y N Control Panel satisfactory? C. INITIATING DEVICES 18. Were signs mounted at each pull station stating Y N "IN CASE OF FIRE: SOUND ALARM AND CALL 911 or THE FIRE DEPARTMENT? 19. Were the manual fire alarm box tests Y N 20. Were the smoke detector inspection/tests Y N 21. Were the smoke detector thermal elements tests Y N 22. Were the smoke detector control output tests Y N 24. Were restorable heat detector tests Y N 25 Were the alarm verification tests satisfactory? Y N 26 Was the sensitivity of all Smoke Detectors tested in Y N accordance with NFPA72 (2007) Section 10.4.4.2.4? (Provide results on page 4 or provide NFPA compliant panel printout) The certification of smoke detector sensitivity shall be performed according to the Philadelphia Fire Code Section below. 27 Were the duct smoke detector tests Y N 23. Were non-restorable heat detectors inspected and in Y N satisfactory condition? F-907 Certification of smoke detector sensitivity; Alternate year sensitivity testing shall begin in odd-numbered years. Where the one-year sensitivity test occurs in an even-numbered year, the next sensitivity test is not due until the second subsequent odd-numbered year. Results of sensitivity tests shall be listed on page 4 of the Annual Certification form each year testing is performed. 81-983 - EFFECTIVE July 2010 ANNUAL FIRE ALARM SYSTEM CERTIFICATION PAGE 1 OF 5

C1. SUBSECTION: SPRINKLER SYSTEM SUPERVISION (IF APPLICABLE) Yes No (If no, explain) 28. Were the water flow switch inspection/tests Y N 29. Were the valve tamper switch inspection/tests Y N 30. Were the low temperature sensor inspection/tests Y N 31. Were low air pressure switch inspection/tests Y N 32. Were the Fire Pump power supervision inspection/tests Y N 33. Were the Fire Pump Running supervision inspection/tests Y N 34. Were the Fire Pump Trouble supervision inspection/tests Y N 35. Were Fire Pump Alternate Power inspection/tests Y N C2. SUBSECTION: OTHER INITIATION (IF APPLICABLE) Yes No (If no, explain) 36. Are all range hood/other suppression systems interconnected to Y N this system as required? 37. Were all range hood/other suppression system inspection/tests Y N 38. Are all existing air handler duct smoke detectors Y N interconnected to this system? 39. Were all air handler duct smoke detector Y N inspection/tests D. AUDIBLE / VISIBLE DEVICES 40. Were the ambient sound levels tested with the normal Y N ambient noises present (HVAC, etc.) and recorded below? 41. Were alarm sounds levels tested and recorded below? Y N 42. Were visible alarms tested and operating properly? Y N 43. Did sound levels reach the minimum requirement noted below: Y N Systems installed prior to January 1984 = Sufficient volume to be heard January 1984 until March 1991= 15 dba above ambient in occupied spaces May 1991 until December 2009 = 70 dba in sleeping rooms, 70 Mechanical spaces, 60 in remaining spaces January 2010 until Present = 75 dba sleeping rooms, 70 in Mechanical spaces and 60 in remaining spaces. AUDIBILITY RECORD: (Describe in detail the locations tested and the results in boxes below - use additional sheets if necessary.) Audibility Readings must be taken in at least one unit per floor AND at least one reading for each style unit in the building. LOCATION TESTED (Fill in exact location next to description; i.e. Unit D-10 etc.) FLOOR AMBIENT LEVEL ALARM LEVEL SLEEPING AREA : 81-983 - EFFECTIVE July 2010 ANNUAL FIRE ALARM SYSTEM CERTIFICATION PAGE 2 OF 5

D1. SUBSECTION: OTHER SYSTEM OUTPUTS / INTERCONNECTIONS (IF APPLICABLE) Yes No (If no, explain) 45. Are all range hood/other suppression systems Y N interconnected to fuel shut off/power disconnects as required? 46. Are all air handlers over 2000 cfm shut down as required? Y N 47. Were all Primary Floor Elevator Recall inspection/tests Y N 48. Were all Secondary Floor Elevator Recall inspections/tests Y N 49. Were all Elevator Power Shutoff/Shunt Trip inspection/tests Y N 50. Were all Elevator Fire Fighters Hat feature inspection/tests Y N 51. Were all Door Hold Open Release inspection/tests Y N E. ELECTRICAL 52. Was the fire alarm system power connected to a branch Y N circuit of house panel? 53. Was the fire alarm system power disconnected for the Y N dedicated branch circuit locked in the "On" position? 54. Was the fire alarm system power disconnect location Y N clearly identified in writing at or on the control panel? 55. Was the test of the primary power source satisfactory? Y N 56. Was the test of the secondary power source (e.g. batteries) Y N satisfactory? 57. Was the system tested using the secondary power source? Y N 58. Were all additional NAC power supply inspection/tests Y N 59. Were all additional sub control, amplifier, firefighter phone Y N panels and auxiliary power supply inspection/tests 60. Were all batteries for additional NAC power supplies Y N sub controls, amplifiers, fire fighter phone panels and auxiliary, power supplies load tests/inspections 61. Were all batteries load tested? Y N Provide Make and Model of tester used? F. VOICE EVACUATION SYSTEM (IF APPLICABLE) Yes No (If no, explain) 62. Is this system applicable to the system being tested? Y N (If YES, complete this section) 63. Was the Fire Command Center operating properly? Y N 64. Were speaker sound pressure and clarity recorded in Y N Section D? 65. Were amplifier/tone generators tested satisfactorily? Y N G. FIRE FIGHTER PHONE SYSTEMS (IF APPLICABLE) Yes No (If no, explain) 66. Was the call-in signal silence function correct? Y N 67. Was the off-hook indicator verified? Y N 68. Were phone jacks tested satisfactorily? Y N 69. Were phone sets tested satisfactorily? Y N 70. Were handset system voice quality and clarity Y N H. MONITORING (IF APPLICABLE) Yes No (If no, explain) 71. Is this system monitored or required to be monitored? Y N (If YES, complete this section) 72. This system is monitored under which of the NFPA 72 monitoring categories? Proprietary Supervising Station Remote Supervising Station Other (Explain in comments section) Central Station Service The system is monitored in compliance with the above Y N checked ( ) method. 73. The system sends a daily test signal to the Y N monitoring station? 74. The system has two telephone lines or other NFPA Y N method of communication with the monitoring station? 75. The monitoring station is UL approved to receive Fire Y N Alarm Signals? 76. The name of the Monitoring Entity is: Telephone #: Account Reference No: UL Certification #: 75. The system was tested to the monitoring station for the following conditions: A. Alarm and Restore Y N B. Trouble and Trouble Restore Y N C. Supervisory Signal and Restore Y N D. Ground Fault and Restore Y N E. AC Power Loss and Restore Y N 81-983 - EFFECTIVE July 2010 ANNUAL FIRE ALARM SYSTEM CERTIFICATION PAGE 3 OF 5

DETECTOR SENSITIVITY RESULTS Location Device Type Visual Check Functional Test Factory Setting Measured Setting Pass Fail NFPA 72, Section 10.6.2 81-983 - EFFECTIVE July 2010 ANNUAL FIRE ALARM SYSTEM CERTIFICATION PAGE 4 OF 5

COMMENTS: (ATTACH ADDITIONAL SHEETS IF NECESSARY) CERTIFICATE HOLDER S NAME (PRINT AND SIGN) EMAIL ADDRESS PHONE NUMBER TEST DATE FIRE ALARM INSPECTOR LICENSE NUMBER 3707-81-983 - EFFECTIVE July 2010 ANNUAL FIRE ALARM SYSTEM CERTIFICATION PAGE 5 OF 5