Electrical Machines II. Week 3: Transformer Tests and voltage regulation

Similar documents
THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

SYNCHRONOUS MACHINES

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Introduction. Three-phase induction motors are the most common and frequently encountered machines in industry

Properties of electrical signals

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

TRANSFORMER: THREE PHASE

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

CHAPTER 5 SYNCHRONOUS GENERATOR

Lab 8: DC generators: shunt, series, and compounded.

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

How To Understand And Understand The Electrical Power System

Lab 14: 3-phase alternator.

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Three-Phase Induction Motor

EEL303: Power Engineering I - Tutorial 4

Transformer circuit calculations

Synchronous generators are built in large units, their rating ranging from tens to hundreds of megawatts.

7CURRENT TRANSFORMERS

Power Quality Paper #3

Using Murrelektronik MICO Modules to Create Low Voltage Limited Energy Circuits in Industrial Control Panels according to UL508A.

Physical Address: City: State: Zip Code:

Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection

Basic Laws Circuit Theorems Methods of Network Analysis Non-Linear Devices and Simulation Models

Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt.

Using Current Transformers with the 78M661x

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

45. The peak value of an alternating current in a 1500-W device is 5.4 A. What is the rms voltage across?

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Large Generators and High Power Drives

Full representation of the real transformer

Chapter 16. Current Transformer Design. Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.

DRAFT. University of Pennsylvania Moore School of Electrical Engineering ESE319 Electronic Circuits - Modeling and Measurement Techniques

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Direct Current Motors

The Flyback Converter

Experiment NO.3 Series and parallel connection

Induction Motor Theory

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

When the Power Fails: Designing for a Smart Meter s Last Gasp

Chapter 14: Inductor design

8 Speed control of Induction Machines

Chapter 24. Three-Phase Voltage Generation

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

GUIDE FOR TESTING POWER TRANSFORMERS

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL

= (0.400 A) (4.80 V) = 1.92 W = (0.400 A) (7.20 V) = 2.88 W

Common Base BJT Amplifier Common Collector BJT Amplifier

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21,

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

Current Transformers

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

USER MANUAL THE RESOLVER

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.

Chapter 10. RC Circuits ISU EE. C.Y. Lee

Chapter 9 Balanced Faults

CT Application Guide for the 489 Generator Management Relay

Modeling of Transmission Lines

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

DIRECT CURRENT GENERATORS

13 ELECTRIC MOTORS Basic Relations

IV. Three-Phase Induction Machines. Induction Machines

Current Transformers Ratio / Polarity / Types

Experiment: Series and Parallel Circuits

Tutorial One: Calculation of leakage inductance of transformer using FEM MVA, 132 kv/33kv, Y/, Ampere-turns: , No.

Basic Electronics Prof. Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati

ACCURACY OF POTENTIALTRANSFORMERS

RLC Resonant Circuits

Building the HVPS High Voltage Power Supply

13.10: How Series and Parallel Circuits Differ pg. 571

Alternating-Current Circuits

FIT TIER 2 Application

Diode Applications. by Kenneth A. Kuhn Sept. 1, This note illustrates some common applications of diodes.

AP Physics Electricity and Magnetism #4 Electrical Circuits, Kirchoff s Rules

Maximum value. resistance. 1. Connect the Current Probe to Channel 1 and the Differential Voltage Probe to Channel 2 of the interface.

EE 221 Circuits II. Chapter 13 Magnetically Coupled Circuits

WINDING RESISTANCE TESTING

DRIVING LOOOONG CABLES

Inductors in AC Circuits

Semiconductor Diode. It has already been discussed in the previous chapter that a pn junction conducts current easily. Principles of Electronics

Experiment 4 ~ Resistors in Series & Parallel

The following table shows approximate percentage wise the

Module Title: Electrotechnology for Mech L7

Common Emitter BJT Amplifier Design Current Mirror Design

Loading Considerations When Paralleling Transformers

Ajay Kumar Garg Engineering College, Ghaziabad CLASS NOTES. Subject Name: ELECTROMECHANICAL ENERGY CONVERSION-I Subject Code: NEE 301

SERIES-PARALLEL DC CIRCUITS

R438 A.V.R. Installation and maintenance R 438. This manual is to be given to. the end user T10. Armature 6- Field X2 Z1 X1 Z2 E+ E- 0V

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

VOLTAGE REGULATOR AND PARALLEL OPERATION

Chapter 12: Three Phase Circuits

Unit 33 Three-Phase Motors

Outline. Systems and Signals 214 / 244 & Energy Systems 244 / 344. Ideal Inductor. Ideal Inductor (cont... )

OPERATIONAL AMPLIFIERS

Transcription:

Electrical Machines Week 3: Transformer Tests and voltage regulation

Determination of Equivalent Circuit Parameters All the circuit parameters can be easily determined by performing three tests, a no-load test (or open circuit test) test D.C. test No information what so ever about the equivalent circuit parameters

1- (no load) test Measured values voltage current power V P Transformer's secondary winding is open-circuited Primary winding is connected to a full-rated line voltage. All the input current must be flowing through the excitation branch of the transformer. The series elements R p and X p are too small in comparison to R C and X M to cause a significant voltage drop, so essentially all the input voltage is dropped across the excitation branch. nput voltage, input current, and input power to the transformer are measured. Calculated values Core loss resistance Magnetizing reactance R c X M

1- (no load) test Measured values voltage current power V P Although it does not matter which side of the transformer is excited, it is safer to conduct the test on the low-voltage side. Another justification for performing the test on the low-voltage side is the availability of the low-voltage source in any test facility. Calculated values Core loss resistance Magnetizing reactance R c X M

1- (no load) test c Circuit Parameters: Open-Circuit Test q o E 1 The open circuit power (no load power) is given by: P V cos M o The open-circuit power factor and power factor angle can be determined: PF cos P V or, cos 1 P V Since the no load current will correspond to the magnetic branch current which constitutes two current components, M and c M cos, c sin Then one can easily determine X M and R c : V X M, M R c V c

2-Short circuit test Measured values voltage current power V P Transformer's secondary winding is short-circuited Primary winding is connected to a fairly low-voltage source. The input voltage is adjusted until the current in the short-circuited windings is equal to its rated value. nput voltage, input current, and input power to the transformer are measured. Excitation current is negligible, since the input voltage is very low. Thus, the voltage drop in the excitation branch can be ignored. All the voltage drop can be attributed to the series elements in the circuit. Calculated values winding resistances leakage reactances R eq X eq

2-Short circuit test Measured values voltage current power V P The low power input at the rated current implies that the applied voltage is a small fraction of the rated voltage. Therefore, extreme care must be exercised in performing this test. Once again, it does not really matter on which side this test is performed. However, the measurement of the rated current suggests that, for safety purposes, the test be performed on the high-voltage side. Calculated values winding resistances leakage reactances R eq X eq

2-Short circuit test Circuit Parameters: Short-Circuit Test The short-circuit power and current can be related as: Z R 2 eq P R X 2 eq 2 R R eq P 2 Since the series impedance (equivalent impedance) can be given by: Z V t is possible to determine the equivalent leakage transformer reactance since the resistive part is already known Take care where have you performed the test

3-D.C. test V dc This test is carried out to measure the resistance of each winding, thus the test can be carried on one side and the other side is concluded with the help of the test To determine the primary winding resistance, the secondary winding is open circuited and the primary winding is excited with dc source. The dc voltage is varied till the primary current reaches rated current. Each time the voltage is dc increased, the corresponding primary current reading is recorded. The resistance of each winding is obtained from the Ohms Law: R dc R 1 V dc dc Measured values Dc voltage Dc current V dc dc

Transformer Voltage regulation Because a real transformer has series impedance within it, the output voltage of a transformer varies with the load even if the input voltage remains constant. The voltage regulation of a transformer is the change in the magnitude of the secondary terminal voltage from no-load to full-load. V %Voltage Re gulation V s no load Vs full load V full load p s no load V p full load V full load p 100 100 Referred to the primary side