A Method to Detect and Locate Roof Leaks Using Conductive Tapes



Similar documents
1.0 Introduction. 2.0 Importance of Integrity Testing. 3.0 How Does EFVM Work? 6.0 Conclusion

Roofing & Waterproofing Forensics for the 21 st Century. Peter Brooks, President

FIELD TESTING SERVICES

Site Inspection Report

Chapter 3: Non-Destructive Testing

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

Inspecting to a higher standard.

SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

A Practical Guide to Dielectric Testing

Exterior Elevated Elements Inspection Guidelines

SMA Waterproof. Cable Assembly. Filtered Audio Connector. Dataport Receptacle. Dataport Plug

WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

Heating Cable. Construction

Title: Grounding and Bonding Rev-01

CHAPTER 6 ASPHALT ROLL ROOFING

Solar Panel Installations

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller

WORLDWIDE. GW400k SERIES MAINTENANCE MANUAL PROVEN PERIMETER PROTECTION

Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA

Avoiding Air Barrier Pitfalls

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

Construction Electrical Terminology. Electricians

Insulation Resistance Testing of Low Voltage Cables in the Field

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN Fax: Re-Roofing: Asphalt Shingles

Electric Heat Tracing INSTALLATION PROCEDURES

The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage

Video Camera Installation Guide

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems

HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION

ACS-30-EU-EMDR-10-MOD

SECTION 19 RESIDENTIAL CONSTRUCTION IN FLOODZONES

State of Connecticut Department of Public Health RADON PROGRAM

Asphalt Shingle Application Requirements

A Guide to Retrofitting an Existing Roof to a Vegetated Green Roof

High Performance PSA in Sheet Membrane in Water Protection

BLUESTAR INFRARED. Description: Thermal Properties Comparison. Project Location: Client: 759 South Federal Hwy 225 Bayshore Drive

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

Chapter 9. Bonding and Grounding

Roofing Signs that Your Roof Needs Repair/Replacement

Detection of Contact Voltage in Electric Distribution Systems

Essential Performance Attributes of Preapplied waterproofing

Troubleshooting accelerometer installations

Infrared Moisture Detection

STANDARD PROCEDURES FOR ROOF MOISTURE SURVEYS

Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at Forest Drive, Annapolis, MD. Provided by: HurleyIR

SELF-REGULATING PIPE TRACING HEATER CABLE

WHAT IS INFRARED (IR) THERMOGRAPHY

Chapter 3 Pre-Installation, Foundations and Piers

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

HSG Engineering Tech Bulletin

I S S U E 1/2013 VOLUME 30 NUMBER 1. Water Testing: Richard P. Kadlubowski, AIA and Courtenay Bauer

How To Control Water Penetration In A Window

University of Iowa Main Power Plant 2008 Flood Preparations, Event, & Recovery

DET3 Contractor Series 3-Terminal Earth/Ground Resistance Testers

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

Roofing Systems. New Applications / Re-Roofing / Maintenance

Water Leak Detection System

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

Nelson MI Cable is a high performance, industrial grade heat tracing cable used for applications requiring:

RECOATING AND RENEWING SPF ROOFING SYSTEMS

FIRERAY 2000 Installation Guide

Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM

Ceiling Mount Air Handler Manual

Excerpts from the Canadian National Building Code (NBC)

ACL 395 Resistivity Meter

Fluid-Applied Roofing for Repair and Renovation FACILITIES & MAINTENANCE PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

Town House Center Highway North Huntingdon, PA 15642

Table of Contents. Inductive Loop Vehicle Detector Applications

University of Missouri Hospitals and Clinics. Structural Repair and Protection of Post-tensioned Parking Garage

Cable and Pipe Locating Techniques

Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, RBA Project No

Nondestructive Evaluation of USCG Hawkins Pt. Road Curtis Bay, MD Provided by: HurleyIR

September 3, Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual

Complete Solar Photovoltaics Steven Magee. Health and Safety

Arc Flash Energy Mitigation Techniques

INFRARED DIAGNOSTIC REPORT ABLE INSPECTION COMPANY Post Office Box Houston, Texas (713)

NORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW

Aerial Infrared Roof Moisture Surveys

Transcription:

BEST2 Moisture Measurement Session WB8-2 A Method to Detect and Locate Roof Leaks Using Conductive Tapes ABSTRACT David Vokey, P.Eng. Detec Systems, LLC Undetected roof leaks and the subsequent deterioration are considered the greatest cause of premature roof failure. This paper describes a method whereby a leak locating grid of conductors is placed on the top of a roof membrane to detect and localize leaks to within an area defined by the grid spacing. The method is particularly useful for roof designs that incorporate a waterproofing membrane under a green roof, wear-course or topping slab where direct inspection of the roof membrane is difficult or impossible. A top-of-membrane grid system can provide an accurate and cost effective method to monitor and maintain a wide range of covered roof types and sizes. The initial mock-up testing as well as examples of subsequent field installations is provided. INTRODUCTION The failure to detect, identify and correct minor roof deterioration and leakage in the earliest stages is considered the greatest cause of premature roof failure [3, 6]. This is particularly true of roofing materials applied on low-slope or flat roofs. Costly roofing problems are often the result of design deficiencies or faulty application of the roof system. Even when properly designed and applied, all roofing materials deteriorate from exposure to the weather at rates determined largely by the kind of material and the conditions of exposure. Roof designs that incorporate a waterproofing membrane under a green roof, wear-course, or topping slab greatly exacerbate the problem of locating leaks [8, 9, and 10]. Flood testing at time of construction [4] is sometimes specified to test roof membranes. The test is difficult to do and often inconclusive. The national roofing contractor associations in both Canada [5] and the US do not support this practice. Several methods [1] have been used in attempting to locate roof leaks after they have occurred. Electric capacitance meters identify leaks using an alternating current signal to measure dielectric constant changes in the roofing material as a result of moisture below the membrane. Infrared cameras allow technicians to scan roof surfaces for temperature differentials that signify moist areas through changes in thermal conductivity or evaporation. Electric field vector mapping uses a wire loop around the perimeter of the roof surface to introduce an electric potential between the structural deck and a selected roof area which is sprayed with water. The electric field potential caused by a conductive path to any roof membrane damage is then traced to the breach using a voltmeter and a pair of probes. These methods are usually employed to assist in locating roof leaks after costly water damage has occurred. Moisture detection sensors [7] can also be placed under the roof membrane to detect the presence of moisture; however several roof designs incorporate membranes that are directly adhered to the 1

roof deck thereby limiting the placement and effectiveness of this type of moisture sensor application. This paper describes a method whereby a leak locating grid of conductors is placed on top of a protected roof membrane to detect and localize leaks to within an area defined by the grid spacing. The method has particular application for inverted, covered and green roofs [2] where the membrane is fully adhered. The mock-up and testing of this application was supported by and carried out at the training facilities of the Roofing Contractors Association of British Columbia (RCABC). METHOD During construction, a flat two-conductor peel-and-stick grid tape is installed on top of a roof membrane to provide conductance testing between the top of the membrane and the roof deck. During a leak test, a measuring voltage is applied between the detection conductors and the roof deck. Any water path between the detection conductors and a damage site will result in a leakage current from the roof deck to the detection conductors through the insulating membrane. For potentially corrosive environments, a small cathodic protection current is applied between the tape conductors and earth ground to inhibit corrosion. In the most severe environments stainless steel conductors can be used. The individual conductors are electrically connected at one end to a switching and measuring system whereby an isolated fault current to ground measurement can be made. In operation, a selected conductor is switched to act as the input of a current sensor, and an electric potential is applied between the selected conductor and the roof deck ground. As illustrated in Figure 1, the adjacent grid conductors that read a high leakage current to ground through the water path identify the grid section with a membrane breach. Figure 1: Basic measuring circuit and illustration of membrane breach locate. 2

A moisture leakage path through the roof membrane will usually cause any selected grid conductor to measure some level of leakage current. To avoid stray current that can create significant error in the membrane breach location survey, all detection conductors not selected for current measurement are connected to a special guard circuit. The guard circuit forms an electric shield between the selected conductor and any other current leakage sites beyond the conductors immediately adjacent to the selected conductor. This eliminates stray current errors and makes this method feasible. EXPERIMENTAL RESULTS Initial tests of the membrane leak locate method were carried out on the roof membrane above a parking garage under construction. The membrane is hot fluid-applied rubberized asphalt with a covering protection board. As shown in Figure 2, a four foot-by-four foot moisture detection tape grid was placed over a 16 foot square section of the roof membrane. The conductor ends were spliced to connecting cables and terminated on a switching box. A 150K ohm membrane fault level was made in the area bounded by the X3-X4 and Y1-Y2 grid locations. The area was wetted down, the measurement system energized and the individual grid tape leakage currents were measured. As illustrated in Figure 2, the measured currents are drawn on the X and Y axis with the Z (or vertical) axis showing the current magnitudes at each grid line. Current maximums occur at the Y1 and Y2 grid lines on the Y axis and the X1 and X2 grid lines on the X axis which encloses the damage site. Figure 2: Leak locate test set-up on parking garage roof membrane Mock-up tests were then carried out at RCABC using a grid of detection tape conductors installed on top of a TPO roof membrane that was laid over a concrete deck (Figure 3). Six 3

strips of detection tape conductors were placed on top of the membrane in both X and Y directions. Connecting cables from the grid conductors were terminated on a manual switch box to allow scanning of the individual conductors for leakage current while placing all other conductors in a guard circuit arrangement. Controlled defects were then made in the membrane and the entire surface wetted. Electric conductance tests were then carried out to evaluate the effectiveness of the fault locate method. Figure 3: Photo of grid mock-up and lab test equipment used in initial evaluations Several tests were performed in various locations, all with similar results. A typical conductance scan leak locate result is shown in Figure 3. Prior to creation of a damage site the site was wetted and tested for residual leakage. No leakage current was detected. A defect of approximately 1/8 inch in diameter was made in the area bounded by the X4-X5 and Y4-Y5 grid locations. The measurement system registered a total leakage current of 1.54 ma with an applied potential of 50V dc thereby giving a fault resistance through the membrane of 32.4 k ohms. The graphs in both X and Y directions show a distinct increase in leakage current on the X4, X5, Y4, and Y5 grid conductors, which corresponds to the fault area bounded by the grid coordinates. Figure 4: Graphs of measured grid-to-deck leakage currents in X and Y directions 4

FIELD INSTALLATIONS Several successful installations have been carried out on over 1,500,000 square feet of waterproofing membrane on projects ranging from green roofs of several hundred square feet (Figure 5) to plaza decks and reservoir caps (Figure 6) of 270,000 square feet or more. Although not discussed in this paper, a quality control electric conductance membrane survey which uses the same measurement principal as the grid system is carried out to ensure that there are no membrane breaches prior to installation of the grid system. These systems have been deployed over the last few years with an increasing interest in application on inverted roof systems. In a few of the installations post-construction membrane leaks have been detected, located and repaired with minimum disruption of the overburden or green roof. Figure 5. Leak locate grid installed on membrane of an intensive green roof system Figure 6. Survey followed by leak locate grid installation on a large reservoir membrane DISCUSSION Leak-locate grid conductors installed on top of waterproof membranes, if monitored on a regular basis, can provide early detection and location of membrane damage. This method is particularly useful for roof designs that incorporate a fully adhered nonconductive waterproofing membrane 5

under a green roof, wear-course or topping slab where direct inspection of the roof membrane is difficult or impossible. By performing a routine leak detection and locate procedure, membrane breaches can be quickly identified and localized to a grid size area. A top-of-membrane grid system provides an accurate and cost effective method to monitor and maintain a wide range of covered roof types and sizes. REFERE CES 1. David M. Bailey et. al., Survey of Passive Leak Location Technologies, US Army Corp of Engineers Construction Engineering Research Laboratories, USACERL Technical Report FM-94/04 2. K.Y. Liu and A. Baskaran, Using Garden Roof Systems to Improve Performance, National Research Council Canada, NRCC-48376 3. Z. Lounis, D. J. Vanier and M. A. Lacasse, A discrete stochastic model for performance prediction of roofing systems, CIB World Building Congress, "Construction and the Environment", June 7-12, 1998, Gävle, Sweden 4. ASTM D 5957 Standard Guide for Flood Testing Horizontal Waterproofing Installations, Developed by Subcommittee: D08.22, Book of Standards Volume: 04.04 5. Canadian Roofing Contractors Association/Association Canadienne Des Entrepreneurs En Couverture, Advisory Bulletin March 2007 6. Graeme Cesare Consiglio, Foreword: The Challenge, Building Science Insight '89, "Roofs that Work", 1989 7. Vokey, D., et al, (2006, summer). A Building Envelope Moisture Detection System Using Contiguous Zone Monitoring. OBEC, 25-27. 8. Hensley, Lester, Sweeping deck joints under the rug, GoStructural.com, Feature Article, Monday, May 01, 2006 9. Hedlin, C.P., CBD-179. Inspection and Maintenance of Flat Roofs, Canadian Building Digest, July 1976 10. Mendel, Bart, Anatomy of a Plaza Deck, FOCUS, CAI, Greater Los Angeles Chapter, May/June 2006 6