PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller
|
|
- Stephen Henry
- 7 years ago
- Views:
Transcription
1 BLZPTS-1 NOVEMBER 19, 2013 TS350 TS752 BLPS PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller DESCRIPTION The BLPS, TS350 and TS752 Series of pressure and temperature sensors are designed for use with the PPC4000 Fuel Air Ratio Controller and BurnerLogix Burner Management System with Integrated Boiler Control. The pressure sensors (P/N BLPS-x) utilize a solid state pressure transducer to indicate steam pressure. The temperature sensors (P/N TS350-x and TS752-x) utilize a platinum, positive temperature coefficient sensing element to provide indication of water temperature, stack temperature, boiler water temperature of a steam boiler, and outdoor air temperature. The pressure sensors have a maximum overpressure specification of 200% Full Scale Output and 800% Burst. The pressure sensors are equipped with a 1/4" NPT male fitting. The Immersion Style Temperature Sensors have a 1/2" NPT mounting for the 2", 4" and 8" thermowell probe. The pressure and temperature sensors provide a 4-20 ma control signal over their respective stated ranges to the PPC4000 and BurnerLogix Control systems. No setting or calibration is required for either type of sensor. The PPC4000 and BurnerLogix Control systems perform continuous safety checks on the operation of all pressure and temperature sensors to insure their safe and proper operation (e.g. under range, over range, open wiring, etc.). WARNING: The PPC4000 Fuel Air ratio Controller and BurnerLogix Control System must only be used with the approved pressure and temperature sensors. (e.g.: BLPS-15, TS350-4, etc.). Do not use with any other types of pressure or temperature sensors. UL approval requires these sensors. 1
2 Fireye P/N BLPS-15 BLPS-25 BLPS-30 BLPS-200 BLPS-300 TS350-2 TS350-4 TS350-8 TS752-2 TS752-4 TS752-8 GENERAL SPECIFICATIONS Temperature Sensors: Description Pressure transducer, 0 to 15 psi (0 to 1030 mb), 4-20 ma output linear with pressure. ¼" NPT mounting. Screw terminal connections and conduit adapter cover. Pressure transducer, to 25 psi (-1013 to 1720 mb), 4-20 ma output linear with pressure. ¼" NPT mounting. Screw terminal connections and conduit adapter cover. Pressure transducer, 0 to 30 psi (0 to 2070 mb), 4-20 ma output linear with pressure. ¼" NPT mounting. Screw terminal connections and conduit adapter cover. Pressure transducer, 0 to 200 psi (0 to 13.8 Bar), 4-20 ma output linear with pressure. ¼" NPT mounting. Screw terminal connections and conduit adapter cover. Pressure transducer, 0 to 300 psi (0 to 20.7 Bar), 4-20 ma output linear with pressure. ¼" NPT mounting. Screw terminal connections and conduit adapter cover. Temperature sensor, Range 32 F to 350 F (0 C to 176 C), 4-20 ma output, linear with temperature. Insertion length is 2 inches. Stainless steel thermowell included with ½"-14 NPT mounting. Temperature sensor, Range 32 F to 350 F (0 C to 176 C), 4-20 ma output, linear with temperature. Insertion length is 4 inches. Stainless steel thermowell included with ½"-14 NPT mounting. Temperature sensor, Range 32 F to 350 F (0 C to 176 C), 4-20 ma output, linear with temperature. Insertion length is 8 inches. Stainless steel thermowell included with ½"-14 NPT mounting. Temperature sensor, Range 32 F to 752 F (0 C to 176 C), 4-20 ma output, linear with temperature. Insertion length is 2 inches. Stainless steel thermowell included with ½"-14 NPT mounting. Temperature sensor, Range 32 F to 752 F (0 C to 176 C), 4-20 ma output, linear with temperature. Insertion length is 4 inches. Stainless steel thermowell included with ½"-14 NPT mounting. Temperature sensor, Range 32 F to 752 F (0 C to 176 C), 4-20 ma output, linear with temperature. Insertion length is 8 inches. Stainless steel thermowell included with ½"-14 NPT mounting. Note: BLPS-25 is not compatible with the Burnerlogix Control System Temperature Measurement Range: TS350-X: 32 F to 350 F (0 C to 176 C) TS752-X: 32 F to 752 F (0 C to 400 C) RTD Type: Platinum, 100 ohms F (0 C) Temperature Coefficient: ohms/ohms/c Output: 4-20 ma, linear with temperature Operating Temperature Range: -13 F to 185 F (-25 C to 85 C) Accuracy: +/- 0.75% of span Thermowell Case: 300 Series stainless steel Mechanical Fittings: 1/2-14 NPT Pressure Sensors: Pressure Measurement Range: 0 to 15, to 25, 0 to 30, 0 to 200, 0 to 300 psig Excitation Voltage: 9-30Vdc (supplied by BurnerLogix control) Accuracy: +/- 0.25% Full Scale (at constant temperature) Output: 4-20 ma, linear with pressure Maximum Over Pressure: 200% of full scale Maximum Burst Pressure: 800% of full scale Operating Temperature Range: -40 F to 185 F (-40 C to 85 C) Fitting: 1/4" NPT Male Electrical: 1/2" Conduit and Terminal Strip 2
3 APPROVALS Underwriters Laboratories Inc.: MCCZ File MP1537 Controls, Primary Safety - Listed MCCZ2 File MP1537 Controls, Primary Safety - Component MCCZ7 File MP1537 Controls, Primary Safety Certified for Canada MCCZ8 File MP1537 Controls, Primary Safety Certified for Canada - Component Factory Mutual: FM Class 7610 Acceptable by: Industrial Risk Insurers (I.R.I.) FIGURE 1. Pressure Sensor - BLPS-15, -25, -30, -200, -300 GND COM OUT EXC 3
4 FIGURE 2. Temperature Sensor - TS350-2, TS350-4, TS350-8 FIGURE 3. Temperature Sensor - TS752-2, TS752-4, TS [279] 7.5 [191] X = 2, 4 or 8 WARNING: 1. Read these instructions carefully. Failure to follow them could result in a hazardous or dangerous condition. 2. Insure that the range of the selected sensor is appropriate for the application. Note: A general rule to follow when selecting the sensor range is that the expected value of the monitored pressure or sensor should fall between 40-70% of the upper range of the sensor. For example, a steam boiler maintains 20 lbs. pressure, select the BLPS-30 Pressure Sensor, with a 0-30 PSIG range 3. The sensors must be located where the ambient temperature will not exceed the maximum ambient operating temperature specified for the sensor. 4. Insure that the pressure range programmed on the BurnerLogix Boiler Room Control matches the installed pressure sensor. Refer to Bulletin BLZ Do not mount any of the sensors where they could be used as a footstep. 6. Installation must be performed by a trained, experienced flame safeguard technician. 4
5 WARNING: The electro-mechanical high steam limit and/or high hot water temperature limit MUST REMAIN in the running interlock circuit of the flame safeguard control. MOUNTING PRESSURE SENSORS Note: Refer to Figure The steam pressure sensors (BLPS-15, -25, -30, -200, -300) provide a 1/4 NPT male fitting for connection to the steam header. Included is a 1/4 coupling. 2. Make sure the boiler is shut down and zero steam pressure exists in the boiler vessel. 3. Disconnect power to the boiler controller so the boiler cannot sequence during installation of the steam pressure sensor. 4. Always mount the steam pressure sensor above the water line of the boiler. 5. Locate the pressure sensors where the ambient temperature will not exceed 185F FIGURE 4. STEAM PRESSURE OR HOT WATER SENSOR ELECTRO-MECHANICAL HIGH LIMIT (STEAM OR WATER) 6. Although the unit can withstand substantial vibration without damage or significant output effects, it is good practice to mount the pressure sensor where there is minimum vibration. 7. A steam trap (siphon loop) must be connected between the boiler and the pressure sensor to prevent boiler scale and corrosive vapors from affecting the pressure sensor element. 8. Use only a small amount of pipe compound to seal the connection joints. Excess pipe compound may clog the fitting and prevent proper operation of the sensor. 9. Make all pipe connections in accordance with approved standards. 10. When tightening the sensor, apply a wrench to the hex flats located just above the pressure fitting. DO NOT tighten by using a pipe wrench on the housing. Do not tighten the pressure sensor by hand. MOUNTING TEMPERATURE SENSORS The immersion style temperature sensors have a ½" NPT mounting for the 2", 4" and 8" thermowell probes, and a ½" conduit fitting. HOT WATER Note: Refer to Figure 4 1. Disconnect power to the boiler controller so the boiler cannot sequence during installation of the hot water temperature sensor. 2. The thermowell must be mounted where it is always exposed to the circulation of the hot water 3. If the water system is full, drain the system below the point where the thermowell will be installed. 4. Tap an appropriate size fitting. (2", 4" and 8" thermowell have ½"NPT fitting). 5. Insert the appropriate thermowell (2", 4", or 8") and tighten. 6. Fill the system to check for leakage. 5
6 LEAD/LAG OPERATION: When two hot water boilers are set-up for lead/lag operation, a hot water temperature sensor must be installed for each boiler. STANDBY WATER TEMPERATURE 1. Disconnect power to the boiler controller so the boiler cannot sequence during installation of the standby temperature sensor. WARNING: Location of the temperature sensor to monitor boiler water temperature of a steam boiler is critical. The sensor should be mounted where it is always exposed to the circulation of the boiler water, not too close to a hot or cold inlet or steam coil. Consult the boiler manufacturer for guidance on the sensor location. 2. The thermowell must be mounted where it is always exposed to the circulation of the hot water. 3. If the water system is full, drain the system below the point where the thermowell will be installed. 4. Tap an appropriate size fitting (2", 4" and 8" thermowells have 1/2" NPT fitting). 5. Insert the appropriate thermowell (2", 4", or 8") and tighten. STACK TEMPERATURE 1. Use the existing well connection for the stack temperature sensor if provided by the boiler manufacturer. 2. If no well connection is provided, select an appropriate location for mounting the temperature sensor. Preferably as close to the boiler outlet as possible. OUTDOOR AIR TEMPERATURE 1. The outdoor air temperature sensor should be mounted on the outside of the building where it will be exposed to representative air temperature, but not to direct sunlight. A sun shield may be required. 2. Mount the temperature sensor high enough so it cannot be covered with snow, leaves, or other debris, or be tampered with. Vents from the building should be avoided. 6
7 WIRING SENSORS CAUTION: Disconnect power supply from the BurnerLogix Control before connecting wires to prevent electrical shock and equipment damage. PRESSURE SENSORS 1. All wiring must be in accordance with National Electrical Code and local codes, ordinances, and regulations. 2. Sensor housing provides connection for 1/2" conduit. 3. The pressure sensors require 2 conductor, 18 gauge, shielded cable. Power limited, rated for Use Belden 9318 or equivalent. GND COM OUT EXC For 4-20 ma output, use + EXC and - COM terminals 4. The shield should be connected to the earth ground terminal on the wiring base of the Burner- Logix Control (Terminal #E) or to the common ground established in the cabinet. The shield should be taped at the sensor to avoid unintended contact with the sensor housing. 5. All sensor wiring should be in a separate conduit. DO NOT install sensor wiring in any conduit or junction boxes with high voltage wiring. 6. Maximum wiring distance for sensor wiring is 100 feet. 7. See Table 1 for wiring terminations to the Burnerlogix 8. See Table 2 for wiring connections to the PPC4000. TEMPERATURE SENSORS 1. All wiring must be in accordance with National Electrical Code and local codes, ordinances, and regulations. 2. Sensor housing provides connection for ½" conduit MINCO For 4-20 ma output, use terminals 1 (+) and 2 (-) Measurement Specialties Temperature Specialists Inc. For 4-20 ma output, use terminals (+) and (-) For 4-20 ma output, use terminals 6 and 7 7
8 3. The temperature sensors require 2 conductor, 18 gauge, shielded cable. Power limited, rated for Use Belden 9318 or equivalent. 4. The shield should be connected to the earth ground terminal on the wiring base of the Burner- Logix Control (Terminal #E) or to the common ground established in the cabinet. The shield should be taped at the sensor to avoid unintended contact with the sensor housing. 5. All sensor wiring should be in a separate conduit. DO NOT install sensor wiring in any conduit or junction boxes with high voltage wiring. 6. Maximum wiring distance for sensor wiring is 100 feet. 7. SeeTable 1 and 2 for wiring terminations. Table 1: Burnerlogix wiring connections TS350/TS752 BLPS PCV AUX1 AUX2 Minco Meas Sp Temp Sp BurnerLogix Terminals EXC X (WHT/BLU) X (WHT/BLU) X (WHT/BLU) COM 11 (WHT/GRN) 22 (WHT/VIO) 23 (BRN/WHT) Table 2: PPC4000 wiring connections TS350/TS752 BLPS PCV AUX1 AUX2 SENS4 SENS5 Minco Meas Sp Temp Sp PPC4000 Terminals EXC P11.2 P11.2 P11.3 P11.3 P COM P11.10 P11.9 P11.8 P11.7 P11.6 CAUTION: PROGRAM AND SET-UP The proper operation of the BurnerLogix System and the pressure and temperature sensors requires that the selected pressure ranges are appropriate for the application and must match the pressure range programmed on the BurnerLogix Control. Insure that the range of the selected sensor is correct for the application and the pressure range programmed on the BurnerLogix Integrated Flame Safeguard and Boiler Controller matches the installed pressure sensor. Refer to Bulletin BLZ NOTICE When Fireye products are combined with equipment manufactured by others and/or integrated into systems designed or manufactured by others, the Fireye warranty, as stated in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the combined system or its overall performance. WARRANTIES FIREYE guarantees for one year from the date of installation or 18 months from date of manufacture of its products to replace, or, at its option, to repair any product or part thereof (except lamps and photocells) which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order. THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANT- ABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED. Except as specifically stated in these general terms and conditions of sale, remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or repair as above provided. In no event shall Fireye be liable for consequential or special damages of any nature that may arise in connection with such product or part. FIREYE BLZPTS-1 3 Manchester Road NOVEMBER 19, 2013 Derry, New Hampshire USA Supersedes November 6,
NEXUS FX04 and FX04-1 Servo Motor Installation. Fireye DESCRIPTION SAFETY INFORMATION. FX04-1 Shown
NEX-3004 AUGUST 4, 2015 Fireye NEXUS FX04 and FX04-1 Servo Motor Installation FX04-1 Shown DESCRIPTION This bulletin describes the installation and operating instructions for the FX04 and FX04-1, 3 lb.-ft./
More informationTABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)
CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.
More informationINSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)
CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage
More informationINSTALLATION INSTRUCTIONS for INSIGHT FIBER OPTIC FLAME SCANNERS
CU-101 DECEMBER 3, 2015 INSTALLATION INSTRUCTIONS for INSIGHT FIBER OPTIC FLAME SCANNERS APPLICATION The FIREYE fiber optic scanners have been designed for installation on burners where movable vanes,
More informationParagon Explorer Lite Communication Software
CU-111 APRIL 11, 2013 Paragon Explorer Lite Communication Software For Fireye Paragon Scanners using Windows XP DESCRIPTION Paragon Explorer Lite, is the basic PC based configuration tool for Paragon model
More informationSeries 510 Submersible Level Transmitters
Series 510 Submersible Level Transmitters The Series 510 Submersible Level Transmitters are solid state instruments designed for direct submergence into many types of liquid for quick, accurate and reliable
More informationA99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
More informationPart I - Installation
400 Series Pressure and Differential Pressure Switches Types: H400, H402, H403, H400K, H402K, J400, J402, J403, J400K, J402K UNITED ELECTRIC CONTROLS Installation and Maintenance Instructions Please read
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationPipe Temperature Sensors
Pipe Temperature Sensors Model TE-703 / 704 RoHS Four immersion thermowell installation options brass adapter with 304 SS probe for adjustable insertion, plastic, galvanized steel or NEMA-4/IP-65 steel
More informationOWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
More information36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
More informationElectric Water Heater
Electric Water Heater Operation and Installation Manual (LIMITED WARRANTY AND TANK REPLACEMENT POLICY) The following information should be noted at time of installation and retained for future reference.
More informationDeltaSpan Submersible Pressure Level Transmitter Manual LD31 Series 22 AUG 08 Rev A
DeltaSpan Submersible Pressure Level Transmitter Manual LD31 Series 22 AUG 08 Flowline, Inc. 10500 Humbolt Street Los Alamitos, CA 90720 Tel: (562) 598-3015 Fax: (562) 431-8507 www.flowline.com 22 AUG
More information4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX
Butterfly Valves 4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com MAY 2013 L-1 BULLETIN BUTTERFLY REV. #5 GLOBE BUTTERFLY VALVE INSTALLATION
More information! WARNING. Before using product, read and understand instructions.
McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes
More informationInstallation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of
More informationSubmersion/Insertion Toroidal Sensor
Instruction Sheet PN 51A-228/rev.P December 2010 Model 228 Submersion/Insertion Toroidal Sensor For additional information, please visit our website at www.emersonprocess.com/raihome/liquid/. CAUTION SENSOR/PROCESS
More information! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
More informationIndirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
More informationABC-1000 Automatic Boiler Level Controller Operation and Installation Manual
QUALITY STEAM SPECIALTIES SINCE ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual Section: C500 Bulletin: C500.40 Date: 06-26-01 Supersedes: New PRODUCT DESCRIPTION: The Clark-Reliance
More informationValve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)
Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC) VPS 504 S06 (120 VAC) is: CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter R-15 (Canada) UL
More informationSOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide
SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide circuit. Reverse connection will damage the module and may result in fire. CAUTIONS Solar electric modules produce DC electricity
More informationBLUE RIBBON CORP. BC001 Birdcage Installation Manual
Product Overview: This manual is applicable for the BC001 Birdcage Submersible Level Transmitters. If the product you have has a different prefix part number than listed above please contact the factory
More informationINSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION When installing or using any high voltage electrical appliance, basic safety precautions
More informationYour safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
More informationSolar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual
Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual 255379 Rev. D0 1015 Printed in U.S.A. Copyright 2015 Federal Signal Corporation Limited Warranty The Alerting and Notification
More informationColor Splash LED Light Fixture Installation and Operation Guide
Color Splash LED Light Fixture Installation and Operation Guide Technical Support Phone: 800.735.4553 ext. 242 For more information about this or other J&J Electronics lighting products, please visit www.jandjpoolspa.com
More informationRGC-IR Remote Gas Calibrator for IR400
Remote Gas Calibrator for IR400 The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by
More informationPre-Fab Easy Installation For Models: 006-CT-USK, 008-CT-USK Installation and Operating Instructions for Existing Homes with Standard Piping
Instruction Sheet 102-140 Pre-Fab Easy Installation For Models: 006-CT-USK, 008-CT-USK Installation and Operating Instructions for Existing Homes with Standard Piping Plant I.D. 001-1024 EFFECTIVE: November
More informationPropane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
More informationThermatel Model TA1 Mass Flow Transmitter
Thermatel Model TA1 Mass Flow Transmitter D E S C R I P T I O N Thermatel Thermal Mass Flow Transmitter, Model TA1, provides a high level of performance in mass flow measurement of air and gases. Powerful
More informationToroidal Conductivity Sensor
Instruction Sheet PN 51A-/rev.C June 2012 Toroidal Conductivity Sensor For additional information, please visit our website at www.emersonprocess.com/rosemountanalytical.com SPECIFICATIONS Wetted Materials:
More informationC. Burner management system to follow requirements of Industrial Risk Insurers (IRI).
SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE
More informationInstalling a Probe. Typical Installation
for hazardous locations. Prior to any installation in a Classified Hazardous Location, verify installation methods by the Control Drawing referenced on the product s name tag 2. The Feed Through Assembly
More informationInstallation Guidelines: Resistance Thermometers and Temptran Thermometers for Building Automation Systems
APPLICATION AID SAA20 Installation Guidelines: Resistance Thermometers and Temptran Thermometers for Building Automation Systems Duct Air page 4 Thermal-Ribbon pages 6-7 Room Air Compact Room Air page
More informationModel SRMD Setra Remote Monitoring Display
Model SRMD Setra Remote Monitoring Display 1.0 GENERAL INFORMATION Thank you for purchasing the Setra Remote Monitoring Display (SRMD). The SRMD is a digital panel meter with a bright 1 LED display for
More informationDuct Temperature Sensors
Duct s Model TE-701 / 702 RoHS More than 16 types of interchangeable NTC thermistors, precision platinum, nickel or balco RTDs are available for universal compatibility. Five installation options probe
More informationTechnical Data. Installation
Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems General Description The Figure 51 (1) Riser Manifolds
More informationDICKSON PW4 DICKSON. Pressure Chart Recorders. Applications & Specifications. Product. Getting Started, Charts & Accessories.
PW4 Pressure Chart Recorders Contents: Applications and Useful Features Operating Instructions / Getting Started Calibrations Troubleshooting Warranty / Factory Service & Applications The PW4 Weather Resistant
More informationBURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS
BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS INTRODUCTION Rupture discs are often used as primary pressure relief devices and to isolate pressure relief valves. When used as a primary pressure relief
More informationThreaded Inline Air Heaters
Threaded Inline Air Heaters FOR SAFETY & LONG HEATER LIFE, CAREFULLY READ THIS MANUAL BEFORE USE. Safety SHOCK HAZARD! Only qualified individuals should install this heater and related controls. Follow
More informationSELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine
More informationCEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
More informationETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
More informationTYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output
133-683 JUNE 28, 2006 TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output DESCRIPTION APPLICATION The Fireye 65UV5-1004 flame scanner is a microprocessor based flame
More informationPART 1 - INTRODUCTION...
Table of Contents PART 1 - INTRODUCTION... 3 1.1 General... 3 1.2 Sensor Features... 3 1.3 Sensor Specifications (CDE-45P)... 4 Figure 1-1 CDE-45P Sensor Dimensions (standard, convertible style)... 4 PART
More informationSDX Submersible Depth Transmitter User Manual
SDX Submersible Depth Transmitter User Manual January 2011 USER INFORMATION Stevens makes no warranty as to the information furnished in these instructions and the reader assumes all risk in the use thereof.
More informationThe Do s and Don ts of Pressure Transducers
The Do s and Don ts of Pressure Transducers ABSTRACT When specifying a pressure transducer for a process measurement, a number of items have to be considered. Some of the more important ones are discussed
More informationSunMaxx Solar Filling Station Operating Instructions
SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...
More informationGAS SAFETY PRECAUTIONS
GAS SAFETY PRECAUTIONS Instructions on what to do when a user smells gas can be obtained from the local gas supplier. These instructions must be posted in a prominent location where the unit is to be operated.
More informationSingle Station Remote Alarm
ADI 5106G Certified ISO 9001:2000 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation
More informationIn-Line Electronic Flow Switches
In-Line Electronic Flow Switches Industries Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor
More informationLight Duty Commercial Electric Water Heater
Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and
More informationSubmersion/Insertion Toroidal Sensor
Instruction Manual 228 Sensor LIQ_MAN_ABR_228 May 2014 PN 51A-228 Submersion/Insertion Toroidal Sensor For additional information, please visit our website at www.rosemountanalytical.com CAUTION SENSOR/PROCESS
More informationCONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page 2-7. 3-Phase Simplex Page 8-13
CONTROL PANEL INSTALLATION INSTRUCTIONS Single Phase Simplex Page 2-7 3-Phase Simplex Page 8-13 Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3 Manufactured by SJE-Rhombus Installation Instructions
More informationVehicle Brake System Monitoring 2-wire, 4-20 ma option; Intrinsic Safety Approval to E Exia IIC T4 (Tamb=60 C) BASEEFA, CENELEC EN50-020
Field proven rugged construction High overpressure capability High reliability for demanding environments Application specific customization Excellent media compatibility Shock and vibration resistant
More informationGlobal Water Instrumentation, Inc.
Global Water Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 Water Level Sensor: WL400 00-997 11/30/09-1 - Congratulations on your
More informationRAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
More informationwith MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
More informationProduct Data. Model 575 Series Submersible Level Transmitters ELECTRONIC PRESSURE MEASUREMENT PRODUCTS DESCRIPTION FEATURES APPLICATIONS
EPP - 1 DECRIPTION The odel 575 is used in general water/wastewater applications. The transmitter is offered in a standard non-clogging snub nose end, flush diaphragm or protected flush diaphragm with
More informationSeaward Products OWNER S MANUAL WATER HEATERS. Serial Number:
Seaward Products WATER HEATERS OWNER S MANUAL Serial Number: IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, basic safety precautions to reduce the risk of fire, electrical shock,
More informationT7079A,B Solid State Remote Temperature Controllers
T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature
More informationSanitary Type Electronic Flow Switches
Industries Pharmaceutical Sanitary Type Electronic Flow Switches Food and Beverage Biotechnology Semiconductor Water Treatment S Series Ameritrol, Inc. Instruments and Controls Features No Moving Parts
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
More informationFIREYE FLAME SCANNERS
UV1A UV8A UV90 UV1A UV8A SC-102 JUNE 17, 2015 FIREYE FLAME SCANNERS UV non self-checking Scanner Models: UV1A3, UV1A6, UV8A, UV2, UV2A6, 45UV3, UV90-3. UV90-6, UV90-9 For UV self-check Scanners refer to
More informationINSTALLATION AND SERVICE MANUAL EPJ SERIES INDIRECT WATER HEATERS
INSTALLATION AND SERVICE MANUAL EPJ SERIES INDIRECT WATER HEATERS FOR MODELS EPJ-40 AND EPJ-56 SEE REAR COVER FOR INDEX Read this instruction manual before installation, operation, or service. Failure
More informationATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
More informationPMP 4000 Series. Druck Amplified Output Pressure Transducers. GE Sensing. Applications. Features
Features Applications The PMP 4000 Series provides a complete range of high level voltage output pressure transducers offering advanced levels of measurement accuracy, stability and flexibility from a
More informationATL Fuel Level Sender Probes
T E C H N I C A L S P E C I F I C A T I O N The ATL EL-AD-151 (Resistance Output) and EL-AD-152 (Voltage Output) Fuel Level Senders are highly advanced sensors for continuously measuring the contents of
More informationSensor for Ammonia. 11511 West 83 rd Terrace email sales@manningsystems.com. 1.800.444.9935 or 913.894.1185. fax 913.894.1296
EC-F2-NH 3 Sensor for Ammonia Instruction and Installation Manual Rev H MOUNT ENCLOSURE THIS END UP. DO NOT BLOCK PERFORATED VENT HOLES. SENSOR 11511 West 83 rd Terrace email sales@manningsystems.com Lenexa,
More informationK Standard Grade Ni-Cr vs Ni-Al (Chromel vs Alumel)
SureGrip TM 80PK-24 Air Temperature Probe Instruction Sheet XWWarning To avoid electrical shock, do not use this probe when voltages exceeding 24 V ac rms or 60 V dc are present. The probe tip is electronically
More informationT775U Series 2000 Electronic Stand-Alone Controller
T775U Series 2000 Electronic Stand-Alone Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of universal controls capable of remote
More informationIntroduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual
Operation and Maintenance Manual Introduction Read all instructions thoroughly. Installation of the OilTector must comply with all Federal, State and Local Codes, Regulations and Practices. The OilTector
More informationModel/Sprinkler Identification Numbers
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-L 5.6 and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description
More informationLOW-VOLTAGE TRANSFORMER QUICK START GUIDE PLANNING GUIDE INSTALLATION GUIDE
LOW-VOLTAGE TRANSFORMER QUICK START GUIDE PLANNING GUIDE INSTALLATION GUIDE Applies to Models: 75W, 150W, 300W, 600W, 900W, 1200W ATTENTION: Please read this guide carefully to ensure safe and efficient
More informationElectronic Flow Switches
Industries Electronic Flow Switches Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor
More informationAmerican Fireglass Outdoor Fire pit kit information. General instructions/warnings for outdoor gas pan and burner systems
American Fireglass Outdoor Fire pit kit information General instructions/warnings for outdoor gas pan and burner systems We strongly recommend that our burner products be installed by a licensed and certified
More informationSprinkler Guards Model C Model D
Bulletin 208 Rev. M Sprinkler Guards Model C Model D Bulletin 208 Rev. M Model C Sprinkler Guards Model C Series sprinkler guards are designed to be assembled onto installed sprinklers. They are constructed
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 36C01 Combination Gas Valves (24 Volt and 120 Volt Models) INSTALLATI INSTRUCTIS FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE
More informationGL-235 Solar Pool Controller
GL-235 Solar Pool Controller Installation & Operation Manual G LDLINE CON TROLS www.goldlinecontrols.com Description The GL-235 is a differential temperature control for solar heating of pools, spas, and
More informationAUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E
AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E SENS part no: 101314 Document revision: F DCN No. 106811 Date 8/3/15 1840 Industrial Circle Longmont, CO 80501 Fax: (303) 678-7504
More informationDUSTTRAK AEROSOL MONITOR SOLAR POWER KIT MODEL 854060
DUSTTRAK AEROSOL MONITOR SOLAR POWER KIT MODEL 854060 (FOR DUSTTRAK II AND DRX AEROSOL MONITOR MODELS 8540 AND 8543) OPERATION AND MAINTENANCE MANUAL P/N 6008416, REVISION A MAY 2015 Copyright TSI Incorporated
More informationFor Multi-Parameter Meters see mvx
BULLETIN BULLETIN EM20607 VORTEX IN-LINE FLOW METERS Design Features For Multi-Parameter Meters see m Principles of Operation n No moving parts to wear or fail. n Electronics can be remotely mounted up
More informationInstallation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1
REMOTE METER TM Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1 1098 Washington Crossing Road Washington Crossing, PA 18977 USA www.morningstarcorp.com
More informationPART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual
PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code
More informationTECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
More informationStainless Steel Single and Dual Circulation Kits
Instruction Sheet P/N 160780 01 Stainless Steel Single and Dual Circulation Kits Introduction The single and dual high-pressure circulation kits allow you to vary and control the circulation rate of coating
More informationModel TJE. Precision Gage/Absolute Pressure Transducer DESCRIPTION FEATURES
Precision Gage/Absolute Transducer DESCRIPTION Model TJE pressure transducers are all-welded stainless steel sensors built for rugged industrial applications that require high accuracy and measurement
More informationOPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE
OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203)
More informationCentro-Matic Automatic Lubrication Systems System Controls
Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the
More informationUtility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
More informationWMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler
WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility
More informationGeneral Purpose ph/orp Sensor
Instruction Sheet General Purpose ph/orp Sensor Sensors LIQ_MAN_ABR_3900 October 2014 General Purpose ph/orp Sensor Specifications Figure 1. 3900 Insertion/Submersion Sensor Sensor Type: General purpose
More informationMachine Safety Switch: SI-LM40 Series Limit Switch Style
Machine Switch: SI-LM40 Series Limit Switch Style SI-LM40 Series Limit Switch Style with Flexible In-Line Actuator Positive-opening safety contacts (IEC 60947-5-1) (not dependent upon springs) Standard
More informationModulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, 1060. Instruction No.
Instruction No. AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA PIPING GUIDE GF-115-P Modulex Gas Fired Boiler Systems Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909,
More informationLAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
More informationDC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL Service Information If service or parts are required, contact the nearest Norcold Service Center. To find an authorized Norcold Service Center
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationGeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control
PARTS & ACCESSORIES GeniSys 12V Model 7556 Advanced 12 Vdc Burner Control Description / Applications The Beckett GeniSys TM 12V Advanced Burner Control is a 12 Vdc primary safety control for oil burners
More information