Essential Performance Attributes of Preapplied waterproofing

Size: px
Start display at page:

Download "Essential Performance Attributes of Preapplied waterproofing"

Transcription

1 Essential Performance Attributes of Preapplied waterproofing Craig Boucher, LEED AP Grace Construction Products 62 Whittemore Ave., Cambridge, MA Phone: Fax: t h R C I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h o w M a R C h , B o u C h e R 3 3

2 Abstract The practice of installing waterproofing onto a soil retention system prior to pouring the concrete foundation is preapplied waterproofing. The presentation will address the challenges of preapplied waterproofing and identify some issues that result in failures of some waterproofing systems. Critical performance attributes of a preapplied waterproofing system namely bond-to-concrete and lateral water migration resistance will be identified to help ensure a successful, leak-free waterproofing system. The presenter will share the knowledge gained from more than 50 years of waterproofing product development and the technical issues that were addressed in the development process. Speaker Craig Boucher, LEED AP Grace Construction Products - Cambridge, MA CrAIG BoUCHer has worked in the construction product industry for over ten years. He currently holds the position of product manager of below-grade waterproofing at W.r. Grace. Craig has been involved in water management and the building envelope for most of his career. He has witnessed waterproofing testing at third-party labs and participates in the ASTM committees that developed the standards. He has a BS in civil engineering from Worcester polytechnic Institute and is a leed Accredited professional. 3 4 B o u C h e R 2 8 t h R C I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h o w M a R C h ,

3 Essential Performance Attributes of Preapplied waterproofing BELOw-GRADE waterproofing BASICS to waterproofing systems adhered to structures that have already been built, while preapplied waterproofing is installed prior to building the structure. While both have their uses, preapplied waterproofing offers a unique set of advantages in certain applications. contact with the exterior of the foundation slab and walls. preapplied waterproofing is usually the only option for the area under the foundation slab, because the area is not excavated to allow for postapplied waterproofing. However, postapplied waterproofing can be used on vertical foundation walls when there is access around the foundation perimeter and the project team decides to excavate out from the perimeter. Figure 2 shows a combination of preapplied waterproofing below the slab and postapplied waterproofing on the vertical walls. For project sites that are confined or where excavation out from the perimeter of the site is not possible and/or desired, preapplied waterproofing will be installed at both the horizontal area, under the slab; protecting buildings from below-grade water ingress is a critical concern for structures of all types. preapplied waterproofing systems offer some important advantages in certain construction applications. But they must be specified and installed correctly to deliver maximum performance over the COMMON USES OF PREAPPLIED long term. What type of system is right for waterproofing your specific application? What are the key In horizontal applications, preapplied factors to consider when selecting a solu- waterproofing is installed onto the mud tion? The answers lie in understanding the slab or earth prior to placing the concrete essential attributes of an effective preap- foundation slab. In vertical applications, plied waterproofing system. the preapplied waterproofing is attached to The purpose of all below-grade water- the soil retention system, such as timber proofing is to protect the foundation and lagging (see Figure 1), prior to the complebuilding from water and moisture ingress. tion of the foundation walls. Typically, the Sources of potential water ingress include preapplied waterproofing will be directly in precipitation, groundwater higher than the lowest elevation of the foundation, or groundwater that fluctuates above the lowest elevation of the foundation. Water ingress due to waterproofing failures can create liability for all parties involved: the design team, the applicator, and the consultant. These parties are often responsible for costly and time-consuming repairs to both the waterproofing system and any resulting water damage in the building. Waterproofing the below-grade area of a building using a quality product installed correctly will help avoid these issues and costs and reduce potential liability for the project team. Waterproofing can be categorized into two main categories: postapplied and preapplied. As their names suggest, postapplied refers Figure 1 Preapplied waterproofing installed against timber lagging in a vertical application. 28th RCI InteRnatIonal ConventIon and trade Show MaRCh 14-19, 2013 BouCheR 35

4 leed rating system credits associated with minimizing excavation of greenfield sites and utilizing brownfield sites. THREE ESSENTIAL ATTRIBUTES A preapplied waterproofing system must demonstrate the following essential attributes: puncture- and tear-resistant (suitable for harsh construction site conditions) Ability to bond to concrete lateral water migration resistance Figure 2 Combination of preapplied waterproofing below the slab and postapplied waterproofing on the vertical walls. Figure 3 A new building is located between two existing developed areas that cannot be removed or excavated, requiring use of preapplied waterproofing at both the horizontal and the vertical areas of the below-grade foundation. and the vertical areas, outside of the foundation walls. These conditions are common in areas such as densely populated urban areas, tourist areas, and universities or other campus environments. Figure 3 illustrates such an example, where an existing building and parking area to either side of the new building site prevent excavation out from the perimeter of the building, necessitating preapplied waterproofing. preapplied waterproofing can also be used in cases where the project team wishes to maximize the usable area of the building by extending the footprint out to adjacent structures. Finally, preapplied waterproofing can be used when the team wishes to minimize the amount of soil required to be excavated both in previously undeveloped greenfield sites and in brownfield (contaminated) sites. This may be particularly advantageous in brownfield sites, where the costs to remediate excavated soil are significant. It is important to note that the manufacturer of the preapplied waterproofing system should be consulted on brownfield sites to ensure the system is suitable for the particular exposure conditions of the site. In addition to cost considerations, using preapplied waterproofing may help projects qualify for These attributes are all important to ensure the preapplied waterproofing system will work as intended. let s review each of these essential attributes in detail. PUNCTURE- AND TEAR- RESISTANT (SUITABLE FOR HARSH CONSTRUCTION SITE CONDITIONS) preapplied waterproofing systems must be able to hold up to harsh job site conditions. During construction, they will be subjected to foot traffic, and objects such as tools and rebar could be placed on top of the waterproofing. Construction trades will use the preapplied waterproofing system as their working surface to build the rebar cage for the concrete that will be placed on top of the waterproofing. Having a system with good puncture resistance is critical to preventing leak paths that allow water to travel through. ASTM e154 is a test method that evaluates puncture resistance. The test prescribes a blunt object being forced through a section of the waterproofing that is clamped into a frame. A testing apparatus that pushes the blunt object also measures the force in pounds or Newton required to puncture the waterproofing. puncture resistance and ASTM e154 can be referenced in a guide specification. resistance of 200 pounds or 890 Newton force for horizontal materials and 100 pounds or 445 Newton force for vertical materials have historically yielded successful results and are referenced in third-party, industry guide specifications. A preapplied waterproofing membrane can be exposed to stresses on the construction site from laborers on the waterproofing, from heavy equipment being rolled across the waterproofing on a dolly, as well as from the concrete placement itself. To resist tears from these stresses, the waterproofing 3 6 B o u C h e R 2 8 t h R C I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h o w M a R C h ,

5 material must have good tensile strength and elongation properties. ASTM D412 is a test method that can be used to evaluate the tensile strength and elongation characteristics of the waterproofing material. ASTM D412 involves cutting a portion of the material into a standard shape and clamping the material into a testing device that can stretch or elongate the material to determine how much it will elongate before breaking. The testing equipment also measures the tensile strength that is applied to the material as it is stretched and records the maximum tensile strength achieved, measured in pounds per square inch or mega-pascal. These properties and ASTM D412 can be referenced in a guide specification. A tensile strength of 4,000 pounds per sq. in. or 27.6 mega-pascal and an elongation of 500% have historically yielded successful results for preapplied waterproofing materials. In addition to serving as a working surface on the job site for several trades, the preapplied waterproofing will also be exposed to the exterior conditions at the job site. It is essential to have a system that can stand up to these conditions and perform as intended to waterproof the below-grade area of the building. Sources used to confirm that the waterproofing system will perform as intended include bulletins from the manufacturer addressing these harsh conditions and a long, successful track record proving that the system is time-tested for the application. To help ensure positive results, a time period that the waterproofing system has been successfully utilized for preapplied waterproofing can be stated in the guide specification. preapplied waterproofing is subjected to harsh conditions. ensuring the preapplied waterproofing system is fit for its purpose in these harsh conditions and has a long track record of successful performance is the first step. Additional steps that could be used to help ensure a leak-free preapplied waterproofing installation include independent third-party inspection of the installed waterproofing system and electronic field vector mapping. These measures may help identify damage and voids in the waterproofing system and allow for repair prior to covering the installation with concrete. BOND TO CONCRETE For a preapplied waterproofing system to work effectively, it must remain bonded Figure 4 Degradation of the soil retention system and soil settlement result in the waterproofing system s being unsupported and unconfined. or adhered to the concrete. The preapplied waterproofing system is secured to a soil retaining system, such as timber lagging or sheet piles, in vertical applications and installed onto a mud slab or gravel base in horizontal applications. These substrates will typically not remain intact or in place over the life of the building. Therefore, a preapplied waterproofing system that bonds to the concrete that is applied against it is essential to ensure the waterproofing does not sag or fall away from the foundation walls and floor. Figure 4 shows a vertical timber lagging soil retention system and soil under the horizontal area. The soil under the building and the soil retention system may have an impact on the preapplied waterproofing system over the life of the building. The wood or timber lagging is below grade and surrounded by dirt and soil. over time, the lagging will likely degrade or rot. Any steel components of the soil retaining system are at risk of degrading due to corrosion. The soil under the slab may settle or fall away from the underside of the building. over time, the corrosion and degradation of the vertical soil retaining system and the soil under the building may settle due to rising and falling groundwater, degradation of organic material in the soil, and seismic activity. Therefore, the preapplied waterproofing system may be left unsupported and unconfined. If the preapplied waterproofing system is not bonded or adhered to the concrete, there is a risk that the waterproofing could sag and fall away. This may result in stresses on the system that could lead to tears or open/failed seams, creating gaps in the waterproofing for water to pass through. Materials that swell or expand in the presence of water to provide a gasket against water infiltration may be rendered ineffective as the vertical soil retention system and soil under the building no longer support and confine the swellable material. Bond to concrete can be referenced in guide specifications. ASTM D903 is a test method that measures the peel strength of a material to a substrate. A strip of the preapplied waterproofing is adhered to a substrate, such as the concrete foundation that will be applied against the waterproofing in the field, and the strip is peeled off of the substrate. The testing device measures the peel strength to concrete in pounds per inch or Newtons per meter. peel adhesion to concrete of at least 5 pounds per inch or 880 Newtons per meter have historically yielded successful results for preapplied waterproofing materials and are referenced in thirdparty, industry guide specifications. Currently, preapplied waterproofing technologies create a bond to concrete via either an adhesive or mechanical bond. An adhesive bond is created when an adhesive on the side of the waterproofing facing the concrete creates a continuous bond to the concrete when the concrete is placed against the waterproofing. It is important to note that the adhesive on the side of the waterproofing will be exposed to the construction process. Therefore, an adhesive that creates a bond to the concrete only when the concrete is placed against it, but is not sticky and tacky before the concrete is applied, is ideal to prevent construction 2 8 t h R C I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h o w M a R C h , B o u C h e R 3 7

6 Figure 5 Photos of mechanical and adhesive bond to concrete. workers, equipment, dust, and debris from adhering to the preapplied waterproofing. A mechanical bond is created by fibers or profiles that become encased by the concrete when the concrete is placed onto the waterproofing. For both types of materials, a good practice is to have the installed preapplied waterproofing system inspected by a third party to help ensure the material is suitable to receive concrete. If the preapplied waterproofing system has debris on top of the membrane or is excessively dirty due to the construction process, a good bond to the concrete may not be achieved. Inspecting, repairing, and cleaning excessively dirty areas of the preapplied waterproofing system will help ensure the expected bond to concrete is achieved. Figure 5 shows an adhesive bond and mechanical bond to concrete. For the mechanically bonded material, the fibers stretch and eventually break as the material is peeled away from the concrete substrate. The mechanical bond looks different than the adhesive bond, which has a continuous adhesive layer between the concrete and the waterproofing membrane. This difference is important when considering the final critical attribute for preapplied waterproofing: lateral water migration resistance. remaining bonded to concrete over time is important to ensure that the benefits of a fully bonded preapplied water- proofing system are realized. The track record of the waterproofing system can be evaluated to help understand if the bond to concrete will be maintained. Some preapplied waterproofing materials have been successfully used for over 20 years, which demonstrates that the system will perform as intended. Accelerated aging and longterm laboratory tests can help provide evidence that the waterproofing system will remain bonded over time, but a successful track record of actual performance in situ is the best indicator that the product will perform as intended over time. LATERAL water MIGRATION RESISTANCE lateral water migration resistance occurs when water is not allowed to travel between the preapplied waterproofing and the concrete foundation wall and floor to which the waterproofing is adhered. Figure 6A shows a proper installation of a preapplied waterproofing system prior to rebar placement, with no apparent voids or punctures in the system that could allow water passage. Figure 6B shows rebar being placed on top of the installed preapplied waterproofing system. During rebar installation, there is some risk that the preapplied waterproofing system could be damaged, punctured, or torn. In order to achieve a good bond between the preapplied waterproofing membrane and the concrete, the preapplied waterproofing membrane must be in direct contact with the concrete. Therefore, protection board cannot be installed on top of the preapplied waterproofing membrane to help prevent rebar punctures. Figure 6 Properly installed preapplied waterproofing (6A, above) and rebar installed on top of the preapplied waterproofing system (6B, right). 38 BouCheR 28th RCI InteRnatIonal ConventIon and trade Show MaRCh 14-19, 2013

7 Figure 7 Breaches or voids are shown in the waterproofing membrane with cracks or water entry points in the concrete a distance away from the breach or void. other trades on the job site could damage the preapplied waterproofing system as well, creating breaches and voids in the system. Inspection of the waterproofing system after installation and before the concrete placement is a good practice to catch any breaches and voids in the system before it is covered. However, in addition to inspection, a preapplied waterproofing system with good lateral water migration resistance can further reduce the likelihood of leaks into the building. Should water enter through a breach or void in the waterproofing system, lateral water migration resistance will prevent it from traveling to a crack or cold joint in the concrete that will allow water into the building. Figure 7 shows a membrane with a breach or void in both the vertical and horizontal membrane surfaces. Some distance away from the breach or void is a crack in the concrete. As precipitation occurs, water impacts the ground surrounding the building and can travel through the soil and down the vertical face of the below-grade wall. Also, groundwater may be present at a level above the lowest elevation of the foundation floor, or the groundwater may fluctuate and rise. eventually, the water will reach the breaches or voids in the membrane. If the 28th RCI InteRnatIonal ConventIon and water is free to move laterally between the membrane and the concrete, the water may get to the crack in the concrete and enter into the building, as shown in Figure 8. For preapplied waterproofing systems that prevent lateral water migration, a breach or void in the waterproofing system would have to be aligned with a crack or cold joint in the concrete for water entry into the building to occur. If leaks should occur, repairing the leak with an injectable grout from the inside of the building is the typical remedy. Because the waterproofing prevents lateral water migration, repairing the area of water leakage will be the extent of the repair. For membranes that do not prevent lateral water migration, the repair may be more extensive and costly, because water will continue to travel laterally between the membrane and the concrete and eventually find another entry point through the concrete and into the building. Chasing the leak from one entry point through the concrete to the next will require more time and material to try to repair the leak, and the task may be neverending if new cracks and cold joints in the concrete occur over time. lateral water migration resistance prevents the water from traveling between the preapplied waterproofing system and the concrete, reducing the likelihood of leaks into the building. This makes lateral water migration resistance a critical attribute of an effective preapplied waterproofing system. BONDING METHOD AND LATERAL water MIGRATION RESISTANCE earlier, we noted that the difference between a mechanical bond and an adhesive bond with the concrete affects lateral water migration performance. Mechanical bonds, using fibers that become encased in the poured concrete, typically do not prevent lateral water migration. The water can move between the mechanically bonded material and the concrete because the intermittent Figure 8 Water from precipitation or groundwater entering into a breach or void in the waterproofing, traveling between the waterproofing and concrete interface and entering the building. trade Show MaRCh 14-19, 2013 BouCheR 39

8 size, and a hole was cut in the center of the material to replicate a breach or void such as a rebar puncture. Metal pipes were placed on top of the materials and held firmly against the top of the material to prevent concrete from entering the bottom of the metal pipes. The metal pipes provide an open channel for water to pass through the concrete, simulating a crack or other path of water entry through a concrete foundation wall or floor. Concrete was placed onto the materials and allowed to cure. The test specimen represents a condition where there is a void or breach in the preapfigure 9 An isometric view from the bottom and a plied waterproofing material section view of the test specimens showing the path and there is an open chanof lateral water migration and water leakage into a nel through the concrete that building. could allow water entry into a building. The test specimens are then clamped into fibers do not provide a continuous adhesive a test apparatus specified in ASTM D5385. bond to prevent lateral water migration. This statement is supported by an inde- Water is pumped into the testing apparapendent, third-party laboratory analysis of tus at various pressures. Figure 9 shows technologies currently available and mar- two views of keted as preapplied waterproofing materi- the test specials, testing their lateral water migration mens. The top image is an resistance and bond to concrete. ASTM D5385, Standard Test Method for isometric view Hydrostatic Head, was used as a basis for from the botthe lateral water migration resistance test- tom, and the ing. Samples of the materials were cut to image at the bottom is a section view. The orange material is the preapplied waterproofing material being evaluated with concrete on top of the material and metal pipes passing through the concrete. During the test, water is introduced to the bottom of the test specimen where there is a void or breach in the waterproofing material. If the water travels laterally between the top of the waterproofing material and the bottom of the concrete, the water will reach the metal pipes and leak out of the specimen. Water used in the test was dyed green to confirm that water coming out of the pipes is the same water introduced to the test specimen. Figure 10 shows one of the materials evaluated in the test apparatus, with green water leaking out of the metal pipes, indicating lateral water migration has occurred. The second part of the third-party laboratory analysis was to measure bond to concrete. Bond to concrete was measured by running an ASTM D903 peel adhesion test on the test specimens. Figure 11 shows preapplied waterproofing materials being peeled off of concrete that was cast on top of the material. The test specimens were clamped to the bottom of the test apparatus, and the clamp at the top of the apparatus pulled the material up and off of the concrete. The performance of the evaluated materials is summarized in Figure 12. The first column is the material or product reference code. The middle two columns show the results of the lateral water migration resistance test (run by exposing the materials to Figure 11 Photos of peel adhesion testing of two specimens. Figure 10 A test specimen that allowed water with green dye to migrate laterally and leak through the specimen, failing the lateral water migration resistance testing. 40 BouCheR 28th RCI InteRnatIonal ConventIon and trade Show MaRCh 14-19, 2013

9 THE IMPORTANCE OF A FULLSYSTEM APPROACH Figure 12 Results of the third-party laboratory analysis. increasing levels of water pressure measured in pounds per sq. in.; 1 pound per sq. in. is equivalent to 2.31 ft. of hydrostatic head); the third column provides the equivalent hydrostatic head to which the product was exposed. products A and B are membranes that adhesively bond to concrete and are similar products (product A is intended for horizontal areas, and product B is intended for vertical walls). products C through H have a fabric or fleece on the side of the membrane in contact with the concrete, intended to provide a mechanical bond. As you will note in the chart, only the adhesively bonded membranes provided good lateral water migration resistance results. The last column in Figure 12 provides the results of the adhesion to concrete test. The adhesively bonded membranes yielded better results than the mechanically bonded membranes. lateral water migration resistance and the modified version of the ASTM D5385 could be referenced in guide specifications to help ensure that the preapplied waterproofing material being specified will work as intended to protect the building from water ingress. Figure 13A soil-retention system tieback. It is commonly said that a system is only as good as its weakest link. This is certainly true for preapplied waterproofing. The detail areas of the system such as corners or penetrations are areas prone to leak. Taking a full-system approach to below-grade waterproofing can help reduce the risk of leaks at these areas. As noted earlier, a horizontal preapplied waterproofing system below the building can be used with a postapplied waterproofing system on the vertical walls. Utilizing a single source for both waterproofing materials helps ensure product compatibility and typically enables the designer to use a standard detail that has been successfully used previously and is provided by the manufacturer. Having one source for all the waterproofing will also eliminate questions about which product manufacturer is at fault if there are leaks at the tie-in detail. The detail areas of a preapplied waterproofing project may require several steps, and performance of the installed detail is often highly dependent on the skill of the installer. Using preformed details can reduce labor costs and ensure continuity Figure 13C Prefabricated tieback cover detail. Figure 13B Field-fabricated tieback cover detail. 28th RCI InteRnatIonal ConventIon and trade Show MaRCh 14-19, 2013 BouCheR 41

10 of the waterproofing system. Furthermore, applying preformed details that prevent lateral water migration and bond to concrete are important in the details areas, and it is recommended that the preformed details be capable of providing those attributes. Ultimately, preformed details can reduce the risk of leaks and liability due to leaks in the detail areas. Use of preformed details can be written into the guide specification to ensure they are used and the benefits are realized. one typical example of a prefabricated detail is a soil retention system tieback cover. The soil retention system tiebacks protrude beyond the interior plane of the soil retention system. often, the tiebacks are covered with a field-fabricated sheetmetal box, and then the waterproofing system is applied over the sheet metal box. Figures 13A, 13B, and 13C show that there are several steps and several layers of the waterproofing material installed to ensure a watertight installation. The preformed tieback cover dome shown in Figure 13C is one piece that is made watertight at the factory. This preformed detail reduces labor time and helps ensure a watertight installation. CONCLUSION: PERFORMANCE MATTERS In summary, we have covered what preapplied waterproofing is and its use in circumstances when access to the outside or exterior side of the foundation is not feasible. We discussed the essential attributes of preapplied waterproofing: that it needs to be durable and fit for harsh job site conditions and, most importantly, that it must prevent lateral water migration and bond to concrete. As with all waterproofing, it is best if the preapplied waterproofing system is fully bonded to the structure it is waterproofing. We discussed a third-party laboratory analysis demonstrating that adhesively bonded waterproofing membranes outperformed the evaluated mechanically bonded preapplied membranes. We covered the advantages of a full-system approach to preapplied waterproofing, using a single source for all the waterproofing components and using preformed, prefabricated details to help avoid risk of leaks at the critical and labor-intensive detail areas. putting all of these principles into practice will lead to a preapplied waterproofing solution that, when installed correctly, reduces the risk of water ingress and minimizes the risk of liability for all parties involved in the project. And that s the ultimate measure of performance. 4 2 B o u C h e R 2 8 t h R C I I n t e R n a t I o n a l C o n v e n t I o n a n d t R a d e S h o w M a R C h ,

High Performance PSA in Sheet Membrane in Water Protection

High Performance PSA in Sheet Membrane in Water Protection High Performance PSA in Sheet Membrane in Water Protection Xia Cao, Senior R&D Chemist, W. R. Grace, Cambridge MA 02140 Jyoti Seth, Strategic Program Leader, W. R. Grace, Cambridge MA 02140 Concrete is

More information

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side

More information

A Guide to Structural Waterproofing

A Guide to Structural Waterproofing A Guide to Structural Waterproofing Part One Waterproofing Protection For Below Ground Structures 1 2012 W. R. Grace & Co Benjamin J. Brooks Table of Contents Grace Around The World Reference Material

More information

SikaProof A Technology

SikaProof A Technology SikaProof A Technology The fully bonded waterproofing system Keep your basements durably and securely watertight What is SikaProof A? How does it work? Where can it be used? What are the advantages of

More information

Comment Form on Proposed Gut Rehabilitation Alternatives

Comment Form on Proposed Gut Rehabilitation Alternatives Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to energystarhomes@energystar.gov by October 10 th, 2012 with the subject line

More information

constructive solutions Fosroc total waterproofing protection of below-ground structures

constructive solutions Fosroc total waterproofing protection of below-ground structures constructive solutions Fosroc total waterproofing protection of below-ground structures Our profile Since the company s beginnings over 50 years ago, Fosroc has developed into an International leader in

More information

WATERPROOFING SikaProof -A TECHNOLOGY

WATERPROOFING SikaProof -A TECHNOLOGY SikaProof -A TECHNOLOGY content What is SikaProof -A? 6 How does it work? 8 Where can it be used? 0 What are the advantages of SikaProof -A? 2 How should it be installed? SikaProof -A system components

More information

External Wrapping of Steel Riser Pipe. Case Study HJ3 CS200902

External Wrapping of Steel Riser Pipe. Case Study HJ3 CS200902 External Wrapping of Steel Riser Pipe Case Study HJ3 CS200902 Introduction Refineries process a wide variety of petroleum products. As part of the process, they rely on cooling towers, which recycle water

More information

Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description

Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description Product Data Sheet Edition 15/10/2014 Identification no: 02 07 04 10 300 0 000002 SikaProof A Edge SikaProof A-08 Edge, A-12 Edge Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information

INVESTIGATING AND REMEDIATING LEAKS IN BELOW GRADE STRUCTURES AND UNDER PLAZAS

INVESTIGATING AND REMEDIATING LEAKS IN BELOW GRADE STRUCTURES AND UNDER PLAZAS INVESTIGATING AND REMEDIATING LEAKS IN BELOW GRADE STRUCTURES AND UNDER PLAZAS JUSTIN HENSHELL, FAIA, FASTM HENSHELL & BUCCELLATO, RED BANK, NJ B U I L D I N G E N V E L O P E T E C H N O L O G Y S Y M

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................

More information

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing 1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize

More information

How To Repair A House

How To Repair A House Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

Residential Foundations and Basements

Residential Foundations and Basements Residential Foundations and Basements Disclaimer All of the following information is based on the 2006 International Residential Code with Kentucky Amendments. As some information is paraphrased, article

More information

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

A. This Section includes rubberized asphalt sheet membrane waterproofing systems. SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced

More information

Waterproofing below-ground with Proofex Engage. constructive solutions

Waterproofing below-ground with Proofex Engage. constructive solutions Waterproofing below-ground with Proofex Engage constructive solutions Our profile Since the company s beginnings over 50 years ago, Fosroc has developed into an International leader in delivering Constructive

More information

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering

More information

Product Systems AQUAFIN-IC CEMENTITIOUS CRYSTALLINE PENETRATING WATERPROOFING. Waterproofing Specification

Product Systems AQUAFIN-IC CEMENTITIOUS CRYSTALLINE PENETRATING WATERPROOFING. Waterproofing Specification AQUAFIN-IC CEMENTITIOUS CRYSTALLINE PENETRATING WATERPROOFING Typical s Table of Contents: No. 4 5 6 7 8 9 0 External waterproofing of below ground concrete wall & slab Internal waterproofing of foundation

More information

Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations

Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations Nathan A. Ingraffea, P.E., S.E. Associate, KPFF Consulting Engineers, Portland, Oregon, USA Abstract The use of steel sheet

More information

Elevating Your House. Introduction CHAPTER 5

Elevating Your House. Introduction CHAPTER 5 CHAPTER 5 Elevating Your House Introduction One of the most common retrofitting methods is elevating a house to a required or desired Flood Protection Elevation (FPE). When a house is properly elevated,

More information

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline

More information

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings

More information

G VYCOR DECK PROTECTOR. For longer lasting decks, install Grace Vycor Deck Protector. It s an easy add-on to your deck projects.

G VYCOR DECK PROTECTOR. For longer lasting decks, install Grace Vycor Deck Protector. It s an easy add-on to your deck projects. For longer lasting decks, install Grace Vycor Deck Protector. It s an easy add-on to your deck projects. G VYCOR DECK PROTECTOR Self-Adhered Flashing NEW FROM THE MAKERS OF G Ice & Water Shield I Moisture

More information

The minimum reinforcement for the stem wall is the placement of:

The minimum reinforcement for the stem wall is the placement of: PolySteel creates an ideal insulated stem wall for concrete slabs that can make this part of your project easier and faster, in addition to making your finished project more energy-efficient. Figures 3.20

More information

Moisture and Resilient Floor Covering

Moisture and Resilient Floor Covering Moisture and Resilient Floor Covering Moisture related failures of resilient floor coverings installed over concrete have focused unfairly over the years on the premise that the flooring product itself

More information

Section 2100-Trenching and Tunneling

Section 2100-Trenching and Tunneling SECTION 5200 - STORM SEWER PART 1 - GENERAL 1.01 SCOPE: This Section covers installation of storm sewer mains and culverts. Topics include permits and fees, trench widths, pipe laying, bedding, initial

More information

DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H

DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H Soil Drainage Mat with Built-In Protection Layer POLYGUARD DRAINAGE MATS are three-part prefabricated geocomposite drain consisting of a

More information

Designed and Engineered to Perform

Designed and Engineered to Perform History EARTH CONTACT PRODUCTS, L.L.C., is a family owned company, based in Olathe, Kansas. This company was built upon Don May s U.S. Patented fourth-generation Steel Piering System that has led to the

More information

Basement Moisture Problems

Basement Moisture Problems Foundations Foundation Purpose The purpose of a foundation is to distribute the weight of a structure securely into the ground. Engineering data regarding soil, rock and water conditions are used to design

More information

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength. INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS Multi-Layer Technology provides increased strength. Specifically designed for interior applications. Compatible with most internal

More information

Basement & Foundation Damage

Basement & Foundation Damage Basement & Foundation Damage Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

STEPS TO CONSTRUCTING A MOISTURE-RESISTANT FOUNDATION SOURCES OF MOISTURE IN NEW CONSTRUCTION. Natural ground slope

STEPS TO CONSTRUCTING A MOISTURE-RESISTANT FOUNDATION SOURCES OF MOISTURE IN NEW CONSTRUCTION. Natural ground slope FOUNDATIONS STEPS TO CONSTRUCTING A MOISTURE-RESISTANT FOUNDATION Build a Better Home Details are critical when constructing a sound building foundation that will withstand water and control dampness.

More information

WATERPROOFING BASEMENTS

WATERPROOFING BASEMENTS WATERPROOFING BASEMENTS CONSTRUCTION CHEMICALS DIVISION Pidilite manufactures and markets a wide range of construction chemical products under two brands Dr. Fixit & Roff covering different aspects of

More information

FORM DESIGN. easy to work with, and generally available.

FORM DESIGN. easy to work with, and generally available. Forms play a major role in concrete construction. They give the plastic concrete its shape and hold it until it hardens. Forms protect the concrete, assist in curing it, and support any reinforcing rods

More information

Site Inspection Report

Site Inspection Report Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems

Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water

More information

Soils, Foundations & Moisture Control

Soils, Foundations & Moisture Control Soils, Foundations & Moisture Control Soil The top loose layer mineral and/or organic material on the surface of the Earth that serves as a natural medium for the growth of plants and support for the foundations

More information

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13) Page 1 of 7 STONE STRONG SYSTEMS SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised ) PART 1: GENERAL 1.01 Description A. Work includes furnishing and installing precast modular blocks

More information

DUPONT TYVEK BUILDING WRAPS VS. ZIP SYSTEM WALL SHEATHING

DUPONT TYVEK BUILDING WRAPS VS. ZIP SYSTEM WALL SHEATHING TECH TALK DUPONT TYVEK BUILDING WRAPS VS. ZIP SYSTEM WALL SHEATHING DuPont offers six different DuPont Tyvek building wraps intended for use on a wide range of buildings from single family homes to high

More information

RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS

RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS Johnson County Building Officials Association January 2008 Residential Foundation Guideline Foundation designs for one-and two-family dwellings may use

More information

Concrete Waterproofing Systems. Integral Protection. www.tritonsystems.co.uk

Concrete Waterproofing Systems. Integral Protection. www.tritonsystems.co.uk Concrete Waterproofing Systems Integral Protection n Type B Integral Protection in accordance with BS 8102 (2009) n Unique chemical admix for waterproofing and protection of concrete n A complete and permanent

More information

The AQUAFIN Approach to Concrete Repair

The AQUAFIN Approach to Concrete Repair Concrete Repair Building Product Systems Waterproofing & Concrete Restoration Decorative Coatings Moisture Vapor Remediation & Flooring Injection Grouting The AQUAFIN Approach to Concrete Repair www.aquafin.net

More information

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam

More information

APPENDIX C MOISTURE GUIDELINES & MOISTURE TESTING

APPENDIX C MOISTURE GUIDELINES & MOISTURE TESTING APPENDIX C MOISTURE GUIDELINES & MOISTURE TESTING Appendix C Moisture Guidelines Determining moisture content is an essential part of quality control within the flooring installation process. Flooring

More information

How to Identify, Evaluate & Repair Shrinkage Cracks in Poured Concrete

How to Identify, Evaluate & Repair Shrinkage Cracks in Poured Concrete How to Identify, Evaluate & Repair Shrinkage Cracks in Poured Concrete What is concrete shrinkage cracking, how and where does it occur? Are concrete floor cracks a structural problem? How to recognize

More information

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel

More information

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Prepared For: Ms Marilyn Bittenbender Colliers International 805 New Hampshire St Lawrence Kansas, 66046 Prepared

More information

Preprufe 160 Sheet Tanking and Waterproofing Membrane

Preprufe 160 Sheet Tanking and Waterproofing Membrane TECHNICAL Technical data may be updated at any time. It is the users responsibility to check data validity by reference to the website or Nuplex Construction Products MANUAL SECTION ISSUE DATE AUTHORISED

More information

Best Basement Water Management Practices

Best Basement Water Management Practices Best Basement Water Management Practices Guide written by Patrick Sluss Sluss Construction (330) 224 5394 When a home owner is faced with a leaking basement there is a way to correct the problem and a

More information

Melbourne balcony Assessments

Melbourne balcony Assessments Balcony Assessment Melbourne balcony Assessments Address: SAMPLE Date: Assessor: Luke O Neill Registered Builder DBL-C 31305 Assessment Guidelines This is an assessment of balcony and elements as presented

More information

Page & Turnbull imagining change in historic environments through design, research, and technology

Page & Turnbull imagining change in historic environments through design, research, and technology DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED

More information

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within

More information

A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS

A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS What is a groundwater protection plan? A groundwater protection plan identifies the activities being conducted that can pollute groundwater and

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13

More information

CONCRETE SEGMENTAL RETAINING WALL SYSTEM

CONCRETE SEGMENTAL RETAINING WALL SYSTEM CONCRETE SEGMENTAL RETAINING WALL SYSTEM PART 1: GENERAL SPECIFICATIONS 1.01 Work Included A. Work shall consist of furnishing and constructing a Rockwood Classic 8 with PCS unit segmental retaining wall

More information

INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles

INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles INSTALLATION RECOMMENDATIONS Outdoor Rubber Tiles Prior to Installation: The Outdoor Rubber Tiles and accessory transition pieces intended for this installation have been shipped to you via a freight carrier

More information

(4020-NY) ARCHITECTURAL BUILDING INSPECTION ASSESSMENT AND REPORT

(4020-NY) ARCHITECTURAL BUILDING INSPECTION ASSESSMENT AND REPORT FEMA Task Order 12-J-0001 (4020-NY) ARCHITECTURAL BUILDING INSPECTION ASSESSMENT AND REPORT Orange County Government Center 255 Main Street, Goshen NY February 15, 2012 1 INDEX and TABLE OF CONTENTS I.

More information

MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS

MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS May 29, 2013 Revision B Structural Guideline for Design and Installation Holes in Composite Floor Slab Terminal 3, Departure Level

More information

University of Missouri Hospitals and Clinics. Structural Repair and Protection of Post-tensioned Parking Garage

University of Missouri Hospitals and Clinics. Structural Repair and Protection of Post-tensioned Parking Garage University of Missouri Hospitals and Clinics Structural Repair and Protection of Post-tensioned Parking Garage 1 University of Missouri Project The University of Missouri Health Care Patient and Visitor

More information

BELOW GROUND TANKING

BELOW GROUND TANKING BELOW GROUND TANKING Basement & Foundation Waterproofing Systems - What, Why & How By Paul Evans MBAV Specialist Contractor, Registered Building Practitioner Vice President Australian Institute of Waterproofing

More information

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section

More information

Site Grading and Drainage to Achieve High-Performance Basements

Site Grading and Drainage to Achieve High-Performance Basements Construction Technology Update No. 69 Site Grading and Drainage to Achieve High-Performance Basements By M.C. Swinton and T.J. Kesik Proper site grading and foundation drainage strategies are required

More information

University of South Carolina/ Preston Residential College

University of South Carolina/ Preston Residential College National Tile Contractors Association September 2013 ON THE COVER: Schluter Systems L.P. University of South Carolina/ Preston Residential College www.tileletter.com Top Ten Reasons to attend Total Solutions

More information

School Construction Authority Architecture & Engineering

School Construction Authority Architecture & Engineering SCOPING GUIDELINES 1.0 GENERAL GUIDELINES 2.0 BUILDING ENVELOPE SCOPING GUIDELINES 3.0 CATEGORIES AND COMPONENTS: The Flood Elimination/Below Grade Capital Category may include some or all of the following

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

MEMORANDUM. General: Foundation:

MEMORANDUM. General: Foundation: MEMORANDUM State of Alaska Department of Transportation and Public Facilities Central Region - Division of Construction and Operations Public Facilities Branch TO: Jennifer Murrel DATE: August 19, 2010

More information

EPDM System Repair and Cleaning

EPDM System Repair and Cleaning EPDM single-ply roof systems have represented a third of the volume of the low-sloped commercial market for close to twenty years. The majority of these roofs were installed to receive the manufacturer

More information

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines: Division 53: Slip-Lining of Existing Sewer Line 53.01 GENERAL: This section includes all labor, materials, transportation, equipment necessary to rehabilitate by means of Instituform deteriorated sections

More information

Section 02702 SEWER PIPE INSTALLATION AND TESTING

Section 02702 SEWER PIPE INSTALLATION AND TESTING PART 1 - GENERAL Section 02702 SEWER PIPE INSTALLATION AND TESTING 1-1. SCOPE. This section covers the installation and testing of all sewer pipe furnished under the following specification sections: Concrete

More information

SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES

SECTION 33 05 16.13 PRECAST CONCRETE UTILITY STRUCTURES SECTION 33 05 16.13 PRECAST CONCRETE PART 1 - GENERAL 1.01 SECTION INCLUDES A. This item shall consist of the construction of both sanitary and storm sewer precast concrete manholes in accordance with

More information

EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES

EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES FAILING WATERPROOFING

More information

Re: Damages to Alaska Building from Legislative Information Office Construction

Re: Damages to Alaska Building from Legislative Information Office Construction 510 L Street Suite 200 Anchorage, AK 99501-1949 (907) 274-22362236 Phone (907) 274-25202520 Fax www.bbfm.com July 22, 2015 Jim Gottstein Alaska Building 406 G Street, Suite 206 Anchorage, AK 99501 Re:

More information

State of Connecticut Department of Public Health RADON PROGRAM

State of Connecticut Department of Public Health RADON PROGRAM State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon

More information

DAMAGE TO FOUNDATIONS FROM EXPANSIVE SOILS

DAMAGE TO FOUNDATIONS FROM EXPANSIVE SOILS DAMAGE TO FOUNDATIONS FROM EXPANSIVE SOILS J. David Rogers, Robert Olshansky, and Robert B. Rogers Expansive soils in many parts of the United States pose a significant hazard to foundations for light

More information

WATERPROOFING SIKAPLAN MEMBRANE SYSTEMS FOR BASEMENTS TECHNOLOGY & CONCEPTS

WATERPROOFING SIKAPLAN MEMBRANE SYSTEMS FOR BASEMENTS TECHNOLOGY & CONCEPTS SIKAPLAN MEMBRANE SYSTEMS FOR BASEMENTS TECHNOLOGY & CONCEPTS SIKAPLAN A RELIABLE AND DURABLE SYSTEM BUILDING STRUCTURES WITH DEEP BASEMENTS that are exposed to highly aggressive ground conditions and

More information

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that

More information

R E S I D E N T I A L H O U S I N G

R E S I D E N T I A L H O U S I N G HL 252 Rev. April 1997 R E S I D E N T I A L H O U S I N G CONTROLLING EXTERNALWATER PROBLEMS FOR RESIDENCES I II III IV V Lot Drainage Gutter Water Management Foundation Waterproofing Floor Slab Waterproofing

More information

Get The Picture. page 2. Congratulations on taking your first step toward becoming a basement waterproofing expert!

Get The Picture. page 2. Congratulations on taking your first step toward becoming a basement waterproofing expert! Thanks for downloading! Get The Picture Congratulations on taking your first step toward becoming a basement waterproofing expert! In this free helpful guide, you learn how to accurately: 1) diagnose your

More information

SECTION 1 GENERAL REQUIREMENTS

SECTION 1 GENERAL REQUIREMENTS Page 1 of 6 SECTION 1 GENERAL REQUIREMENTS 1. SCOPE OF WORK: The work to be performed under the provisions of these documents and the contract based thereon includes furnishing all labor, equipment, materials,

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

STRUCTURES. 1.1. Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.

STRUCTURES. 1.1. Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL. STRUCTURES 1. General. Critical structures may impact the integrity of a flood control project in several manners such as the excavation for construction of the structure, the type of foundation, backfill

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:

More information

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022 M G C O N S T R U C T O R S & E N G I N E E R S, I N C. I N S P E C T O R S E N G I N E E R S B U I L D E R S C A L I F O R N I A E N G I N E E R I N G A N D B U I L D I N G L I C E N S E A / B 6 4 2 0

More information

The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage

The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage Sam Hagerman, Hammer and Hand Sam@HammerandHand.com Florian Speier, Zola Windows Florian@ZolaWindows.com Paul Grahovac,

More information

How To Repair A Boat Landing Deck With A Boat Bed

How To Repair A Boat Landing Deck With A Boat Bed RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing

More information

ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057. Lecturer: Jim Cahill

ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057. Lecturer: Jim Cahill ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057 Lecturer: Jim Cahill 29 th November 2011 TABLE OF CONTENTS SUMMARY 1 MAIN BODY SECTION

More information

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections

More information

Foundation Water Problems. An Overview and Discussion of some Causes and Cures for Water Infiltration into Basements and Foundation Structures

Foundation Water Problems. An Overview and Discussion of some Causes and Cures for Water Infiltration into Basements and Foundation Structures Foundation Water Problems An Overview and Discussion of some Causes and Cures for Water Infiltration into Basements and Foundation Structures This presentation was prepared and presented by Dwight Walker

More information

CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS

CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS CCU Engineering Specifications Section 003300 Effective Date: Nov. 1st, 2011 Page 1 of 5 PRECAST CONCRETE PRODUCTS PART 1 - GENERAL The following specification is intended for use for the design, selection

More information

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS July 14, 2015 1.0 GENERAL BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS This work shall consist of furnishing all materials, equipment, labor, and incidentals necessary for conducting bi-directional

More information

SECTION 221413 FACILITY STORM DRAINAGE PIPING

SECTION 221413 FACILITY STORM DRAINAGE PIPING SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

PRE INSTALLATION MANUAL

PRE INSTALLATION MANUAL REINFORCED CONCRETE PIPE PRE INSTALLATION INSPECTION & REPAIR MANUAL Kentucky Transportation Cabinet Kentucky Department of Highways Division of Materials 1227 Wilkinson Boulevard Frankfort, KY 40601 (502)

More information