Service & Support. How can you transfer a WinCC flexible project via Ethernet to a Windows-based panel? WinCC flexible.

Similar documents
Easy Setup Guide for the Sony Network Camera

Service & Support. How can you establish a connection between an S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

Service & Support. How can you establish a connection between a S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: Rev 6

FAQ Communication over IE

1 crossover cable. the PCs. network

D-Link DAP-1360 Repeater Mode Configuration

Deploying Windows Streaming Media Servers NLB Cluster and metasan

Service & Support. How do you create a communication of RDP with an Industrial Thin Client SIMATIC ITC? Thin Client.

C o v e r. Thin Client Application Options. SIMATIC Thin Client s FAQ h April 2009 e et. Service & Support. Answers for industry.

Service & Support. How do you create a communication of VNC with an Industrial Thin Client SIMATIC ITC? Thin Client.

WinCC. Communication Manual. Manual 2. This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 C79000-G8276-C156-01

1 PC to WX64 direction connection with crossover cable or hub/switch

Ethernet Connection Setup for CCU

Instructions. Setup of Teamviewer VPN. programming remotely With STEP7.

Prestige 314 Read Me First

WinCC Runtime Professional Readme SIMATIC HMI. WinCC V11 SP1. Readme WinCC Runtime Professional. Special considerations for Windows 7.

Computer Networks I Laboratory Exercise 1

Chapter 15: Advanced Networks

Service & Support. How do you configure time synchronization using the NTP procedure (without SICLOCK) for small PCS 7 plants?

Lab Configuring Access Policies and DMZ Settings

Preparing the Computers for TCP/IP Networking

Lab - Configure a Windows 7 Firewall

TECHNICAL NOTE TNOI34

PC/POLL SYSTEMS Version 7 Polling SPS2000 Cash Register TCP/IP Communications

Prestige 650R-31/33 Read Me First

Networking Guide Redwood Manager 3.0 August 2013

Pre-lab and In-class Laboratory Exercise 10 (L10)

AcqKnowledge or better for Windows OS (version compatibility varies each release)

Package Contents. D-Link DSN-3200/3400 Installation Guide. DSN-3200/3400 xstack Storage Area Network (SAN) Array. CD-ROM with User Guide.

Ultra Thin Client TC-401 TC-402. Users s Guide

Internet for Everyone In-Room Instructions January 2011 Version 1.3

ADSL Router Quick Installation Guide Revised, edited and illustrated by Neo

Technical Report CDC PC Station Guide Tutorial Nuno Cruz

EDGE FX Network configuration

C-more Remote Access with Apple ipad or iphone Tutorial

Using a simple crossover RJ45 cable, you can directly connect your Dexter to any computer.

CANON FAX L360 SOFTWARE MANUAL

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3. Simatic. Readme. Readme

1. Hardware Installation

PROFINET IRT: Getting Started with The Siemens CPU 315 PLC

AcqKnowledge for Windows: Upgrade for 1+MP150s and Domain Network Access or Direct Communication Setup (Domain/Non-domain)

Applications & Tools. Configuration of Messages and Alarms in WinCC (TIA Portal) WinCC (TIA Portal) Application description December 2012

In this lab you will explore the Windows XP Firewall and configure some advanced settings.

Prestige 623R-T. Quick Start Guide. ADSL Dual-link Router. Version 3.40

Installing the Microsoft Network Driver Interface

Chapter 2 Preparing Your Network

Configure SPLM 2012 on Windows 7 Laptop

1 Application Description System Topology Hardware and Software Requirements... 3

Prestige 660R-6x Read Me First

Setting up VPN Access for Remote Diagnostics Support

Lab - Configure a Windows XP Firewall

How to configure DVR and computer for running Remote Viewer via IP network

CMP-102U. Quick Installation Guide

CS 326e F2002 Lab 1. Basic Network Setup & Ethereal Time: 2 hrs

1 How configure S7 PLC in the configuration tool

Configuring Devices for Use with Cisco Configuration Professional (CCP) 2.5

CREATING AN IKE IPSEC TUNNEL BETWEEN AN INTERNET SECURITY ROUTER AND A WINDOWS 2000/XP PC

Configuring the WT-4 for Upload to a Computer (Ad-hoc Mode)

Application Note: Connecting to a 2500 Series Processor using PLC Workshop

Enabling Internet Connection Sharing on Windows Enabling ICS On Windows XP As The Host 4 Enabling ICS On Windows XP As The Client 11

Hypercom Key Loading and Management (HKLM) RS232 PPP Key Injection PC Setup Guide

Course: WIN310. Student Lab Setup Guide. Summer Microsoft Windows Server 2003 Network Infrastructure (70-291)

SATO Network Interface Card Configuration Instructions

Quick Note 32. Using Digi RealPort with a Digi TransPort Router. UK Support September 2012

1. Requirements for Network Installation on 840D

Use this guide if you are no longer able to scan to Sharpdesk. Begin with section 1 (easiest) and complete all sections only if necessary.

8/23/13 Configuring the S7 Server for Windows NT 4.0 to Access S7-400 PLCs via the Siemens CP1613 Card for ISO (Industrial Ethernet)

S7 OPC Server Tutorial

UBIQUITI BRIDGE CONFIGURATION PROCEDURE (PowerStation & NanoStation Units ONLY)

Technical Note. Configuring an Omron PLC with Omron FINS Ethernet Driver. 1. Introduction

R&S AFQ100A, R&S AFQ100B I/Q Modulation Generator Supplement

How To Install And Configure Windows Server 2003 On A Student Computer

enervista UR Setup Software Quick Connect Instructions:

Movie Cube. User s Guide to Wireless Function

Network/Floating License Installation Instructions

MaxSea TimeZero NN3D Radar Connection Checklist

Deployment Guide: Transparent Mode

(1) Network Camera

1-Port Wireless USB 2.0 Print Server Model # APSUSB201W. Quick Installation Guide. Ver. 2A

Lab - Configure a Windows Vista Firewall

Omni 56K USB Lite Quick Start Guide

CCProxy. Server Installation

NXT Controller Manual IP Assignment in WAN Environments Application Note

Configuring the WT-4 for ftp (Ad-hoc Mode)

MFC7840W Windows Network Connection Repair Instructions

Connecting the DG-102S VoIP Gateway to your network

8/23/13 Configuring the S7 I/O Server for Windows 95 to Access S7 PLCs Via the Profibus Network

ETHERNET WEATHER STATION CONNECTIONS Application Note 33

HL2170W Windows Network Connection Repair Instructions

Cisco Configuration Professional Quick Start Guide

Intel Active Management Technology with System Defense Feature Quick Start Guide

SIMATIC PCS 7. SIMATIC Maintenance Station PDM A stand-alone Solution. Siemens AG All Rights Reserved.

Installation and Setup

EnGenius ERB M Range Extender. Quick Start Guide

DSL Installation Guide

1. Installing The Monitoring Software

SIMATIC Expert Communication Connecting S7-400H to PC Station (WinCC)

138 Configuration Wizards

Beckhoff TwinCAT. Assigning IP Addresses to Beckhoff Ethernet Devices

Transcription:

Cover sheet How can you transfer a WinCC flexible project via Ethernet to a Windows-based panel? WinCC flexible FAQ November 2011 Service & Support Answers for industry.

Question This entry originates from the Service & Support Portal of Siemens AG, Sector Industry, Industry Automation and Drive Technologies. The conditions of use specified there apply (www.siemens.com/nutzungsbedingungen). Go to the following link to download this document. http://support.automation.siemens.com/ww/view/de/23800567 Caution The functions and solutions described in this article confine themselves predominantly to the realization of the automation task. Furthermore, please take into account that corresponding protective measures have to be taken in the context of Industrial Security when connecting your equipment to other parts of the plant, the enterprise network or the internet. Further information can be found in Entry ID:!50203404!. http://support.automation.siemens.com/ww/view/de/50203404 Question How can you transfer a WinCC flexible project via Ethernet to a Windows-based panel? Answer Follow the instructions and notes listed in this document for a detailed answer to the above question. 2 Version V 1.0, Entry ID: 23800567

Contents Contents 1 Instructions... 4 2 Settings on the Operator Panel... 5 3 Settings on the Configuration Computer... 7 3.1 Settings in Windows 7... 7 3.1.1 Non-integrated Project... 7 3.1.2 Integrated Project... 9 3.2 Settings in Windows XP... 12 3.2.1 Non-integrated Project... 12 3.2.2 Integrated Project... 14 3.3 Checking the Ethernet Connection... 17 3.3.1 Check the Connection to the Panel... 17 3.3.2 Check the Settings on the Operator Panel... 18 4 Settings in WinCC flexible... 20 4.1.1 Non-integrated Project... 20 4.1.2 Integrated Project... 22 Version V 1.0, Entry ID: 23800567 3

1 Instructions 1 Instructions For transfer of a WinCC flexible configuration via Ethernet you must make settings on the operator panel and on the configuration PC. s It is not possible to transfer a project to a Micro Panel, because the Micro Panel does not have an Ethernet interface. Transfer via Ethernet is possible with an OP270 / TP270. Since these two devices have no onboard Ethernet interface you need an NE2000-compatible CF card with Ethernet interface. Information about which panels support Ethernet transfer is available in the relevant manual of each operator panel or in the entry entitled "What transfer options are available in the various operator panels?", Entry ID: 19109408 If you wish to integrate your configuration computer into an existing Ethernet network, you must transfer the parameters of the existing Ethernet network. Please note that the IP address of the PC on the Ethernet network must be unique. In the case of a direct connection without any other active components such as hub, switch or router you need a crossover patch cable. 4 Version V 1.0, Entry ID: 23800567

2 Settings on the Operator Panel 2 Settings on the Operator Panel The illustrations below are from MP 377 and might differ from operator panel to operator panel, because not all the functions are available for each operator panel. Table 2-1 1. Open the "Transfer" dialog in the "Control Panel". 2. Transfer via Ethernet is enabled under Channel 2. Select "Ethernet" for Channel 2. For Channel 2 you also set a check mark for "Enable Channel" and if you wish, "Remote Control". s The "Remote Control" option permits automatic termination of Runtime on the panel when transfer is triggered via the development environment of WinCC flexible. The panel then automatically switches to Transfer mode. 3. Open the advanced settings by clicking the "Advanced" button. 4. Double-click the "Ethernet driver". 5. If you do not take the IP address from a DHCP server, select "Specify an IP address" and specify the IP address and the subnet mask of the panel. The IP address must be unique, in other words, it must not be used by any other node in the network. 6. Close the dialog box with "OK". 7. Click the "System" icon to open the "System Properties" dialog window. Change the name of the operator panel ( HMI_Panel_mp377", for example). If you are using multiple panels in one Ethernet network, you should always change the name of the panel. that the device name must be unique, in other words, it must not already be used by another device. Version V 1.0, Entry ID: 23800567 5

2 Settings on the Operator Panel 8. Close the dialog box with "OK". 9. Close the "Control Panel" as well. 10. Select the "Transfer" button in the "Runtime Loader". 6 Version V 1.0, Entry ID: 23800567

3 Settings on the Configuration Computer Depending on your operating system you select either "Settings in Windows 7" or "Settings in Windows XP". 3.1 Settings in Windows 7 The required settings on the configuration computer are described below. 3.1.1 Non-integrated Project Table 3-1 1. Open the "Network and Sharing Center" menu in the Control Panel of your configuration computer. Version V 1.0, Entry ID: 23800567 7

2. In the "Network and Sharing Center" you click "Change adapter settings". Double-click the relevant "Network" and then click the "Properties" button to open the Properties window of that network. 3. Mark "Internet Protocol Version 4 (TCP/IPv4)" and then click the "Properties" button. 8 Version V 1.0, Entry ID: 23800567

4. Assign a valid IP address and subnet mask. The IP address must be unique. In other words, it must not be used by another node (socket) in the network. 5. Close the Properties dialog and all other dialogs with "OK". 3.1.2 Integrated Project Table 3-2 1. Open the "Set PG/PC Interface" menu in the Control Panel of your configuration computer. Version V 1.0, Entry ID: 23800567 9

2. Alternatively you can also open the PG/PC interface through the SIMATIC Manager. 3. If you have an internal Ethernet interface, you can select the TCP/IP adapter without CP. You can use any NDIS Ethernet card for transfer via Ethernet. : If none of the interfaces listed above is shown, you can install them manually by clicking the "Select..." button in the "Interfaces" "Add/Remove:" field. Click the "Properties" button. 4. Enable "Fast Acknowledge" if you are communicating with an S5 or S7 and are operating less than 16 connections simultaneously. Click the "Network properties..." button. 10 Version V 1.0, Entry ID: 23800567

5. Double-click the relevant "Network" and then click the "Properties" button to open the Properties window of that network. 6. Mark "Internet Protocol Version 4 (TCP/IPv4)" and then click the "Properties" button. 7. Assign a valid IP address and subnet mask. The IP address must be unique. In other words, it must not be used by another node (socket) in the network. 8. Close the Properties dialog and all other dialogs with "OK". Version V 1.0, Entry ID: 23800567 11

3.2 Settings in Windows XP The required settings on the configuration computer are described below. 3.2.1 Non-integrated Project Table 3-3 1. Open the "Network Connections" menu in the Control Panel of your configuration computer. 2. Right-click on the relevant Ethernet network adapter (1) to open the adapter dialog window. Open the Ethernet adapter's Properties window by clicking the "Properties" (2) button. 3. Mark "Internet Protocol (TCP/IP)" and click the "Properties" button. 12 Version V 1.0, Entry ID: 23800567

4. Assign a valid IP address and subnet mask. The IP address must be unique, in other words, it must not be used by any other node in the network. 5. Close the Properties dialog and all other dialogs with "OK". Version V 1.0, Entry ID: 23800567 13

3.2.2 Integrated Project Table 3-4 1. Open the "Set PG/PC Interface" menu in the Control Panel of your configuration computer. 2. Alternatively you can also open the PG/PC interface through the SIMATIC Manager. 3. If you have an internal Ethernet interface, you can select the TCP/IP adapter without CP. You can use any NDIS Ethernet card for transfer via Ethernet. : If none of the interfaces listed above is shown, you can install them manually by clicking the "Select..." button in the "Interfaces" "Add/Remove:" field. Click the "Properties" button. 14 Version V 1.0, Entry ID: 23800567

4. Enable "Fast Acknowledge" if you are communicating with an S5 or S7 and are operating less than 16 connections simultaneously. Click the "Network properties..." button. 5. Right-click on the relevant Ethernet network adapter (1) to open the adapter dialog window. Open the Ethernet adapter's Properties window by clicking the "Properties" (2) button. 6. Mark "Internet Protocol (TCP/IP)" and click the "Properties" button. Version V 1.0, Entry ID: 23800567 15

7. Assign a valid IP address and subnet mask. The IP address must be unique, in other words, it must not be used by any other node in the network. 8. Close the Properties dialog and all other dialogs with "OK". 16 Version V 1.0, Entry ID: 23800567

3.3 Checking the Ethernet Connection 3.3.1 Check the Connection to the Panel Table 3-5 1. Enter "CMD" in the Windows 7 dialog field "Search programs and files". Click the result found. 2. Enter the "ping" command and the IP address of the panel, "150.150.150.20", for example. Confirm with "Enter". You can see the assigned IP addresses in Table 2.5. If you have already integrated the PLC into the network, you should also verify this via the "ping" command. Version V 1.0, Entry ID: 23800567 17

3. If the time is exceeded (no reply from node), then check the following points: Check and if necessary, replace the Ethernet cable (uncrossed patch cable, when using a hub or switch, for example). Check the IP address and subnet mask on the panel and on the configuration PC. Select and enable the correct Ethernet adapter. Check the Transfer settings in "Control Panel > Transfer Settings". If necessary, check the firewall settings on the configuration PC. 4. If the time is not exceeded, the connection configuration at operating system level is OK and you can close the Windows command console. Table 3-6 IP address Subnet mask Node 150.150.150.10 255.255.255.0 Configuration computer 150.150.150.20 255.255.255.0 HMI operator panel 150.150.150.30 255.255.255.0 SIMATIC station (CPU, for example) 3.3.2 Check the Settings on the Operator Panel You can also test the Ethernet connection from the operator panel. Proceed as follows. Table 3-7 1. In Windows CE you open the panel's onscreen keyboard via "Start > Programs > Soft keyboard". Then start the Windows CE command console via "Start > Programs > Command Prompt". 2. Enter the "ping" command and the IP address of the panel, "150.150.150.10", for example. Confirm with the Enter key. If you have already integrated the PLC into the network, you should also verify this via the "ping" command. 3. If the time is exceeded (no reply from node), then check the following points: 18 Version V 1.0, Entry ID: 23800567

Check and if necessary, replace the Ethernet cable (uncrossed patch cable, when using a hub or switch, for example). Check the IP address and subnet mask on the panel and on the configuration PC. Select and enable the correct Ethernet adapter. Check the Transfer settings in "Control Panel > Transfer Settings". If necessary, check the firewall settings on the configuration PC. 4. If the time is not exceeded, the connection configuration at operating system level is OK and you can close the Windows CE command console. Version V 1.0, Entry ID: 23800567 19

4 Settings in WinCC flexible 4 Settings in WinCC flexible As an option you can also integrate the WinCC flexible project into a STEP 7 project. 4.1.1 Non-integrated Project Table 4-1 1. In the project tree structure under "Communication" you select the "Connections" tab. In WinCC flexible you insert a new connection in the menu under "Insert > New Object - Connection". Alternatively you can double-click an empty field in the table in the "Connections" tab and create a new connection. 2. Define the relevant parameters that you have already specified in the panel and in the PG/PC interface. For communication via Ethernet you must change the interface in WinCC flexible to "Ethernet" or "HMI IE". Also make sure that the expansion slot and rack are also correctly specified for SIMATIC stations and that the access point is correct. 3. If you do not implement an S7-300/400 CPU as communications partner, then change the communication driver. The following communication drivers that support the Ethernet protocol are available. Modicon MODBUS TCP/IP OPC SIMATIC HMI http Protocol SIMATIC S7200 SIMATIC S7 300/400 SIMOTION 20 Version V 1.0, Entry ID: 23800567

4 Settings in WinCC flexible 4. Open the dialog window under "Project > Transfer > Transfer Settings...". Alternatively you can also open the transfer settings via the toolbar (1). 5. In the "Transfer Settings" dialog you select the relevant operator panel (2) - only necessary in the case of multiple operator panels. 6. Select Ethernet as the Transfer mode (3) and enter the IP address or the computer name/operator panel name. If you specify the device name of a Windows CE panel, a DNS server is required, because Windows CE does not directly support the name resolution. The configuration computer can also be used as DNS server. More information is available in the entry entitled > How do you integrate an HMI operator panel into a local network? For the possible transfer options please refer to the relevant operator panel manual or the entry entitled >-What transfer options are available in the various operator panels? 7. With the "Transfer" button (4) you can now transfer your configuration to the panel. If you do not want to transfer yet, you can save the settings with "Apply". With the first transfer of the project to an operator panel you should disable the "Delta transfer" option and enable the "Overwrite password list" option (if necessary, also the "Overwrite recipe data records" option). After transfer the panel applies the parameters set in the "Connections" tab. Version V 1.0, Entry ID: 23800567 21

4 Settings in WinCC flexible 4.1.2 Integrated Project Table 4-2 1. If you have not already inserted the project in the SIMATIC Manager, you can insert the project from WinCC flexible into any STEP 7 project with the menu "Project > Integrate in STEP 7...". 2. For this in the SIMATIC Manager you open the Hardware Configuration of the S7. Here you mark the appropriate SIMATIC HMI Station (1) and double-click "Configuration" (2). 3. Click and mark the fifth slot (1) of the panel. 4. Insert the Ethernet module (2) under "SIMATIC HMI Station > CP Industrial Ethernet > HMI IE". 5. Double-click the Ethernet module inserted in the subrack to open the Properties window. Enter the IP address and subnet mask (3) that you have already specified in the panel. 6. Link the HMI IE module with the existing Ethernet network (4). You can use the "New..." button to add more subnets. here that the HMI station and associated SIMATIC station must be in the same subnet. Project transfer via Ethernet with S7 Routing is not supported. 7. Close the dialog window with "OK". 8. Save and compile your configuration via the "Station > Save and compile..." menu. 22 Version V 1.0, Entry ID: 23800567

4 Settings in WinCC flexible 9. Via the corresponding subnet you select the station with which the operator panel is to communicate. 10. Open the dialog window under "Project > Transfer > Transfer Settings...". Alternatively you can also open the transfer settings via the toolbar (1). 11. In the "Transfer Settings" dialog you select the relevant operator panel (2) - only necessary in the case of multiple operator panels. 12. Select Ethernet as the Transfer mode (3) and enter the IP address or the computer name/operator panel name. If you specify the device name of a Windows CE panel, a DNS server is required, because Windows CE does not directly support the name resolution. The configuration computer can also be used as DNS server. More information is available in the entry entitled "How do you integrate an HMI operator panel into a local network?" in Entry ID: 13336639 For the possible transfer options please refer to the relevant operator panel manual or the entry entitled "What transfer options are available in the various operator panels?" in Entry ID: 19109408. Version V 1.0, Entry ID: 23800567 23

4 Settings in WinCC flexible 13. With the "Transfer" button (4) you can now transfer your configuration to the panel. If you do not want to transfer yet, you can save the settings with "Apply". With the first transfer of the project to an operator panel you should disable the "Delta transfer" option and enable the "Overwrite password list" option (if necessary, also the "Overwrite recipe data records" option). After transfer the panel applies the parameters set in the "Connections" tab. 24 Version V 1.0, Entry ID: 23800567