Power Factor Insulation Diagnosis Demystifying Standard Practices

Similar documents
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Understanding Insulation Resistance Testing

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

THE VALUE OF POWER FACTOR TESTING

Power-factor testing of rotating machinery is another valuable test

INDUCTION REGULATOR. Objective:

Introduction. Harmonics and IEEE 519 Page 1 of 19

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

SYNCHRONOUS MACHINES

High Voltage Power Supplies for Analytical Instrumentation

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Current and Temperature Ratings

Chapter 24. Three-Phase Voltage Generation

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES

Using Current Transformers with the 78M661x

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness

AC-Synchronous Generator

Power System Harmonics

AC Generators. Basic Generator

Application Note. So You Need to Measure Some Inductors?

SECTION 13. Multipliers. Outline of Multiplier Design Process:

Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

PM734F - Technical Data Sheet Winding 28

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

AC and DC Drive System Installation Information

WIRE AND CABLE ENGINEERING GUIDE

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Electrical Predictive and Preventative Maintenance

MIT510/2, MIT520/2 and MIT1020/2

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

ON-LINE DIAGNOSTIC CASE STUDY INVOLVING A GENERAL ELECTRIC TYPE U BUSHING

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Product Data Bulletin

A Practical Guide to Dielectric Testing

The following table shows approximate percentage wise the

Insulation Resistance Testing of Low Voltage Cables in the Field

Chapter 12: Three Phase Circuits

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Critical thin-film processes such as deposition and etching take place in a vacuum

Three-phase AC circuits

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

WIRE AND CABLE ENGINEERING GUIDE

Electricity. Confirming Coulomb s law. LD Physics Leaflets P Wie. Electrostatics Coulomb s law

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

UCI274C - Technical Data Sheet

3-Phase AC Calculations Revisited

An Overview of Practical Capacitance Bridge Functioning. by Paul Moses

UCI274H - Technical Data Sheet

Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs)

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

White Paper. Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards.

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Failure code manual. content

VOLTAGE REGULATOR AND PARALLEL OPERATION

Lab 8: DC generators: shunt, series, and compounded.

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

Capacitors for A.C. motor applications

Step Voltage Regulators

Three phase circuits

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

Basics of Electricity

LABORATORY 2 THE DIFFERENTIAL AMPLIFIER

Type SA-1 Generator Differential Relay

Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

Troubleshooting accelerometer installations

S112-XHS. Description. Features. Agency Approvals. Applications. Absolute Maximum Ratings. Schematic Diagram. Ordering Information

Short Circuit Current Calculations

Axial and Radial Leaded Multilayer Ceramic Capacitors for Automotive Applications Class 1 and Class 2, 50 V DC, 100 V DC and 200 V DC

Unit 33 Three-Phase Motors

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

A Guide to Transformer Winding Resistance Measurements

Avoiding AC Capacitor Failures in Large UPS Systems

RLC Resonant Circuits

(3 )Three Phase Alternating Voltage and Current

IEC ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays

ET 332b Ac Electric Machines and Power Systems

Alternating Current and Direct Current

CT Application Guide for the 489 Generator Management Relay

Instrument Transformers Application Guide

Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA

Inductors in AC Circuits

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

Application Guide. Power Factor Correction (PFC) Basics

WHY DIFFERENTIAL? instruments connected to the circuit under test and results in V COMMON.

Insulation resistance testing

Electrical Safety Tester Verification

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

Pump Maintenance - Repair

13 ELECTRIC MOTORS Basic Relations

Transcription:

Power Factor Insulation Diagnosis Demystifying Standard Practices 50 th Annual Minnesota Power Systems Conference Nov 4 th 2014 Dinesh Chhajer, PE MEGGER 1

Agenda Power Factor Fundamentals Power Factor (PF) vs. Voltage Negative Power Factor Values Excitation Current vs. Voltage Temperature Correction Factors for PF Readings 2

Power Factor Testing What is it? A form of AC testing that applies voltage and measures the leakage/loss current of electrical insulation. It is a type of insulation testing used to evaluate the integrity of electrical insulation. C HL Vs Insulation 3

Facts about Insulation Power factor is defined as Cosine of phase angle between voltage and current. For an ideal insulation phase angle is 90. Cos (90) = 0 Power Factor is ZERO for an ideal insulation!! 4

Facts about Insulation No Insulation is ideal. A small amount of current flows through all insulation called as leakage current. Leakage current comprises of two components. Resistive current Capacitive current In real life insulating conditions, in addition to the capacitance current there appears a resistive (or loss) current in-phase with the voltage. 5

Facts about Insulation In practice no insulation is perfect, but has a certain amount of loss and the total current leads the voltage by a phase angle less than 90 Ic Ic I T Vs Vs I R Vs I R 6

Power Factor Testing T T 7

Power Factor Testing H C HL L = C HG C LG G 8

Power Factor Testing UST GST GST with Guard Guard 9

POWER FACTOR vs. VOLTAGE 10

Power Factor vs. Voltage PF test is typically performed at 10 kv or values equivalent to 10 kv are obtained Why not 25 V or 25 kv? What test voltage is good enough? 11

PF (%) Power Factor vs. Voltage Oil-paper type insulation system 0.58 0.57 0.56 0.55 0.54 0.53 0.52 0.51 0.50 0.49 0.48 Power Factor vs. Voltage 0 1 2 3 4 5 6 7 8 Voltage (kv) Three Phase two winding Oil filled Transformer Delta-Delta 13.8/2.4 kv, 3.75 MVA C HL + C HG PF shows a flat response as a function of test voltage 12

Power Factor (%) Power Factor vs. Voltage Solid or dry type insulation Tip up Test 0.7 0.6 0.5 0.4 0.3 0.2 0 50 100 150 % of rated Line to Neutral Voltage Phase A-G Phase B-G Phase C-G 2000 HP, 4000V 3-Φ induction motor The amount of increase in PF value as a function of voltage corresponds to the degree of ionization taking place in voids. 13

Power Factor vs. Voltage Tip up test helps in estimating the presence of voids in dry type insulations. 14

Power Factor vs. Voltage 10 kv test voltage provides immunization against electrostatic interference and electrical noise in HV substations. Four repeat UST measurements on a grading capacitor in a 765 kv Substation A HV test signal provides better signal to noise ratio (SNR) for precise and accurate measurements. 15

NEGATIVE POWER FACTOR VALUES 16

Negative Power Factor Values Specimens like bushings, three winding transformers, inter phase insulation of rotating machinery sometimes exhibits negative PF values. PF values cannot be negative. It is a phantom value. It is caused when phase angle of measuring current exceeds reference voltage by more than 90 deg. This happens typically because of introduction of surface leakage current 17

Negative Power Factor Values I NET I T I s = Total Current = Test Current = Surface Loss Current 18

Negative Power Factor Values Specimens with low capacitance values (smaller current) are more susceptible to this surface loss current and can lead to negative PF values. Vector diagram with different magnitude of current I NET and purely resistive loss current I s 19

Negative Power Factor Values Important to understand the source of negative PF values Some specimens exhibit negative values by virtue of their design Following best testing practices, one should eliminate all external effects Repeated negative values after following best testing practices may point towards some contamination/ moisture or a bad insulation system 20

EXICTATION CURRENT vs. VOLTAGE 21

Excitation Current vs. Voltage Excitation current test is a voltage dependant test. Typical magnetization curve of a power transformer Test is either performed at 10 kv or values equivalent to 10 kv are determined using a linear relation. 22

23

Excitation Current Test 24

Excitation Current vs. Voltage A linear approximation is used to determine the equivalent excitation current values at 10kV 20 ma @ 5kV is 40 ma@ 10 kv equivalent Voltage and Current exhibits non-linear relation!! Linear approximation will only give approximate values and can introduce significant errors. Excitation current test performed at different voltages on a single phase Transformer 25

Excitation Current on Delta Windings Third leg of Delta winding should always be grounded for accurate measurements. Pending the inductance and resistance of each winding, if third leg is not grounded, the results would be approximately 30 to 50% higher than true readings 26

Excitation Current & Residual Magnetism A transformer core with residual magnetism can cause erroneous readings in excitation current measurements. IEEE C57.152 section 7.211.1 states that The transformer core may have residual magnetism present as a result of being disconnected from the power line or, as is frequently the case, as a result of dc measurements of winding resistance. The residual magnetism results in the measurement of higher-than-normal excitation current. If a significant change in the test results is observed, the only known reliable method of excluding the effect of residual magnetism is to demagnetize the transformer core. 27

Temperature Correction Factor for PF Readings 28

Temperature Correction Factors Temperature correction factors (TCF) are based only on nameplate information TCF does not take into account critical information such as the aging of insulation, the quality and type of oil and paper insulation, operating conditions or the history of the transformer Insulation temperature dependence would be different based upon it s condition and age. It can lead to incorrect temperature compensation and false trending of results 29

TCF for Any Oil Filled Power Transformer Above ½ MVA 1970, 500 MVA and 2012, 5 MVA oil filled transformers use the same correction factor Insulation used in power transformers (type of oil and paper) is not taken into account 30

Temperature Correction Factors IEEE C57.12.90 section 10.10.4 Note 3 (b) states that Experience has shown that the variation in power factor with temperature is substantial and erratic so that no single correction curve will fit all cases. When the insulation power factor is measured at a relatively high temperature and the corrected values are unusually high, the transformer should be allowed to cool and the measurements should be repeated at or near 20 ºC. It is imperative to only compare a specimen s PF values that are either taken at a similar temperature or corrected to the same temperature accurately. 31

Temperature Correction Factors Temperature dependence of different transformers with different levels of ageing 32

Temperature Correction Factors Each specimen is unique in its construction, design and ratings. They are each subjected to different kinds of stresses, loading and environmental conditions. Temperature correction factor values are highly dependent on insulating material, their structure, ageing, presence of moisture or contamination and various other factors. The available temperature correction factor data is based upon the average value. 33

Temperature Correction Factors The average correction would introduce some error into the corrected value, as each specimen is unique. New transformers have relatively weak temperature dependence and use of TCF tables would over compensate. An aged transformer, becomes highly temperature dependent. Average TCF values to 20 C lie somewhere between these two extremes. 34

Dielectric Frequency Response (DFR) Also known as Frequency Domain Spectroscopy DFR is a test technique used to determine the moisture concentration in the solid insulation (oil impregnated paper) of liquid-filled power transformers PF measurements are performed in a frequency range of 1 mhz 1000 Hz. PF vs. Frequency plot is generated 35

Power Factor Dielectric Frequency Response Each point is a Power Factor value! Frequency 36

DFR Measurement Measures Capacitance Measures Power Factor Measures MOISTURE % in cellulose Conductor Conductor or Ground Insulation Material Insulation parameters: Z = R + j X Capacitive charging current Resistive watts lost current (heat) Determines Individual Temperature Correction factors (ITC) 37

Temperature Correction Factors The determination of temperature correction factors using DFR method is based on the fact that a power factor measurement at a certain temperature and frequency corresponds to a measurement made at different temperature and frequency. With DFR technique, individual temperature correction factors can be determined and values can be accurately corrected to 20 C The big advantage of this technique is that PF values can now be measured at any insulation temperature ranging from 5-50 C and still can be corrected to 20 C accurately. 38

C HL 39

Case Study to COMPARE Table based Temperature Correction Factors (TCF) Vs. DFR based Individual Temperature Correction Factors (ITC) 40

ITC and TCF Field Results ITC method using DFR technique was verified and implemented on a new 40 MVA core type three-phase delta wye transformer Transformer was tested in a controlled environment at an EFACEC manufacturing plant. The goal was to perform PF test at different temperatures and compare ITC and TCF against real Measured Correction Factors (MCF) 41

Test Setup Windings were heated using short circuit method and temperature was raised to 75º C The transformer was allowed to cool for hours to bring the oil and windings temperature closer Winding resistance test was performed to determine the high and low side temperatures Top oil temperature, top and bottom radiator and ambient temperature were monitored through out the test duration 42

Test Object 43

Short Circuit Test 44

Temperature Measurements 45

Transformer Temperature The average temperature of the transformer oil was estimated using the formula mentioned in IEEE C57.12.90 Avg oil temp = Top oil (Top Rad. Bottom Rad.)/2 Transformer insulation temperature was determined by taking average of high side, low side and average oil temperature Temperatures were measured at the start and end of each test to get a more accurate overall transformer insulation temperature 46

Test Details PF was measured at different temperatures as the transformer was cooling down from 50º C to 20º C Two different test instruments (IDAX 300 and Delta 4000) were used to perform the PF measurement at different temperatures All three insulations (C HL, C HG and C LG ) were measured for this analysis DFR from 1-500 Hz was run for each measurement 47

Test Setup 48

ITC Analysis Three different types of correction factors were used in the case study 1) TCF, traditional temperature correction factors obtained from standard tables 2) Measured (real) Correction Factors MCF @ Temp X = 3) ITC by using DFR 49

Comparison of ITC & TCF against MCF 50

Observation # 1 Comparison of ITC and TCF with respect to Measured Correction Factors (MCF) for C HL insulation 51

Observation # 1 ITC and TCF percent error with respect to Measured Correction Factors (MCF) for C HL insulation 52

Observation # 2 Comparison of ITC and TCF with respect to Measured Correction Factors (MCF) for C HG insulation 53

Observation # 2 ITC and TCF percent error with respect to Measured Correction Factors (MCF) for C HG insulation 54

Observation # 3 Comparison of MCF and TCF for C LG insulation 55

Observation # 4 Comparison of ITC and TCF corrected values to 20º C with respect to measured PF readings at different temperatures and 20º C for C HL insulation 56

DFR ITC Summary The tests performed and analysis of results indicates that TCF being average correction values can introduce error varying from as little as 2% to as high as 92% on the specimen tested The analysis was performed on three different insulations of a single transformer only. Other transformers with different aging and operating conditions can have varying percent errors in measurements when TCF is applied for temperature correction. ITC results were very comparable to MCF and worst case error was 10% With same PF connections and little extra time ITC can be obtained via DFR technology that can better compensate for temperature and correct values to 20 ºC 57

Temperature Correction Factors With the help of Power Factor vs. frequency, Power Factor vs. temperature can be plotted With DFR technique, individual temperature correction factors can be determined and values can be accurately corrected to 20 C The big advantage of this technique is that PF values can now be measured at any insulation temperature ranging from 5-50 C and still can be corrected to 20 C accurately and precisely. 58

Conclusions Electric apparatus have failed and will continue to fail because of insulation deterioration. Power factor readings are dependent on various different factors and it is very important to understand the effect of these factors. Test voltage, electrostatic interference, temperature, humidity, surface losses and various other parameters can greatly influence the PF readings. A better understanding of the impact of these varying parameters would help in obtaining accurate PF measurements. 59

Thank You!! QUESTIONS?? 60