ON-LINE DIAGNOSTIC CASE STUDY INVOLVING A GENERAL ELECTRIC TYPE U BUSHING
|
|
|
- Cory Cross
- 10 years ago
- Views:
Transcription
1 ON-LINE DIAGNOSTIC CASE STUDY INVOLVING A GENERAL ELECTRIC TYPE U BUSHING Pamelyn Bahr and Jon Christensen Intermountain Power Service Corp. Robert C. Brusetti, P.E. Doble Engineering Company ABSTRACT If your on-line bushing monitoring system indicated that a bushing had gone from good to a state of serious deterioration, 5% power factor, in the matter of a few hours how would you respond? Complicate the matter by placing the bushing on the 345 kv winding of a 968 MVA GSU that feeds the base load of Los Angeles. This was the situation facing Intermountain Power Service Corporation the morning of September 13 th, After an exhaustive analysis of the data, which attempted to eliminate all peripheral factors, the decision was made to take the unit off-line. This paper will evaluate the on-line data leading to the decision to remove the GSU from service, and correlate the data with the field test results obtained once the unit was removed from service. The finding of the subsequent factory tear down will illustrate how changes in the capacitance and power factor are manifested in a bushing insulation system. BACKGROUND The on-line monitoring system was installed on the high side bushings of a generator step up transformer rated 968 MVA, 345/26 kv. The transformer was manufactured by GE in The unit feeds a DC line that transmits to the Los Angeles area. The bushing nameplate information is listed in Table 1. TABLE 1 Bushing Nameplate Information Dsg Serial Mfr Type C1 C1 %PF Cap kv Amps Year H GE U H GE U H GE U H GE U X GE T X GE T X GE T The last off-line measurements were performed in March of 2003 (see Table 2), and the on-line bushing diagnostics were installed in June Over the next two years the on-line system showed only a slight capacitance increase in the H3 (phase A) bushing (less the 5pF), which represents less than a 2% increase, with no noticeable change in the power factor. The other bushings did not manifest any changes in either capacitance or power factor. Note these values are extracted from the on-line leakage measurement using a modified sum current approach. On June 10 th, 2005 the transformer was de-energized as part of a plant outage, the unit went back into service on July 14 th, Once back in service in the leakage current of 1
2 the H3 (phase A) bushing exhibited a slight increasing trend. Over a three month period this change represented only a few picofarads increase in capacitance. TABLE 2 March 2003 Off-Line C1 Test Results ID Serial NP %PF NP Cap Test kv ma Watts %PF corr Corr Fctr Cap(pF) IR auto IR man H G H G H G H G X G X G X G RAPID DEGRADATION OF BUSHING INSULATION On September 9 th, 2005 the relative angle associated with the phase A bushing began to decrease. Over the next three days the measured angle decreased by almost half a degree. On September 12 t,h, 2005 at 21:00 the current began to increase,. In the span of seven hours the H3 (phase A) current magnitude went from approximately 24.8mA to 27.2mA and the angle decreased by 2.5. The expert system, which on this system used the sum current, issued an alert based on the drastic change in the sum current. The diagnostics calculated the power factor of the phase A bushing at 5.6% and the capacitance at 350pF. After a comprehensive review, which eliminated the typically external factors that could influence the bushing leakage current, the plant manager was advised of the findings and the decision was made to take the transformer out of service. Once removed from service the bushing was immediately tested; the offline test measurement for the phase A bushing was 333 pf and 5.5% power factor; which is a dramatic increase in the C1 power factor and capacitance from the March 2003 value of 0.27%, and pf. DISCUSSION OF RESULTS Figure 1 plots the hourly current magnitude of the three bushings and attempts to identify the gaps in the data. Figure 2 displays the same information normalized to the reference bushing (which is Phase B). Both Figures 1 and 2 exhibit an increase in the Phase A bushing (H3) current magnitude which becomes more evident following the unit returning to service in July. However, the total change in current magnitude through September 12, 2005 is only 2%. Changes in current magnitude reflect a change in the bushing capacitance. Traditionally a change in capacitance of 2% would not warrant corrective action. Figure 3 is the capacitance calculation for the H3 bushing using the analysis of the on-line bushing diagnostic system. The analysis used by the instrumentation monitoring the bushing employed three trending cycles, one day, one week and one month. Trending over various periods is required to reducing the influence of external factors, such as power system fluctuations and imbalances. The information plotted in Figure 3 suggests the capacitance between January 2005 and the outage in June was essentially stable. Once the unit was put back in service (July 2005) the capacitance of Phase A showed a tendency toward increasing. However, over a two month period the increase was less than 1%, and the total change in capacitance from the start of the on-line monitoring until September 12, 2005 was less than 10 pf. Traditionally these are not levels that would trigger an investigation or a bushing replacement. Over a seven hour period on September 12 th the capacitance of the H3 bushing increased significantly, by more than 10%, based on the daily trend. The rapidly changing condition of this bushing illustrates the need 2
3 for trending over both short and long periods. Long trending cycles employ more data and therefore are less sensitive to external influence; however the longer trending cycles also require more time to accumulate the information and consequently will take longer to register the anomaly 1. Figure 4 plots the phase angle deviation. Note that phase B will always be zero degrees, since it is being used as the reference. There is essentially no change in the angle of the leakage current of the H3 bushing through September 9, From September 9 th to the 12 th the phase angle of the H3 bushing decreased by approximately half a degree. Figure 5 which trends the power factor of the H3 bushing translated the degree in angle to approximately 0.5% power factor increase based on the daily trend. There is a direct correlation between the leakage current angle and the power factor of a bushing. Over the same period of September 12 th when the magnitude of the leakage current of H3 was increasing the leakage current angle decreased by 3 O. Referencing the daily power factor trend on Figure 5 this translated to a power factor of approximately 5.5%. Based on the on-line data the H3 bushing had experienced significant physical change (capacitance) and degradation of the insulation (power factor). Change in capacitance associated with a bushing insulation system is usually associated with short circuiting of condenser layers. June 10, 2005 July 14, 2005 March 31, 2004 January 31, 2005 Hourly Phase Current Magnitude FIGURE 1 3
4 September 12, 2005 Normalized Hourly Current Magnitude FIGURE 2 Capacitance Trend Phase A Bushing (On-line) FIGURE 3 4
5 September 9, 2005 Change in Phase Angle FIGURE 4 % Power Factor Trend of Phase A Bushing (On-line) FIGURE 5 Table 3 represents the bushing C1 test results after the transformer had been removed from service. The temperature compensated H3 power factor was 4.97% and the capacitance had increased to 333.5pF, essentially verifying what the expert system was observing on-line. There were no significant changes in any of the other bushings. 5
6 TABLE 3 September 15, 2005 C1 Test Results ID Serial NP %PF NP Cap Test kv ma Watts %PF corr Corr Fctr Cap(pF) IR auto H G H G H B H G X G X G X G Table 4 contains the dissolve gas analysis results (in ppm) of a sample drawn from the H3 bushing following the September 15 th tests. The presence of high temperature gases, specifically acetylene, and the high quantities measured indicate severe arcing taking place. TABLE 4 DGA Results, Sampled September 15, 2005 Hydrogen H Oxygen O Nitrogen N Methane CH Carbon Monoxide CO 668 Ethane C 2 H Carbon Dioxide CO Ethylene C 2 H Acetylene C 2 H BUSHING TEARDOWN Since both the on-line and off-line test indicated the bushing should not be placed back into service, the bushing was sent to the ABB factory in Alamo TN, were it was dismantled. With the oil drained and the porcelain weather shed removed, dark areas on the lower half of the paper core extending to the exposed conductor were immediately evident (Figure 6). The report from ABB attributed this sooty appears to an indication of partial axial failure. The compositions of these discolorations were later verified, through analysis of the paper, to be carbon deposits. With the outer cellulose removed, overheating was observed on the edges of the paper (Figure 7). Signs of overheating were also observed on the seam of the foil that makes up the grounded condenser layer (Figure 8). The bushing condenser design employed the Rescon Ink condenser (Figure 9). The Rescon (conductive ink) is graphite suspended in a resin solution. The Rescon ink is applied to kraft paper in a herringbone pattern. The bushing core is made up of two electrical grade papers wound onto a single conductor. An ink-lined paper forms the capacitive layers while plain kraft paper is used to establish the insulation between the conductive layers. One of the more common failure mechanisms of the GE Type U bushing is ink migration to the insulating layer, which leads to partial discharge and/or overheating of paper 2. This phenomenon was observed as the core was unwrapped. Figure 10 exhibits how the fault was traveling across multiple layers and Figure 11 shows a similar event where the puncture damage was severe. 6
7 However, no fault location punctured the entire condenser insulation; most only traveled a few layers. The ABB report noted five areas where the burned damage penetrated multiple layers. An interesting observation made by the ABB representative Lonnie C. Elder: It is interesting to note that all the areas of localized burning were actually connected electrically to each other, either through the arcing that burned through adjacent layers of paper, or via the herringbone shaped printed conducting lines. Some of the burned areas were spaced axially quite far apart, but if one followed along the affected printed lines, one of these lines would connect through one of the other burned areas The degree of polymerization of various paper samples ranged between 900 and 1000, suggesting there had not been significant paper aging. Carbon Deposit Bottom Portion FIGURE 6 Indication of Overheat of Paper Edges Portion FIGURE 7 7
8 Discoloration on the Seam of the Grounded Condenser Layer FIGURE 8 Herringbone Conducting Paint Design FIGURE 9 8
9 Overheat Across Multiple Layers FIGURE 10 Insulation Breakdown across Multiple Layer FIGURE 11 9
10 CONCLUSION What is unique about this bushing problem is how quickly the insulation medium deteriorated. Prior online experience involving degraded bushings suggests a long gestation period, with the end user opting to replace the bushing before the condition becomes critical. In this scenario the quality of the bushing insulation deteriorated in a period of three days to the point that the bushing should be removed from service, with no prior indication of degradation. The plotted results of the H3 bushing capacitance seem to suggest a very gradual increase, approximately 2% over a two year period, a rate that typically would not warrant corrective action. It has always been theorized that prior to dielectric breakdown (failure) the insulation medium experiences rapid degradation. The behavior of the H3 bushing may appear to support this theory, however the lack of any interval when the condition is worsening presents a different scenario. While it is impossible to predict when the bushing would have failed, both the on-line and off-line measurements indicated the bushing had to be removed from service. The subsequent tear down of the bushing substantiated the decision to remove the bushing from service, as it revealed burning within the paper insulation. The ABB report attributed the change in power factor to increase real losses in the bushing core. The change was the result of shorted condenser layers. While 3.8% change in capacitance typically does not warrant investigation, the report brings up a valid point. There are thousands of individual herringboneshaped conductive lines, each representing a capacitive value. Even if a few are short circuited, this is still a small percentage of the total number of condenser lines. Therefore, one should not expect the capacitance to increase significantly in Type U bushings with the herringbone design of condenser, even though a significant problem may exist. REFERENCES: 1.Brusetti, R.C., "Update on On-Line Bushings Diagnostic," Seventy-Third Annual International Conference of Doble Clients, 2006, page 3. 2.Duarte, E. M., "A Review of Past Bushing Problems," Seventy-Third Annual International Conference of Doble Clients, 2006, page 10. BIOGRAPHY: Pamelyn J. Bahr received her Bachelor of Science in Electrical Engineering degree from Utah State University in 1986, and a Masters in Business Administration from Brigham Young University in She has been employed at Intermountain Power Service Corporation for the past 19 years, and is currently an Electrical Engineer in the Instrumentation and Electrical Engineering Group. Jon P. Christensen, P.E., received his Bachelor of Science in Electrical Engineering degree from Brigham Young University in He has been employed at Intermountain Power Service Corporation for the past twenty years, and is currently the Engineering Supervisor for the Instrumentation and Electrical Engineering Group. Prior to working for Intermountain Power he worked for the Los Angeles Department of Water and Power in their Quality Assurance Group. Mr. Christensen is a licensed Professional Engineer in the state of Utah. 10
11 Robert C. Brusetti, P.E., received his Bachelor of Science in Electrical Engineer degree from the University of Vermont in 1984 and a Masters in Business Administration from Boston College in He has been employed at Doble Engineering Company for the past sixteen years and currently works in the Client Service department as Product Marketing Manager. Prior to his present responsibility he has held positions as Product Manager and Principal Engineer. Mr. Brusetti is a licensed Professional Engineer in the state of Massachusetts. 11
THE VALUE OF POWER FACTOR TESTING
THE VALUE OF POWER FACTOR TESTING Nov 1, 2005 12:00 PM by John Bleyer and Phillip Prout, National Grid NATIONAL GRID DISCOVERED A HIGH POWER FACTOR DURING ACCEPTANCE TESTING of a new 40-MVA transformer
DGA - Method in the Past and for the Future
DGA - Method in the Past and for the Future Page 2 May 2012 1970 1973 Doerenburg introduced the differentiation between electrical and thermal failure mode and introduced ratios for fault gases with similar
Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid
DSI Ventures, Inc. PHONE: (903) 526-7577 FAX: (903) 526-0021 www.dsiventures.com Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid Introduction Analysis of dissolved gases in transformer
Electrical Maintenance Workshop
Electrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003 Transformer Maintenance & Testing Purpose This presentation provides an overview of the major considerations
DISSOLVED GAS ANALYSIS OF MINERAL OIL INSULATING FLUIDS
DISSOLVED GAS ANALYSIS OF MINERAL OIL INSULATING FLUIDS Written by: Joseph B. DiGiorgio, Ph.D. Dr. DiGiorgio conducts seminars on request. 1996-2013 NTT Copyrighted material. Contact Dr. DiGiorgio Insulating
Hydro Plant Risk Assessment Guide
September 2006 Hydro Plant Risk Assessment Guide Appendix E5: Transformer Condition Assessment E5.1 GENERAL Power transformers are key components in the power train at hydroelectric powerplants and are
GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry
GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry Brian Sparling, SMIEEE GridTech 2007, Delhi February 5-6, 2007 The
Siemens TMDS transformer monitoring and diagnostic system. Solutions for transformer life-cycle management. Answers for energy.
Siemens TMDS transformer monitoring and diagnostic system Solutions for transformer life-cycle management Answers for energy. We strive to unlock value in your transformer monitoring and Smart Grid investments.
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
Enhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
Power-factor testing of rotating machinery is another valuable test
Feature Power-Factor Testing of Stator Winding Insulation: Understanding the Test Technique and Interpretation of Results Power-factor testing of rotating machinery is another valuable test technique providing
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
UNDERSTANDING CORROSIVE SULFUR PROBLEMS IN ELECTRIC APPARATUS. Paul J. Griffin and Lance R. Lewand Doble Engineering Company
UNDERSTANDING CORROSIVE SULFUR PROBLEMS IN ELECTRIC APPARATUS Paul J. Griffin and Lance R. Lewand Doble Engineering Company ABSTRACT Corrosive sulfur in oil has become a problem in electric apparatus.
MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
N O T E S. Environmental Forensics. Identification of Natural Gas Sources using Geochemical Forensic Tools. Dispute Scenarios
Environmental Forensics N O T E S V o l u m e 2 9 Identification of Natural Gas Sources using Geochemical Forensic Tools By Paul Boehm, Ph.D. and Tarek Saba, Ph.D. F o r m o r e i n f o r m a t i o n o
SECTION 13. Multipliers. Outline of Multiplier Design Process:
SECTION 13 Multipliers VMI manufactures many high voltage multipliers, most of which are custom designed for specific requirements. The following information provides general information and basic guidance
A GUIDE TO TRANSFORMER OIL ANALYSIS BY I.A.R. GRAY Transformer Chemistry Services
A GUIDE TO TRANSFORMER OIL ANALYSIS BY I.A.R. GRAY Transformer Chemistry Services INTRODUCTION The fault free operation of power transformers is a factor of major economic importance and safety in power
TMDS Smart Monitor. Solutions for transformer life-cycle management. Answers for energy.
TMDS Smart Monitor Solutions for transformer life-cycle management Answers for energy. TMDS Smart Monitor Selecting a transformer monitoring solution is a critical step in achieving your company s Smart
Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission
Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up
EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES
EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES Sverre Hvidsten*, Peter Werelius**, Jørgen Christensen*** * SINTEF Energy Research (SEfAS),
Explaining and avoiding faults Increasing availability
Explaining and avoiding faults Increasing availability > Cables > Cable joints > Cable terminals Cables, cable joints, cable terminals Increasing availability A cable breakdown usually means an unexpected
WIRE AND CABLE ENGINEERING GUIDE
DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a
employed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
Energy Efficient Operations and Maintenance Strategies for Boilers
Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must
Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
Trace Gas Exchange Measurements with Standard Infrared Analyzers
Practical Environmental Measurement Methods Trace Gas Exchange Measurements with Standard Infrared Analyzers Last change of document: February 23, 2007 Supervisor: Charles Robert Room no: S 4381 ph: 4352
Online Transformer Insulation Monitoring System BushingGard Product Focus. Maximizing Transformer Uptime and Reliability
Online Transformer Insulation Monitoring System BushingGard Product Focus Maximizing Transformer Uptime and Reliability Critical Energy Transfer... Large power transformers are found around the world at
An Overview of Lapp Insulator High Voltage Bushing Design
An Overview of Lapp Insulator High Voltage Bushing Design W.A. Young Lapp Insulator Company LeRoy, NY 14482 USA INTRODUCTION High voltage bushings are devices designed to transmit electric energy through
GETTING TO THE CORE: THE LINK BETWEEN TEMPERATURE AND CARBON DIOXIDE
DESCRIPTION This lesson plan gives students first-hand experience in analyzing the link between atmospheric temperatures and carbon dioxide ( ) s by looking at ice core data spanning hundreds of thousands
Calculate Available Heat for Natural Gas Fuel For Industrial Heating Equipment and Boilers
For Industrial Heating Equipment and Boilers Prepared for California Energy Commission (CEC) Prepared By: Southern California Gas Company (A Sempra Energy Utility) E3M Inc. May 2012 i Disclaimer The CEC
Transformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA
Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation
POWER TRANSFORMER INCIPIENT FAULTS MONITORING
POWER TRANSFORMER INCIPIENT FAULTS MONITORING Cristina CIULAVU, Elena HELEREA Transilvania University of Brasov [email protected], [email protected] Abstract: Power transformers are important
DISTRIBUTION OPERATIONS AND MAINTENANCE
EB-00-00 Filed: 00 Aug Page of DISTRIBUTION OPERATIONS AND MAINTENANCE PREVENTIVE MAINTENANCE Preventive Maintenance is intended to maintain or improve customer service reliability, extend equipment life
EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION INTERNATIONAL ELECTROTECHNICAL COMMISSION
EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION INTERNATIONAL ELECTROTECHNICAL COMMISSION EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION 1 EFFICIENT ELECTRICAL ENERGY TRANSMISSION
Studies of Monitoring and Diagnosis Systems. for Substation Apparatus
Studies of Monitoring and Diagnosis Systems for Substation Apparatus Yishan Liang Thesis submitted to the faculty of the Virginia Polytechnic Institute and State University in partial fulfillment of the
Smart Asset Management
Smart Asset Management Stephen McArthur [email protected] Drivers Environment Solar radiation Wind speed and direction Atmospheric pressure Relative humidity Precipitation Conservator tank Key
On-line Condition Monitoring and Diagnosis for Power Transformers their Bushings, Tap Changer and Insulation System
On-line Condition Monitoring and Diagnosis for Power Transformers their Bushings, Tap Changer and Insulation System Tobias Stirl, Raimund Skrzypek, Stefan Tenbohlen*, Rummiya Vilaithong* AREVA Energietechnik
Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at. 2207 Forest Drive, Annapolis, MD. Provided by: HurleyIR
Nondestructive Evaluation of Outback Steakhouse/Bertucci s Building at 2207 Forest Drive, Annapolis, MD Provided by: HurleyIR On Monday, June 2, 2014, HurleyIR provided a nondestructive evaluation for
On-line PD Monitoring Makes Good Business Sense
On-line PD Monitoring Makes Good Business Sense An essential tool for asset managers to ensure reliable operation, improve maintenance efficiency and to extend the life of their electrical assets. Executive
Investigation on Sampling, Measurement and Interpretation of Gas-in-Oil Analysis for Power Transformers
21, rue d Artois, F-75008 PARIS D1-204 CIGRE 2008 http : //www.cigre.org Investigation on Sampling, Measurement and Interpretation of Gas-in-Oil Analysis for Power Transformers S. Tenbohlen, J. Aragon-Patil,
Compressor Performance
expertise beyond controls Compressor Performance Advisor (CPA) Software Monitoring compressor performance for the purpose of evaluating compressor productivity and optimizing maintenance intervals is an
Balancing chemical reaction equations (stoichiometry)
Balancing chemical reaction equations (stoichiometry) This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit
On-line monitoring of substation condition a Romanian experience. V. ZAHARESCU, Vl. ROSCA Nova Industrial SA. CN Transelectrica SA Romania
21, rue d Artois, F-75008 PARIS http : //www.cigre.org B3_201 CIGRE 2012 On-line monitoring of substation condition a Romanian experience C. MOLDOVEANU*, V. BREZOIANU, S. GAL, V. METIU, A. VASILE, V. URSIANU,
WINDING RESISTANCE TESTING
WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991
Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable
Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable Dr. Uchida Katsumi*, Youichi Katou*, Dr. Hiroyuki Kon, Dr. Kazuo Watanabe and Takenori
On-line Dissolved Gas Analysis
On-line Dissolved Gas Analysis accord. to IEC 567/ASTM 3612 Online-Monitoring of transformers Automatic on-line analysis of 11 gases The analysis is done in 2 steps with high selectivity and accuracy fully
Root-Cause Analysis of Transformer Failure Scenario at Power Sub-Station
Root-Cause Analysis of Transformer Failure Scenario at Power Sub-Station AMBUJ KUMAR Department of Electrical Engineering National Institute of Technology, Hamirpur (HP) India Email: [email protected]
ASSESSMENT OF OIL ANALYSIS DATA FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS
ASSESSMENT OF OIL ANALYSIS DATA FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS A. Müller 1*, M. Jovalekic 1, S. Tenbohlen 1 1 Institute of Power Transmission and High Voltage Technology, University of Stuttgart,
The Ambient Air Monitoring System
The Ambient Air Monitoring System 1.0 Introduction: The Ambient Air Monitoring System (AAMS) can measure a range of toxic and flammable gases, particulate matter, meteorological and environmental parameters
The soot and scale problems
Dr. Albrecht Kaupp Page 1 The soot and scale problems Issue Soot and scale do not only increase energy consumption but are as well a major cause of tube failure. Learning Objectives Understanding the implications
electrical services WWW.AU.SGS.COM/INDUSTRIAL
electrical services WWW.AU.SGS.COM/INDUSTRIAL OUR PROFILE SGS offers a full range of electrical engineering services covering the commissioning test of new plant as well as the maintenance and continual
Intelligent maintenance decisions with ABB TrafoAssetManagement TM proactive services
Intelligent maintenance decisions with ABB TrafoAssetManagement TM proactive services Paul Ammann, Pierre Lorin, Anders Grano ABB Power Products - Transformer Service ABSTRACT Transformers are indispensable
This paper describes Digital Equipment Corporation Semiconductor Division s
WHITEPAPER By Edd Hanson and Heather Benson-Woodward of Digital Semiconductor Michael Bonner of Advanced Energy Industries, Inc. This paper describes Digital Equipment Corporation Semiconductor Division
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.
Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors
Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors www.static-control.in 1 Introduction The detection or monitoring of flue gases and or hazardous gases has been a complex subject
How To Test For Safety On A Power Cable
T H E M A G A Z I N E O F 7 x 2 4 E X C H A N G E I N T E R N AT I O N A L A Green Approach to Building a Superior Data Center S P R I N G 0 9 BUILD FOR TODAY. EXPAND ON DEMAND. Modularity in the data
New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance
New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance Dennis W. Lenk, Fellow, IEEE Abstract-- This paper examines performance
METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS
METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS Contents Foreword --------------------------------------------------------------------------------------------------------------------
A Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
AC-Synchronous Generator
Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to
This chapter is devided into two sections:
This chapter is devided into two sections: Page Installation requirements........................................................................ 127 The installation process..........................................................................
MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.
MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question. 1) If the voltage at a point in space is zero, then the electric field must be A) zero. B) positive.
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
1. INTRODUCTION ABSTRACT
MultiWave Hybrid Laser Processing of Micrometer Scale Features for Flexible Electronics Applications J. Hillman, Y. Sukhman, D. Miller, M. Oropeza and C. Risser Universal Laser Systems, 7845 E. Paradise
T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A
T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test
Respecting the environment
MAIN FEATURE CHAPTER I RESEARCH WITH AN EYE ON THE FUTURE Respecting the environment Low power losses and a lesser visual impact on the landscape make Gas-Insulated Lines (GIL) a very environmentally friendly
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem
LED MOTION ACTIVATED FLOOD LIGHT
Utilitech & UT Design are registered trademarks of LF, LLC. All Rights Reserved. ITEM #0611551, #0611550 LED MOTION ACTIVATED FLOOD LIGHT MODEL #SE1036-BP2-02LF0-U, SE1036-WH3-02LF0-U Français p. 10 Español
EE301 Lesson 14 Reading: 10.1-10.4, 10.11-10.12, 11.1-11.4 and 11.11-11.13
CAPACITORS AND INDUCTORS Learning Objectives EE301 Lesson 14 a. Define capacitance and state its symbol and unit of measurement. b. Predict the capacitance of a parallel plate capacitor. c. Analyze how
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
PRODUCT / APPLICATION INFORMATION
Abstract This paper will discuss performance life testing and stability testing used for self-regulating heating cables. It will show how the techniques were developed and evolved from the 970 s to the
1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
World Leader in HV Testing Technology
World Leader in HV Testing Technology Cable Fault Locators w/tdr Oil/Fluid Dielectric Testers Very Low Frequency AC Technology W/TD & PD Diagnostics Portable AC Hipots ---------------------------------
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of
Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas
Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables
OPTIONS FOR COMMERCIAL GAS DEVELOPMENT OF MARGINAL FIELDS
OPTIONS FOR COMMERCIAL GAS DEVELOPMENT OF MARGINAL FIELDS Gabriel N. Bujulu Principal Petroleum Engineer TANZANIA PETROLEUM DEVELOPMENT CORPORATION PRESENTATION OUTLINE! Introduction! Origin of Natural
COMBUSTION. In order to operate a heat engine we need a hot source together with a cold sink
COMBUSTION In order to operate a heat engine we need a hot source together with a cold sink Occasionally these occur together in nature eg:- geothermal sites or solar powered engines, but usually the heat
Condition Monitoring of equipment to improve quality of supply to customers by averting failures
Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract
Incipient Failure Detection in Power Transformers through Frequency Sweep Response
, October 24-26, 2012, San Francisco, USA Incipient Failure Detection in Power Transformers through Frequency Sweep Response Alberto Avalos Gonzalez, Jaime Cerda Jacobo, Servando Sanchez Ruíz Abstract
Analytical Report RF high voltage cable accessories market
Analytical Report RF high voltage cable accessories market High voltage cable accessory market of Russia, development trends Cable accessories are special devices aimed to connect cables mechanically and
High Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd
High Voltage Electrical Equipment Failure Diagnosis Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd High Voltage Electrical Equipment Failure Diagnosis Definition of High Voltage
Monitoring, Diagnostics, or Changing Condition?
PTPiREE Conference May 12 14 th 2015, Gdansk Poland Monitoring, Diagnostics, or Changing Condition? Mark Tostrud, PE Brian D. Sparling, SMIEEE Ty A. Foren, MBA Dynamic Ratings Inc. Globally, the fundamental
1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
ESCOM BY G.KALINDE SUBSTATIONS ENGINEER
ESCOM BY G.KALINDE SUBSTATIONS ENGINEER Balance Shareholder and Customer Interests Balance Short and Long Term Serviceability Understand trade-offs between Value and Risk Apply Asset Management Tools Build
LANDFILL GAS TO ENERGY- COMBINED ENGINE AND ORC-PROCESS
LANDFILL GAS TO ENERGY- COMBINED ENGINE AND ORC-PROCESS Dr Petri Kouvo Helsinki Region Environmental Services Authority THIRD INTERNATIONAL SYMPOSIUM ON ENERGY FROM BIOMASS AND WASTE Venice, Italy 8-11
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Optimization of Natural Gas Processing Plants Including Business Aspects
Page 1 of 12 Optimization of Natural Gas Processing Plants Including Business Aspects KEITH A. BULLIN, Bryan Research & Engineering, Inc., Bryan, Texas KENNETH R. HALL, Texas A&M University, College Station,
THE OLTC AS AN "OIL ISOLATED SYSTEM" IN THE TRANSFORMER & OIL ANALYSIS IN OLTC. I Hr. Dr. Hurm, Hr. Dr. Schübel I 26.06.2014 I
THE OLTC AS AN "OIL ISOLATED SYSTEM" IN THE TRANSFORMER & OIL ANALYSIS IN OLTC MR Hr. Dr. Hurm, MESSKO Hr. Dr. Schübel 26.06.2014 Seite 1 von 39 Table of contents Part 1: 1. Introduction: working principle
HOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY
Journal of ELECTRICAL ENGINEERING, VOL. 56, NO. 1-2, 25, 31 35 HOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY Motaheruddin Ahmed Mohammad
Keywords: polymer electrolyte membrane fuel cells; stack failure; gasket; indicators
Description of Gasket Failure in a 7 Cell PEMFC Stack Attila Husar, Maria Serra, Cristian Kunusch* Institut de Robòtica i Informàtica Industrial, Parc Tecnològic de Barcelona. Edifici U C. Llorens i Artigas,
Transformers: Basics, Maintenance, and Diagnostics
Basics, Maintenance, and Diagnostics U.S. Department of the Interior Bureau of Reclamation April 2005 Basics, Maintenance, and Diagnostics U.S. Department of the Interior Bureau of Reclamation Technical
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star