CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING, NETWORK SYSTEMS SECTION

Similar documents
Guidelines for ATS selection: How to choose the right transfer solution for your power application.

SPECIFICATION COG-2007

TABLE OF CONTENTS 1.0 INTRODUCTION PURPOSE DEVIATION INTERTIE PROTECTION REQUIREMENTS... 4

Bypass transfer switch mechanisms

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Report in respect of. Service Disruption on 9 April 2012

Grounding of AC generators and switching the neutral in emergency and standby power systems

SOUTH CAROLINA. Standard for Interconnecting Small Generation 100 kw or Less with Electric Power Systems (EPS) (Interconnection Standard)

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT NETWORK SYSTEMS SECTION

The following table shows approximate percentage wise the

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS

Portland General Electric Company P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES

Operational Control of the UKPN Low Voltage Distribution Network for EPN and LPN Regions

Load Dispatcher (Class Code 5223) Task List

Federal Wage System Job Grading Standards for Electric Power Controlling, Table of Contents

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

SERVICE CLASSIFICATION NO. 14-RA STANDBY SERVICE

Chapter 1. Network Structures

Scope of Restoration Plan

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

FIXED CHARGE: This is a cost that goes towards making the service available, including

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

A MODERN DISTRIBUTION MANAGEMENT SYSTEM FOR REGIONAL ELECTRICITY COMPANIES

Planned and Emergency Utility Outage Guidelines

How To Test A Power Switch On A Power Supply

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

N.J.A.C. 14:8-4 NET METERING FOR CLASS I RENEWABLE ENERGY SYSTEMS

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

(2) Words and expressions used and not defined in these regulations but defined in the Act shall have the meaning assigned to them in the Act.

Dakota Energy Cooperative, Inc. POLICY STATEMENT

Unified requirements for systems with voltages above 1 kv up to 15 kv

Implementation of a New Substation Restoration System Using Protective Relays and a Logic Processor

Critical-Power Automatic Transfer Systems Design and Application

S&C BankGuard PLUS Control

Technical Requirements. For Generating Facilities Interconnecting. To The Distribution System. Salt River Project

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

GPD 506/P5 Start-up Procedure and Checklist

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Understanding Emergency Power Off (EPO)

Eaton Automatic Transfer Switches

GTEC transfer switch open transition

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SERVICE CLASSIFICATION NO. 14-RA STANDBY SERVICE

Increased power protection with parallel UPS configurations

SWITCHGEAR. EGP Switchgear

IESO Supply Deliverability Guidelines

Guide to the electrical parameter classifications of IEC and IEC safety standards

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2. Detroit Ann Arbor Mt. Clemens Port Huron

When power interruptions happen.

Storm Ready. 3 Gulf Power Ready for the storm. 4 Be prepared, be safe. 5 Getting the lights back on. 6 Damage to your home s service connection

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

REQUIREMENTS FOR CUSTOMER-OWNED PRIMARY SERVICES SUPPLIED AT 4 kv TO 35 kv PRIMARY GUIDE

Transfer Equipment Controls

Study Guide for Substation Operator

The Application of Circuit Breakers to Reduce Downtime in Datacentres

NTUA GUIDELINES FOR DESIGNING AN ELECTRICAL POWER DISTRIBUTION SYSTEM FOR NEW DEVELOPMENTS

Colorado Springs Utilities Interconnection Guidelines For Transmission to Transmission Interconnections Version 1 12/04/2007

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

DISTRIBUTION OPERATIONS AND MAINTENANCE

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application

New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System

ELECTRICAL: AUTOMATIC TRANSFER SWITCHES

Type SA-1 Generator Differential Relay

Fundamentals of Power

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

Planned, Limited Notice and Emergency Outage Guidelines

Marysville Data Centre Incident Review Final Report

ABB PSPS Erich Steinmann; Generator control-2013

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

PROJECT NO ORDER ADOPTING AMENDMENTS TO AS APPROVED AT THE OCTOBER 12, 2012 OPEN MEETING

Safeguarding Your Plant Automation Programs with Change Management

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Future grid infrastructure Field tests of LVDC distribution

How To Operate A Gec Transfer Switch Open Transition Amp Power Supply

Safety Requirements Specification Guideline

Switchgear and Metal-Enclosed Bus

CAPACITOR BANK TESTING SWP

Engineering innovation

Guidelines for Generation, Tie-Line, and Substation Interconnections

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

The Application and Benefits of Multi-phase Auto-reclosing

RELIABILITY PLANNING CRITERIA

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering

CURTAILABLE RATE PROGRAM FOR INDIVIDUAL CUSTOMER LOADS

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

SDG&E Electric Distribution System Interconnection Handbook. <Revised as of 10/21/2015>

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering

Transcription:

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING, NETWORK SYSTEMS SECTION SPECIFICATION EO-2134 REVISION 2 DECEMBER, 2012 CLOSED TRANSITION TRANSFER FROM AND TO CON EDISON S SUPPLY FILE: APPLICATION AND DESIGN MANUAL NO. 4 TARGET AUDIENCE NESC REFERENCE 2012 ENERGY SERVICES, ELECTRIC OPERATIONS REGIONAL ENGINEERING DISTRIBUTION ENGINEERING 2005-2012 Consolidated Edison Co. of New York, Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution 1/14 Engineering Intranet Site Distribution Engineering or http://distribution for the current version prior to use.

TABLE OF CONTENTS 1.0 PURPOSE 3 2.0 AREAS APPLICABLE 3 3.0 APPROVED SYSTEMS 3 4.0 CLOSED-TRANSITION TRANSFER SWITCH. 3 5.0 CTTS CHARACTERISTICS. 4 6.0 USE OF CTTS UNDER SPECIAL CONDITIONS 5 7.0 THE BYPASS-ISOLATION SWITCH.. 6 8.0 SHORT CIRCUIT DUTY... 6 9.0 CIRCUIT BREAKERS.. 6 10.0 CON EDISON'S APPROVAL OF CUSTOMER'S INSTALLATION 6 11.0 OPERATING AND MAINTENANCE REQUIREMENTS 7 12.0 ATTACHMENTS 8 2/10

CLOSED TRANSITION TRANSFER FROM AND TO CON EDISON S SUPPLY 1.0 PURPOSE This specification covers the requirements and characteristics of the closedtransition transfer (CTT) of the customer s load from Con Edison s supply to the customer s alternate source of power supply and vice versa. In a CTT, both incoming and outgoing sources of power are momentarily paralleled together thus permitting the automatic transfer of load from one supply to another supply and vice versa without power interruptions. The momentary time that the power sources are in parallel is called the interconnection time interval, which for the purpose of this specification, it is limited to 250 ms (15 cycles) or less. 2.0 AREAS APPLICABLE This specification applies to all regions. 3.0 APPROVED SYSTEMS This specification covers the CTT of customer s load from Con Edison's supply to customer's alternate source of generation, and vice versa, requiring an interconnection time interval of 250 ms (15 cycles) or less to accomplish the transfer, and using either (a) automatic closed-transition transfer switches (CTTS) rated 600VAC class, or (b) circuit breakers rated from 4.16kV up to 33kV. Customers with interconnection time intervals longer than 250 ms shall follow the requirements of Specification EO-2115, Handbook of General Requirements for Electrical Service To Dispersed Generation Customers. 4.0 CLOSED-TRANSITION TRANSFER SWITCH A CTTS is a device with overlapping main contacts that permit the automatic transfer of load from one supply to another supply and vice versa without power interruptions. 4.1 After being manually initiated, the switch logic shall be capable of determining if the voltage and frequency as well as the phase relationship between the two sources, are within acceptable limits. If all conditions are correct, the switch contacts will be allowed to make an overlap (make-before-break) transfer. This temporary parallel operation of both sources avoids the 3/10

momentary interruption of the load that occurs with traditional break-beforemake transfer switches. 4.2 If the Con Edison supply has failed, a CTTS shall automatically revert to open transition transfer (break-before-make) operation. A CTTS.must be capable of automatically transferring a customer load from Con Edison s supply to a stable alternate supply, in the event of failure of the Con Edison s supply, and under manual control returning the load to the Con Edison s supply in a closed transition transfer operation after the Con Edison s supply has been restored and has become stable. Voltage and frequency must be restored to normal for a minimum time interval of five minutes before returning the load to the Con Edison s supply. 4.3 If its automatic operation malfunctions, a CTTS must also be capable of manual transfer between sources in an open transition mode of operation. 5.0 CTTS CHARACTERISTICS 5.1 Construction, ratings and performance of automatic CTTS shall be in accordance with ANSI/UL 1008, Automatic Transfer Switches, Paragraph 19.9 of the March 15, 1989, edition. 5.2 The CTTS shall be installed in accordance with all pertinent national, state and local codes and standards. 5.3 A CTTS shall be rated up to 600VAC, 30 through to 4,000 amperes, three-phase, load break, with two mechanically held switches along with sensing and control devices and circuits, as shown in Figure No. 1. The customer load is permanently connected between the two main contacts of the switch. The customer's emergency or stand-by generator, and Con Edison supply are connected to stationary contacts at opposite sides of the switches. Blades of all three phases in both main contacts shall move simultaneously when transferring load to either the Con Edison or the customer emergency/stand-by generator supply. 5.4 The CTTS shall transfer the load between sources using a maximum parallel time that will not exceed 250 ms. 4/10

5.5 The CTTS shall have failure to synchronize and extended parallel time protection to prevent abnormal operation. The protection shall, as a minimum, initiate an alarm, automatically open the emergency or normal main contacts of the CTTS whichever closed last, and lock itself out till is manually reset. It may also be required, at the discretion of Con Edison, to have separate contacts available to shunt trip external circuit breakers. 6.0 USE OF CTTS UNDER SPECIAL CONDITIONS For those cases when paralleling an emergency/stand-by generator with the Con Edison s distribution system would cause the fault duty to exceed the circuit breaker interrupting rating at Con Edison s area substations, closed-transition transfer will be permitted only if all the following requirements are met: 6.1 The interconnection time interval will not exceed 250 ms. 6.2 The additional fault current contribution from the emergency/stand-by generator does not cause the Area Substation circuit breakers to go beyond their Close and Latch momentary rating. 6.3 The CTTS extended parallel time protection to prevent abnormal operation shall initiate an alarm, automatically open the emergency or normal main contacts of the CTTS whichever closed last, and lock itself out till is manually reset. It shall also have separate contacts available to shunt trip the adjacent circuit breakers located on the Emergency side of the CTTS. 6.4 The customer must be a participant in Con Edison s load management program, or 6.5 The customer must be a participant in the New York ISO s program for load curtailment, or 6.6 Con Edison has classified the customer as being sensitive in nature, e.g., hospitals, nursing homes, airports, military facilities, police and fire stations, emergency services, processing plants, data centers, telecommunication providers, financial institutions, etc. With respect to commercial customers, load will generally be considered to be sensitive if momentary interruption of electrical service results: (a) in the shut-down of a production line in the case of processing plants, or (b) in a significant disruption of service to on-line 5/10

telecommunications customers, or (c) in disruption of on-line bulk financial transactions. 7.0 THE BYPASS-ISOLATION SWITCH 7.1 An optional, manually operated, three-phase, double throw, load break before make bypass-isolation switch can be used with each CTTS to provide means of bypassing and isolating the CTTS, thus, permitting its inspection, testing, maintenance and repair (See Figure No. 1) without any interruption of the power to the load. 7.2 A mechanical interlock shall be provided between the CTTS and the bypass switch to prevent the operation of the CTTS whenever the bypass switch is used. 8.0 SHORT CIRCUIT DUTY The CTTS and its bypass-isolation switch, if provided, shall have the ability to withstand the available fault current at the location where the switches are installed 9.0 CIRCUIT BREAKERS 9.1 For high tension applications where the utilization voltage is from 4.16kV up to 33kV, CTT shall be accomplished using two or more circuit breakers arrange in such a manner that overlapping circuit breaker contacts permit the automatic transfer of load from one supply to another supply and vise versa without power interruptions. Control wiring and protective relaying shall be provided, and so arranged, as to mimic the operating and performance characteristics of a CTTS. A CTT using circuit breakers shall meet all the special requirements and conditions found in Section 6.0 of this specification. 9.2 High Tension customers shall follow the requirements of Specification EO- 2022, General Specification For High Tension Service. 10.0 CON EDISON'S APPROVAL OF CUSTOMER'S INSTALLATION Before the customer's emergency/stand-by equipment is installed, the customer shall submit to Con Edison, for its approval, the following documents and information: 6/10

10.1 A one-line electrical diagram, stamped by a Professional Engineer licensed in the State of New York, showing the proposed installation, including both the existing distribution service, the emergency/stand-by generators and nameplate data, all interconnecting CTT equipment and data, and all protective, instrumentation, and control equipment. 10.2 Manufacturer s documentation for the CTTS (illustrating the closed-transition transfer function and the maximum parallel operating time), circuit breakers, and protective devices. 10.3 Short circuit studies to show that the CTTS, circuit breakers, etc. are rated to interrupt/withstand the available short circuit currents at the point of interconnection. 10.4 A description of the system operating procedures under various conditions like: 10.4.1 Normal operation 10.4.2 Periodic testing of load transfer 10.4.3 Load transfer under Con Edison or ISO programs 10.4.4 Interruption of Con Edison s service 10.4.5 Announced Con Edison voltage reduction 10.4.6 Announced Con Edison outage 10.5 A written statement signed by the customer, on the Customer s letterhead, stating that the facilities will be used, operated and maintained in accordance with the requirements of this specification. 10.6 The customer shall provide advance written notice to Con Edison of any proposed change in electrical equipment associated with the CTT, and Con Edison shall promptly inform the Customer whether the contemplated changes are acceptable, consistent with the goal of conducting a safe, reliable and efficient closed-transition transfer. 11.0 OPERATING AND MAINTENANCE REQUIREMENTS 11.1 The customer must notify Con Edison s District Operator prior to making a 7/10

load transfer from the customer s generation to Con Edison s supply with the understanding that Con Edison has the right to postpone the request for transfer until system conditions are more favorable. It is understood that Con Edison will notify the customer prior to performing any switching on the distribution system that may interrupt normal service to the customer. 11.2 The customer must grant Con Edison full access to the generating and transfer equipment, including test records and operating logs. The customer must be able to exhibit, at Con Edison s request, at the time of installation and at any time thereafter, that the equipment functions properly to transfer the load in the specified time interval. 11.3 The customer should be aware of the fact that the closed-transition transfer or soft transfer imposes additional electrical stress on the distribution system. Con Edison therefore retains the right to limit transfers and inspect the transfer equipment for the sake of safeguarding the reliability and safety of the distribution system that supplies other Con Edison customers in the vicinity. 12.0 ATTACHMENTS 12.1 Figure 1, CLOSED TRANSITION TRANSFER SWITCH 8/10

. Elie A. Chebli (Signature on File) Elie A. Chebli Department Manager Network Systems Distribution Engineering Department Distribution Engineering D. Sammon/DPSa Revision 2 File: General review and update. APPLICATION AND DESIGN MANUAL No. 4 Revision : 12/2016 9/10

FIGURE 1 CLOSED TRANSITION TRANSFER SWITCH 2005-2012 Consolidated Edison Co. of New York, Paper copies of procedures and instructions are uncontrolled and therefore may be outdated. Please consult Distribution 10/10 Engineering Intranet Site Distribution Engineering or http://distribution for the current version prior to use.