Harmonic Mitigation, Power Factor Correction & Energy Saving with Proper Transformer & Phase Shifting Techniques



Similar documents
POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Product Data Bulletin

Power System Harmonics

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

Three phase circuits

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Neutral Currents in Three Phase Wye Systems

Harmonics in your electrical system

Line Reactors and AC Drives

Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications

Specifying a Variable Frequency Drive s

Harmonic Distortion and Variable Frequency Drives

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

How To Improve Power Quality

HARMONICS AND HOW THEY RELATE TO POWER FACTOR. W. Mack Grady The University of Texas at Austin Austin, Texas 78712

Application Guide. Power Factor Correction (PFC) Basics

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

415V DISTRIBUTION FOR GREEN DATA CENTERS

Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Meeting Harmonic Limits on Marine Vessels

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

415V DISTRIBUTION FOR GREEN DATA CENTERS

Survey of Harmonics Measurements in Electrical Distribution Systems

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a

How To Improve Power Quality

APPLICATION OF IEEE STD HARMONIC LIMITS

The full wave rectifier consists of two diodes and a resister as shown in Figure

Single-Stage High Power Factor Flyback for LED Lighting

FREQUENCY CONTROLLED AC MOTOR DRIVE

Analysis of AC-DC Converter Based on Power Factor and THD

EET272 Worksheet Week 9

98% Efficient Single-Stage AC/DC Converter Topologies

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

ECONOMIC AND ELECTRICAL BENEFITS OF HARMONIC REDUCTION METHODS IN COMMERCIAL FACILITIES

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC

Considering the effects of UPS operation with leading power factor loads

(3 )Three Phase Alternating Voltage and Current

PHASE CONVERSION TECHNOLOGY OVERVIEW

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Diode Applications. by Kenneth A. Kuhn Sept. 1, This note illustrates some common applications of diodes.

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Line Current Characteristics of Three-Phase Uncontrolled Rectifiers Under Line Voltage Unbalance Condition

Introduction. Harmonics and IEEE 519 Page 1 of 19

Chapter 4: Power Factor Correction

Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

Application Note AN- 1095

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

DATA CENTER POWER SYSTEM HARMONICS: AN OVERVIEW OF EFFECTS ON DATA CENTER EFFICIENCY AND RELIABILITY

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research

Variable Frequency Drives and Energy Savings

TRANSFORMER: THREE PHASE

PIEZO FILTERS INTRODUCTION

Pulse Width Modulated (PWM)

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

DIODE CIRCUITS LABORATORY. Fig. 8.1a Fig 8.1b

Standards of Power Quality with reference to the Code of Practice for Energy Efficiency of Electrical Installations

The following table shows approximate percentage wise the

Properties of electrical signals

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Paralleling Power Sources Which Share a Common Neutral

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

WHITE PAPER GROUND FAULT. Lowering the Limits for Ground Fault Detection

The Different Types of UPS Systems

Three-phase AC circuits

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

POWER FACTOR CORRECTION

The Different Types of UPS Systems

Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit

The Different Types of UPS Systems

INDUCTION REGULATOR. Objective:

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Simulation of Ungrounded Shipboard Power Systems in PSpice

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

Survey of Harmonics Measurements in Electrical Distribution Systems

Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Control of a Three Phase Induction Motor using Single Phase Supply

Principles of Adjustable Frequency Drives

Chapter 4. LLC Resonant Converter

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

Rectifier circuits & DC power supplies

Electricity Meter in the age of Photovoltaic

Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007

Pulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

LABORATORY 10 TIME AVERAGES, RMS VALUES AND THE BRIDGE RECTIFIER. Bridge Rectifier

Typical Data Requirements Data Required for Power System Evaluation

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

Transcription:

Harmonic Mitigation, Power Factor Correction & Energy Saving with Proper Transformer & Phase Shifting Techniques Abstract Harmonics in electrical distribution systems are created from a number of sources and produce a variety of undesirable side effects. It is therefore important to understand all solutions that are available. Phase shifting will be reviewed as one concept for solving certain types of problems related to power quality. Both theoretical concepts and a case study are presented. Index Terms Harmonic Mitigation, Power Factor Correction, Phase Shifting I. INTRODUCTION It is well known that harmonic currents are present in modern electrical distribution systems caused from non-linear loads, such as variable frequency drives, lighting and computers. Harmonics can cause a variety of problems ranging from poor power factor and motor failures, to overloaded transformers and conductors. One of the most effective ways to eliminate harmonics is to use a technique known as phase shifting. The concept of phase shifting as a harmonic mitigation technique is not as well understood as other methods. II. PHASE SHIFTING AND HARMONICS Phase shifting involves separating the electrical supply into two or more outputs; each output being phase shifted with respect to each other with an appropriate angle for the harmonic pairs to be eliminated. The concept is to displace the harmonic current pairs in order to bring each to a 180 phase shift so that they cancel each other out. Positive-sequence currents will act against negative-sequence currents, whereas zero-sequence currents act against each other in a three-phase system. Triplen harmonics are zero-sequence vectors; 5 th, 11 th and 17 th harmonics are negative-sequence vectors, and 7 th, 13 th and 19 th harmonics are positive-sequence vectors. Hence, an angular displacement of: 60 is required between two three phase outputs to cancel the 3 rd harmonic currents 30 is required between two three phase outputs to attenuate the 5 th and 7 th harmonic current pairs 15 is required between two three phase outputs to cancel the 11 th and 13 th harmonic current pairs For instance, in the case of two 6-pulse variable frequency drives of similar rating, installing a delta-wye transformer (30 with respect to the primary) on one drive, and a delta-delta transformer (0 with respect to the primary) on the other drive, gives an angular displacement of 30 between the two outputs, providing the equivalent of a 12-pulse system. On the common supply of both transformers on the primary, phase shifting between the systems will reduce the 5 th and 7 th harmonic currents. An angular displacement of 15 between outputs provides the equivalent of a 24-pulse system, but requires four 6-pulse loads. The approach of phase-shifting non-linear loads can be used to reduce the effects of selected harmonics. Fundamental and 5th harmonic The figure above shows a typical 60 Hz sinusoidal wave, with its 5 th harmonic (at 300 Hz) superimposed on it.

III. CURRENT HARMONICS, VOLTAGE DISTORTION AND TRANSFORMERS The mathematical equation V = I x Z shows that any current flowing within an impedance generates voltage at the impedance terminals. This equation also applies to harmonic currents flowing through the electrical system. Therefore, the higher the harmonic current levels, the greater the resulting harmonic voltages, thus creating distortion in the electrical system voltage. As transformers also have impedance, voltage distortion appears at the transformer s secondary terminals when harmonic currents flow through them. To reduce voltage distortion, two factors can be modified: the level of harmonic currents and transformer impedance. IV. PHASE-SHIFTING TRANSFORMERS DESIGNED FOR NON-LINEAR LOADS The level of harmonic currents may be reduced by using phase-shifting techniques and low impedance plays a crucial role in reducing voltage distortion. New low impedance phase-shifting transformers have been designed to allow the treatment of harmonic currents while providing a path of low impedance. Moreover, these transformers have been designed to withstand the additional overheating caused by harmonic currents and therefore are K-rated. The quality and reliability of the electrical system can be considerably improved through the use of a single piece of equipment. Below are a few examples of such transformers along with a description of their respective use. A. Delta-Zigzag Transformer (0 or -30 primary-secondary angular displacement) The primary of this transformer has a delta connection and its secondary has a zigzag connection. Although there is only one secondary three phase output, the electromagnetic effect of its secondary winding with a zigzag connection ends up cancelling the 3 rd, 9 th and 15 th (triplen) harmonic currents. Transformer features include: A capacity for handling non-linear loads Low impedance cancellation of the 3 rd, 9 th and 15 th harmonic currents (zigzag-connected secondary) A reduction in voltage distortion (3 rd harmonic voltage reduced by low zero-sequence impedance) When two transformers with a delta-zigzag connection (-30 and 0 ) are used for phase-shifting, the 3 rd harmonic currents are cancelled due to the secondary windings with a zigzag connection and the 5 th and 7 th harmonic currents are cancelled in the electrical supply common to both transformers due to the 30 phase shift. If a single delta-zigzag transformer (0 ) is used in a system made up of delta-wye transformers (-30 ), the 5 th and 7 th harmonic currents originating from the delta-zigzag transformer (0 ) will attempt to cancel the 5 th and 7 th harmonic currents originating from the delta-wye transformer (-30 ) already present. This reduces the 5 th and 7 th harmonics in the system with the actual reduction dependent on how similar the secondary loads are in magnitude. B. Double-Output Delta-Zigzag Transformer (0 and -30 primary-secondary angular displacement) The primary of the transformer has a delta connection and its secondary has a double-output zigzag connection. Although there is only a 30 angular displacement, the electromagnetic effect of its secondary windings with a zigzag connection ends up cancelling the 3 rd, 9 th and 15 th harmonic currents. Transformer features include: A capacity for handling non-linear loads Low impedance cancellation of the 3 rd, 9 th and 15 th harmonic currents (zigzag-connected secondary) Attenuations of the 5 th and 7 th harmonic currents (30 phase shift between the outputs) A reduction in voltage distortion (3 rd harmonic voltage reduced by low zero-sequence impedance) If two of these transformers are used, with the primaries of each phase shifted 15 with respect to one another, then cancellation of harmonics up to the 19 th are achievable. Page 2 of 6

V. POWER FACTOR AND HARMONICS The power factor is the ratio between the active power (W) and the apparent power (VA). Electricity supplied by Utilities in North America has a sinusoidal voltage wave of 60 Hz. If the current and voltage curves are not aligned, the efficiency of the electrical system is diminished and the apparent power exceeds the active or true power. In an inductive system the voltage curve leads the current curve. In a capacitive system the current curve leads the voltage curve. Historically, when speaking of power factor, we were actually referring to the displacement factor only. Distortion factor Displacement factor As a result of the increase in non-linear loads in the past few years, we have had to take into account the effect of harmonics in electrical systems and modify certain mathematical equations and include the effect of the distortion factor. Power factor is now defined as follows: PF tot = F d x F dist where PF tot = total power factor F d (displacement factor) as defined above F dist (distortion factor) = fundamental current rms current This new term, distortion factor, is defined as being the fundamental current divided by the RMS current (current measured with a true RMS clamp-on ammeter). There are two elements which combine to reduce total power factor the inductive or capacitive loads which affect the displacement factor and the harmonic currents of the non-linear loads which affect the distortion factor. Reducing the level of harmonic currents in a system therefore improves the system s total power factor. As Utilities measure the total power factor, we have to check the value of both displacement factor and distortion factor if total power factor is to be corrected. The good news is that companies that manufacture measuring instruments now provide the value of both of these factors or at least make it possible to calculate them. This will help us understand the cause of the reduction in power factor and choose the best way to improve it. VI. CAPACITORS Capacitors have been commonly used as harmonic current filters or to correct the power factor in industrial electrical installations. This correction generally assumes we are correcting the displacement factor and that there is little, if any, distortion factor. If a system has not been properly designed or if certain modifications were made without taking existing parameters into account, capacitor impedance nears the inductive impedance of the load at a certain harmonic frequency and creates resonance in the system. Major voltage spikes and distortions will then occur in the system, damaging sensitive electrical equipment and shortening the capacitors lifespan. It is therefore very important to consult electrical system experts when applying this technology. VII. CASE STUDY The subject case study featured the replacement of 84 existing motors with more energy efficient units and the installation of 33 variable frequency drives (6-pulse PWM type). Approximately 1,000 horsepower of motor load was retrofitted, connected to four different motor control centers. Page 3 of 6

Because of the number of s concentrated in the penthouse mechanical room, it was decided to use phase shifting to control the harmonics generated by the new s. Filtering (either active or passive type) would be more expensive and using line reactors would not have met IEEE 519 limits in this application. Similar loads on four busses were achieved by reconfiguring the main motor control center bussing, allowing these loads to be selectively connected to the secondary s of two individual double-output zigzag transformers. The secondary s of the transformers are phase shifted 30 with respect to each other, while the primaries are phase shifted 15, causing all harmonics up to the 19 th to be reduced. In practice, because the loads on each output are not identical, complete harmonic elimination cannot be achieved. Regardless, the test results were impressive, with a 38% reduction in power demand being achieved from the retrofit measures with little degradation in total harmonic distortion. Avg. 90A Per Phase 0 Pf.95 THDi 9.1% THDv 1.36% 38% less Power Demand -30-15 Avg. THDi 45% Per Phase Avg. THDv 4% Per Phase Avg. Total Pf 0.86-45 Two Double Output 300 kva Phase Shifting Transformers Phase Shifting Although a significant amount of non-linear current was introduced into the building distribution system, harmonic voltage and current distortion limits are maintained within IEEE 519 guidelines, based on an I SC /I L of 58.6 at the point of common coupling. The current waveform shots shown below were taken on a single phase of one of the two transformer secondary legs and on a primary leg, respectively. Note the improvement in the wave shape on the primary side relative to the secondary side, which is the input side of the s. The two secondary loads averaged 86.55 A and 92.80 A, with corresponding current THD of 39.62 and 49.31, and voltage THD of 3.44 and 5.42. The resultant primary averaged 164.0 A, with current THD of 9.11 and voltage THD of 1.36. 200 100 Amps 0. 2.08 4.16 6.25 8.33 10.4112.4914.57-100 -200 msec 500 250 Amps 0. 2.08 4.17 6.25 8.34 10.4212.5114.59-250 -500 msec Figure 1 Secondary Figure 2 Secondary Page 4 of 6

The Fourier transforms shown below are another method used to indicate the amount of harmonic current in a particular waveform and shows the relative amount of current that exists at each frequency from the fundamental on the left (60 Hz) up to the 31 st harmonic (1860 Hz). Figure 3 Secondary Amps 80 60 40 20 0 DC1 2 3 4 5 6 7 8 9 10111213141516171819202122232425262728293031 Harmonic Figure 4 Primary 200 Amps 150 100 50 0 DC 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 Harmonic The first chart (secondary side) clearly shows that there is a significant amount of 5 th, 7 th, 11 th and 13 th order harmonics, typical of a harmonic signature. The second chart (primary side) shows how the phase shifting transformer has essentially removed all higher order harmonics, with only a minimal amount of 5 th order harmonic current remaining. The K-factor of the load ranged from 6.10 to 8.65 depending upon the phase that was measured, indicating the choice of a K-13 rating on the phase shifting transformers as appropriate for this application. With regard to power factor improvement, the total power factor on the transformer secondary s averaged 0.86 (corresponding displacement factor was 0.96). On the primary side, the total power factor was measured to be 0.95 (displacement factor was unchanged at 0.96) which indicates a significant total power factor improvement due to the effect of the phase shifting transformer, reducing harmonics and consequently the distortion factor. Note that displacement factor is relatively good at 0.96 because s inherently provide power factor correction on motor loads. VIII. CONCLUSION A thorough understanding of electrical system-related problems will help us implement better solutions. It is estimated that 70% of electrical loads are non-linear. The deterioration of total power factor will therefore mainly be caused by harmonic currents which affect the distortion factor. To find proper techniques for correcting the total power factor and reduce harmonic currents in an electrical distribution system, the following must be considered: Determine the components making up the total power factor Correct the displacement factor at the source (by adding capacitors or s) Correct the distortion factor at the source (by reducing harmonic currents) Page 5 of 6

Case studies show that phase shifting does work as promoted, can mitigate harmonics very significantly, and improve total power factor. Their ability to control harmonics is predicated on how closely matched the individual secondary loads are on the transformer(s). IX. REFERENCES Additional information may be found at the following sources: [1] IEEE Std 519-1992, IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, New York, NY: IEEE. [2] IEEE Std 1100-1999, IEEE Recommended Practice for Powering and Grounding Electronic Equipment, New York, NY: IEEE. [3] Paice, Derek A., Power Electronic Converter Harmonics: Multipulse Methods for Clean Power, New York, NY: IEEE. Copyright Material IEEE Paper No. PCIC-2002-12 Page 6 of 6