ACM8 Series UL Listed Sub-Assembly Access Power Controllers Installation Guide



Similar documents
SECURITY / ACCESS / FIRE / SURVEILLANCE

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

HM-W536 Install Guide

Video Surveillance UPS. Installation Guide

15370 Barranca Parkway Irvine, CA Edge. Connections APPLICATION NOTE. AN0108, Rev B HID Global Corporation. All rights reserved.

AC-115 Compact Networked Single Door Controller. Installation and User Manual

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers

PAC1 Door Access Controller

INSTALLATION INSTRUCTIONS

INSTALLATION/PROGRAMMING INSTRUCTIONS 928 ENTRYCHECK

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

Operating Instructions. UL325 Compliant Non-monitored

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

conventional system operation

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

EQUIPMENT SPECIFICATIONS

FIREDEX Conventional Fire Panels

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.

IEI 232e Standalone TM Keypad Installation/ Programming Manual

INSTALLATION & SERVICE MANUAL. Display Panel

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK

SYSTEM 4C. C R H Electronics Design

MODEL DK-26 DIGITAL KEYPAD SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

UNC500 HARDWARE MANUAL. new generation building security

Understanding Emergency Power Off (EPO)

System components portfolio overview. Power supplies, electromagnetic locks, electric strikes and system accessories

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

ACTIVE 5 ENGINEERING MANUAL

INTELLIGENT CONTROL MODULE SA-2000-II HARDWARE MANUAL. Access Technologies International, Inc.

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Button 1 Button 2. Button 3 Button 4. Programmed Remote Transmitter. Button Function Condition

Fire Pump Controllers Remote Alarm Panels

Troubleshooting and Diagnostics

KCIEN KCIENSBP. Heavy Duty Stainless Steel Illuminated Keypads INSTALLATION MANUAL. Range: DIGICODE (Stand-Alone Keypad)

SECTION DETECTION AND ALARM

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

POINTS POSITION INDICATOR PPI4

4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES

Using your LED Plus keypad

VEHICLE THEFT/SECURITY SYSTEMS

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

Points Position Indicator (PPI1) for Points Motors with Common Ground

TC-9102 Series Surface Mount Temperature Controllers

Secure Keypads for access control

Advantium 2 Plus Alarm

ETZGAR CONVEYOR COMPANY Controls Section v12.05

SYSTEM 45. C R H Electronics Design

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

Configuring Alarms & Relays in the Enhanced Transformer Advantage

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

Digital Keypad Use s Manual

3BASIC RELAY INSTRUCTIONS

Analog Control Wiring & Adjustment Manual for Gyro Tech Swing Door Operators

Contractors Guide Central Inverter System Installation

Integra32. Integrated Alarm Monitoring and Access Control HARDWARE MANUAL

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

Water Leak Detection System

MidNite Solar E-Panels Explained

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

User Guide. Model Insulation Tester / Megohmmeter

Applied Electronics. Commercial Dimming System UPDATE NOTICE

IP Box Camera ACM Ver Hardware User s Manual

Application Technique. Safety Function: Magnetic Door Switch Monitoring

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

PUSH BUTTON START INSTALLATION MANUAL

Modular I/O System Analog and Digital Interface Modules

TS93 EMR T/PT/TDE. Surface applied door closer

TSn SERIES Surge Protective Device

PK-01. Standalone door control module. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

BERMAD Fire Protection

Digi-Motor Installation Guide

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings

SECURITY SYSTEM ADP-CAN

PRO PLM Installation Instructions

AutoRanging Digital MultiMeter

Multifunction devices

16/32 Channel 1U Rack Mount CCTV Power Supply

1 Contactless Smartcard Reader Setup

G3 Series PROFIBUS DP Technical Manual

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

TS510 & TS500. Installation & User Guide. Compatible Equipment

Model 201 Wiegand Touchpad Reader Installation Guide

Combi B Alarm box. Mounting instructions

Self Monitoring Power Supply (BPSM)

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

8900 EMR (WITH DETECTOR)

VARIO PROX CARD READER INSTALLATION MANUAL

e-ask electronic Access Security Keyless-entry

INSTALLATION MANUAL PC2525. Version 1.1

Transcription:

ACM8 Series UL Listed Sub-Assembly Access Power Controllers Installation Guide Models Include: ACM8 - Eight (8) Fuse Protected Outputs ACM8CB - Eight (8) PTC Protected Outputs SECURITY Rev. 042811 More than just power. TM

Overview: These units are UL Listed Sub-Assembly multi-output Access Power Controllers which converts one (1) 12 to 24 volt DC input into eight (8) independently controlled fused or PTC protected outputs. These power outputs can be converted to dry form C contacts (fused models only). Outputs are activated by an open collector sink or normally open [NO] dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. The units will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. Units are designed to be powered by one common power source which will provide power for both the board operation and locking devices, or two (2) totally independent power sources, one (1) providing power for board operation and the other for lock / accessory power. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs. ACM8 & ACM8CB Series Configuration Reference Chart: Altronix Model Number Number of Outputs Fuse Protected Outputs PTC Protected Outputs Output Ratings Class 2 Rated Power Limited ACM8 8 x - 2.5 amp * ACM8CB 8 - x 2 amp x Agency Listings SECURITY Sub-Assembly UL Listings and File Numbers UL File # BP6714 UL Listed for Access Control System Units (UL 294). Signal Equipment Evaluated to CSA Standard C22.2 No.205-M1983 Specifications: 12 to 24 volt DC operation (setting not required). (0.5 amp @ 12volt, 0.3 amp @ 24volt current consumption with all relays energized). Power supply input options: a) One (1) common power input (board and lock power). b) Two (2) isolated power inputs (one (1) for board power and one (1) for lock/hardware power). Eight (8) Access Control System trigger inputs: a) Eight (8) normally open (NO) inputs. b) Eight (8) open collector sink inputs. c) Any combination of the above. Eight (8) independently controlled outputs: a) Eight (8) Fail-Safe and/or Fail-Secure power outputs. b) Eight (8) dry form C 5 amp rated relay outputs. c) Any combination of the above. Eight (8) auxiliary power outputs (unswitched). Output ratings: - Fuses are rated 3.5 amp each. - PTCs are rated 2 amp each. Main fuse is rated at 10 amp. Note: Total output current is determined by the power supply, not to exceed a maximum of 10 amp total. Red LEDs indicate outputs are triggered (relays energized). Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs. Fire Alarm disconnect input options: a) Normally open [NO] or normally closed [NC] dry contact input. b) Polarity reversal input from FACP signaling circuit. FACP output relay (form C contact rated @ 1 amp 28VDC not evaluated by UL). Green LED indicates when FACP disconnect is triggered. Removable terminal blocks facilitate ease of installation. Board Dimensions (approximate): 8 L x 4.5 W x 1.25 H - 2 - ACM8/CB Sub-Assembly

Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only and should be installed by qualified personnel. 1. Refer to Sub Assembly Installation Instruction for mounting Rev. MS042511. Carefully review: Typical Application Diagram (pg. 4) Terminal Identification Table (pg. 5) LED Diagnostics (pg. 5) Hook-up Diagrams (pg. 6) 2. Power supply input: The units can be powered with one (1) power supply which will provide power for both board operation and the locking devices or two (2) separate power supplies, one (1) to provide power for the board operation and the other to provide power for the locking devices and/or access control hardware. Note: The input power can be 12 to 24 volts DC (.5 amp @ 12 volt,.3 amp @ 24 volt current consumption with all relays energized). (a) Single power supply input: If the unit and the locking devices are to be powered using a single power supply, connect the output (12 to 24 volts DC) to the terminals marked [- Control +]. (b) Dual power supply inputs (Fig. 1, pg. 4): When the use of two power supplies is desired, jumpers J1 and J2 (located to the left of the power/control terminals) must be cut. Connect power for the unit to the terminals marked [- Control +] and connect power for the locking devices to the terminals marked [- Power +]. Note: When using DC power supplies polarity must be observed. When using AC power supplies polarity need not be observed. Note: For UL compliance the power supplies must be UL Listed for Access Control Systems and accessories. 3. Output options (Fig. 1, pg. 4): The ACM8 will provide either eight (8) switched power outputs, eight (8) dry form C outputs, or any combination of of both switched power and form C outputs, plus eight (8) unswitched auxiliary power outputs. The ACM8CB will provide eight (8) switched power outputs or eight (8) unswitched auxiliary power outputs. (a) Switched Power outputs: Connect the negative (-) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal marked [NO]. (b) Form C outputs: When form C outputs are desired the corresponding output fuse (1-8) must be removed. Connect negative (-) of the power supply directly to the locking device. Connect the positive (+) of the power supply to the terminal marked [C]. For Fail-Safe operation connect the positive (+) of the device being powered to the terminal marked NC]. For Fail-Secure operation connect the positive (+) of the device being powered to the terminal marked [NO]. (c) Auxiliary Power outputs (unswitched): Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (-) of the device being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads etc. 4. Input trigger options (Fig. 1, pg. 4): (a) Normally Open [NO] input trigger: Inputs 1-8 are activated by normally open or open collector sink inputs. Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND]. (b) Open Collector Sink inputs: Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (-) to the terminal marked [GND]. 5. Fire Alarm Interface options (Figs. 3 through 7, pg. 6): A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will trigger selected outputs. To enable FACP Disconnect for an output open the corresponding switch [SW1-SW8]. To disable FACP disconnect for an output close the corresponding switch [SW1-SW8]. (a) Normally Open [NO] input: For non-latching hook-up (Fig. 4, pg. 6). For latching hook-up (Fig. 5, pg. 6). (b) Normally Closed [NC] input: For non-latching hook-up (Fig. 6, pg. 6). For latching hook-up (Fig. 7, pg. 6). ACM8/CB Sub-Assembly - 3 -

(c) FACP Signaling Circuit input trigger: Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -]. Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition). Jumper must be cut (Fig. 3, pg. 6). 6. FACP Dry form C output (Fig. 1a, pg. 4): Connect desired device to be triggered by the unit s dry contact output to the terminals marked [NO] and [C] FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output. Note: This product is a UL Listed Sub-Assembly for use with Altronix UL Listed power supplies as indicated in the installation manuals for the power supply. Fig. 1 ACCESS CONTROL PANEL OUTPUT RELAY C NO NC Fire Alarm System Power Supply Unit Also suitable for use as a Access Control System Unit Subassembly. 39BA Refer to Installation Instructions IIACM8 - REV. 092503 F1 1 2 3 4 Typical Application Diagram: NORMALLY OPEN N.O. DOOR RELEASING DEVICE 5 6 7 8 F2 F3 F4 F5 F6 F7 F8 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V 3.5A 250V SW5 KEYPAD FACP (Fire Alarm Control Panel) + INP --- T + RET - FACP Dry Form "C" Output SW1-SW8 Fig. 1a FACP FACP Interface Enabled LED1 SW1 SW2 SW3 SW4 SW6 SW7 SW8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 10A 250V MAIN FACP Interface Disabled MAG. LOCK J2 J1 --- + Control OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8 --- + Power ELECTRIC STRIKE ELECTROMAGNETIC DOOR HOLDERS UL Listed POWER SUPPLY For this application corresponding fuse F8 must be removed. MAG. LOCK AC or DC POWER SUPPLY (optional) AC or DC POWER SUPPLY (req'd.) ACM8 ACM8CB F1 3.5A 250V 3.5A 250V SW1 F2 SW2 2A 250V F1 SW1 2A 250V F2 SW2 WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. Replace fuses (ACM8/ACM8E models only) with the same type and rating, 3.5 amp/250v. LED1 LED2 LED1 LED2-4 - ACM8/CB Sub-Assembly

ACM8 & ACM8CB Access Power Controller LED Diagnostics: LED ON OFF LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized. Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition). Terminal Identification Tables: ACM8 & ACM8CB Access Power Controller Terminal Legend Function/Description -- Power + 12VDC or 24VDC input from power supply board. These terminals can be connected to a separate, UL Listed power supply to -- Control + provide isolated operating power for the ACM8/ACM8CB (jumpers J1and J2 must be removed). TRIGGER INPUT 1 - INPUT 8 IN, GND OUTPUT 1-OUTPUT 8 NC, C, NO, COM T, + INPUT - NC, C, NO From normally open and/or open collector sink trigger inputs (request to exit buttons, exit pir s, etc.). 12 to 24 volts AC/DC trigger controlled outputs: Fail-Safe [NC positive (+) & COM Negative (-)], Fail-Secure [NO positive (+) & COM Negative (-)], Auxiliary output [C positive (+) & COM Negative (-)] (When using AC power supplies polarity need not be observed), NC, C, NO become form C 5 amp 24VAC/VDC rated dry outputs when fuses are removed (ACM8). Contacts shown in a non-triggered state. Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open, normally closed from an FACP output circuit (Fig. 3 through 7, pg. 6). Form C relay contact rated @ 1 amp 28VDC for alarm reporting. (This output has not been evaluated by UL). ACM8/CB Sub-Assembly - 5 -

Hook-up Diagrams: Fig. 2 Optional hook-up using two (2) isolated power supply inputs: CUT JUMPERS J1 AND J2 J2 J1 Fig. 4 Normally Open - Non-Latching FACP trigger input: ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (ACM8 POWER) ISOLATED POWER INPUT 12 OR 24 VAC OR VDC (LOCK POWER) Fig. 3 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): Fig. 5 Normally Open FACP Latching trigger input with reset: (This output has not been evaluated by UL) CUT JUMPER FACP OUTPUT EOL -- + FROM FACP OUTPUT CIRCUIT N.O. TRIGGER INPUT JUMPER N.O. TRIGGER INPUT N.C. RESET SWITCH Fig. 6 Normally Closed - Non-Latching FACP trigger input: JUMPER N.C. DRY TRIGGER INPUT Fig. 7 Normally Closed - Latching FACP trigger input with reset: (This output has not been evaluated by UL) JUMPER N.C. RESET SWITCH N.C. TRIGGER INPUT - 6 - ACM8/CB Sub-Assembly

Notes: ACM8/CB Sub-Assembly - 7 -

Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIACM8/ACM8CB series D28K MEMBER - 8 - ACM8/CB Sub-Assembly