Low Voltage Examination Report Re-Examination of a Money Exchange machine



Similar documents
Low Voltage Examination Report Examination of an Electric isolation monitor. Status test report. : Techneo Electronics. Serial numbers : 1 and 2

Electromagnetic Compatibility Test Report Test results of Floww equipment

TEST REPORT. Report nº: LABEL Date: Laboratório de Ensaios Eléctricos Page nº: 1/11

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu,

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Light armature failure investigation report

RY2 miniature industrial relays

Instructions for Safe Use

5320A Multifunction Electrical Tester Calibrator. Verify and calibrate electrical test tools with a single instrument

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Technicaldata General

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

NX safety stand-alone

SURGE PROTECTIVE DEVICES

Relés e Contatores de Estado Sólido SIRIUS

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Guide to the electrical parameter classifications of IEC and IEC safety standards

User's Guide. True RMS Industrial Multimeter

5SV Residual Current Protective Devices

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

PCB transformers. Short circuit proof PCB transformer VB. General Data. Advantages. Applications. Circuit diagram. Standards & 1 Certifications W v

Safety and function tester series 1800

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number:

Cross-beam scanning system to detect slim objects. 100 mm in

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

NEC Class 2 Power Circuits and Power Supplies

Application Switchgear for industrial and commercial applications. U e V AC 230/ (per pole)

Type: DILM50(230V50HZ,240V60HZ) Article No.:

Safety automation solutions

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

IEC Connectors. Introduction

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Integration of a 400W ac dc power supply into a closed system relying only on natural convection cooling

CompactLogix Power Supplies Specifications

FAQs-Main switchboard design criteria

UT202A Operating Manual. Contents

USER S MANUAL. MaxPower UPS. Uninterruptible Power System 28-2MAXPO0018

RM4TG20 three-phase network control relay RM4-T - range V

Type: DILM32 10(24V50HZ) Article No.:

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual

1 POLE - 16A 80A Inrush type. (b) Contact configuration A : 1 form A (SPST-NO) C : 1 form C (SPDT) (standard type "K" only)

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

Problem / Solution. The problem:

Electronic ballasts for fluorescent lamps Products for special applications. PC BASIC, 4 28 W Electronic ballast for system output < 25 W

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

Power Supplies 3. SDN-P DIN Rail Series

AC-DC Converter Application Guidelines

1 Form A Solid State Relay

Safety technique. Emergency stop module BO 5988 safemaster

1 Form A Solid State Relay

38 Series - Relay interface modules A

Type: DILM9 10(24VDC) Article No.:

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in


R.C.C.B. s two-pole LEXIC

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Top Microsystems Proprietary Specification P/N: W090015HK-XP RB V.A0 SPECIFICATION

DATA SHEET COMPACT AND LIGHTWEIGHT, SMALL MOUNTING SIZE, HIGH BREAKDOWN VOLTAGE

Guidance for upgrading to GB (IEC : 2005, MOD)

Power Supplies in Medical Electronics

How To Build A Low Voltage Capacitor Lvcp

How To Use The Vacon 0 Machinery

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

Power supply unit Model: PAC-SC50KUA

AMIS. Automated Metering and Information System. Integration of meters from other manufacturers

E-STOP relays, safety gate monitors

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

Handheld portable appliance testers

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

Technical Data. Dimensions

LAB 1 TECHNICAL DOC 3 IN ONE LAB DEVICE. Velleman Legen Heirweg Gavere Belgium

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

323/324/325. Calibration Manual. Clamp Meter

38 Series - Relay interface modules A

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

1 POLE 5 A (CADMIUM FREE CONTACTS TYPE) NY SERIES

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

SUCCESS EPCOS Capacitors

帝 聞 企 業 股 份 有 限 公 司 DEE VAN ENTERPRISE CO., LTD. SP DSL-20WA Revision: A Date: FOR AC-DC LED DRIVER MODEL NO.

Intertek Research & Performance Testing Technical Report S64604 Issue 1 Page 1 of 17. Report issued by: S64604 Issue 1

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description


Transcription:

Low Voltage Examination Report Re-Examination of a Money Exchange machine Reference number Status test report Brand : 11C01263RPT01 : Final : Suzo-Happ Model number : 182-8000 Serial number : 18211080061/182111200006 Date of receipt : 2011 December 13 Date of examination : 2011 December 14 Date of test report : 2011 December, 22 This publication may be entirely reproduced and/or made public. Separate parts of this publication may not be reproduced and/or published by print, photo print, microfilm or any other means without the previous written consent of D.A.R.E!! Consultancy. All rights and obligations of contracting parties are subject to either the Standard Conditions of D.A.R.E!! Consultancy or the relevant agreement concluded between the contracting parties.

Manufacturer : Suzo International B.V. Postbus 1601 3260 BC Oud-Beijerland Examination carried out on behalf of : Suzo International B.V. Postbus 1601 3260 BC Oud-Beijerland Applicant's representative : Mr. E. Stoel In the capacity of : Manufacturer Tests carried out by : D.A.R.E!! Consultancy Test engineer : P.J. Coenders Senior Test engineer Released : D. van der Vlugt Director Reference number: 11C01263RPT01 Page 2 of 24

Contents 1 Introduction...4 2 EUT details...5 3 Test item particulars...6 4 Standards and Directive...6 5 Environmental test conditions...7 6 Possible test case verdicts...7 7 Explanation Status Report...7 8 Results of examination...8 9 Results of test and measurements...9 9.1 Input...9 9.2 Protection from electric shock...9 9.3 Earth connection resistance...11 9.4 Clearances and creepage distance...11 9.5 Heating...12 9.6 Earth leakage current...12 9.7 Electric strength test...13 9.8 Abnormal operation and fault conditions...13 10 Remarks concerning examination...14 10.1 General remarks...14 11 Conclusion...15 11.1 Remarks...15 12 Appendix A: Equipment used...16 13 Appendix B: List of safety critical components...18 14 Appendix C: Picture(s) of the EUT...20 15 Appendix D: Measurement uncertainty...23 Reference number: 11C01263RPT01 Page 3 of 24

1 Introduction D.A.R.E!! Consultancy has been asked by Suzo International B.V. to carry out an electrical safety examination and re-examination on the Money Exchange machine within the framework of the CE marking process. This report is only to be used for this purpose. At the request of Suzo International B.V. the electrical safety examination and re-examination are carried out in order to find out whether the product complies with the harmonised electric safety standards under the Low Voltage Directive 2006/95/EC (assessment of conformity in accordance with Article 5) as mentioned in chapter 4 of this report. The examination (refer to D.A.R.E!! Consultancy report 11C00792PRP01) and reexamination have been performed at our facilities located in Woerden,. The test results presented in this report relate only to the product tested. In this report, the product tested will be referred to as Equipment Under Test (EUT). This report is in conformity with ISO 17025. Unless otherwise indicated all tests and measurements as reported in chapter 9 of this report are carried out under accreditation L279. Opinions, evaluations and interpretations are excluded from accreditation. All relevant tests and measurements as described in the applied standard(s) are carried out, unless specified in this report. The reported expanded uncertainty of measurement is based on a standard uncertainty of measurement multiplied by a coverage factor of k=2, providing a level of confidence of approximately 95%, but excluding the contribution of the EUT. The expanded uncertainty of measurement has been determined in accordance with UKAS publication LAB34. Reference number: 11C01263RPT01 Page 4 of 24

2 EUT details Test item : Money Exchange machine Brand name, trade mark : Suzo-Happ Model number : 182-8000 Serial number : 18211080061/182111200006 Date of manufacturing : 2011 Condition upon reception : Not damaged and functional The main parts of the EUT are: - Metal enclosure o Switched power supplies o Display o Mechanical money intake/scanner o Mechanical coins distributors o LED lighting Reference number: 11C01263RPT01 Page 5 of 24

3 Test item particulars Rating : 100-240Vac, 50/60Hz, 50W Phases : Single Value accessible fuse : No user accessible fuse Equipment mobility : Fixed equipment Temperature range : 0...50 C Humidity : Max. 90% NC Operating condition : Unmonitored, continuous Environmental : Indoor Altitude : Max. 2000 meters above sea level Installation Category : II Pollution Degree : 2 Protection against electric shock; Class : I Mass of appliance : Approx. 140 kg Protection against ingress of water : IP20 Supply connection : Detachable cord Tested for IT power systems : Not applicable Language user manual : Dutch; Ver. 0.4/Dec. 2011 Language installation/service manual : Included into user manual 4 Standards and Directive The EUT is assessed against the following requirements: EN 60335-1: 2002 + A1 (2004) + A2 (2006) Safety of household and similar electrical + A11 (2004) + A12 (2006) + A13(2008) appliances. Part 1: General requirements. Reference number: 11C01263RPT01 Page 6 of 24

5 Environmental test conditions Ambient temperature ( o C) : 20 21 Relative humidity (%) : 52 62 6 Possible test case verdicts NA or - : Test case does not apply to the EUT P(ass) : EUT does meet the requirement F(ail) : EUT does not meet the requirement O.K. : Does not give rise to remark U(nknown) : Information is not available or unknown Pass or fail statements exclude the measurement uncertainty. 7 Explanation Status Report Final : Formally signed report, with a final conclusion. Changes in the report will lead to a new report with a new report number. Preliminary : Intermediate unsigned report, with a temporary conclusion. Changes in the report will lead to a new report with a new report number. Reference number: 11C01263RPT01 Page 7 of 24

8 Results of examination In the table below, an overview of the results of examination of each chapter of the standard is displayed. Clause Requirement test Result Verdict 4.xx General requirement P 5.xx General conditions for the test P 6.xx Classification P 7.xx Marking and instructions P 8.xx Protection against access to live parts P 9.xx Starting of motor operated appliances P 10.xx Power input and current P 11.xx Heating P 12.xx Void 13.xx Leakage current and electric strength at operating temperature P 14.xx Transient overvoltages P 15.xx Moisture resistance P 16.xx Leakage current and electric strength P 17.xx Overload protection of transformers and associated circuits P 18.xx Endurance NA 19.xx Abnormal operation P 20.xx Stability and mechanical hazards P 21.xx Mechanical strength P 22.xx Construction P 23.xx Internal wiring P 24.xx Components P 25.xx Supply connections and external flexible cords P 26.xx Terminals for external conductors P 27.xx Provision for earthing P 28.xx Screws and connection P 29.xx Creepage distances, clearances and distances through insulation P 30.xx Resistance to heat, fire and tracking P 31.xx Resistance to rusting P 32.xx Radiation, toxicity and similar hazards NA Reference number: 11C01263RPT01 Page 8 of 24

9 Results of test and measurements 9.1 Input (Cl. 10.1, 10.2): Input power measurements Operating condition: Normal working (money changing) Voltage (VAC) Frequency (Hz) Current (A) Avg power (W) Avg power (VA) 209 50 0.26 31 55 216 50 0.26 30 56 230 50 0.25 30 55 244 50 0.25 30 57 253 50 0.24 30 60 Operating condition: Normal working (money changing) Voltage (VAC) Frequency (Hz) Current (A) Avg power (W) Avg power (VA) 108 60.043 39 56 113 60 0.42 38 58 120 60 0.43 39 57 127 60 0.40 39 58 134 60 0.35 39 59 9.2 Protection from electric shock (Cl. 22.5): Capacitance discharge measurement Location Mains supply voltage Required time until measured voltage is below 34V peak (sec) Time until measured voltage is below 34V peak (VAC) (sec) Line to Neutral 253 2 < 1 Line to Protective Earth 253 2 < 1 Reference number: 11C01263RPT01 Page 9 of 24

Discharge voltage measured between line and neutral Discharge voltage measured between line and safety ground Reference number: 11C01263RPT01 Page 10 of 24

9.3 Earth connection resistance (Cl. 27.5): Earth resistance measurement Location Test current (AAC) Required resistance (W) Measured resistance (W) Enclosure 25 < 0.1 < 0.1 Upper door 25 < 0.1 < 0.1 9.4 Clearances and creepage distance (Cl. 29.1): Clearances in primary circuits Distance determined between Minimum required distances (mm) *3 Measured distances (mm) L N 1.5 1.5 L/N PE 1.5 1.5 L/N Secondary circuit 3.0 3.0 (Cl. 29.1): Creepage distances in primary circuits Distance determined between Minimum required distances (mm) *3 *4 Measured distances (mm) L N 2.5 2.5 L/N PE 2.5 2.5 L/N Secondary circuit 5.0 5.0 Note *3: Based on pollution degree 2 and overvoltage category II Note *4: based on material group IIIa/b Reference number: 11C01263RPT01 Page 11 of 24

9.5 Heating (Cl. 11.1): Temperature rise measurements under normal operating conditions Operating condition: Normal operation (frequent money exchange) Location Position number Test voltage (VAC) Temperature ( C) Left (small) Power supply 1 253 25 Right (large) Power supply 2 253 24 User interface 3 253 20 Front side advertising window 4 253 21 Display 5 253 32 Ambient - - 20 9.6 Earth leakage current (Cl. 13.2): Leakage current measurement in well heated condition Test voltage applied between Mains voltage (VAC) Maximum allowed current (ma) Measured current (ma) L PE 253 3.5 < 1 N PE 253 3.5 < 1 (Cl. 16.2): Leakage current measurement in cold condition Test voltage applied between Mains voltage (VAC) Maximum allowed current (ma) Measured current (ma) L PE 253 3.5 < 1 N PE 253 3.5 < 1 Reference number: 11C01263RPT01 Page 12 of 24

9.7 Electric strength test (Cl. 13.3): Breakdown test before humidity treatment Test voltage applied between Test voltage Result (VAC) L/N PE 1000 (1500Vdc) P L/N Secondary circuit 2750 P (Cl. 15.3): Breakdown test after humidity treatment (48h at 23±2 C and 93±3% RH) Test voltage applied between Test voltage Result (VAC) L/N PE 1000 (1500Vdc) P *5 L/N Secondary circuit 2750 P *5 Note *5: The result is evaluated based on the available data of the safety critical components (Cl. 16.3): Breakdown test directly after test 16.2 Test voltage applied between Test voltage Result (VAC) L/N PE 1000 (1500Vdc) P L/N Secondary circuit 2750 P 9.8 Abnormal operation and fault conditions (Cl. 19): Simulated fault condition test Simulated fault Safety assembly affected Result Short circuit in the primary circuit No Pass Building fuse will blow. Wiring is consistent with the expected short circuit currents. Short circuit in the secondary circuit No Pass The applied power supplies are short circuit proof Jamming of motor controlled operations No Will be detected by the control electronics. No hazardous situation will occur. Reference number: 11C01263RPT01 Page 13 of 24

10 Remarks concerning examination No remarks. 10.1 General remarks In case the EUT is used/sold in another country, the manual(s) must be made available in a language commonly accepted in that area. Several metal parts (near the main switch) are not connected to PE. Because double insulation is present in this area, connection of metal parts to PE is not required, but is advised. Near the main switch a label is present indicating the function. Due to the construction of the enclosure, this label is only partly readable. Because of the weight of the EUT it is advised to apply heavy type PVC power cord. Reference number: 11C01263RPT01 Page 14 of 24

11 Conclusion The Money Exchange machine has been examined in conformity with the applicable standard mentioned in chapter 4 and is in compliance. Thus, the Money Exchange machine is in compliance with the harmonized standard, mentioned in chapter 4 of the report, under the Low Voltage Directive 2006/95/EC. 11.1 Remarks It is the responsibility of the manufacturer to make certain all subsequent products are identical to the examined sample and as such ensure all manufactured Money Exchange machines are in compliance with the above mentioned harmonised standard(s) under the Low Voltage Directive 2006/95/EC. Furthermore, in order to fulfill the European CE-legislation it is the responsibility of the manufacturer of the equipment to draw up a declaration of conformity and to have technical file documentation containing information to demonstrate the conformity of the product to the applicable requirements. At the same time every unit brought to the market or put into service has to be marked with the CE-mark. Reference number: 11C01263RPT01 Page 15 of 24

12 Appendix A: Equipment used Description Brand Type no. I.D.no. X High voltage tester SPS electronic HA 2000E 2002 X Protective wire/isolation tester SPS electronic PI 6011D 2001 Insulation resistance tester Megger WM5/500 2036 Digital oscilloscope Le Croy 9361 1032 X Digital oscilloscope Le Croy 64Xs 3138 X Oscilloscope probe 1:100 Coline M15X100 2023 Multimeter Hewlett Packard HP 34401A 1056 X True RMS Multimeter Fluke 175 1392 X True RMS Multimeter Fluke 175 1393 True RMS Multimeter Fluke 187 7236 Temperature probe Fluke 80TK 2087 X Safety insulating transformer/ adjustable Weseman -- 2022 transformer X Digital Power meter Yokogawa 2533 7083 AC power source California Instruments 5000i 1076 Hybrid recorder Yokogawa DR 130 2008 X Infrared temperature meter Raytek RAYST20XBEU 2075 AC/DC current probe Unitest CHB 10 2026 AC current probe Data precision IP1000-IP1001 7352 Temperature & humidity chamber ESPEC PL-3S 2024 Spring impact hammer 0.2 1.0 J PTL Dr. Grabenhorst F 22.50 2030 X Jointed test finger PTL Dr. Grabenhorst P 10.14 2004 Unjointed test finger 0-100N PTL Dr. Grabenhorst P 10.49 2031 Test pin 4mm - 3mm diameter D.A.R.E!! Development TP 1 2009 Test pin 3mm diameter D.A.R.E!! Development TP 2 2010 Test pin 4mm diameter D.A.R.E!! Development TP 3 2011 Test pin 1mm diameter D.A.R.E!! Development TP 4 2012 Test hook 8mm 5mm D.A.R.E!! Development TP 5 2013 Unjointed test finger D.A.R.E!! Development TP 6 2014 Test probe D.A.R.E!! Development TP 7 2015 Test finger telecom D.A.R.E!! Development TP 8 2037 X IEC Leakage current measurement circuit D.A.R.E!! Development AM 1 2025 with integrated wall outlet Leakage current measurement circuit for D.A.R.E!! Development AM 2 2038 high frequency IEC leakage current measurement circuit D.A.R.E!! Development AM 3 2041 Medical leakage current measurement D.A.R.E!! Development AM 4 2042 circuit Medical leakage current measurement D.A.R.E!! Development AM 5 2047 circuit 10mm thick wooden board D.A.R.E!! Development PK 1 2039 20mm thick wooden board D.A.R.E!! Development PK 2 2040 Reference number: 11C01263RPT01 Page 16 of 24

Description Brand Type no. I.D.no. Steel-ball test set D.A.R.E!! Development KPS 1 2028 Ball-pressure test apparatus D.A.R.E!! Development KD 1 2006 250N test set with 30mm diameter surface D.A.R.E!! Development GW 1 2020 Steelyard 50N Salter VU 1 2032 Steelyard 100N Salter VU 2 2029 Steelyard 250N Salter VU 3 2033 X Vernier callipers Mitutoya SM 1 2034 X Calibre PTL Dr. Grabenhorst L 25.81 2005 Scratch pin conform EN 60950:2006 D.A.R.E!! Development - 2086 Electric heater (2kW) Eurom SF2007C 2061 Electric heater (2kW) Eurom SF2007C 2069 Electric heater (2kW) Eurom SF2007C 2080 Electric heater (2kW) Eurom SF2007C 2081 Electric heater (2kW) Eurom SF2007C 2082 Sound pressure meter Bureau Geluid BG-1 2083 Light intensity meter ATP LX-332 2084 Power supply Velleman PS613 3012 Reference number: 11C01263RPT01 Page 17 of 24

13 Appendix B: List of safety critical components Object/part no. Power cord Net entry/ EMI filter 230V Y splitter Power supply 1 Power supply 2 Manufacturer/ trade mark Unity Type/model Technical data Standard Mark(s) of conformity Connector: UNI32 250Vac/16A -- *1 VDE, KEMA Wire: H05VV-F 300/500V 3 x 1mm² PVC IEC 60227-53 60227-5 *1 VDE, KEMA Connector: 250Vac/10A IEC 320 *1 UNI302 High & Low Corp. 06SS1-D-Q(B) 115/250Vac 50/60Hz 6A Dielec.: L-G: 2250Vdc L-L: 1450Vdc UL E179761 Kenic KE-24 250VAV/10A EN 60320-1 VDE 0625 Mean well Li Shin Int. Enterprise Corp. GS120A24- R7B LSE9901B126 0 85-264Vac 120-370Vdc 47-63Hz Out: 24Vdc/5A/120W Dielec.: I-O: 3kVac -30 +70 C SELV 100-240Vac 50/60Hz Out: 12Vdc/5A SELV Mains switch Acrolectric 1250 10A/250VAC Dual pole 3 mm Gap UL94V-2 Dielec.: P-P: 1.5 kv Open cont.: 1.5kV P-Body: 3 kv Connector on the mains switch Acrolectric F1344 UL94V-2 Dielec.: P-P: 1.5 kv Open cont.: UL 60950-1 EN 60950-1 EN 60950-1 ENEC15 EN 61058-1 UL E45221 -- *1 CCC *1 CE, UL, CSA, VDE *1 CE, VDE *1 cul, TüV, CE *1 CE, cul *1 UL, CSA Reference number: 11C01263RPT01 Page 18 of 24

Fastons (main switch conn.) Internal 230V wiring Shrinking sleeve 1.5kV P-Body: 3 kv AMP 60838-1 22-18AWG -- *1 -- Wire: H05VV-F 300/500V 3 x 1mm² Qualtek Electronics Q2-F 600V Dielec.: 20kV/mm -55 +135 C VW-1 Fastons AMP 165566 22-16AWG Nylon Note *1: Components have been checked as part of the appliance. IEC 60227-53 60227-5 UL E236137 -- *1 *1 VDE, KEMA *1 UL, CES Reference number: 11C01263RPT01 Page 19 of 24

14 Appendix C: Picture(s) of the EUT Picture 1: The EUT Picture 2: EUT opened Reference number: 11C01263RPT01 Page 20 of 24

Picture 3: Inner parts (after removal of the coil distributors) Picture 4: Money scanner Picture 5: Power supply 1 Picture 6: Power supply 2 Reference number: 11C01263RPT01 Page 21 of 24

Picture 7: PE connections Picture 8: Double insulation near the main switch Picture 9a/b: Identification label before and after the rubbing test Reference number: 11C01263RPT01 Page 22 of 24

15 Appendix D: Measurement uncertainty Quantity Measurement arrangement Equipment Measurement uncertainty Voltage Breakdown test High voltage tester ± 17% AC/DC to 500V ± 8.3% AC/DC to 1000V ± 12% AC/DC > 1000V Resistance Earth resistance Protective wire/isolation tester ± 10% at 0.1Ω ± 5% at 1Ω Resistance Insulation resistance Protective wire/isolation tester ± 3% at 1 MΩ/500V ± 3% at 10 MΩ/1000V ± 12% at 1 MΩ/500V ± 12% at 10 MΩ/1000V Voltage Capacitance discharge Digital oscilloscope ±21% check Oscilloscope probe 1:100 Current Reverse current Multimeter ± 1.8% Current Leakage current Multimeter ± 1.8% Measurement network Power Rated power Power meter ± 12*10-4*P + 1.2 Voltage Rated voltage Power meter ± 1,3% AC/DC <260V Temperature Component temperature Hybrid recorder ± 0.35ºC Temperature Component temperature Infrared thermometer ± 2% or 2ºC Humidity Environment Temperature & humidity ± 5.8% chamber Temperature Environment Temperature & humidity ± 0.6ºC chamber Energy Mechanical strength Spring impact hammer 0.2 ± 23% 1.0 J Distance Touchable Jointed test finger ± 23% Distance Touchable Unjointed test finger 0-100N ± 23% Distance Touchable Test pin 4mm - 3mm diameter Test pin 3mm diameter Test pin 4mm diameter Test pin 1mm diameter Test hook 8mm 5mm Unjointed test finger ± 0.2mm Distance Touchable Test finger telecom ± 0.2mm Mechanical strength ± 11% housing ± 23% Distance, weight, Energy Steel-ball test set Spring impact hammer 0.2 1.0 J Unjointed test finger 0-100N ± 23% Reference number: 11C01263RPT01 Page 23 of 24

Quantity Measurement arrangement Equipment Force Distance Stability Urnster Tape measure Unjointed test finger 0-100N Distance Distance through Vernier callipers insulation Distance Creepage Calibre Clearance Vernier callipers Measurement uncertainty ± 23% ± 23% ± 23% ± 0.12mm ± 0.2mm 0.12mm 0.2mm Test finger Decibel (A) Sound pressure Sound pressure meter ± 1.7 dba Lux Light intensity Light intensity meter ± 61 lux Reference number: 11C01263RPT01 Page 24 of 24