Substation Grounding Study Specification

Similar documents
SES Training & Certification Programs Welcome to the SES Grounding, EMI and Lightning Academy

EARTHING SYSTEM CALCULATION

GroundRod AC Substation Earthing Tutorial

Coupling Effect in Substation Ground Measurements

TABLE OF CONTENT

Strength and Durability for Life CORROSION CONTROL. The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Estimating AC Mitigation Requirements for Pipelines Installed in High Voltage AC Corridors: Fault Conditions

Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

THE LIGHTNING PROTECTION INTERNATIONAL STANDARD

Hyperlinks are Inactive

Video Camera Installation Guide

A Practical Guide to Dielectric Testing

Grounding Demystified

Earth Ground Resistance

Power Quality Standards for Electric Service

Nexus Technology Review -- Exhibit A

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Typical Data Requirements Data Required for Power System Evaluation

Modeling of Transmission Lines

Screened cable and data cable segregation

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

FEASIBILITY OF ELECTRICAL SEPARATION OF PROXIMATE GROUNDING SYSTEMS AS A FUNCTION OF SOIL STRUCTURE

White Paper: Electrical Ground Rules

Introduction. Harmonics and IEEE 519 Page 1 of 19

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

Digital Systems Ribbon Cables I CMPE 650. Ribbon Cables A ribbon cable is any cable having multiple conductors bound together in a flat, wide strip.

12 Appendix 12 Earth Electrodes And Earth Electrode

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Separation of power and information technology cabling

Earthing Guidance Notes

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Power transformers. Special transformers Railway

Charged cable event. 1 Goal of the ongoing investigation. 2 Energy sources for the CDE. Content

Lightning Protection Introduction

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

Short Circuit Current Calculations

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

Introduction to Data Centre Design

Lightning Arresters P KVA P KVA. Description & Installation

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Complete Solar Photovoltaics Steven Magee. Health and Safety

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

AMSC s Superconductor Cable Technologies for Electric Utilities

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

Gulf Cable & Electrical Ind. Co.

Specifications for Lightning Protection. ASAE Engineering Practice

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Federal Wage System Job Grading Standards for Electric Power Controlling, Table of Contents

Fault location on power cables. Fault location on power cables

Earthing Techniques 1. SOIL RESISTIVITY TESTING THEORY OF SOIL RESISTIVITY INTERPRETATION AND MODELLING OF RESULT...

Transformers. Special transformers Reactors products

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Voltage Detection and Indication by Electric Field Measurement

EMI and t Layout Fundamentals for Switched-Mode Circuits

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

KNOWLEDGE BASE ARTICLE Zero Voltage Transmission (ZVT) Technology. Basics of the GPZ 7000 Technology: Zero Voltage Transmission (ZVT)

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

AN Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC x

Line Reactors and AC Drives

V.A PJM Design and Application of Overhead Transmission Lines 69kV and Above

Cable Solutions for Servo and Variable Frequency Drives (VFD)

PXL-250: Network Wiring

Physics 25 Exam 3 November 3, 2009

DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD OF INSERTION LOSS MEASUREMENT

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Telecommunication Line Protectors

SOIL RESISTIVITY MEASUREMENTS

Unified requirements for systems with voltages above 1 kv up to 15 kv

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

AVX EMI SOLUTIONS Ron Demcko, Fellow of AVX Corporation Chris Mello, Principal Engineer, AVX Corporation Brian Ward, Business Manager, AVX Corporation

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

Estimation of electrical losses in Network Rail Electrification Systems

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Bourns Resistive Products

EMI in Electric Vehicles

EMI/RFI Shielded Cable Tray

An extended EMC study of an electrical powertrain for transportation systems

INTERNATIONAL STANDARD

Telephone- and leased line modem for industrial applications TD-36

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

TDMS Test & Data Management Software

A wave lab inside a coaxial cable

Electrical safety requirements in DC distribution systems

Oscar E. Morel UtilX Corporation

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Comparison of GIS and AIS systems for urban supply networks

Radial Distribution Test Feeders

Transcription:

Substation Grounding Study Specification Introduction A grounding study is required for name of station, a / / kv substation located in name of location and connected to the following circuits: number of lines x kv overhead lines number of circuits x kv buried circuits Further details Station-Specific Attributes Special attributes that can apply to some substations and should be mentioned, if known, are the following: 1. Nearby metallic urban infrastructure, water pipes in particular, cannot be ignored: a. Typically, for a distribution substation with multi-grounded neutrals, the water system acts as an extended grounding system and can considerably reduce touch and step voltages within and outside the substation periphery. b. For transmission substations that are isolated from the water system, earth potential gradients around the substation are exacerbated by the presence of nearby metallic water pipes or other such metallic infrastructure. 2. The same applies for major facilities next to the substation, such as power plants or industrial plants. 3. Large fault current levels. 4. Rock (at surface or shallow depth) or known high resistivity soil at site. 5. Geographic irregularities: significant slope, top of mountain/hill, nearby river/lake/quarry, etc. 6. The presence of one or more railroads, pipelines, fences, or other such long metallic structures running past the substation raises the concern of excessive touch and step voltages appearing along the metallic structures in question or even damage to these structures. 7. If the site is a brown field, measurements of soil resistivity on the substation property may be of limited value. In such a case, it is highly advisable to attempt to measure soil resistivity on larger adjacent tracts of land, if any can be found that are devoid of extensive buried metallic systems. 8. Below-grade power cables, especially on the high voltage side, which can have a considerable impact on fault current split and therefore upon the cost and performance of a substation grounding system, provided that the extent of these cables is sufficiently great. General Requirements A conceptual grounding design study is required that will satisfy the following requirements: 1. Provide a safe and cost-effective conceptual grounding system design for the substation by means of accurate calculations properly accounting for a realistic approximation of the soil structure (typically a multi-layered soil structure), attenuation along ground conductors (i.e., no equipotential conductor assumption for electrically large grounding systems), inductive coupling between ground conductors (if applicable), circulating currents in the grounding system, fault current split between the substation grounding system and power line ground return conductors, and interactions with outside metallic infrastructure. 1

2. Meet touch voltage and step voltage tolerable limits and conductor ampacity limits, determined in accordance with IEEE Standard 80, during worst case fault conditions. Touch and step voltage limits are to be met both inside the substation and around its periphery, including metallic infrastructure in close proximity to the substation. Detailed Design Criteria The study shall be carried out in conformity with the design guidelines listed below and the computer software used for the design calculations shall take into account all of the factors listed: 1. Soil Testing. Soil testing shall be made using the Wenner 4-pin method specified in IEEE Standard 81 Part 1. For each measurement traverse, pin spacings (between adjacent pins) shall begin at 6 to 12 and increase thereafter by a factor of approximately 1.5, up to the maximum pin spacing chosen for that traverse. It is highly desirable to have 2 to 3 traverses centered at different locations, whose maximum pin spacing (between adjacent pins) reaches a distance that exceeds the maximum extent of the substation, i.e., its largest diagonal dimension (and any other facility associated with the substation), preferably twice this diagonal dimension or more, while avoiding the influence of buried metallic structures. A number of additional shorter traverses (6 up to 20 ) are required to obtain data sufficiently representing soil conditions at shallower depths throughout the site. The equipment used shall be accurate to the maximum required pin spacings, for the soil conditions encountered at the site: equipment that can apply low frequency alternating polarity square wave pulses at voltages of up to 400 V and provide power of up to 200 W may be required. The recommended pin to pin spacings for a Wenner configuration are as follows: Very Short Short Spacing Moderate Large Very Large Spacing (feet) (feet) Spacing (feet) Spacing (feet) Spacing (feet) - 1 10 100 1000-2 20 200 2000 0.3 3 30 300 3000 0.5 5 50 500 5000 0.7 7 70 700 7000 Very Short Short Spacing (m) Moderate Large Very Large 0.1 1 10 100 1000 0.2 2 20 200 2000 0.3 3 30 300 3000 0.5 5 50 500-0.7 7 70 700 - Given the capital importance of the soil resistivity data for adequate grounding system design calculations, a well-defined quality control program is required in the field to demonstrate that readings are valid. This includes, as a minimum, reporting of the measured signal voltage, injected current, and standard deviation between pulses of alternating polarity, for each pin spacing and evidence that the instrument provides accurate results for the measured signal voltages and injected currents. 2

2. Soil Resistivity Data Inversion. The measured soil resistivity data shall be inverted in order to obtain equivalent multi-layer soils to be used in the subsequent grounding study. This interpretation shall account for electrode pin depth, any irregular pin spacings (due to obstacles in the field) and known buried metallic structures that mildly to moderately distort the measured values. One or more suitable soil models shall be chosen for the study from those obtained from all measurement traverses and the choice shall be explained in the final report. Any approximations to the soil model shall be justified. Soil structure model variations due to local and seasonal variations shall be accounted for by developing soil model structure limiting cases. 3. Soil Model for Grounding Study. Soil layers down to depths on the same order as the extent of the substation (and any associated facilities) can have a significant impact on its performance. It is anticipated that three or more soil layers may be required in the computer model to adequately represent the grounding medium. Provide graphs of measured apparent resistivity versus computer apparent resistivity curve for each measurement traverse, in order to demonstrate that the soil models chosen for the study adequately represent the actual soil s electrical structure. 4. Grounding System Reactance. Account for the attenuation along (i.e., longitudinal impedances of) grounding grid conductors, which can result in a reactive component of the grounding system impedance that is on the order of ten times the value of the resistive component for large substations. If applicable (e.g., GIS structures), take into consideration inductive coupling between grid conductors. These factors can have a considerable impact on the potential rise of the grounding grid and on the measured ground impedance. 5. Circulating Currents and Voltage Drop in Grid Conductors. Model circulating currents within the substation grounding grid and account for the voltage drop in grid conductors through which current is flowing, in order to correctly calculate touch and step voltages. The largest voltage drops will occur for faults occurring far from the transformers. For large substations, faults occurring at different locations within the substation shall be modeled in order to demonstrate that safety has been achieved for all fault locations studied. 6. Conductive Coupling with Nearby Infrastructure. Model interactions with surrounding metallic infrastructure (water and gas pipelines, railways, fencing, neighboring facilities, communications cables, etc.), which can considerably alter the substation grounding performance both favorably and unfavorably and also represent transferred potential concerns that must be investigated. Any nearby conductors that are imperfectly insulated from ground, such as coated pipelines and railways on ballast shall be included in the model, with their leakage resistances and longitudinal impedances properly represented. Note that inductive coupling with parallel power lines may also occur and must be considered if significant near-parallel exposure occurs. 7. Fault Current Split Calculation. A fault current split calculation shall be carried out based on a circuit model of the high and low voltage power line systems connected to the substation, including the remote substations whose transformers contribute fault current, in order to correctly determine the fault current distribution between the substation grounding system and power line ground return conductors, such as neutral and shield wires. The circuit model shall properly account for overhead and buried circuit characteristics, including conductor impedances, inductive coupling between conductors, leakage and ground impedances. The fault current split calculation shall consider faults occurring not only within the substation but also on circuits outside the substation, in order to determine the worst case fault location. 8. Contingencies. Consider the following contingencies and demonstrate that touch and step voltages remain satisfactory: a. One line down: phase and shield wires become disconnected from substation b. Loss of 10% of ground rods, evenly distributed throughout substation 9. Conductor Ampacity Calculation. Compute the required grounding conductor size, such that the maximum anticipated fault current can be carried, with the worst case asymmetrical transient offset 3

magnitude and backup fault duration, without damaging the conductor, based on the methodology specified in IEEE Standard 80. 10. Touch and Step Voltage Limits. Calculate tolerable safety limits in accordance with IEEE Standard 80 and demonstrate that they are met by the proposed grounding design. 11. Grounding Design. Provide a conceptual grounding system design for the substation, including specification of conductor size and depth, crushed rock or asphalt resistivity and thickness, in accordance with the above design criteria. The grounding design shall indicate the placement of horizontal grid conductors and ground rods for the grounding system: a DXF file from which exact dimensions can be obtained shall be provided such that detailed drawings can be made based on Owner s standard specifications. 12. Recommended Software Packages. The following industry standard software packages are strongly recommended. Alternative software packages can be used if it is proven that they have similar capabilities and that they can perform similar types of computations accurately. Classical Grounding Studies (Low Frequency, Equipotential Systems): MultiGround and MultiGround-Plus Software Packages. This software is suited for grounding studies of electrically small installations where circulating currents within the grid are negligible, where above ground structures and busses are not relevant for the study and where extensive external metallic infrastructure does not exist close to the substation. Extended Grounding Studies: MultiGroundZ and MultiGroundZ-Plus Software Packages. This software is suitable for grounding systems of any size. It accounts for the impedance of the conductors making up the grounding system and allows currents to be injected into the system at any number of locations, thus accounting for the effects of circulating currents. This software can also represent long insulated conductors, such as pipelines and railways. It does not, however, model overhead conductors, nor account for inductive or capacitive coupling effects between conductors: this can be done with MultiFields (see below) Electromagnetic Fields Based Studies (Grounding, EMI, Lightning and Transient Analysis). MultiFields and MultiFields-Plus Software Packages. This software accounts not only for conductor impedance, but also for inductive, capacitive and conductive coupling between all conductors modeled, allowing the user to specify any number of horizontal soil layers and both overhead and buried conductors. Furthermore, in addition to the results computed by MultiGroundZ, this package also computes electric and magnetic fields in air and in soil. MultiFields can be used not only for grounding studies, but also for electromagnetic compatibility studies, safety studies involving induction or capacitive coupling, modeling of grounding grid impedance testing with long leads (and the associated inductive coupling between leads, grounding conductors and overhead conductors). It supports transformer models, cable conductors and GIS structure models. 13. Final Report. A final report shall be submitted summarizing the data, assumptions, computer models, computation results, conclusions and recommendations, including proposed conceptual substation grounding design. The final report shall include the following computation results: a. Effective substation grounding grid impedance (magnitude and angle) for fault current injection at high voltage transformer, b. Summary of fault current split calculation results, c. Summary of ampacity calculation results, d. Summary of tolerable touch and step voltage limit calculation results, e. Plan-view plots of substation grounding grid potential rise for all scenarios studied, 4

f. Plan-view plots of potential rise of any nearby metallic infrastructure modeled, for worst case scenario, g. Plan-view plots of touch and step voltages throughout the substation and around its periphery, for all scenarios studied. h. Plan-view plots of touch and step voltages associated with any nearby metallic infrastructure modeled, for worst case scenario, i. Graphs comparing measured apparent soil resistivity data with values computed from soil model obtained from field data inversion. 5

Additional Situation-Specific Design Tasks The following additional requirements apply to this grounding study: 1. Substation Grounding Grid Test. Provide a detailed methodology to test the grounding system after construction. 2. Simulation of Grounding Grid Test. Simulate the grounding system test, accounting for magnetic field induction between test leads and other conductors, such as transmission and distribution line ground return conductors, grounding grid conductors, water pipes, etc. Also account for conductive coupling between test electrodes, the grounding grid and surrounding infrastructure, in order to provide expected test results that will validate the study predictions. 3. Zone of Influence. Determine the extent of the 300 V contour line, accounting for the influence of transmission and distribution line structures and other nearby infrastructure. 4. Construction Scenarios. Safety calculations for various construction scenarios. 5. Detailed Analysis and Mitigation for Nearby Infrastructure. Design corrective measures for infrastructure on which a touch or step voltage concern has been identified, accounting for both conductive coupling with the substation (and nearby structure grounds) and any inductive coupling with power line circuits associated with the substation. 6. EMI in Communications/Control Cables. Calculation of electromagnetic interference in low voltage circuits. 7. Transients. Calculations related to steep wave front transients (as compared with 60 Hz fault conditions, with asymmetric component), such as those associated with lightning surges and switching operations. 8. Lightning Shielding Study. Create a 3-dimensional model of aboveground structures that must be protected from lightning strikes, along with intentional and non-intentional shielding structures (e.g., structural steel, shield wires, lightning masts, air terminals). Analyze the shielding effectiveness based on the electrogeometric method specified in IEEE Standard 998 and IEC EN 62305. Provide a conceptual shielding design that will yield the required protection. 9. Gas-Insulated Substation. Determination of current flow in GIS and assessment of required ground connections to substation grounding grid. 10. Interactions between Buswork and Grounding Grid. For very large stations, inductive coupling between phase conductors (lines or buswork) and the grounding grid can have a significant impact on the performance of the grounding system. These interactions are to be studied. Owner s Responsibilities Owner shall provide the following assistance: 1. Access to the substation site, for soil resistivity measurements, after final earth moving, but prior to installation of any substation equipment or structures, including fencing and reinforced concrete. This shall be at a time when no major construction activity is occurring. 2. Access to areas outside substation, for soil resistivity measurements: these areas are to be determined from study of local maps. 3. All data required to carry out the study (see below), except for soil resistivity measurements, which are to be carried out by Consultant. 6

Outline of Data to be Provided by Owner for Standard Grounding Study: The following is a summary of the data that shall be provided by Owner for the study, with all maps and drawings to be provided in electronic format: 1. GPS coordinates of site. 2. General description of substation. 3. General equipment arrangement plan. 4. Single line diagrams of the transmission and distribution systems associated with the substation, both within and outside the substation, indicating buried/overhead components and distances between stations. 5. Fault current data: worst case horizon values. Provide breakdown of contributions from all circuits and substation transformers. 6. Fault clearing time and X/R ratio. 7. Transmission and distribution line details for fault current split calculation (e.g., typical circuit cross section, conductor/cable details, structure/manhole grounding, average span length, distance to each source of fault current, etc.). 8. Maps showing lengths of overhead/buried portions of transmission and distribution power lines connected to the substation, up to major transformer sources of fault current. 9. Plan and profile drawings of transmission and distribution lines associated with the substation, if requested by Consultant. 10. Maps, in electronic format, showing metallic or reinforced concrete infrastructure outside the substation: e.g., pipelines, railways, metallic fences, facilities, communications cables, etc. 11. Map showing areas around substation within radius of 1 mile where soil resistivity measurements can (or cannot!) be made. 12. Grounding and general arrangement plans of any major adjacent facilities. 13. Grading information, frost line. 14. If known, minimum resistivity, when wet, of available crushed stone. Consultant shall compile a list of any additional data required, at the start of the study. Specification prepared by: Safe Engineering Services & technologies ltd. 3055, Blvd. des Oiseaux, Laval, Quebec, Canada, H7L 6E8 Tel. : (450) 622-5000 E-mail : info@sestech.com; Web site: www.sestech.com. s:\pcses\proposal\ Proposal Materials\Sample Proposals and Costing\Grounding Study Specification\Grounding Study Specification.docx 7