SIMATIC Expert Communication Connecting S7-400H to PC Station (WinCC)



Similar documents
TECHNICAL NOTE TNOI34

Service & Support. How can you establish a connection between a S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

Service & Support. How can you establish a connection between an S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

SIMATIC NET. S7-CPs for PROFIBUS. CP Basic. Manual Part B3

FAQ Communication over IE

WinCC. Communication Manual. Manual 2. This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 C79000-G8276-C156-01

How-To-Do. Hardware Configuration SLIO CPU 014

PROCESS AUTOMATION PLANNING AND INTEGRATION INFORMATION LB8106* Integration in Siemens SIMATIC PCS 7

FAQ about Drive Technology

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP

s Preface SIMATIC Configuring Hardware and Communication Connections with STEP 7 Contents Basics of Configuring Hardware with STEP 7 1

SIMATIC. Automation System S7-400H Fault-tolerant Systems. Preface, Contents. Fault-Tolerant Programmable Logic Controllers 1

S7 for Windows S7-300/400

1 Application Description Objective Goals... 3

Service & Support. How Can You Have Diagnostics Data of IPCs Displayed in WinCC? WinCC, IPC and DiagMonitor. FAQ July Answers for industry.

8/23/13 Configuring the S7 Server for Windows NT 4.0 to Access S7-400 PLCs via the Siemens CP1613 Card for ISO (Industrial Ethernet)

PROFINET IRT: Getting Started with The Siemens CPU 315 PLC

S7 OPC Server Tutorial

S7-400H SIMATIC. Fault-tolerant systems S7-400H. Preface 1 Fault-tolerant automation systems. S7-400H setup options 3.

Configuration limits for products of the SIMATIC NET PC Software V12 SIMATIC NET. Configuration limits for products of the SIMATIC NET PC Software V12

Service & Support. How do you configure time synchronization using the NTP procedure (without SICLOCK) for small PCS 7 plants?

FAQ Communication over IE

Using the WAGO PROFINET Coupler as Remote I/O with a Siemens S7 PLC

SIMATIC The Process Device Manager Manual Edition 12/2004 A5E

Applications & Tools. Migration to TIA Portal. WinCC Basic / Comfort / Advanced STEP 7 V5.x / WinCC flexible 2008 SP3. Migration Guide September 2013

PROFINET IO Diagnostics 1

Redundant PROFIBUS DP network with S7-400H System and Ponto PO5063V5 Remote

Application about Communication

WinCC Options. Redundancy. Manual C79000-G8263-C142-01

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL E04

1 Application Description System Topology Hardware and Software Requirements... 3

Applications & Tools. Configuration of Messages and Alarms in WinCC (TIA Portal) WinCC (TIA Portal) Application description December 2012

Applications & Tools. Configuration and Diagnostics of a PROFINET IO System. PROFINET IO Configuration Example. Application Description January 2010

ABB industrial drives. Quick start-up guide Drive Manager for SIMATIC


s Preface SIMATIC Configuring Hardware and Communication Connections STEP 7 Contents Basics of Configuring Hardware with STEP 7 1

SOFTLINK 300. CPU Specifications. Reference Manual

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

1 How configure S7 PLC in the configuration tool

SIMATIC PCS 7. SIMATIC Maintenance Station PDM A stand-alone Solution. Siemens AG All Rights Reserved.

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE E05

CP Page 1342 Mar 2008 Siemens ITS

1 Parameterizing field devices

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE A5. PLC-Simulation with S7-PLCSIM

The CP provides access to different communication services of the PROFIBUS bus system:

Applications & Tools. Remote Control Concept with SCALANCE S Modules over IPsec-secured VPN Tunnel SCALANCE S. Application Description February 2010

Operating Instructions

SIMATIC PDM software. Siemens FI /1

Application Note Siemens PLC and SIMATIC STEP 7 / TIA Portal

CPUs - CPU PN/DP

The CP FO provides access to different communication services of the PROFIBUS bus system:

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: Rev 6

Remote Monitoring of Woodward easygen-3000

Cover sheet PROFINET IO. SIMATIC MV440 Code Reading System. FAQ February Service & Support. Answers for industry.

H0/H2/H4 -ECOM100 DHCP & HTML Configuration. H0/H2/H4--ECOM100 DHCP Disabling DHCP and Assigning a Static IP Address Using HTML Configuration

SIMATIC PDM V6.0. Getting Started Edition 12/2004

SIMATIC NET. S7-CPs for PROFIBUS Configuring and Commissioning

HP StoreVirtual DSM for Microsoft MPIO Deployment Guide

Siemens S7 PLC and FC 300 Profibus

GE Proficy Machine Edition Profibus/Profinet SARTUP GUIDE

Visio Enabled Solution: One-Click Switched Network Vision

Continuous PROFIBUS PA Instruments and Step 7. Configuring a Siemens Continuous Level PROFIBUS PA device in a S7-300 or S7-400 PLC

SIMATIC NET. IE/PB Link Gateway Manual. Contents. Properties and Services. Compatibility with the Previous Product. Design How to Commission the IE/PB

How to use the VMware Workstation / Player to create an ISaGRAF (Ver. 3.55) development environment?

HTML Code Generator V 1.0 For Simatic IT Modules CP IT, IT, IT

How-To-Do. EtherCAT Communication with CPU 300S

Application example and brief instruction 04/2015. LOGO! App V3.0. LOGO! 8 and LOGO! 7

SIMATIC. S7 300 PLC CPU 317T-2 DP: Controlling a virtual axis. Introduction. Preparation. Learning units 3. Further information 4.

8/23/13 Configuring the S7 I/O Server for Windows 95 to Access S7 PLCs Via the Profibus Network

SIMATIC NET PC Software V8.2 SIMATIC NET. PG/PC - Industrial Ethernet / PROFIBUS SIMATIC NET PC Software V8.2. Introduction 1

WinCC Runtime Professional Readme SIMATIC HMI. WinCC V11 SP1. Readme WinCC Runtime Professional. Special considerations for Windows 7.

IGSS. Interactive Graphical SCADA System. Quick Start Guide

Development of a Gateway to PROFIBUS for Remote Diagnostics

Third Party System Management Integration Solution

SIMATIC NET. Step by Step: Ethernet Communication between OPC Server and S7-200 incl. CP Overview and Environment. Contents

CPU PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU PN/DP: Configuring an ET 200S as PROFINET IO device

Security basics and application SIMATIC NET. Industrial Ethernet Security Security basics and application. Preface. Introduction and basics

How To Use Mview On A Powerline 2.2 (Powerline) On A Pc Or Macbook 2 (Powerplst) On An Iphone Or Ipa 2 (Aldo) On Your Iphon 2 (

Smart Control Center. User Guide. 350 East Plumeria Drive San Jose, CA USA. November v1.0

SIMATIC WinCC SCADA system - SIMATIC WinCC

8/23/13 Configuring SIDirect DAServer to Communicate with S7 PLC Over TCP Connection

Universal Serial Bus (USB) to DH-485 Interface Converter

PROFINET CPU 314C-2 PN/DP, PN/DP, PN/DP, PN/DP: Configuring the PROFINET interface

NVIDIA Graphics Card and Driver Installation Guide (Windows NT 4.0 and Windows 2000)

HP ProLiant DL380 G5 High Availability Storage Server

SIMATIC NET. S7-CPs for Industrial Ethernet. CP Lean. Manual Part B8. Version 1 or higher (Firmware Version V1.0) for SIMATIC S7-300 / C7-300

Rako Lighting Driver. For use with: Driver software written and provided by:

The goal is to program the PLC and HMI to count with the following behaviors:

ATV71 and ATV32 on Ethernet/IP with M340 and NOC0401 configured on Unity V6.0. Assemblies 20 70

Profinet to EDV111 Series LED Signs Siemens Function Block Software Manual

SIMATIC NET. DP Base Programming Interface for CP 5613/CP Preface, Contents. Basic Steps in Creating a DP Application 1

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3. Simatic. Readme. Readme

Mellanox WinOF for Windows 8 Quick Start Guide

Siemens AG Fieldbus solutions with the SIMATIC PCS 7 distributed control system. Brochure April 2010 SIMATIC PCS 7. Answers for industry.

Quick Start Guide. GV-Redundant Server GV-Failover Server. 1 Introduction. Packing List

Configuring the SST DeviceNet OPC Server

Configuring PROFINET

Schneider OS-Loader usage via Ethernet or USB.

Transcription:

SIMATIC Expert Communication Connecting S7-400H to PC Station (WinCC) Getting Started Edition 08/ 2001

Contents 1 Automation problem... 3 2 Solution description... 3 2.1 S7-400H... 3 2.2 S7-RedConnect... 4 2.2.1 Important notes on S7-RedConnect... 5 2.2.2 Two-path or Four-path Redundancy... 6 3 Configuration... 9 3.1 Configuring S7-400H... 9 3.2 Configuring PC-station... 15 3.3 Configuring fault-tolerant connections... 17 3.4 Setting the PG/PC-Interface of the WinCC-Station... 20 3.5 Configuring WinCC-Station... 22 4 Reference... 25 5 Contact... 25 6 Warranty and Support... 25 Evaluation / Feedback...25 Rev. A - Entwurf 13.08.2002 2/26

1 Automation problem Connecting S7-400H to WinCC Station with S7-RedConnect has always been a problem, not because the system is difficult to handle, but rather due to lack of information provided on the manuals. This solution will show you the necessary steps that you have to do in order to establish a faulttolerant connection between S7-400H and WinCC Station. 2 Solution description This solution is valid for: H-CPU Order Number Hardware Version Firmware Version H optional package Version STEP 7 Version *) CPU 414-4H 6ES7 414-4HJ00-0AB0 1 V 2.1.2 V5.1 V5.1 + SP1 CPU 417-4H 6ES7 417-4HL01-0AB0 1 V 2.1.2 V5.1 V5.1 CPU 417-4H 6ES7 417-4HL00-0AB0 3 V 2.1.2 V5.1 V5.1 *) If STEP7 V5.1+SP2 is installed, then H optional package V5.1+SP2 must be used! If you have H-CPU that is different from the above specification, then you can still use this solution as your guide because the idea behind is the same, but please make sure that you have the components (hardware and software) that can be used for the version of H-CPU you used. Before starting the commissioning you have to take-care of the following: 2.1 S7-400H The following ethernet CPs (CP 443-1) can be used for fault-tolerant communications: Order Number Hardware Version Firmware Version 6GK7 443-1EX02-0XE0 1 V5.2 6GK7 443-1EX10-0XE0 1 V1.0.1 6GK7 443-1EX11-0XE0 1 V1.1.0 Please always refer to the product information of CPU 417-4H / CPU 414-4H, because with the new firmware version of the H-CPU, some modules must be upgraded. The product information should be considered as a separate document and, in case of doubt, takes precedence over information contained in manuals and catalogs. Rev. A - Entwurf 13.08.2002 3/26

Please note that only ISO transport protocol can be used for fault-tolerant communications!. In contrast to the description on the H manual, the Profibus network can not be used for fault-tolerant communication between S7-400H and WinCC station, because the latest version of S7-RedConnect V1.4 does not support the Profibus CPs (CP 5613 and CP 5614). For fault-tolerant communication between S7-400H and WinCC station, an S7 connection redundant must be configured in NetPro. 2.2 S7-RedConnect In order to be able to use fault-tolerant connections between S7-400H and PC (for example, WinCC), the S7-RedConnect software package is required on the PC. The S7-RedConnect software package has the following characteristics: Fault detection, switching over, monitoring of the communication and synchronization are handled in the background invisible to the application. No additional programming required for PC and fault-tolerant system. The application, for example WinCC, communicates with both parts of the fault-tolerant system in the same way as with one S7-CPU. S7-RedConnect provides the same S7 user interfaces (PG/OP functions, S7 Communication) as other SIMATIC NET S7 software products for PCs. Existing Windows applications can continue to be used. An application can monitor the status of the redundant connections using status queries. The status of the connection can be displayed with the aid of the diagnostic tool. Configurable two-path and four-path redundancy Rev. A - Entwurf 13.08.2002 4/26

2.2.1 Important notes on S7-RedConnect S7-RedConnect Version Operating System supported Network Card supported V1.3 1) 6GK1716-0HB13-3AA0 NT 4.0 CP 1413 or CP 5412 (A2) Redundancy Only two-path V1.4 V1.4 Upgrade 6GK1716-0HB14-3AA0 6GK1716-0HB14-3AA4 NT 4.0 or 2000 Pro Only CP 1613 Two-path or Fourpath 2) 1) Please also install the Service Pack 3 for S7-RedConnect V1.3 2) Four-path redundancy connections can only be configured with STEP 7 V5.1 + SP1 or higher S7-RedConnect supports only S7 communication, since the fault-tolerant connections are possible only using the S7 protocol. The transport protocol that can be used is ISO transport protocol or additionally Profibus in case of V1.3. The S7-RedConnect can be used along with other SIMATIC NET products on the same CP. Operating other protocols (for example, TCP/IP, Novell, etc., as used in office networks) on the same network card and on the same network can lead to problems in fault-tolerant communication. It is therefore recommended that you use a separate network card and a separate network. Rev. A - Entwurf 13.08.2002 5/26

2.2.2 Two-path or Four-path Redundancy Two-path Redundancy (Redundant bus) Two-path communication can, for example, be set up with the following components: SIMATIC H station, two CPUs each with a CP Two networks PC station with two CPs A fault-tolerant S7 connection therefore has two communication paths. The failure of one component leads to an automatic failover to the other redundant communication path. Rev. A - Entwurf 13.08.2002 6/26

Two-path Redundancy (Single bus) Two-path communication can also be set up with a line topology (single bus, PC station with one CP). Rev. A - Entwurf 13.08.2002 7/26

Four-path Redundancy Fault-tolerant communication on four-paths with increased redundancy can be set up, for example, with the following components: SIMATIC H station, two CPUs each with two CPs Two networks PC station with two CPs A fault-tolerant S7 connection therefore has four communication paths. Now, for example, rack 0 can fail and network 2 can be down. Since four paths are available, rack 1 and network 1 continue to function automatically. Rev. A - Entwurf 13.08.2002 8/26

3 Configuration The following steps show you how to configure a two-path redundancy system as showed in page 6. 3.1 Configuring S7-400H The following steps show you how to configure the hardware of the S7-400H. Procedure 1. Open SIMATIC Manager, and create a new project. Then insert a new H station: Insert > Station > SIMATIC H Station 2. Open the hardware configuration (HWConfig) of the SIMATIC H Station(1) created (you can change the name) by double-clicking the hardware object (or right-click the Open Object popup menu command). 3. First place a mounting rack from the RACK-400 catalog. You can use one UR2-H rack or alternatively two UR1 or two UR2 racks. Rev. A - Entwurf 13.08.2002 9/26

4. Insert the standard power supply in slot 1 of the mounting rack. Rev. A - Entwurf 13.08.2002 10/26

5. Place the fault-tolerant CPU in slot 3. Please take care of the hardware and firmware version of the CPU. 6. Create a PROFIBUS-DP subnet for the H-CPU in rack 0. Rev. A - Entwurf 13.08.2002 11/26

7. Insert two synchronization modules (H Sync module) at IF1 and IF2. 8. Insert the ethernet communication processor CP 443-1. 9. Configure the ethernet subnet; Deactivate the TCP/IP protocol, assign the MAC-Address and...activate the flag for the fast switchover of the fault-tolerant connections. Rev. A - Entwurf 13.08.2002 12/26

10. If the hardware components in rack 0 are the same as in rack 1, you can copy the rack 0 and paste it as rack 1. While pasting, you will be asked to create the second PROFIBUS-DP subnet and configure the second ethernet subnet. 11. Now, you can configure the PROFIBUS slaves (for example, ET-200M). Add the IM 153-2 directly onto one of the two PROFIBUS subnets, and enter the address. The ET-200M is connected to both subnets automatically. (There is a Redundancy tab in the properties dialog box of the ET-200M). Rev. A - Entwurf 13.08.2002 13/26

12. Insert the input/output modules in ET-200M. 13. Save and compile the current configuration. The system blocks (SDB) are generated and stored in the program container. 14. Download the hardware configuration to the CPU in rack 0 (or CPU 0 for short). Rev. A - Entwurf 13.08.2002 14/26

3.2 Configuring PC-station Before the PC can establish a connection with a fault-tolerant SIMATIC S7 system with S7-REDCONNECT, it requires certain information, such as the addresses of the nodes involved, the network adapters used etc. This information is generated automatically when you configure your S7 project with STEP 7 (version 5 and higher), include the PC as a SIMATIC PC station, and when the communications partners are attached to the same networks. Procedure 1. Insert a new PC station: Insert > Station > SIMATIC PC Station 2. Open the hardware configuration (HWConfig) of the SIMATIC PC Station(1) created. 3. Insert an Application in slot 1 of the PC rack. You can change the name of the Application (for example, WinCC-Application Rev. A - Entwurf 13.08.2002 15/26

4. Insert the communication processor in slot 2 (for example, CP1613). 5. Configure the ethernet network; Deactivate the TCP/IP and assign the MAC-Address. 6. Insert the second communication processor in slot 3 in the same way as described before.then, save and compile the configuration. Rev. A - Entwurf 13.08.2002 16/26

3.3 Configuring fault-tolerant connections Procedure 1. Open NetPro by right-clicking the Connections of the first CPU 414-4H and then choose Open Object. 2. Click on the first CPU 414-4H (Connection table will then be displayed on the lower part of the window). 3. Double-click the first line of the connection table. New Connection window pops up, then choose the connection partner, connection type and activate Display Properties Dialog. Rev. A - Entwurf 13.08.2002 17/26

Connection Partner Station SIMATIC PC Station(1) Application WinCC-Application Connection Type S7 connection redundant 4. Click the Add button and in the following dialog, the configured S7 fault-tolerant connections will be displayed. NOTE: If you configure the four-path redundancy, you must activate the check box Enable max. CP redundancy (with 4 connection paths). This is only possible with STEP7 V5.1 + SP1 or higher and S7-RedConnect V1.4 or higher. 5. Save and compile the configuration. 6. Download the configuration to the CPU 0 (CPU in rack 0). Rev. A - Entwurf 13.08.2002 18/26

Rev. A - Entwurf 13.08.2002 19/26

3.4 Setting the PG/PC-Interface of the WinCC-Station The connection information created by STEP7 (NetPro) for the PC station must also be transferred to the WinCC-Station. The communication configuration is adopted on the PC from the STEP 7 project in the form of an XDB file. The XDB file contains certain information required for the PC, such as the addresses of the nodes involved, the network adapters used etc. In the Properties dialog of the SIMATIC PC station you can see the storage location of the XDB file. Rev. A - Entwurf 13.08.2002 20/26

Procedure Open the Set PG/PC-Interface. Under register Configure STEP7, define where the XDB file is located (Click on Search button to search for the XDB file). C:\SIEMENS\STEP7\S7proj\Fault NOTE: As you can see, the WinCC can also run on different PC. Important is that the XDB file must be defined in Set PG/PC-Interface of the WinCC-PC. Please make sure that whenever the connection configuration is changed in STEP 7, an up-to-date XDB file must be copied to the WinCC-PC. Rev. A - Entwurf 13.08.2002 21/26

3.5 Configuring WinCC-Station Procedure 1. Open WinCC, create a new WinCC project and insert the SIMATIC S7 Protocol Suite driver. 2. Insert a new connection under the Named Connections channel. Rev. A - Entwurf 13.08.2002 22/26

3. Click on the Properties button to define the connection parameter. In register Connection, search for the Application name and Connection name from the XDB file. NOTE: If the XDB file is not defined in Set PG/PC-Interface, then there will be no selection for the application name and connection name in WinCC. Rev. A - Entwurf 13.08.2002 23/26

4. Now, as usual, you can define your WinCC tags and WinCC screens. NOTE: S7-RedConnect provides diagnostic tool, which can be used to diagnose the S7 fault-tolerant connections. The diagnostic tool can be found under SIMATIC > SIMATIC NET > S7 Connection Diagnostic. Rev. A - Entwurf 13.08.2002 24/26

4 Reference S7-400H Programmable Controller, Fault-Tolerant Systems Order Number: 6ES7 988-8HA10-8BA0 Edition: 07/2000 5 Contact Darman Putra A&D AS CS Telephone: +65 740 Fax: +65 740 7001 E-mail: Darman.Putra@sae.siemens.com.sg 6 Warranty and Support No liability is accepted for the foregoing/following internal Siemens information. A&D accepts no liability, regardless of the legal grounds, for damages arising from the use of the examples, tips, programs, configuration and performance data described in Expert Communications, apart from the statutory liability accepted, for example, for damage to items used for personal purposes, personal accident or for malicious intent or gross negligence. Rev. A - Entwurf 13.08.2002 25/26

Jörg Freitag A &D AS CS2 Evaluation / Feedback D-90327 Nürnberg-Moorenbrunn Tel.: +49 (0) 911 895-2407 Fax.: +49 (0) 911 895-2501 Expert Communication Applications Getting Started INTERNET: SIMATIC.Fachkomm@nbgm.siemens.de Sender Name: Department: Site: Telephone: Internet address: If you discover typographical errors in this document, please inform us using this sheet. We shall be grateful for your suggestions for improvement. Document evaluation I like it very much I like it I don t like it because.... Good choice of topic Topic incomplete Coverage suitable Too detailed Too superficial Clear More or less clear Not clear Well designed Satisfactorily designed Poorly designed Often used Seldom used Used once only Time saved by using document compared with before: No time saved Approx. 5% Approx. 10% Other:...% Suggestions:......... Rev. A - Entwurf 13.08.2002 26/26