Steady State and Transient Short Circuit Analysis of 2x25 kv High Speed Railways



Similar documents
Power System review W I L L I A M V. T O R R E A P R I L 1 0,

Modeling of electric railway vehicle for harmonic analysis of traction power-supply system using spline interpolation in frequency domain

Coupling Effect in Substation Ground Measurements

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Power transformers. Special transformers Railway

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

Multi-conductor Train Simulations for Electrification Systems

CIRCUITS LABORATORY EXPERIMENT 3. AC Circuit Analysis

Chapter 9 Balanced Faults

Estimation of electrical losses in Network Rail Electrification Systems

METHODOLOGICAL CONSIDERATIONS OF DRIVE SYSTEM SIMULATION, WHEN COUPLING FINITE ELEMENT MACHINE MODELS WITH THE CIRCUIT SIMULATOR MODELS OF CONVERTERS.

Common Mode and Differential Mode Noise Filtering

Three phase circuits

A NEAR FIELD INJECTION MODEL FOR SUSCEPTIBILITY PREDICTION IN INTEGRATED CIRCUITS

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Comparison of Power Título Transmission Line Models with Finite Elements

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

The full wave rectifier consists of two diodes and a resister as shown in Figure

New Control Strategy To Improve Power Quality Using A Hybrid Power Filter

SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS

High Intensify Interleaved Converter for Renewable Energy Resources

Typical Data Requirements Data Required for Power System Evaluation

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

High Voltage Transient Analysis

ANADOLU UNIVERSITY DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

Wireless Power Transfer System Design. Julius Saitz ANSYS

2Azerbaijan Shahid Madani University. This paper is extracted from the M.Sc. Thesis

EMI in Electric Vehicles

EDUMECH Mechatronic Instructional Systems. Ball on Beam System

Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off.

ES250: Electrical Science. HW7: Energy Storage Elements

Product Data Bulletin

Modeling of Transmission Lines

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

Introduction. Harmonics and IEEE 519 Page 1 of 19

High Performance Railway Power

Frequency-dependent underground cable model for electromagnetic transient simulation

A wave lab inside a coaxial cable

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

How To Improve Power Quality

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

Chapter 3. Diodes and Applications. Introduction [5], [6]

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Current transformer selection guide

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Substation Grounding Study Specification

Laboratory 4: Feedback and Compensation

Reduction of Power Losses Using Phase Load Balancing Method in Power Networks

AN Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC x

Power Quality Paper #3

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Numerical Differential Protection

Electron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution

FREJA Win Software for FREJA relay testing system

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

DC/DC BUCK Converter for Renewable Energy Applications Mr.C..Rajeshkumar M.E Power Electronic and Drives,

Simulation of Cable Overloading Problem on a University Distribution System

Instrument Transformers Application Guide

Estimating Line-Flow Limits

The Critical Length of a Transmission Line

Wide Area Monitoring Current Continental Europe TSOs Applications Overview

Using the Impedance Method

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Experiment #11: LRC Circuit (Power Amplifier, Voltage Sensor)

EE 1202 Experiment #4 Capacitors, Inductors, and Transient Circuits

MAS.836 HOW TO BIAS AN OP-AMP

Guide to the electrical parameter classifications of IEC and IEC safety standards

zcable Model for Frequency Dependent Modelling of Cable Transmission Systems

EARTHING SYSTEM CALCULATION

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

T Substation Maintenance and Commissioning Test Equipment

Properties of electrical signals

How To Improve Power Quality

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Coupled Inductors. Introducing Coupled Inductors

SECTION 2 Transmission Line Theory

Radial Distribution Test Feeders

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

SERIES-PARALLEL DC CIRCUITS

Electronic Power Management for Bicycles

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

reduction ore = metal oxides metal oxidation

See Horenstein 4.3 and 4.4

Transistor Characteristics and Single Transistor Amplifier Sept. 8, 1997

Phasors. Phasors. by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department. ^ V cos (wt + θ) ^ V sin (wt + θ)

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

Planar Inter Digital Capacitors on Printed Circuit Board

Transcription:

Steady State and Transient Short Circuit Analysis of 2x25 kv High Speed Railways 1 L Battistelli, M Pagano DProto, 2 A Amendola, L Cundurro, A Pignotti Università degli Studi di Napoli Federico II, Napoli, Italy 1 ; Ansaldo Segnalamento Ferroviario,Napoli, Italy 2 Abstract In the paper, a detailed model for the short circuit analysis of the AC 2x25 kv-5 Hz traction system has been derived and implemented Two different methods have been used: the time domain and frequency domain approaches The two approaches are discussed and numerical applications are reported In particular, in order to assess the feasibility of both the two methodologies, the results have been compared in steady state condition Then a transient analysis has been performed by means of the time domain simulator evidencing the short circuit current transient behavior Introduction The 2x25 kv feeding system is considered an optimal solution for high speed railways The reduction in the number of electric substations as well as a greater efficiency due to the use of higher transmission voltages (5 kv supply between catenary and return feeder) with lower currents and lower voltage locomotive traction equipment (25 kv rail-catenary voltage) are the main advantages of the system [1] Moreover, other advantages are related to the reduction of electromagnetic interference between traction converters and adjacent telecommunications circuits as well as the reduction of voltage drops Notwithstanding, critical operating conditions related to short circuit events can occur interfering with the traction system components so compromising the functionality of the whole system The short circuit levels are particularly critical also due to the presence of the autotransformers that increases the fault currents Short-circuit analysis is important not only for determining the rating of power equipment and the setting of protection devices but also for checking the voltage profiles of the network and of the buses near the fault as well as the electromagnetic compatibility with adjacent circuits Thus, a detailed short-circuit study is required in both steady state and transient condition [2-3] The accuracy of the system components is an important concern for the short circuit analysis since it significantly affects the simulation results A critical issue, for example, is the identification of the impedances of the system components and the configuration of the network since they mainly determine the short-circuit results Particular attention must be paid to an accurate modeling of the autotransformers as well as of both self and mutual impedances of the contact wire, rails and feeder In this paper the 2x25 kv electric railway system has been modeled in order to perform detailed steady state and transient short-circuit analyses The steady state model has been implemented by means of a sequence of impedance matrices (chain matrices) representing each component [4-5] The same system has been implemented also by using computer simulations developed in time domain by means of Matlab Power System Blockset, allowing to easily evaluate complex system behavior by representing each power system component by an equivalent block The toolbox is suitable for efficient time-domain simulations, allowing to capture the functional dependence of system characteristics on time and various interest parameters Through the time domain simulation, the short circuit analysis has been performed in transient condition In the paper the description of the considered traction system and of the problem formulation as well as the description of both the two proposed methodologies has been detailed Both steady state and transient conditions have been investigated Some experimental results on a measurement campaign conducted on the actual Italian system validate the results obtained in the simulation procedure

Problem Description In the 2x25 kv traction system the substation transformer feeds the overhead contact wire that supplies the trains as well as the feeder wire that runs along the track The voltage of the overhead contact wire and feeder are respectively +25 kv and -25 kv Autotransformers spaced along a section of track connect the contact wire, feeder and rails through a median tap The electrical substations are equipped with 2 single phase transformers, each one feeding a railway line section of about 25 km Autotransformers distanced by approximately 12 km divide the line sections in cells In this configuration the current flows through the contact line and the feeder and there is no current in the rails except in the cell occupied by the train The simplified scheme of the system operating condition (1 A traction load) is shown in Fig1-25 kv FEEDER 5A 5A 25A 25A 5A 5A + 25 kv CONTACT WIRE 5A 25A 5A 1 st cell 2 nd cell 3 rd cell Fig1: 2x25 kv traction system scheme A 12 km cell contains all the basic elements constituting the 2x25 kv traction system: - the substation equipped with two single phase 6 MVA transformers; - the parallel post (PP) equipped with two single phase 15 MVA autotransformers; - the supply circuit containing messenger, contact lines, feeders and rails; - the earth circuit containing the protection and buried earth conductors - capacitive compensators, located between the rails every 1 m; - inductive bonds, connecting the rails to the earth circuit for interference mitigation, located every 15 m The transversal section of Fig2 shows 14 conductors: the double track system (2 contact lines, 2 feeders, 2 messenger, 4 rail tracks, 2 buried earth conductors, 2 overhead earth conductors) Two alternative implementations have been considered for short-circuit analysis The former is performed by means of the frequency domain algorithm The latter is performed by means of time domain simulation Messenger wire Messenger wire Feeder Feeder Contact wire Contact wire Protection wire Protection wire Buried earth Fig2: Transversal section of the 2x25 kv railway system To perform the analyses in the frequency domain, each element is represented by means of an equivalent impedance matrix The system is solved by means of algebraic matrix operations

In the time domain simulation, each component is represented by its differential equations Finally, the system is represented by the whole set of the differential equations In the following the system modeling for both the two approaches is briefly discussed [6] Solving Procedures Frequency domain model This algorithm starts representing the traction system by the node impedance matrix through inspection and, then, it deduces the fault current in each branch of the traction network as well as the curve of fault current versus fault location The algorithm has the following advantages: - all system components are described in exactly the same manner by defining their "primitive Z-node matrix"; - some more complex cases that often require "approximations" in classical methods can be handled in a clean manner without numerical difficulties The basic idea of the frequency domain model is the representation of the whole system through a sequence of impedance matrices (chain matrices) representing each component According to the aim of the approach, each element is represented by a chain matrix, which relates the output voltages and currents to the input values: V I out out = V I A A in 1 2 in [ A] = in 3 A V A 4 I in (1) where V out (I out ) is the [nx1] output voltage (curren vector, V inp (I inp ) is the [nx1] input voltage (curren vector, and A is the [2nx2n] chain matrix Matrix A can be divided in four submatrices of [nxn], where, in particular, A 2 is the impedance matrix, and A 3 is the admittance matrix Chain matrices can be calculated as the product of the matrices of each individuated element Aim of the model is the identification of voltage and current phasors at all the system locations It is worth noting that the model of the system components significantly affects the level of accuracy of the simulations In the following a description of each component s frequency domain model is detailed Substation model The substation model is basically constituted by the single phase transformer and the substation earth circuit Fig4 shows the equivalent circuit model adopted for the substation transformer Z 1 Z 2 Z 3 Messanger Contact Feeders V S Buried and overhead earth conductors R T Fig4: Substation equivalent circuit For this representation 14 equivalent circuit equations and the corresponding matrix equation have been derived: [ V( ) ] [ V ] [ Z ] [ I() ] = S s (2) The substation model is represented by a [14x1] matrix V S assumes value of +25kV for messenger and contact, -25kV for feeder; Z S is derived from the equivalent circuit of the figure

Parallel post model The parallel post is constituted by the autotransformer whose equivalent circuit is shown in Fig5 The characteristic chain matrix is: [ V( x) ] = [ Zpp ] [ I( x) ] where Z PP is derived from the equivalent circuit of Fig5 (3) Messanger Messanger Contact Contact Buried and overhead earth conductors Zm Z1 Buried and overhead earth conductors ZT Z2 Feeders Feeders Fig5: Parallel Post equivalent circuit Multi-conductor line model The line section is modeled according to the method proposed in [7] The model includes 14 conductors whose auto and mutual impedances have been considered The governing multi transmission line (MTL) equations are a coupled set of firstorder partial differential equations: V( = RI( L I( z z I( = GV( C V( z z where V contains the line voltages with respect to the reference conductor; I contains the line currents; and R, L, G, and C denote the per-unit-length parameters The parameters are calculated from the geometry of the multi-conductor line configuration and the physical characteristics of the conductors The solution of the general phasor MTL equations for a line of length A can be written in the chain matrix form as: (4) V( A) Θ = I( A) Θ 11 21 ( A) ( A) Θ Θ 12 22 ( A) V() ( A) I() (5) Signalling track circuit element model Two main components have to be considered for an accurate modelling of the system behaviour: the capacitive compensators and the inductive bonds a) Capacitive compensator The chain sub-matrices of the element are calculated by output-input relations derived according to the circuit of Fig7: V1C I1C AC1 AC2 = [ ] = I1C A (6) C V2C I 2C AC3 AC4 I 2C where [A C1 ]= [A C4 ]=[I], [A C4 ]= and

[ A & ] C3 = jωc jωc jωc jωc V I 1C 1C rail V2C I2C C rail Fig7: Compensator capacitor b) Inductive bond Similarly, the chain submatrices of the inductive bond are calculated by output-input relations derived according to the circuit of Fig8 Earth conductors L rails V1i I1 i V2i I 2i L rails Earth conductors Fig8: Inductive bonds Time domain model The time domain simulations are developed by means of Matlab Power System Blockset (PSB) Each component is represented by a block, suitable to physically represent the behaviour of the component In the following the description of each component s time domain model is detailed Substation model The substation model is a 14 output line block basically composed by a single phase three windings transformer whose secondary windings are connected to feeders, contact and rails, Fig9 SSE 6 MVA, 5 kv Fe 1 1 2 AC Fe 2 3 FP 1 4 LDC1 5 FP 2 6 LDC 2 7 rot ext 1 8 rot int 1 9 rot int 2 1 rot ext 2 RT 11 Cdt 1 12 Disp 1 13 Cdt 2 14 Disp 2 Fig9: PSB Substation model

Parallel post model For the autotransformer model, a 14 I/O line block composed by a single phase three windings transformer connected as represented in Fig1 has been used Fig1: PSB parallel post model Multi-conductor line model The multi-conductor line has been implemented by the PSB Distributed Parameters Line Block, that implements a N-phase distributed parameter line model with lumped losses The resistance R, inductance L, capacitance C line parameters are specified in [nxn] matrices Signalling track circuit elements model To reproduce the effects of capacitive compensators and inductive bonds, equivalent electrical lumped elements have been introduced in the model, according to the data reported in Tab1 Capacitive compensator (rail to rail) Inductive bond (rail to buried earth conductor) 25e-6 F 12 mh Table 1: Capacitive compensator and inductive bond values It can be noted that the time domain model allows to perform analyses in both steady state and transient conditions The frequency domain model is an optimal tool for performing steady state analysis and is particularly suitable for harmonic studies [7,8] It can be also used to analyze transients subject to the limitations of the superposition principle (applicable to linear systems) In the current paper the following assumptions have been made: - According to the technical literature [8,9], the electromagnetic fields have TEM structure, which corresponds to the assumption of planewave propagation along the line - The multi conductor line representation does not take into account the inequalities in the earth s surface and its lack of conductive homogeneity whose estimation can be found in [1] - According to [11], for short circuit analyses, the lumped compensator capacitors have been neglected Numerical Applications In order to test the two implemented simulation methods for the short circuit analysis, several system configurations have been considered In the following the results obtained for two system configurations: a single cell of 12 km and a 4-cell system of about 5 km The first case implemented consists of a short circuit (between the overhead catenary and rail) located at 7 km far from the substation The single cell is included between the substation and the parallel post The short circuit has been simulated with a resistance of 1 Ω Tab I shows the numerical results in steady state conditions

Monitored RMS values [A] Distances from the substation [km] Time Domain Frequency domain I f 7 9973 9597 I cl 12 9367 8447 I fe 12 9241 8683 I rail 12 4146 4732 I cl 936 8753 I fe 9235 8677 I rail 6652 7518 Table 2: Comparison of the results of the steady state short circuit analysis [6] Tab 2 evidences that the two models give similar results A slightly higher fault current can be observed in the time domain simulation In order to test the system in transient condition a 5 km traction system has been considered The system of 4 cells includes 1 feeding substation and 4 parallel posts The short circuit is located at the distance of 5 km from the substation in correspondence of the fourth parallel post The short circuit occurs at 5 ms between overhead and buried earth Fig 11 shows the instantaneous waveform of the peak fault current Fig 11: Waveform of the fault current in case of overhead-buried earth wire short circuit By the analysis of the figure it can be noted that the system is characterized by a typical first order dynamic where the peak value depends on the instantaneous system conditions when the short circuit occurs The time constant is a function of the system parameters and for severe short circuit it very slightly depends on the short circuit resistance value To focus on the transient in Fig 12 the positive peak values of the fault current are reported

Fig 12: Positive fault current peak values Conclusions Two methodologies for short circuit current calculation in the 2x25 kv traction system have been proposed The two approaches are performed in frequency and time domains They both represent the physical components by means of respectively the chain matrix and partial differential equation mathematical models The numerical application reported investigates on steady state and transient operating conditions The results of the application are able to assess the suitability to perform short circuit analyses by both the two models Future works will be aimed at validating the numerical applications with experimental results obtained through a measurement campaign References [1] I Senol, H Gorgun, MG Aydeniz: General comparison of the electrical transportation systems that are fed with 1 25 kv or 2 25 kv and expectations from these systems, Electrotechnical Conference, 1998 MELECON 98, 9th Mediterranean, Vol2, 18-2 May 1998 Page(s): 885 887 [2] T H Chen, Y F Hsu, Systematized short-circuit analysis of a 2x25 kv electric traction network, Electric Power Systems Research, Vol 47, 1998, pp 133-142 [3] PC Coles, M Fracchia, RJ Hill, P Pozzobon, A Szelag: Identification of catenary harmonics in 3 kv DC railway traction systems, Proceedings of the 7th Mediterranean Electrotechnical Conference, Vol 2, April 1994, pp 825-828 [4] Clayton R Paul: Analysis of Multiconductor Transmission Lines, John Wiley & Sons, November 27 [5] J Arillaga, NR Watson, S Chen: Power System Quality Assessment, John Wiley and Sons, 2 pp171-228 [6] A Amendola, LBattistelli, LCundurro, MPagano, DProto: Short Circuit Modelling and Simulation of 2x25 kv High Speed Railways, accepted to the 1 th International Confeence on Computer Modelling and Simulation, 1-3 April 28 [7] R Cella, G Giangaspero, A Mariscotti, A Montepagano, P Pozzobon, M Ruscelli, and M Vanti: Measurement of AT Electric Railway System Currents at Power-Supply Frequency and

Validation of a Multiconductor Transmission-Line Model, IEEE Transactions on Power Delivery, Vol 21, N3, 26, pp 1721-1726 [8] A Mariscotti, P Pozzobon: Determination of the electrical parameters of railway traction lines: Calculation, measurement and reference data, IEEE Trans Power Del, vol 19, no 4, Oct 24, pp 1538 1546 [9] RJ Hill, DC Carpenter: Rail track distributed transmission line impedance and admittance: theoretical modeling and experimental results, IEEE Transactions on Vehicular Technology, Vol 42, Issue 2, May 1993, pp 225-241 [1] JRCarson: Wave propagation in overhead with ground return, The Bell System Technical Journal, Vol 5, 1926, pp 539-544 [11] CEI EN 699-, Correnti di cortocircuito nei sistemi trifasi in corrente alternata, 21-12 Appendix The results reported are obtained for following parameters of the traction system: Substation transformer parameters Power: 6 MVA, voltage ratio: 132/2x275 kv, short circuit voltage: 1% Auto-transformer Parameters Power: 15 MVA, voltage ratio: 275//-275 kv, short circuit voltage: 1% Multi conductor line parameters Tab A shows the materials, resistivity (Ω/km), sections and positions of all the conductors involved in the systems Description Material Resistance Section X Y [Ω/km] [mm 2 ] [m] [m] Left side track system Feeder Al,19 37-6,6 8, Messanger Cu,15 12-2,5 6,55 Contact line Cu,12 15-2,5 5,3 External Rail UNI6-3,26,1 Internal Rail UNI6-1,74,1 Buried earth wire Cu,19 95-5, -1,12 Protection wire Al,225 15-6,12 5,5 Right side track system Feeder Al,19 37 6,6 8, Messanger Cu,15 12 2,5 6,55 Contact line Cu,12 15 2,5 5,3 External Rail UNI6 3,26,1 Internal Rail UNI6 1,74,1 Buried earth wire Cu,19 95 5, -1,12 Protection wire Al,225 15 6,12 5,5 Table A: Track line parameters