High Performance Railway Power

Size: px
Start display at page:

Download "High Performance Railway Power"

Transcription

1 High Performance Railway Power Introduction to Autotransformer system (AT) Banebranchen Session infrastructure May 9th 2012 Tommy O. Jensen/Atkins Danmark 1

2 Agenda Historical AT system reinvented Principle of operation AT supply system AT system at HSL-railways AT system in Sweden AT system in Norway Advantages/drawbacks of AT Suitable for use in Denmark? 2

3 Historical Valtellina 3 kv 15 Hz, Italien1902 Introduction of AC-systems 1900 AC locomotives are introduced Ganz develops the first AC locomotive (3 kv) 1905 Many AC systems open in the eastern US, among others New York New Haven (11 kv) 1910 Auto transformer supply tends to become a standard on densely traficated lines in USA (e.g. AT-systems +11/-22 kv 25 Hz) 1915 The Iron Ore line Kiruna-Narvik was electrified (15 kv 15 Hz with 80 kv supply) New Haven-system 11/22 kv 25 Hz CG1- loco at kw New York

4 AT system reinvented Increased demands for power necessitates new solutions for train power systems 1972 Japan, Sanyo Shinkansen (25/25 kv 60 Hz) 1981 France, TGV Paris-Lyon (25/25 kv 50 Hz) 1987 Hungary, simplified AT system (25/25 kv 50 Hz) 1995 Sweden, Kiruna Svappavaara (15/15 kv 16,7 Hz) Suitable for busy conventional railways, heavy haul and high speed lines. Substations are expensive and technical complicated installations. 4

5 Operation for Auto Transformer Principle of operation for an Auto Transformer 250 A e 1 +e 2 e A Ampere winding balance: I 1 N 1 = I 2 N 2 ( the ideal transformer ) Power for autotransformator: S AT = U 1 I 1 = U 2 I 2 Common winding = reduced weight, smaller volume, reduced losses Lower price compared to normal two winding transformer. Option for low leak reactance, particularly important in a train power system Draw back no galvanic separation (easier "path" for short circuit currents) 5

6 Terminology for AT systems Normally used terms: Auto transformer only has one coil with three terminations Primary and secondary side have no galvanic separation *) Plus conductor is connected to contact wire and positive feeder (PL) Minus conductor is only connected to negative feeder (NL) Midpoint termination ideally 0 V is connected to track / return circuit Angel between plus and minus conductors is 180 Normal designations are 2x25 kv or +25/-25 kv *) Power supply (transformer) from the high voltage grid, e.g. 220 kv, will normally be galvanic separated from the train power system. 6

7 AC supply system Direct supply running rail (RR) or Direct supply with return conductor (RC) Return conductor RC 7

8 AC supply systems Booster transformer with return conductor (BT-RC) 8

9 AC supply systems Auto transformer with full range voltage supply (AT-2U) Train power transformer with two secondary coils 9

10 AC supply systems Auto transformer with contact wire voltage supply (AT-1U) Train power transformer equipped with one secondary coil Some times named AT-Light 10

11 AC supply systems Earth currents with direct supply (RR) Earth currents with direct supply with return conductor (RC) 11

12 AC supply systems Earth currents with BT system Earth currents with AT system 12

13 AC supply systems Why choose a complicated AT system? Source: Comparison of BT and AT system, EMC-symposium York 1-2. July Prof. György Varju, Budapest University Because supply conditions will improve significantly! 13

14 AC supply systems Why choose a complicated system? NL (-25 kv) Inductance in an overhead line AC system is heavily dependent on the geometric design PL (+25 kv) CL (+25 kv) Inductance can be reduced by a symmetric configuration and small distances between conductors Reduced EMC impact on the surroundings and reduced stray currents with balanced impedances in PL and FL (reduced "leakage" of currents) RR (0 kv) 14

15 AC supply systems Why choose a complicated system? Principle of supply (normal operation) Relative impedance Acceptabel distance single track Booster transformer (BT-RC) 100 % km Direct (RR-RC) ~ 65 % km Direct with supply feeder (RR-RC-FL) ~ 60 % km Auto transformer (AT) ~ % km Possible increased distance between substations Significantly improved quality of voltage Reduced losses Better utilization of brake energy 15

16 AT system at HSL-railway French AT transformer 225 kv /2x27,5 kv Nominal power 72 MVA (36-36 MVA) SNCF TGV 16

17 AT system at HSL-railway Electric layout for AT supply Supply station, feeder cables, substation 17

18 AT system in Sweden Supply system with distributed auto transformers ( AT-Light ) Source: BVS Kraftförsörjningsanläggningar Autotransformatorsystem systembeskrivning, 18

19 AT system in Sweden Supply system with distributed auto transformators ( AT-Light ) Banverket AT system 2 x 15 kv AT-transformers 5 MVA Used at Vännas Umeå line 19

20 AT system in Sweden Supply system with distributed auto transformators ( AT-Light ) 20

21 AT system in Norway Supply system with distributed auto transformators ( AT-Light ) Omformerstasjon 15 kv samleskinne returstrøm samleskinne 1o km 1o km 1o km Negativledning NL -15 kv Positivledning PL + 15 kv Kontaktledning KL + 15 kv 21

22 AT system in Norway 22

23 AT system in Norway 23

24 Advantages / drawbacks AT-system AT system compared to BT system + Very low voltage drop in overhead catenery system. + Reduced losses in overhead catenary system = saved energy! + Auto Transformer every 10th km compared to Booster Transformer every 3rd km. + Possible longer distance between substations. - More conductors mounted in overhead catenary system. - More complicated switching equipment in train power system - Risk of locally higher earth current caused by higher power levels. BT system employed on lines with parallel signaling and telecommunication cables in order to avoid electromagnetic disturbances. AT system can offers the same advantages. AT system is widely used on high speed lines and railways with heavy freight traffic. AT system can be used on long single track lines to reduce numbers of substations. 24

25 AT system interesting in Denmark? Electrification 2011 Existing network too expensive to rebuild. Cost for Kystbanen estimated at 120 mio.kr! Lines to be electrified in the future could prove interesting. 25

26 AT system interesting in Denmark? Electrification till 2020 Lunderskov-Esbjerg København - Ringsted Ringsted Rødby/Femern Note: Yellow substations not yet decided! 26

27 AT-system interesting in Danmark? Probable development after 2020 The rest of Sealand Main lines in Jutland Other local lines

28 Banebranchen Session 2012 May 9th Thank you for your attention! Electric railway at Skærum Teglværk 1909 Electric railway at Ørestad 2012 Questions? 28

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

Estimation of electrical losses in Network Rail Electrification Systems

Estimation of electrical losses in Network Rail Electrification Systems Estimation of electrical losses in Network Rail Electrification Systems Page 1 of 16 Contents 1. BACKGROUND...3 2. PURPOSE...3 3. SCOPE...3 4. DEFINITIONS & ABBREVIATIONS...4 5. NETWORK RAIL INFRASTRUCTURE

More information

Multi-conductor Train Simulations for Electrification Systems

Multi-conductor Train Simulations for Electrification Systems Multi-conductor rain imulations for Electrification ystems 1 Michael Chen, Atkins Roger White, ony Fella, Atkins tuart Hillmansen, Paul Weston University of Birmingham Abstract Railway Operators and Infrastructure

More information

Earthing Guidance Notes

Earthing Guidance Notes Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head

More information

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems Knowing the FACTS FACTS that enhance power quality in rail feeder systems ROLF GRÜNBAUM, PER HALVARSSON, BJÖRN THORVALDSSON The increase in traffic on existing tracks combined with new high-speed rail

More information

Appendix 7. Conceptual Design of Electrification System. December 2010

Appendix 7. Conceptual Design of Electrification System. December 2010 Appendix 7 Conceptual Design of Electrification System December 2010 APPENDIX 7 Conceptual Design of Electrification System December 2010 Prepared for: Prepared by: 20 Bay Street, Suite 901 Toronto ON

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

Modeling of Transmission Lines

Modeling of Transmission Lines Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward

More information

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13 Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

DISCONNECTORS AND LOAD SWITCHES for railways

DISCONNECTORS AND LOAD SWITCHES for railways DISCONNECTORS AND LOAD SWITCHES for railways GRID Disconnectors and load switches for railways Alstom Grid delivers transmission solutions worldwide to utility and large industrial customers seeking smarter,

More information

The electrical energy produced at the gen

The electrical energy produced at the gen 300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5

More information

Steady State and Transient Short Circuit Analysis of 2x25 kv High Speed Railways

Steady State and Transient Short Circuit Analysis of 2x25 kv High Speed Railways Steady State and Transient Short Circuit Analysis of 2x25 kv High Speed Railways 1 L Battistelli, M Pagano DProto, 2 A Amendola, L Cundurro, A Pignotti Università degli Studi di Napoli Federico II, Napoli,

More information

Simulation of Cable Overloading Problem on a University Distribution System

Simulation of Cable Overloading Problem on a University Distribution System Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 765-770 Research India Publications http://www.ripublication.com/aeee.htm Simulation of Cable Overloading

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009 Impedance Matching and Matching Networks Valentin Todorow, December, 2009 RF for Plasma Processing - Definition of RF What is RF? The IEEE Standard Dictionary of Electrical and Electronics Terms defines

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS

SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sawsan Henein AIT Austrian Institute of Technology Electric Energy Systems Research Group SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sustainable Places 2015 Savona,

More information

AMSC s Superconductor Cable Technologies for Electric Utilities

AMSC s Superconductor Cable Technologies for Electric Utilities International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

Figure. 1 - Split Phase 240/120V circuit (180 phase shift) This technical note describes the option of connecting the 60Hz XW Inverter/Charger to a three-phase source by using a transformer to convert the AC source to split-phase 240/120V. INTRODUCTION: Split-phase

More information

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2

More information

Evaluation of first power simulation

Evaluation of first power simulation Evaluation of first power simulation The New Line Copenhagen Ringsted Alignment and Railway Technology 2013-02-12 Alignment and Railway Technology (ART-contract) Page 1 of 47 Evaluation of first power

More information

Alternating Current and Direct Current

Alternating Current and Direct Current K Hinds 2012 1 Alternating Current and Direct Current Direct Current This is a Current or Voltage which has a constant polarity. That is, either a positive or negative value. K Hinds 2012 2 Alternating

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Measure 9: Updating the interoperability directives on high-speed and conventional railway networks First page:

Measure 9: Updating the interoperability directives on high-speed and conventional railway networks First page: Measure 9: Updating the interoperability directives on high-speed and conventional railway networks First page: Policy package: 2A: Rail liberalisation and harmonisation Measure 9: Updating the interoperability

More information

Full representation of the real transformer

Full representation of the real transformer TRASFORMERS EQVALET CRCT OF TWO-WDG TRASFORMER TR- Dots show the points of higher potential. There are applied following conventions of arrow directions: -for primary circuit -the passive sign convention

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008 CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand

More information

Module Title: Electrotechnology for Mech L7

Module Title: Electrotechnology for Mech L7 CORK INSTITUTE OF TECHNOLOGY INSTITIÚID TEICNEOLAÍOCHTA CHORCAÍ Autumn Examinations 2012 Module Title: Electrotechnology for Mech L7 Module Code: ELEC7007 School: School of Mechanical, Electrical and Process

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Properties of electrical signals

Properties of electrical signals DC Voltage Component (Average voltage) Properties of electrical signals v(t) = V DC + v ac (t) V DC is the voltage value displayed on a DC voltmeter Triangular waveform DC component Half-wave rectifier

More information

Phase Attribute Identification using GPS Technology

Phase Attribute Identification using GPS Technology Phase Attribute Identification using GPS Technology Date 11 June 2009 John Sinclair Power Quality Manager Slide 1 Topics of Discussion Remote Phase Identification How it works Principals of operation Benefits

More information

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR 1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.

More information

Background Information

Background Information Background Information Munich, June 4, 2015 ehighway: a vision of electrified freight traffic As it will not always possible to transfer more freight traffic to the rail, this traffic will have to be carried

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

reduction ore = metal oxides metal oxidation

reduction ore = metal oxides metal oxidation Cathodic Protection and Interferences René Gregoor Madrid, June 18 th and 19 th 2009 1 Cathodic protection and interferences Corrosion Cathodic protection Protection criterion ON potential measurements

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity

More information

Inductors & Inductance. Electronic Components

Inductors & Inductance. Electronic Components Electronic Components Induction In 1824, Oersted discovered that current passing though a coil created a magnetic field capable of shifting a compass needle. Seven years later, Faraday and Henry discovered

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

Reduction of Power Losses Using Phase Load Balancing Method in Power Networks

Reduction of Power Losses Using Phase Load Balancing Method in Power Networks Proceedings of the World Congress on Engineering and Computer Science 009 Vol I WCECS 009, October 0-, 009, San Francisco, USA eduction of Power Losses Using Phase Load Balancing Method in Power Networks

More information

Radial Distribution Test Feeders

Radial Distribution Test Feeders Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published

More information

Report on structure and functionalities of the new online energy efficiency screening tool for railways

Report on structure and functionalities of the new online energy efficiency screening tool for railways Railenergy Calculator Report on structure and functionalities of the new online energy efficiency screening tool for railways Project No. FP6 031458 Railenergy Innovative Integrated Energy Efficiency Solutions

More information

(3 )Three Phase Alternating Voltage and Current

(3 )Three Phase Alternating Voltage and Current EEE 2015 EECTRCS (3) Monophase 1 Three phase Three phase electric power is a common method of alternating current electric power generation, transmission, and distribution. t is a type of polyphase system

More information

AN96-07. Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x

AN96-07. Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x On January 1, 1996, exports into Europe began facing some tough transient immunity standards. The International Electrotechnical Commission (IEC), a worldwide

More information

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope 3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service

More information

Definition AC Power Distribution

Definition AC Power Distribution COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility

More information

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12 Table of Contents The Basics of Electricity 2 Using a Digital Multimeter 4 IDEAL Digital Multimeters An Introduction The Basics of Digital Multimeters is designed to give you a fundamental knowledge of

More information

Business Area Power Supply

Business Area Power Supply Business Area Power Supply 1 Our competence areas Alternating current supply for Main line railways Feeder stations (16.7 Hz, 25 Hz and 50 Hz) Transformer stations Substations Sectioning stations Switchgear

More information

EMI in Electric Vehicles

EMI in Electric Vehicles EMI in Electric Vehicles S. Guttowski, S. Weber, E. Hoene, W. John, H. Reichl Fraunhofer Institute for Reliability and Microintegration Gustav-Meyer-Allee 25, 13355 Berlin, Germany Phone: ++49(0)3046403144,

More information

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/ Course Learning Outcome (CLO) Upon completion of this course, students should be able to: Apply the principles of three phase systems,

More information

Summary of Electric Transmission Assessment Report

Summary of Electric Transmission Assessment Report Summary of Electric Transmission Assessment Report January 2010 Assessment and Analysis of the State-Of-the-Art High-Voltage Electric Transmission Systems with Specific Focus on High-Voltage Direct Current

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Increasing Data Center Efficiency by Using Improved High Density Power Distribution Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

13 ELECTRIC MOTORS. 13.1 Basic Relations

13 ELECTRIC MOTORS. 13.1 Basic Relations 13 ELECTRIC MOTORS Modern underwater vehicles and surface vessels are making increased use of electrical actuators, for all range of tasks including weaponry, control surfaces, and main propulsion. This

More information

PowerWorld Transmission Line Parameter Calculator

PowerWorld Transmission Line Parameter Calculator PowerWorld Transmission Line Parameter Calculator Introduction The PowerWorld Transmission Line Parameter Calculator is a tool designed to compute characteristic line parameters given the type of the conductor

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT S METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to center of meter ± 100 mm ( 4

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Kinetic energy recovery on railway systems with feedback to the grid

Kinetic energy recovery on railway systems with feedback to the grid Kinetic energy recovery on railway systems with feedback to the grid Authors: J.M. ORTEGA, METRO DE BILBAO;S:A: H. IBAIONDO, A. ROMO. INGETEAM TRACTION,S.A. 1. Introduction The increasing concern with

More information

Data center power dynamics within the settings of regional power grid

Data center power dynamics within the settings of regional power grid Data center power dynamics within the settings of regional power grid Gulnara Zhabelova 1, Alireza Yavarian 1, Valeriy Vyatkin 1,2 1 Department of Computer Science, Electrical and Space Engineering Lulea

More information

Comparison of Power Título Transmission Line Models with Finite Elements

Comparison of Power Título Transmission Line Models with Finite Elements CEPEL Comparison of Power Título Transmission do trabalho Line Models with Finite Elements Carlos K. C. Arruda, Anny A. Silveira, Fernando C. Dart Autor/apresentador Área Departamento de Linhas e Estações

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS Bachelor's Thesis Electrical Engineering June 2014 SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS MD FARUQUL ALAM SALMAN SAIF HAMID ALI School of Engineering Blekinge Tekniska

More information

Paralleling Power Sources Which Share a Common Neutral

Paralleling Power Sources Which Share a Common Neutral Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share

More information

Electrical Fault Level Calculations Using the MVA Method

Electrical Fault Level Calculations Using the MVA Method J.M. PNG & SH PT LTD Chapter lectrical ault Level Calculations Using the Method 5 With modern day personal computers, hand calculations for electrical fault level are becoming a thing of the past. The

More information

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB

More information

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use

More information

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012 INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably

More information

DC Traction Power Supply. Powerful, efficient and safe. siemens.com/mobility

DC Traction Power Supply. Powerful, efficient and safe. siemens.com/mobility DC Traction Power Supply Powerful, efficient and safe siemens.com/mobility 2 DC traction power supply More people, more challenges, one solution: Complete mobility. Needed more than ever before: Not only

More information

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49 Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large

More information

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Variable Frequency Drives - a Comparison of VSI versus LCI Systems Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been

More information

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission

More information

Treasure Valley Electric Plan - Community Advisory Committee

Treasure Valley Electric Plan - Community Advisory Committee Treasure Valley Electric Plan - Community Advisory Committee What is a transmission line and why are they necessary? A transmission line is used to conduct electricity between two points. Without high

More information

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Electrical safety requirements in DC distribution systems

Electrical safety requirements in DC distribution systems Electrical safety requirements in DC distribution systems PAUL J.L.AN TICHELEN, DOMINIQUE WEYEN ITO Boeretang 200, 2400 Mol BELGIUM Abstract: This paper focuses on the safety requirements for the DC bus

More information

OFFSHORE WIND FARM ELECTRICAL CONNECTION OPTIONS. W.Grainger 1 and N.Jenkins 2 SYNOPSIS

OFFSHORE WIND FARM ELECTRICAL CONNECTION OPTIONS. W.Grainger 1 and N.Jenkins 2 SYNOPSIS OFFSHORE WIND FARM ELECTRICAL CONNECTION OPTIONS W.Grainger 1 and N.Jenkins 2 1 Border Wind Ltd, Hexham 2 Dept of Electrical Engineering and Electronics, UMIST SYNOPSIS The development of large scale offshore

More information

EARTHING SYSTEM CALCULATION

EARTHING SYSTEM CALCULATION BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331) Lab 5: Single-phase transformer operations. Objective: to examine the design of single-phase transformers; to study the voltage and current ratios of transformers; to study the voltage regulation of the

More information

Three phase circuits

Three phase circuits Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors

More information

Chapter 11. Inductors ISU EE. C.Y. Lee

Chapter 11. Inductors ISU EE. C.Y. Lee Chapter 11 Inductors Objectives Describe the basic structure and characteristics of an inductor Discuss various types of inductors Analyze series inductors Analyze parallel inductors Analyze inductive

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables

More information