Thermal efficiency characteristics of indirect evaporative cooling systems



Similar documents
Analysis of data centre cooling energy efficiency

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Chapter 3.4: HVAC & Refrigeration System

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

AIR CONDITIONING TECHNOLOGY

Legacy Data Centres Upgrading the cooling capabilities What are the options?

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

Research on the Air Conditioning Water Heater System

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

HVAC Efficiency Definitions

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Waste Heat Recovery through Air Conditioning System

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS

Heating, Ventilation & Air Conditioning Equipment

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

Large Energy Savings Per Installation VFDs for Large Chillers

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Thermal Coupling Of Cooling and Heating Systems

ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS

District Cooling Plant : Refrigeration Plant Simulation

How To Design A Building In New Delhi

Data Centre Cooling Air Performance Metrics

OPTIMIZATION OF DATA CENTER CHILLED WATER COOLING SYSTEM ACCORDING TO ANNUAL POWER CONSUMPTION CRITERION

Evaporative Cooling for Residential and Light-Commercial

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Small-Scale Solar Heating and Cooling Systems

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

Heating, Ventilation & Air Conditioning Equipment

EVALUATION OF UNDERGROUND RAILWAY NETWORKS OPERATING SUSTAINABLE COOLING SYSTEMS. J.A. Thompson*, G.G. Maidment, J.F. Missenden and F.

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

Evaporative Cooling System for Aquacultural Production 1

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.

Development and testing of a multi-type air conditioner without using AC inverters

Model-Based Approach for Optimizing a Data Center Centralized Cooling System

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

Energy Recovery Ventilation Equipment

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

3/29/2012 INTRODUCTION HVAC BASICS

Performance Rating of Room Fan- Coils

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

Wet Bulb Temperature and Its Impact on Building Performance

AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

Building HVAC Load Profiling Using EnergyPlus

HVAC Systems: Overview

STULZ Water-Side Economizer Solutions

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Cooling kw Heating kw

Todd M. Rossi, Ph.D. President

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Information Guide Domestic Air Source Heat Pumps

Tips and Tricks for Estimating Energy Savings. Celeste Cizik, P.E. Project Manager E M C Engineers, Inc.

Energy savings in commercial refrigeration. Low pressure control

Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions Sponsored by:

ASHRAE Climatic Data Activities. Dru Crawley Didier Thevenard

A heat pump system with a latent heat storage utilizing seawater installed in an aquarium

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

*At the AHRI Standard flow rate of 3 gpm/ton, using today s efficient chillers, the ΔT is 9.3 F rather than the 10 F often assumed.

Testing methods applicable to refrigeration components and systems

Optimization of a Hybrid Ground Source Heat Pump using the Response Surface Method

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

News in Data Center Cooling

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

How Ground/Water Source Heat Pumps Work

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

FEASIBILITY OF A BRAYTON CYCLE AUTOMOTIVE AIR CONDITIONING SYSTEM

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

SWISSOLAR 2104 TASK 44 SOLAR AND HEAT PUMP SYSTEMS

HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium

Simulation of a small size solar assisted adsorption air conditioning system for residential applications

Transcription:

International Conference Paive and Low Energy Cooling 549 Thermal efficiency characteristics of indirect evaporative cooling systems B. Costelloe Department of Building Services Engineering, Dublin Institute of Technology, Ireland D.P. Finn Department of Mechanical Engineering, University College Dublin, Ireland ABSTRACT Recent developments in enhancing heat transfer in cooling towers, together with the succe of chilled ceilings, have prompted a review of the evaporative cooling technique. in temperate maritime climates. The thermal efficiency of such systems is a key parameter, as a measure of the degree to which the system has succeeded in exploiting the cooling potential of the ambient air. This paper presents the results of experimental research into the thermal efficiency of a water-side open indirect evaporative cooling test rig designed to achieve low (1-4 K) approach conditions. Secondary efficiencies in the range 4-0.76 have been achieved. 1. INTRODUCTION For many years, interest in evaporative cooling, NOMENCLATURE T ps primary loop supply temp. ( C) T pr primary loop return temp. ( C) T secondary loop supply temp. ( C) T secondary loop return temp. ( C) T as ambient adiabatic sat. temp. (AST) ( C) T pa primary approach temp. (PAT)(K) T sa secondary approach temp. (SAT)(K) η t thermal efficiency Subscripts ps primary supply pr primary return secondary supply secondary return as adiabatic saturation pa primary approach sa secondary approach as an effective cooling technique for buildings, was focus on hotter dry latitudes (Watt, 1986), where it was seen as being mainly applicable. Up to quite recently this focus has persisted (Bom et al., 1999). Recent work however on airside (IEA, 2001), and water-side (Costelloe and Finn, 2003a) evaporative cooling, has demonstrated the considerable potential of the technique in temperate and maritime European regions. While the water-side evaporative cooling technique can be exploited with any water based building cooling system, the technique is particularly advantageous when used in conjunction with a chilled ceiling system, due to the higher cooling water temperatures (14-18 C) which are employed and hence the higher cooling water availability levels which result. The natural governing parameter in evaporative cooling is the wet bulb temperature (WBT) of the ambient air. The difference between the adiabatic saturation temperature (AST) and WBT is generally le than 5 K where the wet bulb depreion is le than 11 K (Kuehn et al., 1998). The AST is used in this paper, in preference to the WBT as it is a fundamental property and can be determined without using empirical quantities. Figure 1 shows a simplified schematic of a water side indirect evaporative cooling system, with the key operating parameters indicated. An important performance parameter is the primary approach temperature (PAT) which is equal to T ps - T as. This aspect is complicated by the requirement, in contemporary applications, to separate the tower water circuit from the building cooling circuit with a heat exchanger. Hence the significant performance parameter becomes the secondary approach temperature (SAT)

550 International Conference Paive and Low Energy Cooling air out T pr T secondary circuit pump typical 18ºC open counter flow cooling tower range temperature K counterflow plate heat exchanger chilled ceiling or other cooling load fan T ps T typical 15ºC adiabatic saturation temperature or wet bulb temperature of ambient air at inlet T as (AST) primary circuit pump (PAT) T pa primary approach temperature K T sa (SAT) secondary approach temperature K Figure 1: Simplified schematic of a water-side indirect evaporative cooling system. which is equal to T - T as. It has been shown that cooling water availability levels heavily depend on the approach conditions achieved in European locations and that SATs as low as 3K are technically feasible with contemporary cooling tower packing surface densities of 200m 2 /m 3 and low approach plate heat exchangers (Costelloe and Finn, 2003a). Hence when chilled ceiling systems are used, with typical cooling water supply temperatures of 14-18 C considerable levels of cooling water availability are poible in many European (Costelloe and Finn, 2003a) and some Middle Eastern cities, as indicated in Table 1. These cities have similar design WBTs (the variation range is +/- 1.3 K) but have significantly different and in some cases widely different dry bulb temperatures (DBT) and locations. There are two basic approaches to this form of indirect cooling system (i) the closed wet cooling tower and (ii) the open tower with external plate heat exchanger. Each arrangement has advantages in particular circumstances and locations (Costelloe and Finn, 2000). While much research has been done on the closed tower in this application (Facao and Oliveira, 2000) there is a need to investigate the thermal performance of the open tower in operating conditions well outside those encountered in refrigeration condenser heat rejection - range and approach conditions as low as 1-4 K, cooling water temperatures of 14-18 C and ambient conditions of < 20 C AST. These conditions result in much smaller levels of enthalpy difference, the key driving force in the tower, and therefore smaller aociated heat and ma transfer rates with, crucially, resulting higher air and water flow rates. To addre these iues an experimental research facility has been developed at the Dublin Institute of Technology and is described elsewhere (Costelloe and Finn, 2000). The thermal efficiency (η t ) of the proce is defined as the cooling achieved as a fraction of the maximum poible cooling which could have been achieved in the ambient conditions pertaining. As such it is a key performance parameter and is a suitable means of aeing the thermal characteristics of the system. For the secondary circuit this parameter is defined by equations (1), similar equations define the primary circuit: T ηt = s T = as = ( T ) + ( T ) Sec. Range ( Sec. Range) + ( Sec. Approach) T as (1)

International Conference Paive and Low Energy Cooling 551 Table 1: European and Middle Eastern cities with similar design wet bulb temperatures (WBT) but different design dry bulb temperatures (DBT). Table in ascending order of the 1% design WBT (ASHRAE, 1997) City 1% DBT C 1% WBT C 2% WBT C Dublin 2 17.1 16.3 Uppsala 23.7 17.2 16.2 Copenhagen 23.2 17.4 16.5 Oslo(Fornebu) 24.8 17.4 16.5 Helsinki 24.1 17.6 16.7 Birmingham 23.9 17.6 16.7 Plymouth 22.1 17.6 17.0 Stockholm (Bromma) 24.2 17.7 16.7 Al Jawf 39.7 17.7 17.3 Hof 25.0 17.8 16.8 Ankara 3 17.8 17.0 Bristol 24.5 18.2 17.3 Khamis Mushayt 3 18.2 17.6 Gdansk 24.8 18.3 17.2 Luxembourg 26.1 18.5 17.6 Brest 23.5 18.6 17.7 Salamanca 32.0 18.6 17.8 Prague 26.8 18.7 17.8 London (Heathrow) 25.7 18.7 17.8 Hamburg 25.9 18.8 17.9 Oostende 23.0 18.8 18.0 Munich 27.1 18.8 18.1 Zurich 26.4 18.9 18.1 Abha 29.9 19.0 18.3 Salzburg 27.9 19.1 18.2 Leipzig 27.6 19.2 18.4 Amsterdam 24.8 19.2 18.4 Koln 27.7 19.4 18.3 Geneva 28.5 19.4 18.6 Moscow 26.0 19.5 18.6 Vienna (Schwechat) 28.4 19.6 18.9 2. RESULTS AND DISCUSSION OF TESTS Tests were conducted to investigate the impact of a range of operating variables on the thermal efficiency achieved. These variables include the cooling load imposed, the primary and secondary circuit water flow rate, the cooling tower air flow rate and the ambient AST. The parameter being examined was varied while the other test rig variables were maintained constant. As there is no control over the ambient AST a larger number of tests were conducted and those tests with near similar AST selected. Generally the criterion used is that the AST should not vary within the selected test group by more than +/- 0.9 K. 2.1 Return water temperature variation It would be expected that tower return water temperature has no significant bearing on the primary thermal efficiency (PTE) achieved when primary water flow rate, load and cooling tower air flow rate are maintained constant. Holding these variables constant maintains the tower range temperature constant and as the AST is also approximately constant (and therefore the approach is constant) the thermal efficiency is maintained approximately constant. By the same reasoning, for the secondary circuit, the secondary thermal efficiency (STE) is also maintained approximately constant. Figure 2 shows the results of the tests conducted to verify this aspect. It is seen that the tower return water temperature has no impact on the thermal efficiency achieved in these tests. 2.2 Cooling load variation Tests were conducted to investigate the impact of load variation on the PTE and STE. In these tests as the imposed cooling load changes the range temperatures change in direct proportion, as the cooling water flow rates remain constant. Table 2 shows the results of these tests. The results clearly show that the thermal efficiency is not affected by changes in load. This implies, as shown in Equation (2), that the proportional change in the approach condition (F a ) must be approximately equal to the proportional change in the range condition (F r ), as the load is varied. As the change in the range condition is linear Secondary Thermal Efficiency 1 0 19.8 20.3 2 21.3 21.8 Sec. Cooling Water Return Temperature (C) Figure 2: Constant secondary thermal efficiency with variation in secondary cooling water return temperature (load 20kw; AST 15.7 C +/- 0.5 K; flow rates: primary 2.3 kg/s, secondary 1.6 kg/s, air 3.3 kg/s).

552 International Conference Paive and Low Energy Cooling Table 2: Variation in thermal efficiency with load (flow rates: primary 2.3kg/s, secondary 1.6 kg/s, air 3.3 kg/s). Cooling load kw Adiabatic saturation temp. C Primary thermal efficiency Secondary thermal efficiency 24 8.9 0.52 0.50 24 9.2 0.53 0.51 20 8.5 0.56 0.52 20 9.1 0.52 0.51 15 8.7 0.56 0.52 15 9.3 0.50 0.50 15 9.8 0.50 0.50 9 9.2 0.56 0.51 this implies a near linear correlation, for the rig between the load and the approach temperature. η = t p ( T pr ( T )( F ) )( F ) + ( T )( F ) ps pr r ps ps r as a (2) 2.3 Primary Loop Water Flow Rate Variation A large series of tests were conducted to investigate the dependence of the thermal efficiency on the primary water flow rate. These tests were conducted in three groups. For each group the air flow rate and secondary water flow rate was maintained constant while the primary water flow rate was varied. For each group, therefore, there is a constant air to secondary water flow rate ratio (ASWR). A summary of the results of these tests is shown in Figure 3. The results show that the dependence of the secondary thermal efficiency (STE) on the primary water flow rate is generally not particularly strong. The dependence is strongest at the low ASWR of 1.9 and weakest at the high ASWR of 5.5, with dependence weakening as the ASWR increases. While the primary water flow rate has a minimal impact on the STE it has a considerable impact on the energy performance of the proce as measured by the coefficient of performance (COP) achieved. The energy performance of the rig has been described elsewhere (Costelloe and Finn, 2003b). As, in general, the evaporative cooling system should operate at COPs above those achievable with vapour compreion refrigeration, this limits primary water flow rate to a maximum of 1.4 kg/s. Hence, in the next series of tests, conducted to investigate the impact of the air flow rate and secondary water flow rate variation, the primary water flow rate was maintained at 1.4 kg/s. 2.4 Air and Secondary Water Flow Variation Figure 4 shows the impact of air flow rate on the STE for a series of 3 secondary water flow rates (SWFR) - reducing in three equal steps of 33%. It is seen that the impact of both of these variables is highly significant. These are also the two variables, which are controlled, in an actual chilled ceiling installation. The room cooling load is typically controlled by an energy efficient two port valve arrangement (ASHRAE, 2000), which results in a variable secondary water flow rate at the heat exchanger. Cooling tower air flow rate can also be efficiently controlled by using a fan motor inverter to maintain a constant secondary supply water temperature Secondary Thermal Efficiency 0.7 0.5 0.3 y = 8x 0.08 R 2 = 8 y = 1x 0.16 R 2 = 0.95 y = 0.58x 0.11 R 2 = 0.76 ASWR 1.9 ASWR 3.7 ASWR 5.5 0.7 1 1.3 1.6 1.9 2.2 2.5 Primary Loop Flow Rate (kg/s) Figure 3: Variation in secondary thermal efficiency with primary loop flow rate (load 20kW, AST 1 C +/- K, ASWR- air flow rate to secondary water flow rate ratio).

International Conference Paive and Low Energy Cooling 553 Secondary Thermal Efficiency 0.7 0.5 0.3 y = 6x 3 R 2 = 0.98 y = 0.31x 0.58 R 2 = 0.99 y = 4x 7 SWFR 1.2 kg/s R 2 = 0.99 SWFR kg/s SWFR kg/s 1.2 1.6 2.0 2.4 2.8 3.2 3.6 Air Flow Rate (kg/s) Figure 4: Variation in secondary thermal efficiency with air and secondary water loop flow rate (load 20kw, AST 8.4 C +/- 0.9 K, primary water flow rate 1.4 kg/s, SWFR- secondary water flow rate). Thermal Efficiency 1.0 0.9 0.7 0.5 0.3 0.1 0.0 y = 0.020x + 27 R 2 = 0.738 Prim. Ther. Effic. y = 0.013x + 0.377 R 2 = 0.902 Sec. Ther. Effic. 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Ambient AST (C) Figure 5: Variation in thermal efficiency with annual range of AST in Dublin; test rig at full flow rate capacity; lowest primary and secondary approach temperatures (load 20kW, flow rates: primary 2.3 kg/s, secondary 1.6 kg/s, air 3.3 kg/s). (T see Fig. 1), as ambient AST varies (Costelloe and Finn, 2003b). However it is seen that the highest levels of STE (for the test rig 76%) are obtained when the ambient AST is high and the room load is low, a combination which is infrequent in practice, in narrow-plan buildings but which may occur more frequently in deep-plan buildings. It is also seen from the results that approximately similar efficiencies are obtained when both the air flow rate and secondary water flow rate are maximum (52%) and when both are minimum (46%). This indicates that a control strategy, such as described above, maintains a near constant efficiency as air flow rate and water flow rate is reduced in tandem, when ambient AST falls in the off-peak cooling season. 2.5 Ambient AST Variation To examine this aspect a large series of tests were conducted with ambient AST varying from 2-18ºC. For these tests the rig was maintained at maximum air and water flow rate capacity. The results of these tests which are summarised in Figure 5 indicate that both the PTE and STE are

554 International Conference Paive and Low Energy Cooling significantly affected by the ambient AST, with PTE being marginally more affected than STE. The STE increases at a rate of approximately 1.3% per degree rise in ambient AST acro the 16 K range of the tests. This is comparable with but larger than the variation of % per degree in a different range of 10 20ºC WBT reported for the closed tower (Facao and Oliveira, 2000). Hence these results demonstrate that efficiency is inherently greater when the external component of the cooling load is higher in summer. This strengthens the case for water-side evaporative cooling in buildings. 3. CONCLUSIONS The thermal efficiency of an evaporative cooling test rig has been investigated under conditions of varying load, air and water loop flow rates and ambient adiabatic saturation temperature (AST). A range of secondary thermal efficiency (STE) of 4-0.76 has been found with primary thermal efficiency (PTE) in the range 6-2. The following specific conclusions can be drawn: - Primary and secondary water return temperatures and the imposed cooling load have no significant effect on the efficiency achieved (Fig. 2, Table 2). - Primary water flow rate has minimal impact on the STE achieved. The impact is stronger but not dominant at lower air to secondary water flow rate ratios (Fig. 3). - Air flow rate has considerable impact on the STE achieved with efficiency decreasing with reducing air flow rate. However STE increases as the secondary water flow rate is reduced. A control strategy, therefore, which uses a variable air and water ma flow rate to respond to varying ambient and load conditions tends to maintain a near constant thermal efficiency (Fig. 4). - Results indicate that the ambient AST has a substantial impact on the PTE and a marginally lower impact on the STE. The STE increases at a rate of approximately 1.3% per degree rise in ambient AST acro the 16 K range of the tests (Fig. 5). ACKNOWLEDGEMENTS This work is supported by research grants from CIBSE, Enterprise Ireland and the Dublin Institute of Technology. REFERENCES ASHRAE, 1997. Fundamentals. Atlanta, GA: ASHRAE ASHRAE, 2000. HVAC Systems and Equipment. Atlanta, GA: ASHRAE. Bom, J.G., R. Foster, E. Dijkstra and M. Tummers, 1999. Evaporative Air-Conditioning - Applications for Environmentally Friendly Cooling. Washington, D.C.: World Bank Technical Paper No. 421. Costelloe, B. and D. Finn, 2000. The design and performance of an evaporative cooling test rig for a maritime climate, Proceedings, Joint CIBSE/ASHRAE Conference, Dublin, September, pp.830-845. Costelloe, B. and D. Finn, 2003a. Indirect evaporative cooling potential in air-water systems in temperate climates. Energy and Buildings 35 (6): pp. 573-591. Costelloe, B. and D. Finn, 2003b. Experimental energy performance of open cooling towers used under low and variable approach conditions for indirect evaporative cooling in buildings. Building Services Engineering Research and Technology 24 (3): 163-177 Facao, J. and A.C. Oliveira, 2000. Thermal behaviour of closed wet cooling towers for use with chilled ceilings. Applied Thermal Engineering. 20. pp 1225-36. IEA, 2001. Low Energy Cooling - Annex 28 Subtask 2. (ed. Barnard, N. and D. Jaunzens)International Energy Agency/Construction Research Communications, UK. Kuehn, T.H., J.W. Ramsey and J.L. Threlkeld, 1998. Thermal Environmental Engineering. N.J:Prent. Hall. Watt, J.R., 1986. Evaporative air conditioning handbook. New York: Chapman and Hall.