HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet



Similar documents
PM734F - Technical Data Sheet Winding 28

UCI274C - Technical Data Sheet

UCI274H - Technical Data Sheet

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI734D - Technical Data Sheet

PI734B - Technical Data Sheet

BCI184E - Technical Data Sheet

3790 en / d. Alternators LSA Pole. Electrical and mechanical data

STAMFORD Product Guide

IGSA POWER GENERATION SYSTEMS

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

SYNCHRONOUS MACHINES

Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Physical Address: City: State: Zip Code:

CUKUROVA GENERATOR SYSTEMS

CUKUROVA GENERATOR SYSTEMS

CUKUROVA GENERATOR SYSTEMS

Automatic Voltage Regulator User s Manual

Rules for Classification and Construction Additional Rules and Guidelines

CUMMINS SERIE 6B. Definiciónes. Potencia Prime. Potencia Stand by. Estos valores son aplicables para el suministro de energía eléctrica continua

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

CUKUROVA GENERATOR SYSTEMS

Verification of Short Circuit Test Results of Salient Poles Synchronous Generator

Torque motors. direct drive technology

Basics of Electricity

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

CUKUROVA GENERATOR SYSTEMS

Application Information

Paralleling Power Sources Which Share a Common Neutral

AC-Synchronous Generator

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

WIND TURBINE TECHNOLOGY

R448 & R448 V50 A.V.R.

High Efficiency Motor Protection. Industry White Paper

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Lab 8: DC generators: shunt, series, and compounded.

FIT TIER 2 Application

Synchronous motor. Type. Non-excited motors

Offshore Platform Powered With New Electrical Motor Drive System

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:

Generators TEM. for small hydroelectric power stations. Electric Machines

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual

Annex-A TECHNICAL SPECIFICATION

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

Mounting Instructions. Torque Transducer. A en

FAULT FINDING MANUAL. For Stamford AC Generators

TECHNICAL DATA 50HZ MPMC POWERTECH CORP. DIESEL GENERATING SET

FREQUENCY CONTROLLED AC MOTOR DRIVE

Diesel Generator Set Model DFHC 60 Hz

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP

TECHNICAL DATA 60HZ MPMC POWERTECH CORP. DIESEL GENERATING SET

3753 en /b VE/B - VE/RG Va V riable speed drives

Diesel Generator Set Model DFMB 60 Hz

Table of Contents. TransformerIQ FAQs 1

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

R438 A.V.R. Installation and maintenance R 438. This manual is to be given to. the end user T10. Armature 6- Field X2 Z1 X1 Z2 E+ E- 0V

Welcome to Linear Controls Quarterly Training

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

Unit 33 Three-Phase Motors

S Y N C H R O N O U S G E N E R A T O R S

Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR

Diesel Engine Driven Generators Page 1 of 6

ET 332b Ac Electric Machines and Power Systems

Spark-ignited generator set

DIESEL GENERATOR SET. 60 Hz FEATURES GENERATOR SET

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

DIESEL GENERATOR SETS

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

IV. Three-Phase Induction Machines. Induction Machines

Brochure. Electric generators to power the world

SHIP SERVICE GENERATORS (AC)

Motor Fundamentals. DC Motor

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

Rotary screw compressors kw 5,5 7, , bar MODULO

The following table shows approximate percentage wise the

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw

The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.

D.C. Motors. Products and specifications subject to change without notice.

SUNON SPECIFICATION FOR APPROVAL

How the efficiency of induction motor is measured?

COMPUTER AIDED ELECTRICAL DRAWING (CAED) 10EE65

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw

Cable Solutions for Servo and Variable Frequency Drives (VFD)

6. Synchronous machine dynamics

The reliability of the grid

Thyristor-controlled power supplies and battery chargers

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

C Standard AC Motors

Diesel Generator Set Model DGDK 60 Hz

Mecc Alte 400Hz In Depth

Power System Harmonics

Transcription:

HCM434F - Winding 311 Technical Data Sheet

HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and certifications can be considered on request. VOLTAGE REGULATORS MX341 AVR - STANDARD This sophisticated Automatic Voltage Regulator (AVR) is incorporated into the Stamford Permanent Magnet Generator (PMG) control system, and is standard on marine generators of this type. The PMG provides power via the AVR to the main exciter, giving a source of constant excitation power independent of generator output. The main exciter output is then fed to the main rotor, through a full wave bridge, protected by a surge suppressor. The AVR has in-built protection against sustained over-excitation, caused by internal or external faults. This de-excites the machine after a minimum of 5 seconds. An engine relief load acceptance feature can enable full load to be applied to the generator in a single step. If three-phase sensing is required with the PMG system the MX321 AVR must be used. We recommend three-phase sensing for applications with greatly unbalanced or highly non-linear loads. MX321 AVR The most sophisticated of all our AVRs combines all the features of the MX341 with, additionally, three-phase rms sensing, for improved regulation and performance. Over voltage protection is built-in and short circuit current level adjustments is an optional facility. WINDINGS & ELECTRICAL PERFORMANCE All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches, when in parallel with the mains. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion. TERMINALS & TERMINAL BOX Standard generators are 3-phase reconnectable with 12 ends brought out to the terminals, which are mounted on a cover at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access. SHAFT & KEYS All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key. INSULATION/IMPREGNATION The insulation system is class 'H'. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components. QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2% DE RATES All values tabulated on page 8 are subject to the following reductions 5% when air inlet filters are fitted. 3% for every 500 metres by which the operating altitude exceeds 1000 metres above mean sea level. 3% for every 5 C by which the operational ambient temperature exceeds 50 C. Note: Requirement for operating in an ambient exceeding 60 C must be referred to the factory. NB Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding. Front cover drawing typical of product range. 2

HCM434F WINDING 311 CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G. A.V.R. MX321 MX341 VOLTAGE REGULATION ± 0.5 % ± 1.0 % With 4% ENGINE GOVERNING SUSTAINED SHORT CIRCUIT INSULATION SYSTEM PROTECTION RATED POWER FACTOR STATOR WINDING WINDING PITCH WINDING LEADS STATOR WDG. RESISTANCE ROTOR WDG. RESISTANCE EXCITER STATOR RESISTANCE EXCITER ROTOR RESISTANCE REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7) CLASS H IP23 0.8 DOUBLE LAYER LAP TWO THIRDS 12 0.0073 Ohms PER PHASE AT 22 C SERIES STAR CONNECTED 1.37 Ohms at 22 C 18 Ohms at 22 C 0.068 Ohms PER PHASE AT 22 C R.F.I. SUPPRESSION WAVEFORM DISTORTION MAXIMUM OVERSPEED BEARING DRIVE END BEARING NON-DRIVE END WEIGHT COMP. GENERATOR WEIGHT WOUND STATOR WEIGHT WOUND ROTOR WR² INERTIA SHIPPING WEIGHTS in a crate PACKING CRATE SIZE BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0% 1 BEARING 1160 kg 535 kg 463 kg 5.4292 kgm 2 1230 kg 155 x 87 x 107(cm) 50 2250 Rev/Min BALL. 6317 (ISO) BALL. 6314 (ISO) 2 BEARING 1160 kg 535 kg 440 kg 5.2304 kgm 2 1230 kg 155 x 87 x 107(cm) TELEPHONE INTERFERENCE COOLING AIR THF<2% 0.80 m³/sec 1700 cfm TIF<50 0.99 m³/sec 2100 cfm VOLTAGE SERIES STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277 VOLTAGE PARALLEL STAR 190/110 200/115 208/120 220/127 208/120 220/127 230/133 240/138 VOLTAGE SERIES DELTA 220/110 230/115 240/120 254/127 240/120 254/127 266/133 277/138 kva BASE RATING FOR REACTANCE VALUES 340 340 340 340 395 405 415 425 Xd DIR. AXIS SYNCHRONOUS 2.31 2.09 1.94 1.72 2.85 2.61 2.45 2.30 X'd DIR. AXIS TRANSIENT 0.15 0.14 0.13 0.11 0.16 0.14 0.13 0.13 X''d DIR. AXIS SUBTRANSIENT 0.11 0.10 0.09 0.08 0.11 0.10 0.10 0.09 Xq QUAD. AXIS REACTANCE 2.00 1.80 1.67 1.49 2.52 2.31 2.16 2.03 X''q QUAD. AXIS SUBTRANSIENT 0.26 0.24 0.22 0.20 0.37 0.34 0.32 0.30 XL LEAKAGE REACTANCE 0.05 0.05 0.04 0.04 0.06 0.06 0.05 0.05 X2 NEGATIVE SEQUENCE 0.19 0.17 0.16 0.14 0.25 0.23 0.22 0.20 X0 ZERO SEQUENCE 0.07 0.06 0.06 0.05 0.09 0.08 0.07 0.07 REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED T'd TRANSIENT TIME CONST. T''d SUB-TRANSTIME CONST. T'do O.C. FIELD TIME CONST. Ta ARMATURE TIME CONST. SHORT CIRCUIT RATIO 0.08s 0.019s 1.7s 0.018s 1/Xd 60 3

50 HCM434F Winding 311 THREE PHASE EFFICIENCY CURVES 4

60 HCM434F Winding 311 THREE PHASE EFFICIENCY CURVES 5

30 50 HCM434F Winding 311 Locked Rotor Motor Starting Curve 346V 380V 400V 415V 440V 25 PER CENT TRANSIENT VOLTAGE DIP. PER CENT TRANSIENT VOLTAGE DIP. 20 15 10 5 0 30 25 20 15 10 0 200 400 600 800 1000 1200 1400 LOCKED ROTOR kva 60 380V 416V 440V 460V 480V 5 0 0 200 400 600 800 1000 1200 1400 LOCKED ROTOR kva 6

50 HCM434F Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed Based on star (wye) connection. 10000 SYMMETRICAL ASYMMETRICAL CURRENT (Amps) 1000 60 100 Sustained Short Circuit = 1,750 Amps CURRENT (Amps) 10000 1000 100 0.001 0.01 0.1 1 10 TIME (secs) SYMMETRICAL ASYMMETRICAL 0.001 0.01 0.1 1 10 TIME (secs) Sustained Short Circuit = 2,000 Amps Note 1 Note 2 The following multiplication factors should be The following multiplication factor should be used to convert the used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable to time 0.001 seconds and the minimum current the various types of short circuit : point in respect of nominal operating voltage : 50 60 3-phase 2-phase L-L 1-phase L-N Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30 380v X 1.00 416v X 1.00 Minimum x 1.00 x 1.80 x 3.20 400v X 1.05 440v X 1.06 Sustained x 1.00 x 1.50 x 2.50 415v X 1.09 460v X 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec. 440v X 1.16 480v X 1.15 All other times are unchanged The sustained current value is constant irrespective Note 3 of voltage level Curves are drawn for Star (Wye) connected machines. For other connection the following multipliers should be applied to current values as shown : Parallel Star = Curve current value X 2 Series Delta = Curve current value X 1.732 7

HCM434F Winding 311 / 0.8 Power Factor RATINGS Class - Temp Rise Cont. E - 65/50 C Cont. B - 70/50 C Cont. F - 90/50 C Cont. H - 110/50 C 50 Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220 Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254 kva 260 260 260 260 275 275 275 275 310 310 310 310 340 340 340 340 kw 208 208 208 208 220 220 220 220 248 248 248 248 272 272 272 272 Efficiency (%) 94.5 94.5 94.5 94.5 94.4 94.5 94.5 94.5 94.1 94.3 94.3 94.4 93.9 94.0 94.1 94.2 kw Input 220 220 220 220 233 233 233 233 264 263 263 263 290 289 289 289 60 Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480 Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240 Series Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277 kva 305 315 320 330 320 330 335 345 365 375 380 395 395 405 415 425 kw 244 252 256 264 256 264 268 276 292 300 304 316 316 324 332 340 Efficiency (%) 94.5 94.5 94.6 94.6 94.4 94.5 94.5 94.5 94.2 94.3 94.4 94.4 93.9 94.1 94.2 94.2 kw Input 258 267 271 279 271 279 284 292 310 318 322 335 337 344 352 361 DIMENSIONS 8

Head Office Address: Barnack Road, Stamford Lincolnshire, PE9 2NB United Kingdom Tel: +44 (0) 1780 484000 Fax: +44 (0) 1780 484100 www.cumminsgeneratortechnologies.com Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd Cummins and the Cummins logo are registered trade marks of Cummins Inc. HCM4F-311-TD-EN-SG-A