Steam Coil Installation, Operation and Maintenance



Similar documents
Contents and Nomenclature

Float and Thermostatic Traps Series H, C and X

Steam System Best Practices Condensate System Piping

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

HS-901(A) BASIC STEAM HEATING SYSTEMS

Operation & Maintenance Manual

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

In-Line Air Separators

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

TYPE E Main Valve Sizes 3 /8 through 12

Air Eliminators and Combination Air Eliminators Strainers

BRAZED PLATE INSTALLATION MANUAL

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

Defining Quality. Building Comfort. Heating and Cooling Coils

REGULATING VALVE APPLICATIONS

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Transformer oil cooler ALFA A02

Mechanical Seal Piping Plans

COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here.

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

PBX Series Quick Fit Connector Bimetallic Steam Traps

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Steam System Design and Best Practices Related to Kiln Drying

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Heating Water by Direct Steam Injection

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

VACUUM REFRIGERATION SYSTEMS

DESIGN STANDARDS SECTION

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, Instruction No.

EJECTOR AIR REMOVAL SYSTEMS ENGINEERING DATA BULLETIN # PVS ARS PAGE 1 OF 5

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Purpose:

LH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_001_ Products that provide lasting solutions.

Boiler Preparation, Start-Up and Shutdown

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Installation Manual DIAPHRAGM WELL TANK

Select Radiators Installation Guide

Gas-Fired, Residential Storage Type Water Heaters

FLASH TANK ECONOMIZER PRODUCT GUIDE

INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9

Air/Vacuum Valves. Removal of Air from Pipelines. Allow the Entry of Air into Pipelines. Application:

Theory, Application, and Sizing of Air Valves

WD600 STEAM TRAPS. Thermodynamic Steam Trap

Refrigeration Installation 101

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

C. starting positive displacement pumps with the discharge valve closed.

NFPA31FuelOilPiping 1 Revised

Installer s Guide 18-AH39D1-13

Characteristics of Evaporators

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

What is a successful Steam Trap Management Program?

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

Mechanical Seal Piping Plans

Your safety and the safety of others are very important.

Packaged Terminal Air Conditioner Wall Sleeve Installation

Ceiling Mount Air Handler Manual

Steam Jet Vacuum Pumps

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

Heat exchangers & coolers for industrial applications

REMOTE AIR-COOLED CONDENSERS. Installation and Maintenance Data. Models Bulletin H-IM-73A June 2000 Part Number

LSA LSE, LSR & LST LPA LPE, LPG & LPH LAA LAE, LAG & LAH COMMERCIAL WALK-IN COOLERS AND FREEZERS

Oil and Coolant Circulating Heating System. Model - OCSM

Element D Services Heating, Ventilating, and Air Conditioning

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

SAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE

How To Clean Water From An Ammonia Refrigeration System

Filtering Samples to On-Line Process Analyzers. Guidelines for Proper Filtration and Delivery of Samples to On-Line Process Analyzers

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Circulation Systems for Single and Multiple Seal Arrangements-Part Three

Installation, Operation, & Maintenance Instructions For JFD Shell & Tube Heat Exchangers

Test Code: 8297 / Version 1

Why is my air conditioner dripping on my customers?

Installation and maintenance instructions. Danfoss Vent

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

Service Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.

When Should Examination Preparation Begin?

Miami Heat Pump HP Series Installation Guide

System Solutions for Boiler Air Preheating

AIR CONDITIONING TECHNOLOGY

Motor & Generator coolers QLKE, QDKR A03

Automobile Air Conditioning Primer

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

ASX7-4-IOM-7 J

PREPIPED LIQUID FUEL MANIFOLDS PLPM

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

& MAINTENANCE INSTRUCTIONS INSTALLATION, OPERATION AIR COOLED CONDENSERS FLUID COOLERS HEAT RECLAIM UNITS

Commercial Semi-Instantaneous Water Heaters

MUELLER FALLING FILM CHILLERS

Air Cooled Condensers. Operation and Installation Manual

Direct steam injection humidifiers

First irst Co. Products

Transcription:

Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils manufactured by Luvata in Grenada, MS have been provided to help insure proper performance of the coils and their longevity. These are general guidelines that may have to be tailored to meet the specific requirements of any one job. As always, a qualified party or individual should perform the installation and maintenance of any coil. Protective equipment such as safety glasses, steel toe boots and gloves are recommended during the installation and routine maintenance of the coil. CAUTION! Steam, even at low pressure, can cause serious bodily injury that may result in death. Be sure the system is off or the components are isolated before beginning work Heatcraft steam coils Receiving Instructions All Heatcraft coils are factory tested, inspected and carefully packaged. Damage to the coils can occur after they have left the factory. Therefore, the coils should be inspected for shipping damage upon receipt. The freight bill should also be checked against items received for complete delivery. Damaged and/or missing items should be noted on the carrier s freight bill and signed by the driver. For additional assistance, contact your local Luvata coil representative. Installation, Operation and Maintenance Guide About Luvata Luvata is a world leader in metal solutions manufacturing and related engineering services. Luvata s solutions are used in industries such as renewable energy, power generation, automotive, medicine, air-conditioning, industrial refrigeration, and consumer products. The company s continued success is attributed to its longevity, technological excellence and strategy of building partnerships beyond metals. Employing over 6,300 staff in 17 countries, Luvata works in partnership with customers such as Siemens, Toyota, CERN, and Carrier.

Nomenclature and Mounting Nomenclature 5 = Tube O.D. 5 = 0.625 8 = 1 5 SA 12 01 C 24.00 x 144.00 SA = Coil Type Distributing Tube 5JA, 8JA: same end conn 5GA, 8GA: same end conn 5DA, 8DA: dual supply, opp end conn 5LA, 8LA: dual supply, opp end conn 5RA, 8RA: opp end conn 5TA, 8TA: opp end conn Single Tube 5SA, 8SA: opp end conn 5HA, 8HA: opp end conn 5SB: opp end conn, 3 center-to-center 5HB: opp end conn, 3 center-to-center Standard Steam 5SS: same end conn 5SH: same end conn 12 = Fins Per Inch 01 = Rows C = Fin Design A - flat (Al, Cu) B - corrugated (Al, Cu) C - sine wave (Al, Cu) D - raised lance (Al) F - flat (SS, CS) G - corrugated (SS, CS) H - sine wave (SS, CS, Al, Cu) 24.00 = Finned Length (inches) 144.00 = Fin Height (inches) Mounting Steam coils must be properly mounted for condensate removal. This will aid in preventing destructive water-hammer, keeping coils from freezing, and preventing corrosive elements from collecting in the tubes. Pitched case coils should be installed level as shown in Figure 1a - Pitched in Case. Models SA, SB, HA, JA, GA, DA, LA, RA and TA come standard pitched in the casing. Models SS and SH utilize return bend construction and are not pitched in the casing, but need to be installed level as in Figure 1a. Coils that are unpitched, must be installed with the tubes pitched towards the return connection as shown in Figure 1b (with the exception of models SS and SH). A minimum pitch of 0.125 per foot of coil length is required (pitch has been exaggerated in Figure 1b for illustration to show a case that was not pitched). Unless otherwise requested, all Heatcraft steam coils shall be pitched in case 0.125 /ft. as shown in Figure 1a. Figure 1a: Pitched in Case Supply Return Figure 1b: Unpitched in Case JA, GA DA, LA SS, SH RA, TA SA, HA Figure 2: Steam Coils 2 www.luvata.com

Coil Types Coil Types Distributing Models JA, RA and DA jet-tube steam distributing coils are excellent for any general purpose heating application. With the superior freeze resistance provided by the tube-within-a-tube construction, it is ideal for low temperature preheating and special process applications. The construction features inner tubes with directional orifices to aid in steam distribution and condensate removal. Model JA offers same-end supply and return connections. Model RA offers opposite-end supply and return connections. Model DA offers dual-supply opposite-end connections for long coils that see sub-freezing air temperatures. Models GA, TA and LA utilize cupro-nickel, carbon steel and stainless steel tubing for high-pressure construction. Single Tube Model SA steam coil is designed for general purpose heating. The construction features a single tube design with opposite-end supply and return connections. A perforated baffle located directly behind the supply connection insures proper steam distribution. Model HA utilizes cupro-nickel, carbon steel and stainless steel tubing for high-pressure construction. Standard Steam Model SS steam coil features return-bend construction and same-end connections. Model SH utilizes cupro-nickel, carbon steel and stainless steel tubing for high-pressure construction. Figure 3: Steam Horizontal Coil Piping Diagram Figure 4: Steam Vertical Coil Piping Diagram Air Vent Control Vacuum Breaker Union Optional Location for Air Vent Gate Supply Dirt Leg (6 Min.) Gate Steam Trap 5 PSIG Min Vacuum Breaker Control Air Vent Steam Drip Leg (14 Min.) Union Check Steam Trap Gate Dirt Leg (6 Min.) To Condensate Return Note 1: Vacuum breakers and air vents should be piped to a drain or other suitable location where discharged steam cannot lead to personal injury. 18 (Min) Float & Thermostatic Steam Trap Check Note: If there is back pressure in the condensate reutrn line or if the condensate line is elevated higher than the steam trap, then a pressure powered pump is required in order to drain coil at all times. To Condensate Return Gravity Drain www.luvata.com 3

Installation and Operation Installation 1. Carefully remove the coil from the shipping package to avoid damage to the finned surface area. Damaged fins can be straightened using an appropriate fin comb. 2. Heatcraft recommends cleaning the coil with a commercially available coil cleaner prior to installation. Refer to Maintenance on Page 5 for cleaning recommendations. 3. Mount coil properly to insure positive condensate drainage. Refer to Mounting instructions on page 2. 4. Proper clearance should be maintained between the coil and other structures such as the fan, filter racks, transition areas, etc. 5. Utilize vacuum breakers on each coil. Steam traps require a positive pressure differential to force the condensate through the valve seat. If the coil s pressure drops below atmospheric, the pressure differential across the valve will be negative and the condensate will not drain. This condition can lead to serious damage or failure of the coil due to freezing, water hammer and corrosion. Refer to piping diagram for recommended placement. See Note 1 in Figure 3 - Steam Horizontal Coil Piping Diagram on Page 3. 6. Trap each coil separately. Differences in pressure from coil to coil can result in the backing-up of condensate which will result in poor coil performance and possible damage. 7. Provide an air vent for each coil at its highest location. Luvata provides a 0.5 threaded vent connection on the return manifold as a standard on all steam coils. Non-condensable gasses present in the steam will collect in a coil and reduce its capacity. Therefore, it is necessary to provide a means for the removal of these gasses. Also, these gasses can diffuse into the condensate forming byproducts, which can lead to severe corrosion. See Note 1 in Figure 3 - Steam Coil Piping Diagram on Page 3. 8. Steam supply lines need to be drained of condensate. This can be accomplished by the use of drip legs. This ensures that high quality steam enters the coil. 9. Condensate return piping should be the same size as the coil s return connection from the coil outlet to the steam trap. Not following this guideline could result in the coil to become filled with condensate and the system to stall. For more information on steam stall, see page 5. 10. Once installed, the coil should be pressurized to 100 psig with dry nitrogen or other suitable gas. The coil should be left pressurized for a minimum of 10 minutes. If the coil holds the pressure, the field connections can be considered leak free. If the pressure drops by 5 psig or less, re-pressurize the coil and wait another 10 minutes. If the pressure drops again, there are more than likely one or more small leaks, which should be located and repaired. Pressure losses greater than 5 psig would indicate a larger leak, which should be isolated and repaired. Be sure to check valves and fittings as potential sites for leakage or bleed. 11. All field brazing and welding should be performed using high quality materials and an inert gas purge (such as nitrogen) to reduce oxidation of the internal surface of the coil. 12. All field piping must be self supporting. System piping should be flexible enough to allow for thermal expansion and contraction of the coil. The use of flexible connections and/or swing joints is recommended. 13. The coil along with the control valve and trap should be isolated by manual valves to allow for servicing. 14. For horizontal coil installation, refer to Figure 3 - Steam Horizontal Coil Piping Diagram on Page 3 for general piping. 15. For vertical coil installation, refer to Figure 4 - Steam Vertical Coil Piping Diagram on Page 3 for general piping. 16. If you are unsure about any portion of the installation, contact your local steam specialist for assistance. Failure to properly install the coil can result in irreparable damage to the coil as well as other components in the system. Operation 1. Proper airflow distribution is vital to coil performance. Air-flow anywhere on the coil face should not vary by more than 20%. 2. Air velocities should be maintained between 200 and 1500 feet per minute. 3. Operating pressures must be at or below the maximum operating pressure for that coil at the steam temperature. Pressure and temperature limitations can be determined through Luvata s Pressure and Temperature program. Contact your local Luvata coil representative for assistance. 4 www.luvata.com

Maintenance and System Stall Maintenance 1. Scheduled plant maintenance should include the draining and flushing of the condensate drip legs and sediment traps as well as inspection of condensate traps, vacuum breakers, air vents and valves. Boiler water analysis should also be performed on a regular basis. 2. To continually deliver optimum heating capacity, both the external and internal heat transfer surfaces must be maintained as clean and corrosion free as possible. The finned surface can be maintained by the use and constant inspection of prefilters. The filters should be replaced as needed. 3. Should the finned surface become fouled, the coil can be cleaned utilizing commercially available coil cleaning fluids. Caution should be exercised in selecting the cleaning solution as well as the cleaning equipment. Improper selection can result in damage to the coil and/or health hazards. Be sure to carefully read and follow the manufacturer s recommendations before using any cleaning fluid. Clean the coil from the leaving air-side so that foreign material will be washed out of the coil rather than pushed further into the coil. 4. Internal coil maintenance consists primarily of preventing scale and corrosion. This is accomplished through aggressive boiler water treatment, removal of dissolved oxygen and the removal of non-condensable gasses such as carbon dioxide. NOTE! Boiler water treatment is beyond the scope of this manual. Contact your local water treatment specialist for assistance in establishing a proper boiler-water treatment program. System Stall System stall is lack of positive differential across the steam trap, and temperature controlled equipment will always be subject to this problem when the trap must operate against back pressure. Under these conditions, a vacuum breaker is ineffective because stall always occurs above atmospheric pressure. Even when steam is supplied at a constant pressure or flow to batch type equipment, stall can occur for some period of time on startup when the steam condenses quickly and the pressure drops below the required differential. What happens when the system stalls is that the effective coil area drops as the steam chamber floods and heat transfer is reduced until the control valve responds to deliver an excessive supply of steam to the coil. This results in a hunting system with fluctuating temperatures and hammering coils as the relatively cooler condensate alternately backs up, then at least some portion is forced through the trap. This hunting occurs on the milder temperature days because the coil is sized for the lowest possible air temperature. The coil cannot change surface area, so the steam pressure/temperature control valve takes over to accommodate the change in load. The solution to all system stall problems is to make condensate drain by gravity under all conditions including vacuum. Atmospheric systems tend to operate more predictably and are generally easier to control but major heating equipment is usually not drained into an atmospheric return because of the large amount of energy that is lost from the vent. Primary Types of Drainage Systems 1. Gravity drain to atmospheric (0PSIG) condensate return with no elevation after the steam trap. This gravity drainage system must assure that there is never pressure above atmospheric in the condensate return. CAUTION, failed open steam traps and other leaks from the steam piping to the condensate return piping will pressurize the condensate return enough to cause steam stall. High temperature/pressure condensate will flash back into steam immediately downstream of the steam traps and cause back pressure on the steam traps draining the coil causing steam stall. Condensate return lines designed for atmospheric pressure must be adequately sized to allow for the flash steam and condensate. They must be pitched toward the condensate receiver which is vented to atmosphere. The vent line off of the atmospheric receiver must be sufficient size to vent all flash steam without building up a back pressure in receiver. 2. Closed loop system using an Automatic Pump Trap. To make equipment drain by gravity against back pressure, the steam trap should be replaced by an Automatic Pump Trap (APT). In this arrangement, the equipment does not have a vacuum breaker but is pressure equalized to drain by gravity to the APT, then the equalizing line is isolated while condensate is pumped from the system. This arrangement will drain the coil free of condensate at all times (even under a vacuum). If there is sufficient differential pressure to move the condensate through the APT then it functions as a normal steam trap. Then when needed it functions as a pump, using steam as a motive force to move the condensate to the condensate system. The APT is a simple and efficient solution to a difficult problem. Without the need for high Net Positive Suction Head NPSH, the APT will operate with only 8 installation head from the base of the pump, and remove condensate from a coil under vacuum, atmospheric or higher pressures, discharging to either high or low level condensate return lines. www.luvata.com 5

Luvata Grenada LLC Grenada, MS, USA coils@luvata.com Tel +662 229 4000 Fax +662 229 4212 www.luvata.com Copyright 2014 Luvata