REGULATING VALVE APPLICATIONS
|
|
|
- Randell Godfrey Brooks
- 9 years ago
- Views:
Transcription
1 REGULATING APPLICATIONS GENERAL REGULAR APPLICATION & INSTALLATION NOTES Regulator Application & Installation Notes The following are considerations for all steam regulator installations, as system operation is dependent upon proper design, installation, start-up and maintenance procedures: Inlet & Outlet Pipe Sizing Improperly sized piping can contribute to erratic control and excessive noise in a steam system. Make certain inlet and outlet piping to the regulator is adequately sized for the flow, velocity and pressure requirements. 1-2 SIZES LARGER THAN REGULAR INLET PORT 2-3 SIZES LARGER THAN REGULAR OUTLET PORT RULE OF THUMB: Inlet piping is typically 1-2 sizes larger and outlet piping 2-3 sizes larger than the connection ports of a properly sized regulator. REGULAR Straight Run of Pipe Before and After the Valve Pipe fittings, bends and other accessories contribute to fluid turbulence in a system which can result in erratic control. To limit this and ensure optimum system operation, follow recommended guidelines for minimum straight run lengths of pipe before and after a regulator. DIAMETERS MINIMUM Note: Any isolation valves or pipeline accessories should be full-ported. DIAMETERS MINIMUM Reducer Selection Concentric pipe reducers should be avoided on the inlet side of regulators as they can allow entrained condensate to collect, potentially leading to damaging and dangerous waterhammer. Therefore, when reducers are required in the steam piping to accommodate properly sized valves and pipes, use eccentric reducers on regulator inlets and concentric or eccentric reducers on regulator outlets. CONCENTRIC REDUCER ECCENTRIC REDUCER ACCUMULATED AT LOW POINT 296
2 REGULATING APPLICATIONS GENERAL REGULAR APPLICATION & INSTALLATION NOTES Strainers with Blowdown Valves Regardless of any filters provided on a regulator, a strainer with blowdown valve is recommended before (upstream of) all regulator installations. Pipeline debris and scale can damage internal valve components, potentially leading to poor operation and/or failure. INLET PORT OUTLET PORT BLOWDOWN BELOW PORTS Note: Consider strainer orientation to avoid collection of condensate (see diagram). BLOWDOWN ORIENTED AT SAME ELEVATION AS PORTS AVOID COLLECTION Drip Legs & Steam Traps To prevent condensate accumulated during shutdown from possibly damaging the regulator or piping at start-up, an adequately sized drip leg with steam trap should be installed prior to all regulators. This will also help protect the regulator during normal operation. Note: Separators may be necessary when boiler carryover or wet steam is a concern. DRIP LEG Proper Start-up & Maintenance Procedures It is important to follow good start-up practices to avoid operational complications and potential system damage. Starting a steam system too quickly or using an improper sequence may lead to a potentially hazardous working environment. Lack of system maintenance over time can also contribute to this situation. It is imperative to develop proper start-up and maintenance procedures and train personnel on the importance of following them at all times. Consult equipment manufacturers for specific guidelines, if necessary. 297
3 REGULATING APPLICATIONS SINGLE STAGE REDUCING STATION USING SPRING-LOADED PURPOSE: For reducing system inlet pressure to a constant outlet pressure. OPERATION: The pressure reducing valve (PRV) can be easily adjusted to set the desired outlet pressure and modulates to maintain that pressure setting. The PRV requires no external power source. INSTALLATION GUIDELINES: (see Figure 8) This example depicts a pilot-operated steam PRV, whereby an external sensing line is required to sense downstream pressure. The end of the sensing line is placed away from the turbulent flow of the valve outlet. This helps to improve accuracy of the set pressure. Set pressure is adjusted by turning a screw on the pilot to increase or decrease compression on a balancing spring. For optimum operation and service life, maintain recommended minimum piping straight runs before and after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream of the regulator is to keep the steam velocity constant on both sides of the regulator. The pressure sensing line should slope downwards, away from the regulator, to prevent condensate from entering the pilot. Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could become entrained with high-velocity steam, possibly resulting in dangerous waterhammer. While the separator shown upstream is appropriate for protection of the PRV, it is not always required as a properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known to be wet and the entrained moisture could affect valve performance and/or result in component damage. Consider installing a properly sized bypass line with globe valve to provide continuous operation should regulator maintenance be required. Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging into condensate return lines. Check valves eliminate the possibility of condensate backing up through the steam trap into the system. A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle the complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRV sizing guidelines. 298
4 REGULATING APPLICATIONS SINGLE STAGE REDUCING STATION USING SPRING-LOADED Figure 8: INLET VENT SRV BYPASS GLOBE SEPARAR DIAMETERS MINIMUM HDP REGULAR SENSING LINE DRIP PAN ELBOW APPLICATION DEPENDENT ECCENTRIC REDUCER CONCENTRIC REDUCER DIAMETERS MINIMUM SINGLE STAGE REDUCING STATION USING SPRING-LOADED (HD REGULAR APPLICATIONS) OUTLET 299
5 REGULATING APPLICATIONS REDUCING STATION with AIR-LOADED for REMOTE INSTALLATIONS PURPOSE: For reducing system inlet pressure to a constant outlet pressure when valve is located in a remote location and/or using air pressure for control is desired. OPERATION: This combination of HD regulating valve and A-pilot (HDA) allows air to be used to control outlet pressure in lieu of the spring of a standard P-pilot. Using air allows for simple adjustment of control pressure when valve is installed in a remote and/or difficult to access location. INSTALLATION GUIDELINES: (see Figure 9) The desired set outlet pressure will determine the specific A-Pilot required as well as the air supply pressure to attain the set pressure. Consult the appropriate section of this catalog or the factory for selection guidelines. For optimum operation and service life, maintain recommended minimum piping straight runs before and after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream of the regulator is to keep the steam velocity constant on both sides of the regulator. The pressure sensing line should slope downwards, away from the regulator, to prevent condensate from entering the pilot. Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could become entrained with high-velocity steam, possibly resulting in dangerous waterhammer. While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known to be wet and the entrained moisture could affect valve performance and/or result in component damage. Consider installing a properly sized bypass line with globe valve to provide continuous operation should regulator maintenance be required. Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging into condensate return lines. Check valves eliminate the possibility of condensate backing up through the steam trap into the system. A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle the complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRV sizing guidelines. 300
6 REGULATING APPLICATIONS REDUCING STATION with AIR-LOADED for REMOTE INSTALLATIONS Figure 9: INLET VENT SRV BYPASS GLOBE SEPARAR DIAMETERS MINIMUM A SENSING LINE DRIP PAN ELBOW APPLICATION DEPENDENT HDA REGULAR CONTROL AIR LINE DIAMETERS MINIMUM PL2 AIR SUPPLY AIR REGULAR REDUCING STATION with AIR-LOADED for REMOTE INSTALLATIONS (HD REGULAR APPLICATIONS) OUTLET 301
7 REGULATING APPLICATIONS TWO-STAGE (SERIES) REDUCING STATION PURPOSE: For reducing system inlet pressure to a constant outlet pressure when the pressure drop exceeds the recommended operation of a single-stage pressure regulating valve (PRV). OPERATION: The 1st stage PRV reduces inlet pressure to an intermediate pressure. The 2nd stage PRV then reduces pressure to the final outlet pressure. Individual valve setting and operation is the same as for single-stage applications. INSTALLATION GUIDELINES: (see Figure 10) This example depicts a two-stage (series) pilot-operated steam PRV pressure reducing station using HDP regulators. An external sensing line is required to sense downstream pressure from each regulator. The end of each sensing line is placed away from the turbulent flow at the valve outlet. This helps to improve accuracy of the set pressures. Set pressure for each PRV is adjusted by turning a screw on the pilot to increase or decrease compression on a balancing spring. For optimum operation and service life, maintain recommended minimum piping straight runs before and after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream of the regulator is to keep the steam velocity constant on both sides of the regulator. Each pressure sensing line should slope downwards, away from the regulator, to prevent condensate from entering the pilot. Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could become entrained with high-velocity steam, possibly resulting in dangerous waterhammer. While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known to be wet and the entrained moisture could affect valve performance and/or result in component damage. Consider installing a properly sized bypass line with globe valve on each stage, to provide continuous operation should regulator maintenance be required. Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging into condensate return lines. Check valves eliminate the possibility of condensate backing up through the steam trap into the system. A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle the complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRV sizing guidelines. 302
8 REGULATING APPLICATIONS TWO-STAGE (SERIES) REDUCING STATION Figure 10: VENT INLET DRIP PAN ELBOW BYPASS GLOBE BYPASS GLOBE SEPARAR DIAMETERS MINIMUM HDP REGULAR P DIAMETERS MINIMUM P DIAMETERS MINIMUM APPLICATION DEPENDENT SENSING LINE 20 PIPE DIAMETERS MINIMUM HDP REGULAR SENSING LINE 1st Stage 2nd Stage TWO-STAGE (SERIES) REDUCING STATION (HD REGULAR APPLICATIONS) SRV OUTLET 303
9 REGULATING APPLICATIONS PARALLEL REDUCING STATION PURPOSE: For reducing system inlet pressure to a constant outlet pressure when steam flow rates vary widely. OPERATION: Typically referred to as 1/3-2/3 system, one valve may be sized for 1/3 of the total load demand and the other for 2/3. When full load is required, both valves will be open and regulating. The primary valve is set at a pressure 2 PSI higher than the secondary valve to allow the secondary valve set at the lower pressure to modulate closed when flow demand is reduced and outlet pressure begins to rise. The primary valve may be selected as either the larger or smaller PRV, based on expected load demands. INSTALLATION GUIDELINES (see Figure 11) This example depicts a parallel pilot-operated steam PRV pressure reducing station using HDP regulators. An external sensing line is required to sense downstream pressure from each regulator. The end of each sensing line is placed away from the turbulent flow at the valve outlet. This helps to improve accuracy of the set pressures. Set pressure for each PRV is adjusted by turning a screw on the pilot to increase or decrease compression on a balancing spring. Proper setting of the valves is key to proper operation. The chosen primary valve should be set at a pressure approximately 2 PSI higher than that of the secondary valve. For optimum operation and service life, maintain recommended minimum piping straight runs before and after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream of the regulator is to keep the steam velocity constant on both sides of the regulator. Each pressure sensing line should slope downwards, away from the regulator, to prevent condensate from entering the pilot. Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could become entrained with high-velocity steam, possibly resulting in dangerous waterhammer. While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known to be wet and the entrained moisture could affect valve performance and/or result in component damage. Consider installing a properly sized bypass line with globe valve to provide continuous operation should regulator maintenance be required. Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging into condensate return lines. Check valves eliminate the possibility of condensate backing up through the steam trap into the system. A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle the complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRV sizing guidelines. 304
10 REGULATING APPLICATIONS PARALLEL REDUCING STATION Figure 11: INLET Primary Secondary DIAMETERS MINIMUM DIAMETERS MINIMUM SEPARAR HDP REGULAR P APPLICATION DEPENDENT SENSING LINE BYPASS GLOBE SEPARAR HDP REGULAR P SENSING LINE APPLICATION DEPENDENT PARALLEL REDUCING STATION (HD REGULAR APPLICATIONS) VENT DRIP PAN ELBOW SRV OUTLET 305
11 REGULATING APPLICATIONS TWO-STAGE PARALLEL REDUCING STATION PURPOSE: For reducing system inlet pressure to a constant outlet pressure when both flow conditions vary widely and a high pressure drop (i.e. higher than the recommended range of a single stage regulator) is required. OPERATION: This system is a combination of Two-Stage (Series) and Parallel pressure reducing stations and operates based on the individual principles of each system. This allows for accurate control of outlet pressure when both high pressure and high flow turndowns are required. INSTALLATION GUIDELINES: (see Figure 12) This example depicts a two-stage parallel pilot-operated steam PRV pressure reducing station using HDP regulators. An external sensing line is required to sense downstream pressure from each regulator. The end of each sensing line is placed away from the turbulent flow at the valve outlet. This helps to improve accuracy of the set pressures. Set pressure for each PRV is adjusted by turning a screw on the pilot to increase or decrease compression on a balancing spring. Proper setting of the valves is key to proper operation. The chosen 1st stage primary valve should be set at a pressure approximately 2 PSI higher than that of the 1st stage secondary valve. For optimum operation and service life, maintain recommended minimum piping straight runs before and after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream of the regulator is to keep the steam velocity constant on both sides of the regulator. Each pressure sensing line should slope downwards, away from the regulator, to prevent condensate from entering the pilot. Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could become entrained with high-velocity steam, possibly resulting in dangerous waterhammer. While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known to be wet and the entrained moisture could affect valve performance and/or result in component damage. Consider installing a properly sized bypass line with globe valve on each stage, to provide continuous operation should regulator maintenance be required. Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging into condensate return lines. Check valves eliminate the possibility of condensate backing up through the steam trap into the system. A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle the complete volume of steam from the regulator and bypass loops. Consult the factory for appropriate SRV sizing guidelines. 306
12 REGULATING APPLICATIONS TWO-STAGE PARALLEL REDUCING STATION Figure 12: VENT INLET APPLICATION DEPENDENT SEPARAR HDP REGULAR P DIAMETERS MINIMUM HDP REGULAR P DIAMETERS MINIMUM DRIP PAN ELBOW BYPASS GLOBE SENSING LINE BYPASS GLOBE SENSING LINE SEPARAR HDP REGULAR HDP REGULAR SENSING LINE 20 PIPE DIAMETERS MINIMUM SENSING LINE 1st Stage 2nd Stage TWO-STAGE PARALLEL REDUCING STATION (HD REGULAR APPLICATIONS) SRV OUTLET Primary Secondary 307
13 REGULATING APPLICATIONS TEMPERATURE CONTROL of a HEAT EXCHANGER with LIMITING PURPOSE: For accurately controlling both temperature of a product being heated in heat transfer equipment as well as limiting the pressure of the incoming steam, providing optimum heat transfer characteristics. OPERATION: When a pilot-operated HD valve is selected, a single valve can be used for both pressure and temperature control when equipped with a P-pilot and T-pilot (HDPT). As temperature at the sensing bulb falls below set point, the valve begins to modulate open to supply steam for heating. Supply pressure to the heat exchanger is then controlled by adjusting the pressure pilot to the recommended value for optimum heat transfer and/or a limiting pressure of the heat transfer equipment. The HDPT Regulator requires no external power source. INSTALLATION GUIDELINES: (see Figure 13) The temperature and pressure pilots should be set individually, starting slowly and gradually with the T-pilot. Care should be given to the installation of the temperature sensing bulb to ensure full immersion in the liquid. The sensing bulb should be placed as close as possible to the heat exchanger vessel to ensure accurate temperature control of the process fluid. For optimum operation and service life, maintain recommended minimum piping straight runs before and after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream of the regulator is to keep the steam velocity constant on both sides of the regulator. The pressure sensing line should slope downwards, away from the regulator, to prevent condensate from entering the pilot. Eccentric reducers, if required, are used on valve inlets to prevent accumulation of pipeline moisture which could become entrained with high-velocity steam, possibly resulting in dangerous waterhammer. While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known to be wet and the entrained moisture could affect valve performance and/or result in component damage. Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging into condensate return lines. Check valves eliminate the possibility of condensate backing up through the steam trap into the system. The vacuum breaker and auxiliary air vent located at the top of the heat exchanger vessel promotes proper drainage and optimum heat transfer. The vacuum breaker allows system equalization with atmospheric air to allow gravity condensate drainage when vacuum is formed from condensing steam. The air vent improves heat-up times and overall heat transfer by expelling accumulated air on start-up. A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere protection of downstream piping and equipment from over-pressurization is desired. Consult the factory for appropriate SRV sizing guidelines. 308
14 REGULATING APPLICATIONS TEMPERATURE CONTROL of a HEAT EXCHANGER with LIMITING Figure 13: HDPT REGULAR VENT APPLICATION DEPENDENT SEPARAR T P SENSING LINE SRV DRIP PAN ELBOW WVBSS VACUUM BREAKER TEMPERATURE SENSING BULB SUPPLY CAPILLARY HEAT EXCHANGER HOT WATER OUTLET F&T COLD WATER INLET F&T TEMPERATURE CONTROL of a HEAT EXCHANGER with LIMITING (HD REGULAR APPLICATIONS) AV2000 AIR VENT 309
15 REGULATING APPLICATIONS AUMATIC TEMPERATURE CONTROL of a BATCH PROCESS with Electrical Time Sequence Programmer (Solenoid Pilot) PURPOSE: For accurately controlling temperature of a batch process where on-off operation is to be electronically controlled. OPERATION: Operation is similar to that of the pressure and temperature combination pilot-operated regulator whereby the temperature (T) pilot senses the temperature inside the autoclave and appropriately modulates the flow of steam. Pressure is limited by the pressure (P) pilot. The solenoid valve (S-pilot) is electronically activated to control on-off operation of the batch process. (The HD Regulator operating with these three pilots is known as the HDPTS Regulator.) INSTALLATION GUIDELINES: (see Figure 14) The temperature and pressure pilots should be set individually, starting slowly and gradually with the T-pilot. For optimum operation and service life, maintain recommended minimum piping straight runs before and after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream of the regulator is to keep the steam velocity constant on both sides of the regulator. The pressure sensing line should slope downwards, away from the regulator, to prevent condensate from entering the pilot. Eccentric reducers, if required, are used on valve inlets to prevent accumulation of pipeline moisture which could become entrained with high-velocity steam, possibly resulting in dangerous waterhammer. While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known to be wet and the entrained moisture could affect valve performance and/or result in component damage. Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging into condensate return lines. Check valves eliminate the possibility of condensate backing up through the steam trap into the system. The thermostatic air vent located at the top of the autoclave chamber promotes optimum heat transfer. The air vent improves heat-up times and overall heat transfer by expelling accumulated air on start-up. A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere protection of downstream piping and equipment from over-pressurization is desired. Consult the factory for appropriate SRV sizing guidelines. 310
16 REGULATING APPLICATIONS AUMATIC TEMPERATURE CONTROL of a BATCH PROCESS with Electrical Time Sequence Programmer (Solenoid Pilot) Figure 14: VENT HDPTS REGULAR POWER SRV DRIP PAN ELBOW FILTER SENSING LINE ELECTRIC OPERAR P T SUPPLY S SEPARAR THERMOSTATIC APPLICATION DEPENDENT THERMOSTATIC AIR VENT TEMPERATURE SENSING BULB CAPILLARY F&T AUCLAVE F&T F&T AUMATIC TEMPERATURE CONTROL of a BATCH PROCESS with Electrical Time Sequence Programmer (Solenoid Pilot) (HD REGULAR APPLICATIONS) 311
17 REGULATING APPLICATIONS TEMPERATURE CONTROL of a SEMI-INSTANTANEOUS HEATER using a Self-Contained Temperature Regulating Valve PURPOSE: For accurate control of the temperature of a product being heated when the benefits of a self-contained regulator are required. OPERATION: A self-contained temperature regulating valve (TRV) such as the W91, offers response times and characteristics suitable for semi-instantaneous heating applications. The temperature sensing bulb senses the temperature of the liquid being heated and allows modulation of the valve for appropriate supply of steam. INSTALLATION GUIDELINES: (see Figure 15) Care should be given to the installation of the temperature sensing bulb to ensure full immersion in the liquid. The sensing bulb should be placed as close as possible to the heater tank to ensure accurate temperature control of the process fluid. For optimum operation and service life, maintain recommended minimum piping straight runs before and after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream of the regulator is to keep the steam velocity constant on both sides of the regulator. All pressure sensing lines should slope downwards, away from the regulator, to prevent condensate from entering the pilot. Eccentric reducers, if required, are used on valve inlets to prevent accumulation of pipeline moisture which could become entrained with high-velocity steam, possibly resulting in dangerous waterhammer. While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known to be wet and the entrained moisture could affect valve performance and/or result in component damage. Consider installing a properly sized bypass line with globe valve to provide continuous operation should regulator maintenance be required. Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging into condensate return lines. Check valves eliminate the possibility of condensate backing up through the steam trap into the system. The vacuum breaker and auxiliary air vent located at the top of the heater tank promotes proper drainage and optimum heat transfer. The vacuum breaker allows system equalization with atmospheric air to allow gravity condensate drainage when vacuum is formed from condensing steam. The air vent improves heat-up times and overall heat transfer by expelling accumulated air on start-up. A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle the complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRV sizing guidelines. 312
18 REGULATING APPLICATIONS TEMPERATURE CONTROL of a SEMI-INSTANTANEOUS HEATER using a Self-Contained Temperature Regulating Valve Figure 15: W91 TEMPERATURE REGULATING CAPILLARY APPLICATION DEPENDENT INLET SEPARAR BYPASS LINE SEMI-INSTANTANEOUS HOT WATER HEATER WITH W91 TEMPERATURE REGULAR (TEMPERATURE REGULAR APPLICATIONS) HOT WATER OUTLET GLOBE WVBSS VACUUM BREAKER AV2000 AIR VENT TEMPERATURE SENSING BULB SEMI-INSTANTANEOUS HEATER COLD WATER INLET 313
REGULATORS D& HD Series
Watson McDaniel reserves the right to change the designs and/or materials of its products out notice. 2002 Watson McDaniel Company Ductile Iron body - HD Series Full port strainer & blowdown valve on pilot
Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409
Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam
HS-901(A) BASIC STEAM HEATING SYSTEMS
HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,
DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES
SECTION 15062 STEAM AND CONDENSATE PIPING PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Comply with the provisions of the following: 1.2 DESIGN CRITERIA 1. ASME B 31.9 Building Services Piping : for
Heating Water by Direct Steam Injection
Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space
Steam System Best Practices Condensate System Piping
Steam System Best Practices Condensate System Piping Summary The best method for improving steam system energy efficiency, reducing chemical costs, and reducing make-up water costs is to return the maximum
DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING
By Philip Sutter Pick Heaters, Inc. DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING INTRODUCTION Many process plants currently use steam or hot water to heat jacketed devices such as tanks,
PBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
Float and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
CHAPTER II. This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192.
CHAPTER II REGULATOR AND RELIEF DEVICES This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192. BASIC CONCEPT In understanding
Steam Coil Installation, Operation and Maintenance
Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils manufactured by Luvata in Grenada, MS have been
Frequently Asked Questions
Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.
REGULATORS 175/153 Series
175/153 Series 175 HEATING 153 COOLING Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2002 Watson McDaniel Company Revised 7/2002 175 / 153 Screwed
Mechanical Seal Piping Plans
Mechanical Seal Piping Plans Single Seals plans 01, 02, 03, 11, 13, 14, 21, 23, 31, 32, 41 Dual Seals plans 52, 53A, 53B, 53C, 54, 55 Quench Seals plans 62, 65A, 65B, 66A, 66B Gas Seals plans 72, 74, 75,
Air Eliminators and Combination Air Eliminators Strainers
Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.
TYPE E Main Valve Sizes 3 /8 through 12
SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,
Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
Industrial Steam System Process Control Schemes
Industrial Steam System Process Control Schemes This paper was developed to provide a basic understanding of the different process control schemes used in a typical steam system. This is however a fundamental
In-Line Air Separators
Air Elimination & Control In-Line Air Separators The AC models of air separators deliver all the quality and performance you expect from Taco products. They are built to last with shell, heads and ANSI
Desuperheater Online Program Sizing Guidance
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
C. starting positive displacement pumps with the discharge valve closed.
KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the
Element D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
Select the Right Relief Valve - Part 1 Saeid Rahimi
Select the Right Relief Valve - Part 1 Saeid Rahimi 8-Apr-01 Introduction Selecting a proper type of relief valve is an essential part of an overpressure protection system design. The selection process
Steam System Design and Best Practices Related to Kiln Drying
Steam System Design and Best Practices Related to Kiln Drying New England Kiln Drying Association Steam Design and Best Practices HerLine Technologies What is Steam? Like other substances water can exist
PRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
Pressure and Temperature Controls
Pressure and Controls Pressure Reducing Armstrong pressure reducing valves (PRVs) and temperature regulators help you manage steam, air and liquid systems safely and efficiently. And assure uninterrupted
Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.
Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description
Product Manual CVS Type 67AFR Filter Regulator Introduction This CVS Controls product manual includes instructions for the installation, adjustment, maintenance and parts ordering of the CVS Type 67AFR
FILLING AND PURGING THE SYSTEM
FILLING INSTRUCTIONS FOR WATER HEATER OR CONDENSING BOILER (City Water) Safety tip: Before beginning, turn off power to boiler and circulator. FILLING AND PURGING Step 1: Close Return Manifold Isolation
Boiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE
Page 1 of 9 PURPOSE Steam is the most commonly used heating medium for maintaining process temperatures. Compared to other heating media, steam contains a significant amount of heat energy, and this heat
POLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
77 ILLINOIS ADMINISTRATIVE CODE, PART 890 (NEW) ILLINOIS PLUMBING CODE (02/04) SUBPART I: WATER SUPPLY AND DISTRIBUTION
SUBPART I: WATER SUPPLY AND DISTRIBUTION Section 890.1110 Quality of Water Supply All premises intended for human habitation or occupancy shall be provided with a potable water supply. The potable water
Indirect-fired Steam & Boiler Water Heaters
Indirect-fired Steam & Boiler Water Heaters High Recovery ASME Constructed & Stamped Factory Packaged Applications Thermomaster water heating systems provide high recovery, tight temperature control and
Contents. LWN 750.30 edition: 24.02.10 3-0
Contents 3.1 Introduction...3.1-1 3.2 List of Referenced Codes and Standards...3.2-1 3.3 Overview Terms and Definitions...3.3-1 3.4 Description Terms and Definitions...3.4-1 LWN 750.30 edition: 24.02.10
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, 1060. Instruction No.
Instruction No. AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA PIPING GUIDE GF-115-P Modulex Gas Fired Boiler Systems Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909,
BERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
A basic introduction to steam
A basic introduction to steam FOR HOT, COLD, MOIST AND DRY, FOUR CHAMPIONS FIERCE. STRIVE HERE FOR MASTERY Milton 1666 Steam Wonderful Steam Very high heat content Recyclable Clean, non toxic Biodegradable
Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.
DAN-LIQ-TG-44-rev0208 February 2008 Daniel Liquid Control Valves Technical Guide www.daniel.com Daniel Measurement and Control Theory, Principle of Operation and Applications This brochure has been prepared
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
Example. Fluid Power. Circuits
Example Fluid Power Circuits To Enhance Symbol Reading Skills To Work On Circuit Reading Skills With Answers HI LO Pump Circuit 18 A1 B1 17 16 15 13 Set 14 2,000 PSI PG2 Set 500 PSI 12 11 7 8 10 PG1 9
Type HSR Pressure Reducing Regulator for Residential, Commercial or Industrial Applications
Instruction Manual Form 5753 Type HSR February 014 Type HSR Pressure Reducing Regulator for Residential, Commercial or Industrial Applications P154 TYPE HSR ANGLE BODY P175 TYPE HSR STRAIGHT Figure 1.
Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
Type 25P & 25PA Pressure Reducing Valves
INSTAATION AND MAINTENANCE INSTRUCTIONS IM-3-000-US October 2015 Type 25P & 25PA Reducing s Safety Information Safe operation of these products can only be guaranteed if they are properly installed, commissioned,
Commercial Semi-Instantaneous Water Heaters
FEATURES HWI Models A. O. Smith s HWI models are available for operation with steam or boiler water as the energy source. They are factory assembled with components sized, piped and checked at the factory
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
Blowdown vessels Meeting the requirements of HSE PM60
Blowdown vessels Meeting the requirements of HSE PM60 BDV60 blowdown vessels complete range of equipment for the safe disposal of boiler blowdown Boiler blowdown Steam boilers must be blown down to remove
Electric Flow Boiler
Electric Flow Boiler EHC offer the most comprehensive range of electric boilers in the market and with our wealth of knowledge and technical expertise we have designed the Slim Jim Electric Flow Boiler
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard
Solenoid Valves and Their Importance in Refrigeration Systems. October 2007
Solenoid Valves and Their Importance in Refrigeration Systems October 2007 Overview Introduction Solenoid valves play an important role within refrigeration and air conditioning systems, controlling the
ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL
ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL The Viking Corporation 210 N Industrial Park Road Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:
FLASH TANK ECONOMIZER PRODUCT GUIDE
FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.
Factory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves
Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves CRANE Energy Flow Solutions TM Donald H. Johnson Crane Energy Flow Solutions 1 Crane Co. Resolution Made By Richard Teller
VAD. Variable Area Desuperheaters
Desuperheater overview Steam used in process plants can be superheated, that is, heated to a temperature above saturation. The excess of temperature above its saturation is called 'superheat'. Desuperheated
Schematic Symbols Chart (Design Hydraulic and Pneumatic circits)
Page 1 of 6 (Home) Symbols / Visit us on: Fluid Power, Automation and Motion Control for all Industries About Us Products Services Catalogs Place an Order Training & Information Contact Us Employee Access
FT43, FT44, FT46 and FT47 Ball Float Steam Traps
0667050/9 IM-S02-30 ST Issue 9 FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
Laddomat 21-60 Charging unit
Laddomat 21-60 Charging unit User and installation instructions NOTE! Diagrams in this brochure only describe connection principles. Each installation must be measured and carried out according to the
Steam-jet vacuum systems combine ejectors, condensers
DESIGNING STEAM JET VACUUM SYSTEMS For cost-effective vacuum pumping, the proper placement of condensers and pipe supports are critical DAVID B. BIRGENHEIER AND THOMAS L. BUTZBACH, Graham Manufacturing
Sizing, Selection, and Installation of Pressure-relieving Devices in Refineries
Sizing, Selection, and Installation of Pressure-relieving Devices in Refineries Part I Sizing and Selection API STANDARD 520 EIGHTH NINTH EDITION, DECEMBER 20082013 2 API STANDARD 520, PART 1 SIZING AND
Air/Vacuum Valves. Removal of Air from Pipelines. Allow the Entry of Air into Pipelines. Application:
/Vacuum Valves Micro-Irrigation and vacuum control is essential to the safety, longevity, efficiency, and performance of an irrigation system. must be allowed to exit pipelines 1) upon startup to prevent
Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW
Installation, Operating and Maintenance Instructions 90/4.5.5 Rev. 0 Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Table of Contents SECTION I... 2 INSTALLATION...
How To Clean Up A Reactor Water Cleanup
General Electric Systems Technology Manual Chapter 2.8 Reactor Water Cleanup System TABLE OF CONTENTS 2.8 REACTOR CLEANUP SYSTEM... 1 2.8.1 Introduction... 2 2.8.2 System Description... 2 2.8.3 Component
VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX.
Cavitation in Valves VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX. (630) 941-8042 www.valmatic.com CAVITATION IN VALVES INTRODUCTION Cavitation
FAQ and Device/Usage Chart. What Is a Cross-Connection? What Is Backflow Prevention? What Is Backflow?
What Is a Cross-Connection? A cross-connection is a direct arrangement of piping that allows the potable (safe drinking) water pipe to be connected to a pipe supply that contains a contaminant or pollutant.
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:
VAD Variable Area Desuperheaters
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters
Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters When water is heated, it naturally expands and allowance has to be made for this. Vented water heaters usually
BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap
1263050/6 IM-P126-07 ST Issue 6 BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation
Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001
Pressure Control Chapter 3 Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Introduction Pressure control is a key element in the design of any circuit. Used correctly, it can
Type 92S Pilot-Operated Steam Regulator
Type 92S Pilot-Operated Steam Regulator Introduction The Type 92S steam regulator is piston actuated for high cycle steam service which includes a Type 6492L, 6492H or pilot (see Figure 1). These pilots
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
Why use Tigerloop in fuel heating systems?
The Original Oil De-aerator Why use Tigerloop in fuel heating systems? Reliability New products are continually being developed in the modern oil heating industry in order to satisfy new laws and regulations
Description of functions
Description of functions Laddomat 21 is designed to......allow the boiler to reach a high working temperature soon after firing....to preheat the cold tank water in the bottom of the boiler so that the
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
Filtering Samples to On-Line Process Analyzers. Guidelines for Proper Filtration and Delivery of Samples to On-Line Process Analyzers
Filtering Samples to On-Line Process Analyzers Guidelines for Proper Filtration and Delivery of Samples to On-Line Process Analyzers Filtering samples to on-line analyzers Use these guidelines to ensure
Basic Hydraulics and Pneumatics
Basic Hydraulics and Pneumatics Module 1: Introduction to Pneumatics PREPARED BY IAT Curriculum Unit March 2011 Institute of Applied Technology, 2011 ATM 1122 Basic Hydraulics and Pneumatics Module 1:
UNDERSTANDING HOT WATER SYSTEMS IN THE HOME
UNDERSTANDING HOT WATER SYSTEMS IN THE HOME This advice guide is part of a series of free guides produced by the Association of Plumbing & Heating Contractors Ltd. which provide consumers with essential
DEFROSTING. Service Engineers Section Technical Bulletin No 3
Service Engineers Section Technical Bulletin No 3 DEFROSTING 1. INTRODUCTION This bulletin is presented to cover the methods used and problems experienced with defrosting of coils for chill and frozen
WD600 STEAM TRAPS. Thermodynamic Steam Trap
WD600 Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2010 Watson McDaniel Company WD600, WD600L Sizes 3/8, 1/2, 3/4, 1 NPT Material Stainless
Steam Jet Vacuum Pumps
By: S.G. Ketterer and C.G. Blatchley The use of steam jet ejectors for entraining air or gases at subatmospheric pressures is increasing rapidly, particularly in the range of pressures below mm absolute.
HOT WATER SYSTEMS CONTENTS
HOT WATER SYSTEMS CONTENTS MECHANICAL CONSIDERATIONS.............................................. 3 Code Considerations..................................................... 3 Boiler Selection Considerations..............................................
DESIGN OF FLUID SYSTEMS STEAM UTILIZATION
DESIGN OF FLUID SYSTEMS STEAM UTILIZATION Published by $19.95 per copy Copyright 2004 by Spirax Sarco, Inc. All Rights Reserved No part of this publication may be reproduced, stored in a retrieval system
D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00
SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information
Basic Symbols. Lines. Circular. Square. Diamond. Miscellaneous Symbols. -continuous line - flow line. -dashed line - pilot, drain
Airline Hydraulic's Main Page Basic Symbols Lines continuous line flow line dashed line pilot, drain envelope long and short dashes around two or more component symbols. Circular Square Diamond large circle
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant
OWNER & INSTALLER MANUAL AND WARRANTY INFORMATION.
COPPERFLOW SERIES MAINS PRESSURE ELECTRIC WATER HEATER INDOOR/OUTDOOR MODEL OWNER & INSTALLER MANUAL AND WARRANTY INFORMATION. PLEASE READ THIS MANUAL CAREFULLY BEFORE INSTALLING AND OPERATING. THIS WATER
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
Theory, Application, and Sizing of Air Valves
Theory, Application, and Sizing of Air Valves VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX. (630) 941-8042 www.valmatic.com 1 THEORY, APPLICATION,
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
ARTICLE 1141 Cross Connection Control Program
43 ARTICLE 1141 Cross Connection Control Program 1141.01 Purpose. 1141.07 Degree of hazard. 1141.02 Authority. 1147.08 Existing in-use backflow 1141.03 Responsibility. prevention devices. 1141.04 Definitions.
Commercial Electric Water Heater
Commercial Electric Water Heater Provides Tepid Water For Emergency Fixtures Features Heavy Duty Construction Hydrastone cement lining provides tank longevity Copper-silicon alloy tappings cannot rust
