Service Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007
|
|
|
- Abigayle Nash
- 10 years ago
- Views:
Transcription
1 Service Guide Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines ORDER No: UN-SVG001A-EN DATE: October 9, 2007 Introduction This document defines American Standard and Trane s recommendations for cleaning and maintaining evaporator coils and condensate lines in American Standard and Trane Residential Air-handlers, Furnace Coils and Packaged units. The intent of this paper is not to endorse any particular cleaning products. The use of product names is only to provide clarification for the service person of the ph of some products. The Technician performing the service or maintenance is required to read the Material Safety Data Sheet (MSDS) for all coil-cleaning products. The Service Technician is required to identify not only an individual product s ph; the Service Technician should also have a complete understanding of all safety and handling instructions for each cleaning product used and the air conditioning equipment. NOTICE: Warnings and Cautions appear at appropriate sections throughout this bulletin. Read these carefully. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. CAUTION Indicates a situation that may result in equipment or property-damage-only accidents. WARNING Hazardous Service Procedures! The maintenance and troubleshooting procedures recommended in this guide could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this guide concerning these procedures. When possible, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury. American Standard
2 WARNING Personal Protective Equipment (PPE) Required! Always refer to appropriate MSDS and OSHA guidelines when handling fluorocarbon refrigerants. Use proper breathing, eye, and body protection during the handling of fluorocarbon refrigerants. Failure to follow proper handling guidelines could result in death or serious injury. Discussion Coil and Cabinet Cleaning 1. American Standard s and Trane s recommendation for coil cleaning is to use neutralph cleaners. This is required to avoid the use of strong acids and strong base cleaners. Thus, cleaners with ph range from 5 to 11 are suitable for coil cleaning. This range includes such over-the-counter cleaners as Simple Green All Purpose Cleaner, or HVAC coil cleaners like Nu-Calgon Evap Pow'r. 2. Strong acidic cleaners (ph of 5 or less) that contain hydrochloric, sulfuric, nitric, or acetic acid are not recommended for use on copper-tube, aluminum fin coils or on aluminum tube, aluminum fin coils. Presence of these acids will result in rapid corrosion of the metals. 3. Strong alkali (base) cleaners (ph of 11 or more) containing sodium, potassium, or ammonium hydroxide are not recommended as they will aggressively corrode aluminum tubes and fins. Strong ammonium hydroxide cleaners will also cause stress corrosion cracking of copper tubes. 4. American Standard and Trane recommend completely rinsing all cleaner from the coil - including cleaners identified as No-Rinse cleaners. Residual cleaners may decompose over time producing low molecular weigh, organic acids that lead to formicary corrosion. 5. We agree with many of our dealers that only removing an evaporator coil is the best way to effectively clean a coil that is heavily contaminated. This is accomplished by removing it from the cabinet and using a strong water stream such as from a garden hose. Lightly spraying cleaners on a coil with a spray bottle and rinsing with water from a spray bottle does not effectively clean it and certainly does not effectively rinse the cleaner from the coil. 6. A coil operating for many months without an air filter will likely require removal to achieve proper cleaning. Visual inspection of the indoor equipment is the ideal determining factor if a coil is contaminated enough to warrant coil removal for cleaning. Evidence of this would be a heavy mat of fiber and hair on the inlet side of the coil and discoloration of the fins on both sides of the coil. Another, easily detectable symptom is a dirty blower wheel. A dirty blower wheel indicates a need for coil inspection as this means contaminants have been getting past the filter at some time or the unit has been operated without a filter. Air handler or Packaged Unit: Remove the evaporator coil and fan assembly for proper cleaning if there is also contamination on the inside of the cabinet and/or contamination other than normal household dirt, lint (etc.) on the coil. Proper cleaning of the cabinet insulation, wiring, and other components are required as well. Wipe these surfaces down with the same neutral or moderate ph cleaners described in item number 1 above Cased Coil: Remove the evaporator coil for proper cleaning if there is also contamination on the inside of the cabinet and/or contamination other than normal household dirt, lint (etc.) on the coil. Proper cleaning of the cabinet insulation and other components are required as well. Wipe these surfaces down with the same neutral or moderate ph cleaners described in item number 1 above. If the coil is to be removed we require adherence to all safety warnings and cautions that appear in the literature shipped with the equipment and affixed to the units itself. Recommended refrigerant handling precautions and practices must be followed as well. Routine maintenance cleaning should not be done using chemical cleaners unless the coil is removed. In place cleaning can be done with the use of a vacuum cleaner using an upholstery brush attachment or by other brushes that will not damage or distort the coil fins. UN-SVG001A-EN 2
3 Conclusion Coil and Cabinet Cleaning Cleaning the coil, filter, blower wheel and cabinet interior is an integral part of system performance and reliability. This paper does not cover all possible evaporator coil-cleaning situations; however, it has pointed out the importance of regular air filter changes. The Installing Dealer should review the Home Owners Guide with the end-user and reinforce the importance of regular air filter changes. For further clarification, the Servicing Dealer should consult with the supplier of the cleaning products for directions on how to achieve a ph of 5 to 11. Your local American Standard or Trane Field Service Representative can provide instruction on evaporator coil removal, servicing of the refrigeration system and reinstallation of coils. Discussion Condensate Management and Maintenance Condensate management and maintenance is a key to the proper operation of the A/C system. Moisture removed by the A/C system contains pollutants (chemicals, smoke, etc.) that are in the air. These elements, as well as the moisture, must be removed from the drain pan and the condensate lines to ensure comfort and coil reliability. Traps must be installed within 4 feet of the air handler or cooling coil per the installer guide. (See Figure 1) Secondary drain lines do not need to be trapped. Additionally, the secondary drain connection should not be used to connect a float switch or emergency shutoff switch. If local codes require the secondary drain line connection to be used for a float switch or emergency shutoff switch, the switch should be positioned at a level below the primary drain outlet. This will prevent the level of condensate in the coil drain pan from rising above the level of the weep hole (in some drain pans) and overflowing. American Standard / Trane recommends that the secondary drain terminate at a conspicuous location where the occupants can easily see any condensate draining from the secondary line and notify their servicing contractor. All primary drain lines should be insulated if there is a possibility of the condensate line reaching the dew point of the surrounding air. The trap is an integral part of condensate removal that provides a positive seal and is necessary for proper condensate removal. The close coupling in the linear piece of the trap ensures a complete cleansing of the trap on most cooling cycles and, therefore, will reduce the chance of a clogged trap resulting in condensate overflow. The trap must be a minimum of 2 inches in depth The linear piece of the trap (the bottom horizontal piece) should be as close coupled as possible The trap must be within 4 feet of the unit The guidelines above are shown in figure 1. The following information covers evaporator condensate management system installation and maintenance guidelines for under slab drains (Figure 2 and 3) as well as recommendations for cleaning all condensate drains The outlet side of the trap must be vented to atmosphere to prevent the effects of double trapping. The stand pipe must be higher than the primary drain connection UN-SVG001A-EN 3
4 Typical Air Handler Condensate Recommendation Horizontal run of trap should be as close coupled as possible Figure 2 UN-SVG001A-EN 4
5 Typical Furnace and Coil Condensate Recommendation Figure 3 Preventative maintenance of the condensate line is also recommended at least once a year, preferably before the cooling season. American Standard and Trane recommend the use of only fresh water to flush the line. This can be performed by disconnecting the condensate line from the coil and connecting it to a garden hose. Using high pressure and volume, flush the line for a minimum of 30 seconds or until clear water is observed. An alternative to this would be to install a ball valve between the stand pipe and the outlet of the trap (figure 4). Close the ball valve and connect the garden hose to the stand pipe. Flush per the aforementioned instructions. Detailed Ball Valve Installation Figure 4 UN-SVG001A-EN 5
6 NOTE: In upflow & horizontal applications, use sealant on condensate weep hole in air handler drain pan if present.. (Figure 5) Figure 5 Conclusion Condensate Management and Maintenance American Standard/Trane has performed studies on condensate piping applications and has published best practice instructions in our products Installer Guides and Condensate Application Guidelines (Pub ). The preceding instructions outline methods associated with condensate removal which, if followed, should reduce the risk of contaminants entering the coil and reduce condensate related problems. This will also assist in mitigating the risks associated with formic and acetic acids. Literature Order Number File Number UN-SVG001A-EN UN-SVG001A-EN10/09/2007 Supersedes New Stocking Location Inland La Crosse, or Electronic Only American Standard and Trane has a policy of continuous product data and product improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this bulletin. UN-SVG001A-EN 6
Air Conditioning System
Owner s Information Manual Air Conditioning ystem NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the space provided. This information,
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
The Owners Coated Coil, Cleaning and Maintenance Service Manual.
The Owners Coated Coil, Cleaning and Maintenance Service Manual. Revision: July, 2011 Section INDEX Pages Forward 1 2 Importance of Proper & Timely Coil Cleaning 3 Coil Cleaner Characteristics 4 Selecting
Installation Instructions
CNPVU CNRVU Uncased Coils Upflow - Downflow Heating - Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...
How to Maintain an Air Conditioner
How to Maintain an Air Conditioner by Fix-It Club How to Troubleshoot a Central Air Conditioning System Publications International, Ltd. Central air conditioners are made up of two separate components:
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
Installer s Guide 18-AH39D1-13
18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,
Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split
Multi System 16 SEER, Inverter System 9,000 to 18,000 BTU/Hr Single Split 4MXW8-A 4TXM6-A March2013 42 Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate
WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:
Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do
Why is my air conditioner dripping on my customers?
De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These
Tankless Water Heater
Tankless Water Heater USER S INFORMATION MANUAL Models WGRTNG199 / WGRTLP199 WGRTCNG199 / WGRTCLP199 NOTICE: Westinghouse reserves the right to make product changes or updates without notice and will not
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
123 street Salt Lake City, Utah 84092
Salt Lake City, Utah 84092 Prepared for: Sample AC inspection Prepared by: Page 1 of 8 Table of Contents Definitions 2 General Information 2 Air Conditioning 3 Heating System 6 Summary 8 Page 2 of 8 Definitions
Air Conditioner Maintenance
Central air conditioning systems are wonderful features of many homes in the US. In hot and humid climates it s hard to imagine living without AC, although this convenience has been common in only the
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
Central Air Conditioner
Central Air Conditioner USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL AIR CONDITIONER NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. WELCOME
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
SYSTEM Inverter Air Conditioners
OPERATION MANUAL SYSTEM Inverter Air Conditioners MODEL Ceiling Suspended type FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU Read these instructions carefully before installation. Keep this manual in a handy place
ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t. www.ice-air.com
80 Hartford Avenue Mount Vernon New York 10553 Tel: 914-668-4700 EXT. 203 Fax: 914-668-5643 www.ice-air.com Wo r l d C l a s s C o m f o r t Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE
Heat Pump USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL HEAT PUMP
Heat Pump USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL HEAT PUMP NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. WELCOME TO EFFICIENT YEAR-ROUND
CENTRAL AIR CONDITIONER A GUIDE TO OPERATING AND MAINTAINING YOUR RESIDENTIAL AIR CONDITIONING UNIT.
CENTRAL AIR CONDITIONER A GUIDE TO OPERATING AND MAINTAINING YOUR RESIDENTIAL AIR CONDITIONING UNIT. NOTE TO INSTALLER: THIS MANUAL SHOULD BE LEFT WITH THE EQUIPMENT USER. WELCOME TO EFFICIENT HOME COOLING
PTAC Preventive Maintenance Guide. Step-by-step instructions and information to keep your units operating in peak condition
PTAC Preventive Maintenance Guide Step-by-step instructions and information to keep your units operating in peak condition The Importance of Proper PTAC Maintenance Welcome to the PTAC Preventive Maintenance
How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.
Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)
heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.
3 & cooling 17 heating 2010 PulteGroup, Inc. All Rights Reserved. condensation The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. Air conditioning
UV100A Ultraviolet Air Treatment System
UV100A Ultraviolet Air Treatment System INSTALLATION INSTRUCTIONS APPLICATION When installed in forced air heating and cooling systems, the UV100A Ultraviolet Air Treatment System kills airborne microorganism
THREE. Heating and Cooling
THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Owner s Manual Model 5000 Safety, Operating and Maintenance Instructions
Electronic Air Cleaner 90-1147 Owner s Manual Model 5000 Safety, Operating and Maintenance Instructions READ AND SAVE THIS MANUAL WARNING 120 Volts may cause serious injury from electrical shock. Disconnect
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
CENTRAL AIR CONDITIONER with PURON REFRIGERANT
USER S INFORMATION MANUAL CENTRAL AIR CONDITIONER with PURON REFRIGERANT NOTE TO INSTALLER: This manual must be left with the equipment user. WELCOME TO EFFICIENT HOME COOLING COMFORT Congratulations on
How To Install An Evaporator Coil
EVAPORATOR COIL INSTALLATION INSTRUCTIONS EVAPORATOR COIL SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... System Requirements... Location Requirements... Drain Requirements... INSTALLATION INSTRUCTIONS...
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you
Basics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
Radford University. Indoor Air Quality Management Plan
Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings
0150506194 C Limited 2nd through 5th Year Functional Parts Warranty During the 2nd through 5th year,haier will provide functional parts which prove to be defective due to workmanship
Name: Air Conditioning, Heating and Refrigeration (47.0201)
Name: Air Conditioning, Heating and Refrigeration (47.0201) Directions: Evaluate the student by entering the appropriate number to indicate the degree of competency. Rating Scale (0-6): 0 No Exposure no
Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03
Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cooling Coil Nomenclature 4 C X C B 0 3 6 C C 3 C U A A Refrigerant Type 4 - R410A Product Family T-Premium (Heat Pump or Convertible
Protecting Your Home From Water Damage
1 P a g e Protecting Your Home From Water Damage The first signs of water damage might seem trivial. But warnings like water stains on the ceilings or a leak under the kitchen sink can lead to real problems,
CEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
Installer s Guide 18-GJ11D1-2 : Models: BAYUVCLK001-40 Watt, 2 Lamp NOTE: A BAYCC24VK01 can be installed for Series 8 Air Handlers to extend the life of the lamp. This accessory kit will disable the lamp
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Attachment J-C18.1. HVAC Work Instructions
. RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual
Rental Services Temporary Cooling - Flexible Water Hose
Engineering Bulletin Rental Services Temporary Cooling - Flexible Water Hose September 2006 CHS-PRB007-EN Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate
DEPARTMENT OF CODES AND BUILDING SAFETY FLOOD RECOVERY INFORMATION
May 2010 DEPARTMENT OF CODES AND BUILDING SAFETY FLOOD RECOVERY INFORMATION GUIDELINES FOR PERMITS ASSOCIATED WITH THE REPAIR OF FLOOD DAMAGED HOMES AND BUILDINGS The Department of Codes and Building Safety
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
Applying improper cleaning solutions and techniques for
Carefully Choosing Proper selection of chemicals and cleaning techniques are critical in A/C coil cleaning. BY JAMES BOWMAN Images courtesy of RectorSeal Corp. Applying improper cleaning solutions and
NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS
NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS National Air Duct Cleaners Association 1518 K Street, N.W. Suite 503 Washington, DC 20005 (202)
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS BULLETIN 240-10-3 June 2004 Supersedes June 1983 Many centrifugal systems get little maintenance. As a result they operate with the refrigerant highly contaminated
Model 800 Residential Steam Humidifier Owner s Manual. Includes Safety & Operating Instructions and Warranty Information
Steam Humidifier Model 800 Residential Steam Humidifier Owner s Manual Includes Safety & Operating Instructions and Warranty Information READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS Safety Cautions...
Mechanical Systems Competency 1.20
Competency 1.20 Mechanical systems personnel shall demonstrate a working level knowledge of the safety and health fundamentals of mechanical systems and/or components. 1. Supporting Knowledge and Skills
Use and Care Manual. Model CPA12KH AIR CONDITIONER
Use and Care Manual Model CPA12KH AIR CONDITIONER Introduction Thank you for choosing this air conditioner to provide you and your family with all of the "Home Comfort" requirements for your home, cottage
A brief explanation on how air conditioning works and what terms mean
A brief explanation on how air conditioning works and what terms mean -presented by- Before we begin, let s explain the air conditioning process. In the most basic of terms, air conditioning simply takes
The Importance of Clean Coils In Commercial Equipment
Article reprinted with permission from RSES Journal, June 2002 The Importance of Clean Coils In Commercial Equipment Keeping coils clean helps equipment operate in nearnew conditions, which keeps customers
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
01-3 6820-11 6820-11 AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON 2010.01
682011 013 GENERAL 1. SPECIFICATIONS 682011 014 682011 2. REPAIR INSTRUCTIONS 1) Precautions for Working with R134a R12 refrigerant and R134a refrigerant are not compatible. These refrigerants must never
KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850
INSTALLATION AND OPERATING INSTRUCTIONS KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850 Product advantages Automatic float switch as water
KODAK Developer System Cleaner and Neutralizer
KODAK Developer System Cleaner and Neutralizer TECHNICAL DATA / CHEMICAL March 2010 TI-2000 GENERAL INFORMATION KODAK Developer System Cleaner and Neutralizer is designed to remove the buildup of silver
CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
LOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table
HVAC Preventative Maintenance Basics. Presented by Mike Crawley
HVAC Preventative Maintenance Basics Presented by Mike Crawley Air Handlers/Package Units: Coils have to be clean! The main purpose of any coil is to absorb or reject heat If coils are dirty; air flow
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler
WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility
OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
Diagnostics for Mobile Homes: HVAC
Diagnostics for Mobile Homes: HVAC Adam Harris NYSWDA Wade Thompson - IWTC Objectives Identify different types of HVAC used in mobile homes Provide an overview of duct systems Demonstrate various tests
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE
OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:
ON-VEHICLE INSPECTION
Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI
Automobile Air Conditioning Primer
Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the
HVAC 1-877-626-8350. Schedule. Contract # GS-07F-9452S Contract # GS-06F-0091S 2008 NCH CORPORATION 2009 NCH CORPORATION
2008 NCH CORPORATION 2009 NCH CORPORATION Schedule Contract # GS-07F-9452S Contract # GS-06F-0091S 1-877-626-8350 H V A C Application Chart TYPE OF COILS Non-Acid Aluminum Cleaner and Brightener Aerosol
The Uniform Building Inspection Report Condensed
The Uniform Building Inspection Report Condensed Single Family Residence:, Scottsdale, AZ Condensed Report Version Prepared for: John Doe Inspection Date: 9/19/2005, 1:00:00 AM Report Number: 091805s Inspection
Control of Hazardous Energy LOCKOUT/TAGOUT 29 CFR 1910.147
Control of Hazardous Energy LOCKOUT/TAGOUT 29 CFR 1910.147 Contents I. Introduction II. Scope and Application III. Definitions IV. Lockout/Tagout Manual V. Energy Control Procedures 1. Applying Energy
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning
FJ2. 2 Ton Trolley Floor Jack Assembly & Operating Instructions
FJ2 2 Ton Trolley Floor Jack Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. This manual provides important information on proper operation & maintenance.
Installation Manual CLIFC Fan & Coil Variable Speed
Installation Manual CLIFC Fan & Coil Variable Speed General Description GENERAL DESCRIPTION FANS EQUIPMENT Totally Factory assembled within the unit all piping, wiring, and required controls for operation
White rust on galvanized and galvanized pre-painted steel. Technical Information
Technical Information White rust on galvanised steel Prevention It is easier to prevent white rust than to cure it! Reasonable precautions to protect steel during both transport and storage can considerably
OWNER S GUIDE OPERATION & INSTALLATION
OWNER S GUIDE OPERATION & INSTALLATION CARRIER RECREATIONAL VEHICLE AIR CONDITIONER PRODUCT INFORMATION Model Number Date in Service Unit Serial Number Ceiling Assembly Serial Number INSTALLER Date of
Indoor Coil Corrosion Industry Research Report
Indoor Coil Corrosion Industry Research Report Identifying Common Sources Introduction Fin Pack Leaks Formicary Corrosion Indoor coil corrosion failures are an issue in the HVAC industry today. Although
MAINTAINING YOUR SPA WATER
MAINTAINING YOUR SPA WATER Tap water that is safe to drink is not always safe for a spa. Normal tap water is usually filled with minerals and microcontaminants that are not visible to the naked eye. Properly
Orlando Home Inspection Services
PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
1/3 HP Submersible Sump Pump with Vertical Float Switch
1/3 HP Submersible Sump with Vertical Float Switch Item 68476 Specifications Float Switch Operation Height 7.1 IN. ON / 2.8 IN. OFF Electrical Requirements 120V~ / 60Hz / 7.6A Power Length Maximum Capacity
Operating Instructions Air Conditioner
P07-T10130 Operating Instructions Air Conditioner Indoor Unit CS-F24DD1E5 CS-F28DD1E5 CS-F34DD1E5 CS-F43DD1E5 CS-F50DD1E5 Outdoor Unit Inverter Model (HBE5 Series) CU-YL24HBE5 CU-YL28HBE5 CU-YL34HBE5 CU-YL43HBE5
Use and Care. Central Air Conditioning 22-5157-03-2705 (EN)
Use and Care Central Air Conditioning 22-5157-03-2705 (EN) Contents Contents How It Works... 3 Maintenance... 3 Peak Performance... 4 Problem Solver... 5 Extra Energy Tips... 5 Service Information... 6
air conditioners how to choose a cooling system
air conditioners how to choose a cooling system taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home and a reduced
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
WALL MOUNTED SPLIT TYPE AIR CONDITIONER
WALL MOUNTED SPLIT TYPE AIR CONDITIONER MANUAL 8 OM-G12-ACSON CONTENTS - Operating Guide page 1 - G12 Remote Controller Indication page 2 - Indicator Lights page 4 - Installation of Aroma page 5 - Auto
SOLAR PV SYSTEM MAINTENANCE GUIDE
SOLAR PV SYSTEM MAINTENANCE GUIDE GUYANA HINTERLANDS STAND-ALONE SOLAR PV INSTALLATIONS IMPROVING HEALTH FACILITY INFRASTRUCTURE (IHFI) GUYANA CONTRACT NO. EPP-I-00-03-00008-00, TASK ORDER 07 APRIL 2013
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)
Form #SB4-304AS AirSourceR SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION) Second only to refrigerant hose leaks, compressors have the highest rate
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for