DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES
|
|
|
- Hannah Hilary Hart
- 9 years ago
- Views:
Transcription
1 SECTION STEAM AND CONDENSATE PIPING PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Comply with the provisions of the following: 1.2 DESIGN CRITERIA 1. ASME B 31.9 Building Services Piping : for materials, products, and installation. Safety valves and pressure vessels shall bear the appropriate ASME label. 2. ASME Boiler and Pressure Vessel Code, Section IX, Welding and Brazing Qualification for qualifications for welding processes and operators. A. The campus steam distribution system is twenty psig, and the system operating pressure shall be designed for 20 psig. All system components, including systems after building pressure reducing valves, shall be designed to withstand 30 psig. B. The designer shall not rely on lift after the steam trap when a steam trap serves a device such as a coil or heat exchanger controlled by a modulating valve. Lift may only be considered when the trap will always have full line pressure. C. Steam mains shall have isolation valves space no further than 200 apart. Steam isolation valves larger than 6 shall be equipped with 2 ball warm-up valves. D. Select steam safety valves for full relief of capacity of equipment served, in accordance with ASME Boiler and Pressure Vessel Code. Provide valves for use with boilers rated ASME Section I, valves for use with unfired pressure vessels, including the low pressure side of pressure reducing valves, rated for ASME Section VIII. Furnish complete with cast iron drip-pan elbow having threaded inlet and outlet with threads (FPT) conforming to ANSI B1.20.1; sized for full size of safety valve outlet connection. E. The designer shall indicate and dimension on the drawings all expansion loops, anchors, & guides. F. Where pressure reducing valves are utilized, the designer shall consult with the specified manufacturer s representative to insure the proposed valve is appropriate for the intended application, including turn down ratio for all expected loads. PART 2 PRODUCTS 2.1 PIPE, FITTING, AND JOINT MATERIALS A. General: Refer to Part 3 Article PIPE APPLICATIONS for identification of where the below materials are used STEAM AND CONDENSATE PIPING Page 1 of 6
2 B. Steam Supply Pipe: Threaded and welded ends. ITEM SIZE ASTM SPEC NO. MATERIAL WEIGHT & TYPE Pipe all sizes A53 or A106, grade B, type S Schedule 40, ANSI B36.10 Fittings 2" A197, Malleable Iron Standard, threaded, ANSI B16.3 >2" A234, WPB, wrought carbon steel Schedule 40, butt weld, ANSI B16.9 Flanges 2" A105, forged carbon steel class 150, RF, threaded, ANSI B16.5 >2" A105, forged carbon steel Bolts All A193, grade B7 carbon steel Nuts All A194, Grade 2H, Carbon steel Gaskets Per flange standard A304, stainless steel, Grafoil filled, spiral wound class 150, RF, weld neck or slip on, ANSI B16.5 Hex head (ANSI B18.2.1), B1.1, class 2A course thread Heavy hex (ANSI B18.2.2), B1.1,class 2B course thread class 150, RF, ring style, ANSI B16.20 C. Gravity & Pumped Condensate: Threaded and welded ends. ITEM SIZE ASTM SPEC NO. MATERIAL WEIGHT & TYPE Pipe 2" A53 or A106, grade B, type S Schedule 80, ANSI B36.10 >2" A53, grade B, type S Schedule 80, ANSI B36.10 Fittings 2" A197, Malleable Iron Extra Heavy, threaded, ANSI B16.3 >2" A234, WPB, wrought carbon steel Extra Heavy, butt weld, ANSI B16.9 Flanges 2" A105, forged carbon steel class 300, RF, threaded, ANSI B16.5 >2" A105, forged carbon steel Bolts All A193, grade B7 carbon steel Nuts Gaskets All Per flange standard A194, Grade 2H, Carbon steel A304, stainless steel, Grafoil filled, spiral wound class 300, RF, weld neck or slip on, ANSI B16.5 Hex head (ANSI B18.2.1), B1.1, class 2A course thread Heavy hex (ANSI B18.2.2), B1.1,class 2B course thread class 150, RF, ring style, ANSI B16.20 D. Unions: ANSI B16.39, malleable-iron, class 300 for schedule 80 piping system, hexagonal stock, with ball and socket joints, metal to metal bronze seating surfaces; female threaded ends. Threads shall conform to ANSI B JOINING MATERIALS A. Welding Materials: Comply, with Section II, Part C. ASME Boiler and Pressure Vessel Code for welding and per the contractor s approved qualification record. 2.3 GENERAL DUTY VALVES A. General duty valves (i.e., gate, globe, check, ball, and butterfly valves) are specified in Division 15 Section VALVES STEAM AND CONDENSATE PIPING Page 2 of 6
3 2.4 SAFETY VALVES A. Cast iron body and bronze seat, Class 250; forged copper alloy disc and nozzle; fully enclosed stainless steel spring having an adjustable pressure range and positive shut off; threaded end connections for valves 2" and smaller, raised face flanged inlet and threaded outlet connections for valves 2 1/2" and larger. Factory set valves to relieve at 10 psi above operating pressure. B. Manufacturers: Manufacturer Bronze Cast Iron Drip Pan Elbow O.C. Keckley Co. #40 #300 Drip Pan Elbow Spence Engineering Co., Inc. #41 #41 DPE Spirax/Sarco #6010 SVI DPE 2.5 PRESSURE REGULATING VALVES A. Pilot actuated, diaphragm type, class 250, with adjustable pressure range and positive shut off; cast iron body with flanged or threaded end connections, hardened stainless steel trim, and replaceable valve head and seat. Provide main head stem guide fitted with flushing and pressure arresting device. Provide cover over pilot diaphragm for protection against dirt accumulation. 1. Spirax/Sarco 2. Spence Engineering Co., Inc 2.6 STEAM TRAPS A. Balanced Pressure Thermostatic Traps: Cast brass, angle pattern body, with integral union tailpiece and screw-in cap; maximum operating pressure of 25 psig; balanced pressure stainless steel or monel diaphragm or bellows element, with renewable hardened stainless steel valve head and seat. 1. Spirax/Sarco TA-125, TH-125, TV Tunstall series TA. B. Float and Thermostatic Traps: ASTM A 278, Class 30 cast iron body and bolted cap; renewable, stainless steel float mechanism, with renewable, hardened stainless steel head and seat; balanced pressure thermostatic air vent made of stainless steel or monel bellows with stainless steel head and seat. 1. Spirax/Sarco FT-30, FTI-30 (no substitutions) C. Inverted Bucket Traps: ASTM A 278, Class 30 cast iron body and cap, pressure rated for 250 psi; stainless steel head and seat; stainless steel valve retainer, lever, guide pin assembly, brass or stainless steel bucket. 1. Spirax/Sarco B series. 2.7 AIR VENTS A. Cast iron or brass body, with balanced pressure stainless steel or monel thermostatic bellows, and stainless steel heads and seats. 1. Spirax/Sarco VS206 (steam) 2. Spirax/Sarco - 13WS (condensate) STEAM AND CONDENSATE PIPING Page 3 of 6
4 2.8 VACUUM BREAKERS A. Stainless steel or brass construction, factory set to open at 2" H 2 O of vacuum, and shall be of a hardened ball check valve or spring restrained style. All spring style components shall be encapsulated with a protective cover. 1. Spirax/Sarco #VB EXPANSION JOINTS A. Externally pressurized bellows type expansion joints. Bellows shall be made of a minimum 3 ply multi-layer 304 stainless steel. Bellows shall be welded to the internal guide ring and housing. Expansion joint shall be preset for ambient conditions on the construction site and shall have a minimum 3/4 compensation for contraction. B. Expansion joints shall be flanged whenever possible and shall be equipped with a drain port. Housing shall be made of carbon steel piping matching the installation. C. Approved manufacturers are HySpan series 3500 and Pathway X-Press. PART 3 EXECUTION 3.1 PIPING INSTALLATIONS A. Install drains at all low points consisting of a tee fitting, 3/4" ball valve, and short 3/4" threaded nipple and cap. B. Install steam supply piping at a uniform grade of 1/32" in 12" downward in the direction of flow. C. Install condensate return piping at a uniform grade of 1/8" in 12" downward in the direction of flow. D. Install steam branch connections to supply mains using 45º elbows on the branch with the main take-off at a 45 angle up from the main. Where the length of a branch takeoff is less than 10', pitch branch line down toward mains, 1/8" in 12". E. Make reductions in schedule 40 pipe systems using an eccentric reducer fitting installed with the level side down. F. Anchor piping to ensure proper direction of expansion and contraction. Install expansion loops and joints as indicated on the Drawings and/or specified. G. Install air vent/eliminators at all high points of steam & condensate piping systems. Where necessary, pipe vent outlets to outdoors, condensate receiver, or drain STEAM AND CONDENSATE PIPING Page 4 of 6
5 H. Install drip legs at low points and natural drainage points in the system, such as at the ends on mains, bottoms of risers, and ahead of pressure regulators, control valves, isolation valves, pipe bends, expansion joints, at intervals not exceeding 150' where pipe is pitched down in the direction of the steam flow, a maximum of 100' where the pipe is pitched up in the direction of steam flow. 1. Drip legs, dirt pockets, and strainer blowdowns shall be equipped with drain valves (& caps) to allow removal of dirt and scale. 2. Install steam traps close (<3') to drip legs and at least 8" below the header. Drain valves serving drip legs shall be lower than the trap connection and never attached to the trap connection. 3. Drip legs shall be sized per the following schedule: Header Size Drip Leg Size 4" Same size as header 4" & 8" 4" 10" & 14" 6" 14" 8" 3.2 STEAM TRAP INSTALLATIONS A. Install steam traps in accessible locations as close as possible to connected equipment. B. Install isolation valve, strainer (leg vertical), and union upstream from the trap; install union, test tee with test valve, check valve, and isolation valve downstream from trap. C. Install the inlet of F & T steam traps a minimum of 12 below the outlet of the device served. 3.3 PRESSURE REDUCING VALVE INSTALLATIONS A. Install pressure reducing valves as required to regulate system pressure in a location readily accessible for maintenance and inspection. Install in strict accordance with the manufacturer s recommended piping practices for straight pipe upstream and downstream of the valve. Provide a bypass around each reducing valve, with a globe valve equal in size to the area of the reducing valve seat ring. Install isolation valves and unions around each reducing valve to facilitate removal and repair of reducing valves. Unions may be omitted for reducing valves with flanged connections. Install strainers upstream for each reducing valve. Install safety valves downstream from each reducing valve set a 5 psig higher than the reduced pressure B. Install pressure gages on both sides of each reducing valve, on the system side of the shutoff valves. On two stage reducing stations, install a drip trap and pressure gage upstream from the second stage reducing valve. 3.4 SAFETY VALVE INSTALLATIONS A. Install relief valves in accordance with and where required by ASME B 31.1 Power Piping. Pipe discharge to atmosphere outside the building, without valves, and terminate vent pipe with screened air gap. Install a drip pan elbow fitting adjacent to the safety valve pipe drain connection to the nearest floor drain without valves. Comply with ASME Boiler and Pressure Vessel Code for installation requirements. 3.5 VACUUM BREAKERS A. All steam generating devices shall be fitted with a vacuum breaker located on the coil inlet piping STEAM AND CONDENSATE PIPING Page 5 of 6
6 3.6 FIELD QUALITY CONTROL A. Prepare steam and condensate piping in accordance with ASME B Verify all components in the piping system can withstand the pressures of testing. Isolate those components that will be damaged by excessive pressure. Clean strainers, flush system with clean water. 1. Isolate equipment that is not to be subjected to the test pressure from the piping. If a valve is used to isolate the equipment, its closure shall be capable of sealing against the test pressure without damage to the valve. Flanged joints at which blinds are inserted to isolate equipment need not be tested. 2. Install relief valve set at a pressure no more than 1/3 higher than the test pressure, to protect against damage by expansion of liquid or other source of overpressure during the test. B. Hydronic testing of steam and condensate piping as follows: 1. Use air vents installed at high points in the system to release trapped air while filling the system. Use drip legs installed at low points for complete removal of the liquid. 2. Examine system to see that equipment and parts that cannot withstand test pressures are properly isolated. Examine test equipment to ensure that it is tight and that low pressure filling lines are disconnected. 3. Subject piping system to a hydrostatic test pressure which at every point in the system is not less than 1.5 times the design pressure or city water pressure, whichever is greater. The test pressure shall not exceed the maximum pressure for any vessel, pump, valve, or other component in the system under test. Make a check to verify that the stress due to pressure at the bottom of vertical runs does not exceed either 90% of specified minimum yield strength, or 1.7 times the "SE" value in Appendix A of ASME B After the hydrostatic test pressure has been applied for at least 10 minutes, examine the system for leakage. Eliminate leaks by tightening, repairing, or replacing components as appropriate, and repeat hydrostatic test until there are no leaks. C. Air testing of steam & condensate piping as follows: 3.7 CLEANING 1. Remove air vents installed at high points and plug. Isolate drip legs using isolation valves. Examine system to see that equipment and parts that cannot withstand test pressures are properly isolated. 2. Subject piping system to a test pressure of 60 psig. The test pressure shall not exceed the maximum pressure for any vessel, pump, valve, or other component in the system under test. 3. After the test pressure has been applied for at least two hours, check the pressure gauge and examine the system for leakage. Eliminate leaks by tightening, repairing, or replacing components as appropriate, and repeat test until there are no leaks. A. Refer to the DC Standards, WATER TREATMENT SYSTEMS. END OF SECTION STEAM AND CONDENSATE PIPING Page 6 of 6
5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
TYPE E Main Valve Sizes 3 /8 through 12
SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,
Float and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
SAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE
1 Which tool is used to correct internal hi-low when preparing a 4-in. steel pipe for welding? A. 4-in. grinder with cutting disc. B. Mini-grinder with flapper disc. C. Pencil grinder with cone stone.
ASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.
ASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.4-1998 - Cast Iron Threaded Fittings ASME/ANSI B16.5-1996 - Pipe
WD600 STEAM TRAPS. Thermodynamic Steam Trap
WD600 Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2010 Watson McDaniel Company WD600, WD600L Sizes 3/8, 1/2, 3/4, 1 NPT Material Stainless
HS-901(A) BASIC STEAM HEATING SYSTEMS
HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,
PRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
RMF Engineering 23 05 23
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
V47 Series Temperature Actuated Modulating Water Valves
V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate
Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW
Installation, Operating and Maintenance Instructions 90/4.5.5 Rev. 0 Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Table of Contents SECTION I... 2 INSTALLATION...
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
DESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
REGULATING VALVE APPLICATIONS
REGULATING APPLICATIONS GENERAL REGULAR APPLICATION & INSTALLATION NOTES Regulator Application & Installation Notes The following are considerations for all steam regulator installations, as system operation
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant
3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
Vogt Valves The Connection Bulletin for Extended Body Forged Steel Valves Welded Bonnet, Bolted Bonnet, Class 800 & Class 1500 CB 22
The Connection Bulletin for Extended Body Forged Steel Valves Welded Bonnet, Bolted Bonnet, Class 800 & Class 1500 CB 22 Extended Body Forged Steel Valves An extended body gate valve specifically designed
NFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
In-Line Air Separators
Air Elimination & Control In-Line Air Separators The AC models of air separators deliver all the quality and performance you expect from Taco products. They are built to last with shell, heads and ANSI
PBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
SECTION 15010 GENERAL REQUIREMENTS, MECHANICAL. 1. All piping entering the Shipyard must be controlled per Shipyard Standard Procedure # 21.1-1.
SECTION 15010 June 16, 2005 GENERAL REQUIREMENTS, MECHANICAL A. GENERAL 1. All piping entering the Shipyard must be controlled per Shipyard Standard Procedure # 21.1-1. 2. All piping shall be in accordance
KUNKLE SAFETY AND RELIEF VALVE PRODUCTS OVERVIEW
KUNKLE SAFETY AND RELIEF VALVE PRODUCTS OVERVIEW ISSUED FEBRUARY 2014 KUNKLE SAFETY AND RELIEF VALVE PRODUCTS OVERVIEW Contents Models 1 and 2 Brass Safety Valves... 4 Models 19, 19M, 20, 20M, 20P, 20MP,
Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).
Fittings for CO 2 Pipe Threads Pipe thread references quoted in this catalogue conform with the requirements specified in the latest issue and amendments of the following ISO Standards: ISO 7-1 (BS21)
Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves
Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves CRANE Energy Flow Solutions TM Donald H. Johnson Crane Energy Flow Solutions 1 Crane Co. Resolution Made By Richard Teller
BERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
REGULATORS D& HD Series
Watson McDaniel reserves the right to change the designs and/or materials of its products out notice. 2002 Watson McDaniel Company Ductile Iron body - HD Series Full port strainer & blowdown valve on pilot
VAD. Variable Area Desuperheaters
Desuperheater overview Steam used in process plants can be superheated, that is, heated to a temperature above saturation. The excess of temperature above its saturation is called 'superheat'. Desuperheated
BLADDER SURGE CONTROL SYSTEM
PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures
Blowdown vessels Meeting the requirements of HSE PM60
Blowdown vessels Meeting the requirements of HSE PM60 BDV60 blowdown vessels complete range of equipment for the safe disposal of boiler blowdown Boiler blowdown Steam boilers must be blown down to remove
Style 07 Zero Flex Rigid Coupling. Style 75 Flexible Coupling. Style 77 Flexible Coupling 11. Description
Style 07 Zero Flex Rigid Coupling The unique angled pad design adjusts to standard pipe tolerances to positively clamp the pipe to resist flexural and torsional loads. Working pressures are based on standard
APCO SLOW CLOSING AIR/VACUUM VALVES
BULLETIN 1 JULY 01 APCO SLOW CLOSING AIR/VACUUM VALVES Series 1900 APCO Slow Closing Air/Vacuum s Maximum Air Flow Velocity in Good Pipeline Design The Air/Vacuum operates in the normal fashion allowing
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...
OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS INTRODUCTION...1 Scope...1 Description...1 Valve Identification...2 1.0 VALVE INSTALLATION...2 2.0 VALVE MAINTENANCE...3 Actuator Disassembly...3
Type 92S Pilot-Operated Steam Regulator
Type 92S Pilot-Operated Steam Regulator Introduction The Type 92S steam regulator is piston actuated for high cycle steam service which includes a Type 6492L, 6492H or pilot (see Figure 1). These pilots
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
BERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features
Pressure Relief/Sustaining Valve Prioritizing pressure zones Ensuring controlled pipeline fill-up Preventing pipeline emptying Pump overload & cavitation protection Safeguarding pump minimum flow Excessive
PRESSURE REDUCER AND RELIEF VALVES WITH METALLIC BELLOW FOR WATER STEAM
PRESSURE REDUCER AND RELIEF VALVES WITH METALLIC BELLOW FOR WATER STEAM PRESSURE REDUCER AND RELIEF VALVES These devices are used to reduce and control a gaseous flow pressure (air, steam, gas ). The PRESSURE
Jay R. Smith Mfg. Co.
Jay R. Smith Mfg. Co. Automatic Backwater Valve SMITH CUSTOMER DRIVEN FLOOD-GATE FEATURES Index Page Flood-Gate Features and Applications 2 How Flood-Gate Works 3 Flood-Gate Operation & Approvals 4 Valve
Pilot Operated Pressure Reducing Valve PRV 47 (Steel) PRV47I (St.Steel)
OPTIONS: USE: AVAILABLE MODELS: Pilot Operated Pressure Reducing Valve PRV 47 (Steel) PRV47I (St.Steel) DESCRIPTION The ADCA PRV47 pilot operated pressure reducing valves are designed for use on steam,
INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS PARTS LIST
12501 Telecom Drive, Tampa Florida 33637 INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS PARTS LIST 90/4.5.1 Rev.1 CONSTANTEMP LOW PRESSURE STEAM-WATER HEATERS Models E-1500L, E-1520L, E-300L, E-320L,
AURORA. 1030 AND 1040 Series SUCTION DIFFUSERS, COMBINATION AND TRIPLE DUTY VALVES WWW.AURORAPUMP.COM
UROR 1030 ND 1040 Series SUCTION DIFFUSERS, COMINTION ND TRIPLE DUTY VLVES WWW.URORPUMP.COM UROR 1030 ND 1040 Series Suction Diffusers, Combination and Triple Duty Valves Designed for Direct Mounting on
Steam Coil Installation, Operation and Maintenance
Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils manufactured by Luvata in Grenada, MS have been
valve solutions Chemical Cosmetic Cryogenic Food & Beverage Marine Mining Nuclear Oil & Gas Paint Pharmaceutical Pulp & Paper www.quilinox.
valve solutions www.quilinox.com Chemical Cosmetic Cryogenic Food & Beverage Marine Mining Nuclear Oil & Gas Paint Pharmaceutical Pulp & Paper valvulas esfera PBM.pdf (1753) 2015/01 1/10 D E SIGN F E A
PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta
PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification Number: 3503-11.2.610 Rev. 2 Rubber Lined Steel Pipe and Fittings Mechanically Coupled Plain End Type System Issued Revised Approved
Steam System Design and Best Practices Related to Kiln Drying
Steam System Design and Best Practices Related to Kiln Drying New England Kiln Drying Association Steam Design and Best Practices HerLine Technologies What is Steam? Like other substances water can exist
Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
VAD Variable Area Desuperheaters
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
BERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
ELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
API Flanged Safety Relief Valves Series 526 CATALOG
API Flanged Safety Relief Valves Series 26 CATALOG The-Safety-Valve.com 1 Valve finder How to find the right product group High operating to set pressure ratio, high backpressure or low total height? Yes
Caps STANDARD WEIGHT Inches / Pounds
Standard Caps you are here: Home > Weldbend Catalog > Fittings > Caps Caps STANDARD WEIGHT Inches / Pounds For Metric Units >Click Here Nominal Pipe Size Outside Inside Wall Thickness (T) Length (E) Pipe
Morrison Bros. Co. General Product Specifications
Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage
Steam System Best Practices Condensate System Piping
Steam System Best Practices Condensate System Piping Summary The best method for improving steam system energy efficiency, reducing chemical costs, and reducing make-up water costs is to return the maximum
BERMAD Waterworks. Quick Active Check Valve. 700 Series. Model 740Q. Features and Benefits. Major Additional Features
Booster Pump Control Valve Quick Active Check Valve Isolates system from the effects of pump starts and stops for: Solitary single speed pumps Battery of single speed pumps (add & switch) Battery of variable
Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409
Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam
THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494
THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494 1. BEFORE YOU BEGIN IMPORTANT INSTRUCTIONS READ AND SAVE FOR THE CONSUMER WARNING: Risk of scalding or other severe injury. Before completing installation,
These features have made Lo Torc valves the choice of high pressure plug value users, worldwide:
LO TORC Plug Valve The high value, dependable performance, and low maintenance requirements of Halliburton Lo Torc valves can help reduce overall operating costs and help cut downtime. These features have
Commercial Semi-Instantaneous Water Heaters
FEATURES HWI Models A. O. Smith s HWI models are available for operation with steam or boiler water as the energy source. They are factory assembled with components sized, piped and checked at the factory
Installation, Maintenance, & Repair Series 4000B/LF4000B
Installation, Maintenance, & Repair Series 4000B/LF4000B Reduced Pressure Zone Assemblies Sizes: 1 2" 2" (15 50mm) RP/IS-A-4000B 4000B/LF4000B Size: 3 /4"! WARNING Testing Read this Manual BEFORE using
OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT
OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT INDEX AMERICAN - DARLING 5-1/4 IN. B-84-B-5 FIRE HYDRANT OPERATION AND MAINTENANCE MANUAL OPERATION AND MAINTENANCE REPAIRS Operation and Maintenance...
Type 25P & 25PA Pressure Reducing Valves
INSTAATION AND MAINTENANCE INSTRUCTIONS IM-3-000-US October 2015 Type 25P & 25PA Reducing s Safety Information Safe operation of these products can only be guaranteed if they are properly installed, commissioned,
Installer s Guide 18-AH39D1-13
18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,
TECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
FLASH TANK ECONOMIZER PRODUCT GUIDE
FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.
SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS
SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS PART 1: GENERAL 1.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of AW facilities. Closely coordinate construction work
Hose Clamps & Fittings
All Stainless Steel Marine or Underground Hose Clamps 5/16 HEX HEAD SCREW 60000 SERIES Highly corrosion resistant Use for marine or underground applications Stainless Steel Band, Housing Plated Steel Screw
INSTRUMENTATION & CONTROLS VALVE & AUTOMATION EXPERTS VALVE REPAIR TUBE SERVICES
INSTRUMENTATION & CONTROLS VALVE & AUTOMATION EXPERTS VALVE REPAIR TUBE SERVICES GREAT PRODUCTS ARE ONLY PART OF OUR SUCCESS. YOU SHOULD MEET OUR PEOPLE. From the machinist with over 20 years experience
One Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty
One Year Warranty ELECTRIC Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches Fused Ceramic Shield tank lining is corrosion-resistant for years of dependability. Adjustable
STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE
Page 1 of 9 PURPOSE Steam is the most commonly used heating medium for maintaining process temperatures. Compared to other heating media, steam contains a significant amount of heat energy, and this heat
FLANGED END BALL VALVE
Specification: FLANGED END BALL VALVE - Chem Oil s two-piece ball valve has been designed to handle extreme service applications with unsurpassed reliability. Valve body machined from solid wrought material
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
CHEXTER TM FITS YOUR APPLICATION, PROFITABLY
CHEXTER TM FITS YOUR APPLICATION, PROFITABLY Commercial Construction CHEXTER TM Check Valves are economically used in chilled and hot water air conditioning systems, refrigeration and other piping and
Copper and Copper Alloy Tube, Pipe and Fittings
Copper and Copper Alloy Tube, Pipe and Fittings COPPER and COPPER ALLOY TUBE and PIPE Seamless Copper Pipe: Copper pipe is almost pure copper manufactured to the requirements of ASTM B 42 - Standard Specification
Valves, Automation & Controls. series 84 /99 HIGH PERFORMANCE 3-PIECE BALL VALVE REDUCE & FULL PORT, STANDARD & FIRE SAFE. www.sharpevalves.
Valves, Automation & Controls series 8 /99 & FS8 /FS99 HIGH PERFORMANCE -PIECE BALL VALVE REDUCE & FULL PORT, STANDARD & FIRE SAFE www.sharpevalves.com Design & Features SHARPE VALVES - SERIES 8/99 Fire
BOWIE PUMPS OPERATION - MAINTENANCE
BOWIE PUMPS OPERATION - MAINTENANCE PUMPING PRINCIPLE: The meshing owieeof the gears cause a slight depression, with the resulting enmeshing of the gears causing a vacuum drawing the fluid being pumped
Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, 1060. Instruction No.
Instruction No. AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA PIPING GUIDE GF-115-P Modulex Gas Fired Boiler Systems Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909,
Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description
Product Manual CVS Type 67AFR Filter Regulator Introduction This CVS Controls product manual includes instructions for the installation, adjustment, maintenance and parts ordering of the CVS Type 67AFR
STORAGE, INSTALLATION AND MAINTENANCE PROCEDURES
GATE VALVE O.S. & Y 1.0 Periodic Inspections 1.1 The valve stem packing should be inspected at least monthly. If the stem packing shows signs of leakage, simply tighten the adjusting nuts to compress the
Application Guide. Compensators Hose Assemblies Expansion Joints FLEX-WELD INCORPORATED FLEX-WELD.COM. Manufactured By:
Compensators Hose Assemblies Expansion Joints Manufactured By: FLEX-WELD INCORPORATED FLEX-WELD.COM What we need to know... A. Physical / System Parameters 1 Size of Assembly: Measure Pipe size (ID) of
DV-5 Deluge Valve with Remote-Resetting, Pressure-Reducing Trim 4 Inch and 6 Inch (DN100 and DN150) General Description.
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim 4 Inch and 6 Inch (DN and DN5) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water
REGULATORS 175/153 Series
175/153 Series 175 HEATING 153 COOLING Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2002 Watson McDaniel Company Revised 7/2002 175 / 153 Screwed
OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE
OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203)
SPECIFICATION DIVISION 22 SECTION DESCRIPTION DIVISION 22 PLUMBING SECTION 220519 - THERMOMETERS, PRESSURE GAUGES, AND ACCESSORIES
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
SECTION 221413 FACILITY STORM DRAINAGE PIPING
SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
AIR LINE VALVES AND GAUGES
AIR LINE VALVES AND GAUGES INGERSOLL-RAND AIR LINE VALVES AND GAUGES Maintaining consistent air pressure throughout the entire system is crucial for maximum performance and productivity. Ingersoll-Rand
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
Arapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Types 66R and 66RR Low-Pressure Relief Valves
November 2009 Types 66R and 66RR Low-Pressure Relief Valves W1953 W1908 TYPE 66R RELIEF VALVE TYPE 66RR RELIEF VALVE Figure 1. Typical Constructions Introduction Types 66R and 66RR low-pressure throttling
James M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions
4057250/8 IM-P405-16 AB Issue 8 ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Operation
American- Darling 5¼" B-84-B-5.
-5 Sealed Lubrication Chamber Seals operating threads from water and debris which greatly reduces routine maintenance. Top Travel Stop Nut Helps prevent stem buckling and damage to bronze components which
Installation Instructions 4508 4508S
SYMPHONY Spread Lavatory Faucet with Speed Connect Drain Congratulations on purchasing your American Standard faucet with Speed Connect drain, a feature found only on American Standard faucets. Speed Connect
SIMPLAIR PIPING. www.irtools.com 1-800-376-TOOL
SIMPLAIR PIPING INGERSOLL-RAND SIMPLAIR PIPING With push-in fittings and lightweight anodized aluminum pipe, a SimplAir system provides ideal connection throughout your entire air distribution system.
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
