CO 2. fire extinguishing systems



Similar documents
Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230

COMITÉ EUROPÉEN DES ASSURANCES

GAS EXTINGUISHING SYSTEMS INERT GAS EXTINGUISHING SYSTEMS. Argotec Liquid Argon Gas Extinguishing Technology (LAR)

INERGEN - EXTINGUISHING SYSTEMS

Alarm and Detection/Suppression

Conventional Fire Detection and Extinguishant Control System Specification

BRANCH SOLUTION. Fire protection for wind turbines. Safe for certain

PLAN REVIEW GUIDE FOR FIRE ALARM

Requirements for Hydrogen Storage and Use

BRANCH SOLUTION. Automatic fire extinguishing systems for paint spraying plants. Safe for certain.

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Element D Services Plumbing

Fire suppression system for engine compartments USER MANUAL

GUIDELINES - Gas Inspection Regulations 1. Recommendations for camping site owners

Certificate of Conformity Certificate num. Registration date Version Valid until

TEDDINGTON. Intuitive control. TLC 700 The multifunctional controller

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

On-Line Fire Extinguisher Training

Fire protection in archives and storage vaults

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

AUTOCLAVE STEAM STERILIZERS

OREGON FIRE CODE Interpretations and Technical Advisories

MAP COFFEE MIA CAPSULE COFFEE MACHINE INSTRUCTION MANUAL MODEL: CM4725. Read this manual thoroughly before using and save it for future reference

UFGS (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System

Visions become real. Temperature control and cooling systems. The innovative and reliable solution

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

Module 5. Fire and Emergency Alarm System Part I- Basics

BERMAD Fire Protection

LIQUEFIED PETROLEUM GASES

Fire Pump Plan Review March 2010

NITROX // safer diving

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

San josé OWNER S MANUAL

FIRE ALARM SYSTEM RECORD OF COMPLETION

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

Thyristor-controlled power supplies and battery chargers

THE GAS UTILITIES S AND THE JAPAN GAS ASSOCIATION S EFFORTS TO IMPROVE SAFETY

FIRE ALARM SYSTEM RECORD OF COMPLETION

Owner s Guide. ca6554

ENGINEERING SPECIFICATIONS

Electronic Diesel Control EDC 16

FIRE EXTINGUISHER TRAINING

SET-UP AND TECHNICAL MANUAL

The Fastest Breaking Fogging Systems

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

General Fire Code Requirements Within Commercial Tenant Spaces

OVERSEAS MARINE CERTIFICATION SERVICES (OMCS)

EuroFID Total Hydrocarbon Analyzer. Precise Determination of Total Hydrocarbons in Air for Corrosive as well as Condensing Gases

ŠkodaOctavia Supplement - for vehicles with LPG drive

Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1

Ethanol Vehicle and Infrastructure Codes and Standards Citations

E2-E3: ELECTRICAL CHAPTER-13 FIRE PROTECTION SYSTEM- EVOLVING TRENDS AND APPLICABILITY TO DATA CENTRE

DCSS (DCL) Data Center Fire Suppression Procedures

KEMPER Leak Detection System

IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

Standard Operating Procedure

EXHIBIT A SCOPE OF WORK

How intelligent must an extinguishing solution be to keep fire virtual?

BERMAD Fire Protection

Manual for Fire Suppression & Methane Detection System

Basic Hydraulics and Pneumatics

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

CA 1050 Owner s Guide

LMS The modular management system for condensing boilers. Control Products & Systems OEM. Answers for infrastructure.

How To Control A Car Alarm On A Car With A Remote Control System

This is how you solve burning problems on forklift trucks and construction machines

Fire Extinguishers Water Extinguishers

USER MANUAL OPERATION AND USE OF CAR WITH. Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM

Emergency Response Guide

The Buhl Electric Secure Home. Brought to you by Buhl Electric. Security Packages and Options

Potential problems with computer hard disks when fire extinguishing systems are released

The IoT s application to protect your family

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.

Volkswagen Jetta, Golf, GTI 1999, Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Automatic fire-extinguishing systems for commercial cooking

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

Gas Turbine Combustor Technology Contributing to Environmental Conservation

Fire Alarm System Plans Review Checklist Property location Date of Review

RAD-SYS-NEMA4X-SMS Control Cabinet. Solution guide for SMS-based remote access control and intrusion detection system

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

E - THEORY/OPERATION

To: All Shipowners, Ship Managers, Ship Masters and Classification Societies

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

Fire & Safety. Fire Safety Training For FHSc Staff and Students in Health Care Facilities

Class A - Wood, paper, cloth, trash, plastics Solid combustible materials that are not metals. (Class A fires generally leave an Ash.

Guidelines for operation of minimum flow control valves

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Rules for Classification and Construction Additional Rules and Guidelines 3 Machinery Installations

CBD-233. Fire Alarm and Detection Systems

HEAVY-DUTY HAND CUTTING TORCHES AND ACCESSORIES. Page 1 Version no.: V

Thermal Conductivity Detector

ODYSSEY. Security System Owner s Manual. Kit No. 08E51-SHJ E55-SHJ American Honda Motor Co., Inc. - All Rights Reserved.

OPERATING INSTRUCTIONS SECURITY SYSTEM KIT NO.: 08E51-EP American Honda Motor Co., Inc. - All Rights Reserved. 1

Electro-Pneumatic Bus Door Control Mechanism

ICP-CP500. User's Guide ICP-CP500 Codepads

The ABB i-bus KNX Room Master Concept Your first step into the KNX world

Transcription:

fire extinguishing systems

Extinguishing technique is a colourless, odourless and electrical non-conductive gas. In systems the is mixed with a special identifiable odour. The extinguishing effect of is based on the principle of lowering the oxygen content in the air to a value at which the combustion process cannot be sustained. Cooling is a secondary action of the agent. As a gaseous extinguishing agent, penetrates the volume to be flooded quickly and evenly. is a suitable extinguishing agent for example at fires of the following materials or arrangements: Combustible liquids and other materials which behave like combustible liquids under fire conditions. Combustible gases, provided no ignitable gas / air mixture can be formed after extinguishment. Electronic devices. Combustible solids such as wood, paper and textiles which require a higher concentration and a longer exposure time. In applications where the discharge of may endanger people, the system will be delay released. The discharge of is effected after a pre-warning period during which people can leave the room safely. The Kidde Brand- und Explosionsschutz retarding device is a pneumatic delay device. By this means it is ensured that, even in the event of a malfunction in the fire detection panel, the start of the discharge is delayed. The warning to people in the area is made by audible or if necessary by optical signals. Kidde Brand- und Explosionsschutz extinguishing systems designed, installed and maintained by highly experienced engineers approved by VdS achieve rebates on insurance premiums available with UL/FM listed system components and the environment The emission of is increasingly being discussed in connection with global warming. The for fire extinguishing systems is not specially manufactured, but is taken from byproducts of technical processes or from natural resources. Furthermore, extinguishing systems prevent the formation of and other environmentally harmful materials from fires. There is therefore no need to forbid the use of for economical reasons. On the contrary, fire extinguishing with systems plays a major role in environmental protection.

Installation examples Section valves for high pressure systems low pressure system with fire detection panel, pneumatic time delay device and section valves high pressure extinguishing system with pneumatic time delay device low pressure container high pressure extinguishing system low pressure section valves

high pressure systems The extinguishing medium is stored as liquid in steel cylinders (approx. 60 bar). The following cylinder sizes are available: 8 l / max. 6 kg - filling 10 l / max. 8 kg - filling 40 l / max. 30 kg - filling 67 l / max. 50 kg - filling According to the required quantity of extinguishing medium cylinder batteries (of uniform bottle size) are combined. Each cylinder is supervised by a scale for loss. The response of a scale can be signalled remotely at the fire detection panel via a light barrier. When fire is identified by the automatic detector (1) or the actuation of the manual push button (2) the fire detection panel (3) will electrically open the alarm and control bottles. The discharged activates a pneumatic delay device (6) and sounds a mechanical horn (7) in the protected room. Section valves with fire detection panels VdS approval S 302007 E 3780007 bottle battery with section valves and pneumatic time delay

Parallel to this an electric horn (4) is actuated by the fire detection control panel. At the end of the object related adjusted delay the extinguishing medium bottles (8) are pneumatically opened and the is discharged through the extinguishing nozzles (9) into the room. Extinguishing medium container with scale and pneumatically controlled quick opening valve Sketch of a high pressure system

low pressure systems For cost reasons quantities of extinguishing medium from approximately 2 t and above are not stored in single bottles but in a container. The is cooled down to 20 C in an insulated tank and is liquid at this temperature at a pressure of approximately 20 bar. The complete tank (8) stands on a scale which responds on a loss of approximately 10% by weight. The transfer of this signal of a loss to a fire detection panel (3) is possible via a limit switch. On a fire signal from the automatic (1) or the manual (2) detectors the fire detection panel actuates a solenoid valve via the time delay device (6) and the pneumatic siren (7) is actuated together with the electric alarm devices (4, 5). At the same time the pre-warning time starts to run in a pneumatic and in an electric timer. After the elapse of the prewarning time in both devices the section valve (9) is opened pneumatically and the fire area is flooded. Prior to the start of the flooding doors and other openings are closed electrically or pneumatically, but not locked. After the elapse of the flooding time, which is normally 120 seconds, the section valve is closed. Sketch of the low pressure system

All described control functions are related to the extinguishing area in which the fire has been detected. For this reason, a malfunction in another extinguishing area is impossible without a simultaneous alarm and the running of a delay time. Distributing manifold with section valves for low pressure systems VdS approval S 302001 E 3780007 storage container with control cabinets Installation of pneumatic time delay devices for 4 extinguishing areas storage container with electronic weighing appliance for loss supervision

Kidde Brand- und Explosionsschutz GmbH Harkortstr. 3 40880 Ratingen Telephone +49 (0)2102 57 90-0 Fax +49 (0)2102 57 90-109 info@kidde.de www.kidde.de Kidde Brand- und Explosionsschutz GmbH Sales office South Steinerne Furt 78 86167 Augsburg Telephone +49 (0)821 74 82 95-0 Fax +49 (0)821 74 82 95-10 Subject to changes! The information in this brochure are only general descriptions and/or performance data which, as described herein, are not always applicable to the specific case of application and/or which can be changed due to further development of the products. The performance data desired will only then have binding character if they are agreed expressively at contract conclusion. Issue: November 2006