OREGON FIRE CODE Interpretations and Technical Advisories
|
|
|
- Benedict Cox
- 9 years ago
- Views:
Transcription
1 OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application of Oregon s fire prevention and life safety regulations. Date: April 4, 2011 Ruling: Technical Advisory No (Revised TA# 08-02) Subject: Motor Vehicle Fuel Storage and Dispensing Guidelines Code Reference: 2010 Oregon Fire Code, Chapter 22 and 34. Content: Plan Review Requirements Prior to installation and operation when an above ground storage tank has a capacity of more than 1,000 gallons, single or aggregate, two sets of plans shall be submitted to the Office of State Fire Marshal for review. Plans shall include details for all applicable provisions. Application An application to request a plan review shall be submitted with the plans on a form supplied by the Office of State Fire Marshal. Tank Design Criteria Above ground storage tanks shall be designed, fabricated and constructed in accordance with nationally recognized standards. For the purpose of the Oregon Fire Code, the following standards are recognized: UL 142 Non-protected Tanks UL 2085 Protected Tanks Piping All piping is required to be designed and fabricated from suitable materials having adequate strength and durability to withstand the pressures, structural stresses and exposures to which they can be subjected. All piping is required to be tested before being placed in service. Hydrostatic testing is required to be 150 % of the maximum anticipated pressure of the system, or pneumatic testing is required to be 110 % of the maximum anticipated pressure of the system when operating, but not less than 3 psi and not more than 5 psi. All under ground piping shall be properly designed, installed and maintained, and protected from corrosion by either a cathodic protection system or by being constructed of corrosion-resistant materials. Page 1 of 6
2 Quantity of Fuel to be Stored UL 142 (Non-protected Tanks) 6,000 gallon individual shell or 18,000 gallon aggregate capacity. UL 2085 (Protected Tanks) 12,000 gallon individual shell or 48,000 gallon aggregate capacity. NOTE: Tanks containing Class II or III-A liquids may be of greater capacity as approved by the fire code official. Vehicle Impact Protection Protection shall be provided when tanks are subject to vehicle impact. When guard posts are installed, the posts shall be: Constructed of steel, not less than 4 inches in diameter and concrete filled. Spaced not more than 4 feet between posts on center. Set not less than 3 feet deep in a concrete footing of not less than a 15 inch diameter. Set with the top of the post not less than 3 feet above ground, and Located not less than 3 feet from the protected object. Separation of LPG Tanks The minimum horizontal separation between an LP-gas container and a Class I, II or III-A liquid storage tank shall be 20 feet. Separation Requirements Tank Capacity Non-Protected Tanks UL 142 Property Lines or Near Side of Public Way Opposite Side of a Public or Important Building Way All Tank Capacity Protected Tanks UL 2085 Property Lines or Opposite Side of a Public Way Near Side of Public Way or Important Building Distance Between Tanks Distance Between Tanks Less than or equal to ,000 Greater than 6, Overfill Protection Tanks shall not be filled in excess of 95 % of their capacity. An overfill prevention system shall be provided that shall: Provide an independent means of notifying the person filling the tank that the fluid level has reached 90 percent of tank capacity by providing an audible or visual alarm signal, providing a tank level gauge marked at 90 percent of tank capacity or other approved means, and Page 2 of 6
3 Automatically shut off the flow of fuel to the tank when the quantity of liquid in the tank reaches 95 percent of tank capacity or other approved method of overfill prevention. A permanent sign shall be provided at the fill point for the tank documenting the filling procedure and the tank calibration chart. The filling procedure shall require the person filling the tank to determine the gallonage required to fill it to 95 percent of capacity before commencing the fill operation. Spill Containment A spill container having a capacity of not less than 5 gallons shall be provided for each fill connection. For tanks with a top fill connection, spill containers shall be noncombustible and shall be fixed to the tank and equipped with a manual drain valve that drains into the primary tank. For tanks with a remote fill connection, a portable spill container shall be provided. Venting (normal and emergency) Vent pipe outlets for tanks storing Class I, II or III-A liquids shall be located such that the vapors are released at a safe point outside of buildings and not less than 12 feet above the adjacent ground level. Vapors shall be discharged upward or horizontally away from closely adjacent walls to assist in vapor dispersion. Vent outlets shall be located such that flammable vapors will not be trapped by eaves or other obstructions and shall be at least 5 feet from building openings or property lines of properties that can be built on. Stationary, above ground tanks shall be provided with additional venting that will release excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and III-A liquids shall not discharge inside buildings. Exception: Tanks larger than 12,000 gallons in capacity storing Class III-B liquids which are not within the diked area or the drainage path of Class I or II liquids do not require emergency relief venting. Warning Signs Warning signs shall be conspicuously posted within sight of each dispenser in the fuel-dispensing area and shall state the following: No smoking. Shut off motor. Discharge your static electricity before fueling by touching a metal surface away from the nozzle. To prevent static charge, do not reenter your vehicle while gasoline is pumping. If a fire starts, do not remove nozzle use emergency fuel shut off. It is unlawful and dangerous to dispense gasoline into unapproved containers. No filling of portable containers in or on a motor vehicle. Place container on ground before filling. Page 3 of 6
4 Dispenser Specifications and Location(s) Dispensing devices shall be located as follows: 1) Ten feet or more from property lines. 2) Ten feet or more from buildings having combustible exterior wall surfaces or buildings having noncombustible exterior wall surfaces that are not part of a 1 hour fire-resistancerated assembly or buildings having combustible overhangs. Exception: Canopies constructed in accordance with the Building Code providing weather protection for the fuel islands. 3) Such that all portions of the vehicle being fueled will be on the premises of the motor fuel-dispensing facility. 4) Such that the nozzle, when the hose is fully extended, will not reach within 5 feet of building openings. 5) Twenty feet or more from fixed sources of ignition. Dispensing devices except those installed on top of a protected above-ground tank that qualifies as vehicle-impact resistant, shall be protected against physical damage by mounting on a concrete island 6 inches or more in height or by other approved methods. Dispensing devices shall be installed and securely fastened to their mounting surface in accordance with the dispenser manufacturer s instructions. Dispenser hoses shall be a maximum of 18 feet in length unless approved. Dispenser hoses shall be listed and approved. When not in use, hoses shall be reeled, racked or otherwise protected from damage. Dispenser hoses for Class I and II liquids shall be equipped with a listed emergency breakaway device designed to retain liquid on both sides of a breakaway point. Emergency Disconnect Switches An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location, to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet of but not less than 20 feet from the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations. Secondary Containment Secondary containment for outdoor storage areas shall be designed to contain a spill from the largest individual vessel. If the area is open to rainfall, secondary containment shall be designed to include the volume of a 24-hour rainfall as determined by a 25-year storm and provisions shall be made to drain accumulations of ground water and rainwater. Page 4 of 6
5 An approved monitoring method shall be provided to detect hazardous materials in the secondary containment system. The monitoring method is allowed to be visual inspection of the primary or secondary containment, or other approved means. Where secondary containment is subject to the intrusion of water, a monitoring method for detecting water shall be provided. Where monitoring devices are provided, they shall be connected to approved or audible alarms. Drainage Control and Diking The area surrounding a tank or group of tanks shall be provided with drainage control or shall be diked to prevent accidental discharge of liquid from endangering adjacent tanks, adjoining property or reaching waterways. Exceptions: 1) The fire code official is authorized to alter or waive these requirements based on a technical report which demonstrates that such tank or group of tanks does not constitute a hazard to other tanks, waterways or adjoining property, after consideration of special features such as topographical conditions, nature of occupancy and proximity to buildings on the same or adjacent property, capacity and construction of proposed tanks and character of liquids to be stored, and nature and quantity of private and private fire protection provided. 2) Drainage control and diking is not required for listed secondary containment tanks. Fire Extinguishers Approved portable fire extinguishers with a minimum rating of 2-A:20- B:C shall be provided and located such that an extinguisher is not more than 75 feet from pumps, dispensers or storage tank fill-pipe openings. Unsupervised Dispensing (Cardlock/Fleet) A telephone not requiring a coin to operate or other approved clearly identified means to notify the fire department shall be provided on the site in a location approved by the fire code official. An approved emergency procedure sign, in addition to other required signs, shall be posted in a conspicuous location and shall read: IN CASE OF FIRE, SPILL OR RELEASE 1. Use emergency pump shutoff. 2. Report the accident! Fire department telephone No. Facility address Dispenser operating instructions shall be conspicuously posted in approved locations on every dispenser and shall indicate the location of the emergency shutoff controls. Page 5 of 6
6 Dispensing equipment used at unsupervised locations shall comply with one of the following: 1. Dispensing devices shall be programmed or set to limit uninterrupted fuel delivery to 40 gallons and require a manual action to resume delivery. Exception: Class II or III-A liquids may be programmed or set to limit uninterrupted fuel delivery of up to 250 gallons. 2. The amount of fuel being dispensed shall be limited in quantity by a preprogrammed card as approved. Contact the Office of State Fire Marshal for additional rules regarding cardlock operations. NOTE: Compliance with the Oregon Fire Code does not automatically constitutes compliance with EPA or other federally mandated rules, and further research may be necessary. It is the responsibility of the applicant to ensure that all installations are in full compliance with applicable statutes of the State of Oregon and any local codes and ordinances. Other References: NFPA 30 and 30A Page 6 of 6
The following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
The following definitions apply with regard to requirements specified in this document:
GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved
Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil)
Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil) References: Comm 10 2009 EDITION / NFPA 30 2008 EDITION ITEM DESCRIPTION Comm 10 / NFPA General
ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS
Facility Name: ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS The following is intended to be used as a guideline for information required to appear on engineered drawings involving petroleum storage
Pressure Vessels (Air Compressors) and LPG Tanks
Pressure Vessels (Air Compressors) and LPG Tanks 1. Identification of Workplace Hazard Any container, tank or vessel that contains pressurized material is a potential hazard to employees due to the force
Sample Written Program. For. Flammable Liquids
Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
Requirements for Hydrogen Storage and Use
Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These
Ethanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
Waste Oil Collection / Storage
ENVIRONMENTAL & REGULATORY SERVICES Storage Tank Regulation Section P. O. Box 7837 Madison, Wisconsin 53707-7837 TDD #: (608) 264-8777 http://www.commerce.state.wi.us http://www.wisconsin.gov Jim Doyle,
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
MOTOR FUEL DISPENSING SAFETY
STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
1. Site plans assist the Fire Department to determine where a potential spill can be contained. The detailed site plan shall include the following:
Secondary Containment, Spill Control and Drainage Guidelines for Hazardous Materials per 2010 CFC PURPOSE The intent of this guideline is to provide the requirements for the design and construction of
ADMINISTRATIVE SERVICES MANUAL
Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of
NFPA 30-2008: Basic Requirements for Storage Tanks
NFPA 30-2008: Basic Requirements for Storage Tanks New York City Metro Chapter Society of Fire Protection Engineers New York, NY February 22, 2011 NFPA 30, Flammable and Combustible Liquids Code Storage
MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
CHAPTER 22 MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES SECTION 2201 GENERAL 2201.1 Scope. Automotive motor fuel-dispensing facilities, marine motor fuel-dispensing facilities, fleet vehicle motor
Civil Engineering Sector Labour-Management Health and Safety Committee
PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION SITES Civil Engineering Sector Labour-Management Health and Safety Committee July 2008 PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION
Code Compliance Guideline: Swimming Pool Chemicals
A publication of Fairfax County, Virginia CODE COMPLIANCE GUIDELINE SWIMMING POOL CHEMICALS AND FIRE SAFETY REQUIREMENTS RELATED TO POOL OPERATIONS This publication outlines the Fire Prevention Code requirements
NFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems
Page 1 of 5 Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems New Hampshire Department of Environmental Services
FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes
FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
All You Ever Wanted to Know About Fire Extinguishers...
All You Ever Wanted to Know About Fire Extinguishers... There are basically four different types or classes of fire extinguishers, each of which extinguishes specific types of fire. Newer fire extinguishers
LIQUEFIED PETROLEUM GASES
CHAPTER 38 LIQUEFIED PETROLEUM GASES SECTION 3801 GENERAL 3801.1 Scope. Storage, handling and transportation of liquefied petroleum gas (LP-gas) and the installation of LP-gas equipment pertinent to systems
FLAMMABLE AND COMBUSTIBLE LIQUIDS
CHAPTER 57 FLAMMABLE AND COMBUSTIBLE LIQUIDS SECTION 5701 GENERAL 5701.1 Scope and application. Prevention, control and mitigation of dangerous conditions related to storage, use, dispensing, mixing and
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
FLAMMABLE AND COMBUSTIBLE LIQUIDS
CHAPTER 34 FLAMMABLE AND COMBUSTIBLE LIQUIDS SECTION 3401 GENERAL 3401.1 Scope and application. Prevention, control and mitigation of dangerous conditions related to storage, use, dispensing, mixing and
FLAMMABLE AND COMBUSTIBLE LIQUIDS
CHAPTER 34 FLAMMABLE AND COMBUSTIBLE LIQUIDS SECTION 3401 GENERAL 3401.1 Scope and application. Prevention, control and mitigation of dangerous conditions related to storage, use, dispensing, mixing and
Farm Fuel Tank Safety Guide
Farm Fuel Tank Safety Guide This brochure is provided by North Dakota Department of Emergency Services, your Local Emergency Planning Committee, and the State Emergency Response Commission along with assistance
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
A. Fire Protection Plan. B. Access and Parking
Standards for Construction Site Fire Safety For Use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire Code (CFC) These standards are intended to prescribe
September 2008 AFC 4.6.2.1.(2) Page 1 of 5. Maximum Size and Aggregate Capacities of Aboveground Storage Tank Systems at Fuel Dispensing Stations
FIRE CODE VARIANCE September 2008 AFC 4.6.2.1.(2) Page 1 of 5 ISSUE Maximum Size and Aggregate Capacities of Aboveground Storage Tank Systems at Fuel Dispensing Stations The Alberta Fire Code (AFC) limits
OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES
OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES Reference: National Fire Protection Association (NFPA) Pamphlet No. 58 Liquefied Petroleum Gas Code, 2001, Chapter 11 Type of Facility: Petroleum
ACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas
ACTIVITY NAME Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas CY 2014 BOTTOM LINE UP FRONT To prevent oil discharges
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
The Fuel Storage Tank Regulations 2009
The Fuel Storage Tank Regulations 2009 October 2009 ED/RO1/015 The Fuel Storage Tank Regulations Issued by: The Regulation and Supervision Bureau for the water, wastewater and electricity sector in the
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES
527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES Section 14.01: Scope 14.02: Definitions 14.03: Storage 14.04: Handling of Flammable Fluids 14.05: Handling of Flammable
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN Adopted October 5, 2009 Table of Contents Chapter Description Page 1 Facility Descriptions... 3 1.1 Municipal Power Plant, 1001 Park
FLAMMABLE AND COMBUSTIBLE LIQUIDS
GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
Safe Operating Procedure
Safe Operating Procedure (Revised 3/14) ABOVEGROUND PETROLEUM STORAGE TANKS INTRODUCTION Aboveground storage tanks (ASTs) are used to store petroleum products at several UNL locations. For example, ASTs
Spill Prevention, Control and Countermeasure (SPCC) Rule
Spill Prevention, Control and Countermeasure (SPCC) Rule Code of Federal Regulations Title 40 CFR Part 112 Training Guide for Oil and Fuel handlers on Farms 1 Purpose of SPCC Rule To prevent oil discharges
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
BP WIND ENERGY POLICIES AND PROCEDURES
BP WIND ENERGY POLICIES AND PROCEDURES Document Control Details 1.0 Purpose/Scope 1.1 This procedure provides the minimum requirements to be followed for the storage of flammable or combustible materials
Morrison Bros. Co. General Product Specifications
Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage
TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES
CHAPTER 24 TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES > SECTION 2401 GENERAL 2401.1 Scope. Tents, canopies and membrane structures shall comply with this chapter. SECTION 2402 DEFINITIONS 2402.1 Definitions.
Model Safety Program
Model Safety Program DATE: SUBJECT: Flammable and Combustible Liquids Safety Program REGULATORY STATUTE: OSHA 29 CFR 1910.106 OVERALL RESPONSIBILITY: The (YOUR COMPANY) Safety Officer is. He/she is solely
FUEL-OIL PIPING AND STORAGE
CHAPTER 13 FUEL-OIL PIPING AND STORAGE SECTION MC 1301 GENERAL 1301.1 Scope. This chapter shall govern the design, installation, construction and repair of fuel-oil storage and piping systems. The storage
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.
Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered
Above-Ground Petroleum Storage Tank Manual With Data on NC Gasoline Vapor Recovery & EPA Spill Plan Information
Above-Ground Petroleum Storage Tank Manual With Data on NC Gasoline Vapor Recovery & EPA Spill Plan Information By The North Carolina Petroleum & Convenience Marketers 7300 Glenwood Avenue Raleigh, North
DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY. August 2012
DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY August 2012 SECTION 2 The storage requirements in Directive 055 apply to upstream petroleum facilities, well sites, and pipelines
INTERNATIONAL FIRE CODE SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES
INTERNATIONAL FIRE CODE SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES 3103.1 General. All temporary tents and membrane structures shall comply with this section. 3103.2 Approval required. Tents
Flammable and Combustible Liquids. Slide 1 (of 23)
Flammable and Combustible Liquids Slide 1 (of 23) Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids
OIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS. Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040
ABSTRACT OIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040 The SPCC regulations entail numerous requirements for the
Steel Tank Institute AST Inspections. Dana Schmidt, PE STI/SPFA
Steel Tank Institute AST Inspections Dana Schmidt, PE STI/SPFA Agenda Brief review of SPCC Rule SPCC relevance to small tanks and small facilities. SP001 Standard for Inspection of Aboveground Storage
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
ABOVE-GROUND STORAGE TANKS
ABOVE-GROUND STORAGE TANKS Above-ground storage tanks in Georgia are regulated by the State Fire Marshall and by the EPA. Above-ground tanks containing 1,100 gallons or less do not require any secondary
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN XXXX FARM (CITY OR COUNTY), MICHIGAN CONTACT (NAME), OWNER CERTIFICATION: I hereby certify that I have examined the facility, and being familiar with the
Fire and Life Safety Requirements for Special Events and Temporary Use of the Facilities at the Kitsap County Fairgrounds.
Fire and Life Safety Requirements for Special Events and Temporary Use of the Facilities at the Kitsap County Fairgrounds. PURPOSE This document is developed to assist event planners and responsible parties
Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
Section A SPCC Plan Implementation Checklist This section of the report addresses compliance with certain requirements of Federal Regulations 40 CFR 112. I. STATUS OF SPCC PLAN (40 CFR 112.3) YES NO A.
NATURAL GAS EMERGENCY PROCEDURES AND ACCIDENT PREVENTION
NATURAL GAS EMERGENCY PROCEDURES AND ACCIDENT PREVENTION Fire and Life-Safety Group (FLS) I. EMERGENCY PROCEDURES The emergency procedures for natural gas emergencies are similar to that for fire emergencies.
Flammable Liquids Storage
A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
How To Safely Handle A Spill
WD DWGB 22 6 2010 Best Management Practices for Fueling and Maintenance of Excavation and Earthmoving Equipment Env Wq 401, Best Management Practices for Groundwater Protection, applies to a variety of
Shop Fabricated Aboveground Tank Construction Standards
Shop Fabricated Aboveground Tank Construction Standards Wayne Geyer Steel Tank Institute Fourth Biennial Freshwater Spills Symposium 2002 March 19-12, 2002 Cleveland, OH One key to clean freshwater is
Queen's University Environmental Health and Safety
April, 2009 1 SOP-Chem-08 1.0 Introduction This document is intended as a guide to the Queen s University requirements for handling and storing flammable and combustible material in non-laboratories areas.
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
Installation Guidance: CNG Refueling Stations
Installation Guidance: CNG Refueling Stations Gas Technology Institute > Delaware Valley Regional Planning Commission (DVRPC) Webinar Gas Technology Institute (GTI) Overview Natural Gas Research and Development
Section III Hazardous Materials Management
Section III Hazardous Materials Management This section of the Everyday Hazmat User s Training Guide covers various types of hazardous materials commonly found in the USDA Forest Service. Federal regulations
Flammable Liquids 29 CFR 1910.106
Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,
Inspections Standard Operating Procedure 5 Aboveground Storage Tanks
Aboveground Storage Tanks Aboveground Storage Tank Inspection This Standard Operating Procedure describes the steps that campus units that manage aboveground oil storage tanks (ASTs) or containers must
A Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
In accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids
Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
Special events and tents Fire and life safety requirements
Special events and tents Fire and life safety requirements Section A - Temporary Use Occupancies or Operations Fire and Life Safety Requirements In order to provide a standard method of inspection of temporary
Northern Region. Underground Storage Tank
California CUPA Northern Region Presents Underground Storage Tank Designated Operators Workshop Workshop Agenda Definitions Tank Construction Corrosion Protection Spill Prevention Overfill Prevention Piping
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program
IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1
IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1 CHAPTER 44 ON-SITE CONTAINMENT OF PESTICIDES, FERTILIZERS AND SOIL CONDITIONERS [Prior to 7/27/88, see 21 Ch 9] PESTICIDES 21 44.1(206) Definitions.
ELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
Cubetainer. The competition can t stack up to Snyder! Stackable Tanks, Stands and Containments
Cubetainer The competition can t stack up to Snyder! Stackable Tanks, Stands and Containments Providing Bulk Storage Solutions for Motor Oil, Lubricants, Hydraulic Fluids, ATF, Antifreeze & DEF www.snydercubetainer.com
MAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION
Oxford Hills Bus Garage 36 Brown St, Norway, ME Oil Storage Inspection 2/20/14 CONDITIONS OBSERVED Underground Oil Storage: 12,000 gallon underground oil storage tank (split 10,000 gallon diesel/2,000
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
UST RULES CHANGES. Heather Peters, Environmental Specialist
UST RULES CHANGES Heather Peters, Environmental Specialist Today s Topic 2011 Rule package- what s left? Upcoming rule changes Federal Regulation Changes & Testing Protocols How are you doing? 2011 Rule
Flammable Liquids Storage
A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario