Potential problems with computer hard disks when fire extinguishing systems are released
|
|
|
- Madlyn Peters
- 9 years ago
- Views:
Transcription
1 Extinguishing White Paper Potential problems with computer hard disks when fire extinguishing systems are released Disclaimer All statements, information and recommendations in this document are believed to be accurate but are presented without warranty of any kind, expressed or implied. These documents are being provided solely for informational purposes and Siemens does not warrant or represent that they will satisfy the specific requirements of any project. The information in this document may contain specifications or general descriptions related to technical possibilities of individual products which may not be available in certain cases (e.g. due to product changes). You are solely responsible for determining whether the documents are suitable and consistent with the requirements of any project that you are working on. Further, Siemens does not represent that the documents are complete regarding the planning steps that need to be taken for any particular project, or that they represent customer-specific solutions. They are only intended to provide basic information for typical applications. User waives and releases any rights of recovery against Siemens that it may have related to its use of these documents and agrees that Siemens shall not be liable for any form of loss, damage, claim or expense, irrespective of origin, including negligent acts or omissions, even if Siemens have been advised of the possibility of such damages. We reserve the right to make changes to these documents at any time without prior notice. Version Validity of this document: to In 2009 rumors started in the fire safety industry that computer hard disks drives (HDDs) may face problems when fire extinguishing systems are released. Siemens as the world leader in fire safety has a variety of different extinguishing systems in its portfolio and is highly interested to investigate this topic. This document describes the current state of knowledge of Siemens experts, which are based on tests as well as the discussions with customers, external specialists and approval bodies. Investigations are not finished at the moment. Therefore this document has a limited validity. If the working group is convinced that new facts are relevant enough to be published, an updated version of this document can be found at Otherwise the validity of this document will be extended.
2 White Paper Extinguishing Potential problems on computer hard disks with fire extinguishing systems 2 Contents Potential problems with computer hard disks when fire extinguishing systems are released... 3 What is the problem?... 3 Is the overpressure generated by a dry extinguishing causing the problem?... 3 Is the noise generated by a dry extinguishing causing the problem?... 4 Are the laboratory results transferable to real extinguishing systems?... 6 What can be done to avoid potential problems?... 6 Select less sensitive HDDs or other less noise sensitive data storage technologies... 6 Improve existing HDDs by Firmware-Updates... 7 Minimize direct exposure of the HDDs to the sources of noise... 7 Use technologies like fault-tolerant RAID-systems to better immunize systems... 7 Reduce test releases when systems are running... 7 Be aware that testing warning systems might influence performance... 7 Work on less noisy system concepts... 7 Are there any inert gases or chemical agents which are better?... 7 Are watermist-systems an alternative?... 8 What should I do if I already installed a dry extinguishing system in my data center?... 8 What should I plan to protect my data center by an extinguishing system?... 8 Abbreviations... 9
3 White Paper Extinguishing Potential problems on computer hard disks with fire extinguishing systems 3 Potential problems with computer hard disks when fire extinguishing systems are released What is the problem? Today it is state of the art to protect data centers or EDP rooms with dry extinguishing systems with inert gases or chemical agents, to ensure the intervention takes place as soon as possible after the automatic detection of a fire by a fire detection system. This is to minimize possible damages caused by a fire or smoke, to a level as low as ever possible. In very rare cases customers of dry extinguishing systems from different manufacturers reported problems with computer hard disk drives, after the release of the system. Problems ranged from automatic shutdown of a hard disk drive with no damage after restart, to hard disks which really could no longer be used. In case of a real fire this may be acceptable, and may be caused by the fire itself or the smoke. But there have been also cases reported when dry extinguishing systems have been released accidently or for test purposes. Even if the possible benefits of a dry extinguishing system by far outperforms this very seldom side effects, Siemens has a clear vision to identify if it is really the dry extinguishing system causing this effect, and if yes - to avoid or limit it as far as possible. Is the overpressure generated by a dry extinguishing causing the problem? Every dry extinguishing is generating an overpressure in the room protected. Inert gases (Nitrogen, Argon, CO2, or blends of the before listed) base their extinguishing effect on the displacement of oxygen. Typically the used amount of inert gas is in the range of half of the room volume. Overpressure flaps are used to limit the overpressure by allowing the displacement of the correspondent air volume to the outside. Depending on the robustness of the room, design criteria for the overpressure flaps is typically between 1 and 10 mbar overpressure, 3 mbar for a normal building construction. Chemical agents also need overpressure flaps. The dimensions are smaller, because less agent is needed, and therefore less air is to be displaced. The extinguishing principle is not the displacement of oxygen, its action is chemical and works by inhibiting the oxidation reactions produced between the combustible and the oxygen. When discussing possible effects on Hard Disk Drives we assumed that it may be not the maximum overpressure controlled by the overpressure flaps, but the rate of rise (pressure gradient) which may cause problems. The overall amount of agent is for chemicals much smaller than for inert gases, but they are brought into the room in a much shorter time (typical for chemicals: 10s, typical for inert gases s), and chemical agents create an underpressure before they create an overpressure. Therefore differences on the pressure gradient may be closer between inerts and chemicals, as this would be the case or the maximum overpressure without overpressure flaps. To check the effects of maximum overpressure and pressure gradient on Hard Disk Drives, Siemens performed a series of tests with typical HDDs 1 from different manufacturers. Figure 1 shows the test setup with 1 TB SATA HDDs from four different manufacturers typically used today in a lot of data centers. To monitor the effects during the test we set the HDDs under constant operation and recorded typical performance parameters (SMART information, data transfer performance, seek performance linear and random) drives in the enterprise storage category, 1TB capacity, 24/7 operation, purchased in August 09
4 White Paper Extinguishing Potential problems on computer hard disks with fire extinguishing systems 4 PC + 4 x esata P_in Inlet valve Pressure - Control / -Measurement PC1Labview+IO Control Restrictor HDD 1 HDD 2 HDD 3 HDD 4 PC+Labview+IO Outlet valve Pressure sensor Restrictor Figure 1: Test setup pressure During the tests the pressure was increased via a nozzle, opened by a solenoid valve. The pressure was monitored by two pressure sensors: one for the absolute pressure and one sensitive differential pressure sensor. We performed series of tests increasing the maximum overpressure and the gradient stepwise. We tested up to a maximum overpressure of 170 mbar, and a maximum gradient of 30 mbar/s in the test chamber, which was the limit of the test setup. No irritation of the HDDs could be found after the test. To go even further we removed the flow limiting nozzle. Even at 220 mbar within 3s with a gradient up to 100mbar/s: No effect on performance or even damage was reported for all drives under test. Conclusion: It is very unlikely that the overpressure created by a state of the art dry extinguishing system with overpressure flaps, or the pressure gradient in such a setup, has any negative effects on typical HDDs. Is the noise generated by a dry extinguishing causing the problem? There is some evidence that HDDs are sensitive to noise 2. Dry extinguishing systems are a source of noise: Sounders and horns are activated to warn people before the agent is released, and the release itself is also a source of noise. According to standards and codes alarming devices for dry extinguishing systems have to generate sound levels between 90 and 120 db 3. Electrical horns are typically on the lower end of the range, pneumatic horns are at the upper end. During the release of a dry extinguishing system also high noise levels are produced when the agent expands and flows through the nozzle(s) into the room. This is true for inert gases as well as for chemical agents. The sound level created depends on several different design factors. It can even go above 120 db. To check the effects of sound on the same HDDs the following test setup was used: 2 If you are looking for more information try to search the internet with the term "unusual disk latency" 3 See for example EN :2003 Fixed firefighting systems - Components for gas extinguishing systems - Part 12: Requirements and test methods for pneumatic alarm devices
5 White Paper Extinguishing Potential problems on computer hard disks with fire extinguishing systems 5 Sythesizer Creation Synthesizer of Sinus Device under test Device Harddisk under test Distance 1m SATA SATA EDIROL UA-25 USB JBL JBL PRX515 Benchmarktest HDD Tune Benchmarkt 2.55 Test Bench ADOBE Audition ADOBE 2.0 Audition 2.0 Creation of pink noise 1/3 octave Sound level meter B&K 2238 Figure 2 - Test setup sound HDD Tests Performance measurement setup and HDDs used was identical with the one used for the overpressure tests. Pink noise was created broadband (500 Hz 10 khz) and thirds (beginning from 353 Hz up to 10 khz) using a sound generator with a loudspeaker placed in one meter distance from the HDDs. The sound levels have been measured in very close distance to the HDDs. Sounds created by dry extinguishing systems show the characteristics of white noise. nance) with strong impact were found not shown here. As additional remark, please be aware that the tests we conducted were in the worst possible condition for noise impact, since the disks were directly exposed to the noise source, without being mounted in a rack or computer. Note: Pink noise was chosen in the test not to damage the loudspeaker by the high frequency spectrum produced by white noise. The advantage of using a sound generator instead of a real extinguishing system is the high controllability and reproducibility of the test conditions. As you will see below, we also performed tests with real dry extinguishing systems. Figure 3 shows the results on which noise level the performance of the HDDs is reduced to 50%. It was found, that excessive noise, at levels harmful to human health, can have also negative effects on HDD performance up to total temporary malfunction and damage of some sectors. The levels are typically 120dB, but may begin a little below 110 db, at certain HDD types and frequencies (Figure 3). In our tests we did not come to a point, where a HDD was unusable afterwards. All tested HDDs showed to be sensitive at least in the frequency range of 500 Hz to 5 khz. As expected some frequencies (reso-
6 White Paper Extinguishing Potential problems on computer hard disks with fire extinguishing systems db 130 db 130 db 125 db 120 db 120 db 115 db 110 db 110 db 105 db 100 db 100 db HDD A HDD B HDD C HDD D Data Pink noise 50% point (db) Figure 3 - Noise Sensitivity of tests HDDs (50% Performance reduction) HDD Third Thirds 50% point (db) Conclusion: Noise levels created by the warning and / or the extinguishing process may have negative effects on typical HDDs, one effect could be a possible reduction in performance. Are the laboratory results transferable to real extinguishing systems? After the laboratory tests we went one step further and used the same performance measurement setup and HDDs, to observe the effects when exposed to full scale extinguishing discharges. A series of tests was conducted with the following Siemens extinguishing technologies: Sinorix TM 1230 (agent FK / 42bar cylinder pressure), Sinorix TM 227 (agent: HFC227ea / 42 bar and 25 bar cylinder pressure), Sinorix TM N2 (agent: Nitrogen IG100 / 300 bar cylinder pressure), Sinorix TM CDT Constant Discharge Technology (agent: Nitrogen IG100 / 300 bar cylinder pressure / regulated valve) What can be done to avoid potential problems? There are three areas where measures can be taken: on the side of the Hard Disk Drives, on the side of the extinguishing systems and their alarming devices, and at the point where they come together especially tests and test releases. Select less sensitive HDDs or other less noise sensitive data storage technologies. The problem of noise sensitive Hard Disk Drives may disappear on its own, when new technologies like Solid State Disks or Flash Memory Devices or whatever will replace the today s technologies. Probably you are looking for answers today. Our tests showed variances in the sensitivity of the HDDs tested. May be you contact your HDD-manufacturer to verify if they have information on this issue. As expected, some negative effects on performance could be observed. After the discharge was finished, no loss of information or HDD destruction was registered in any of the tests.
7 White Paper Extinguishing Potential problems on computer hard disks with fire extinguishing systems 7 Improve existing HDDs by Firmware-Updates We informed the manufacturers of the HDDs we tested about our observations and results. From one of the companies we then got an updated firmware version, which should improve the robustness of the HDDs. We did not test it because we will concentrate on the extinguishing side (see below). Maybe you contact your HDDmanufacturer to verify if they have information on this issue. Minimize direct exposure of the HDDs to the sources of noise Whenever possible choose noise isolated cabinets with closeable doors and keep them closed during operation. Every noise isolation measure will reduce the influence of noise on HDDs operation. When designing the warning and extinguishing system, select siren and nozzle locations so that they don t irradiate the HDDs directly. Use technologies like faulttolerant RAID-systems to better immunize systems For important data in many cases fault-tolerant data-storage systems are used anyway (RAIDsystems, Mirroring, ). Maybe you check your storage concepts and bring them on a level where the loss of HDDs will not lead to a loss of data. There are many reasons, why HDDs may fail. Reduce test releases when systems are running Sometimes customers and certification bodies require a flooding test after the extinguishing system is commissioned. Although we haven t experienced any loss of information or HDD destruction, be aware that in certain rare cases, malfunction of HDDs may be observed when warning and extinguishing systems are tested. Be aware that testing warning systems might influence performance As already described above, HDDs are sensitive to noise. Sirens and horns produce noise levels up to 120 db and above. If such a warning system needs to be tested, we recommend reducing the noise level (e.g. by system configuration or by covering the warning devices). Work on less noisy system concepts Since the very beginning of the extinguishing technologies at Siemens, our systems have been designed to meet the highest standards in quality, reliability, performance and regulations. Among several other design parameters, noise was always considered to be one of the key attributes. At the light of the latest facts and the development of the HDD technologies, noise has become a more sensitive attribute of the extinguishing system. Siemens, the innovation leader in dry extinguishing that for example introduced Sinorix TM CDT and Sinorix TM H2O Gas, is currently working on concepts that will also show in the area discussed in this whitepaper the power of innovation of Siemens. Are there any inert gases or chemical agents which are better? The agent used in an extinguishing solution doesn t define per-se the noise level of the system overall. But, as mentioned before, it is the noise only, which can reduce the performance of the HDDs and not the influence of the special type or brand of a gas. Several design factors influence this noise level. Every gas nozzle used to distribute the agent into a room, will necessarily produce sound energy independently from
8 White Paper Extinguishing Potential problems on computer hard disks with fire extinguishing systems 8 the type of agent. We believe it is not serious to conclude that using a certain type of agent will solve the problem. Which reliability do test reports about releases without problems have? Reports of test releases without problems describe the normal situation for all suppliers, all agents and all system technologies in dry extingsuihing systems today. Effects on hard disks have only been witnessed in very rare cases, they are the exception. Are watermist-systems an alternative? Spraying water inside the data center, no matter the size of the droplets, is something strange when thinking about the risks. Nevertheless it is sometimes discussed as an alternative to dry extinguishing systems, even if water mist systems cannot guarantee extinguishing a fire i.e. in spray shadow areas. Water mist systems are, like sprinkler systems, approved as suppression only systems. When dry extinguishing systems are discharged, the agent is neutral to electronics and surfaces in general. In contrast, when a watermist system is discharged, thin layers of water cover all surfaces. On top the harmful substances of smoke, now diluted in the water, may be deposited on sensitive surfaces. Therefore the inherent risk of spraying water in a data center, may in case of a real fire, be increased due to the presence of smoke. sensitivity of HDDs. So we see no need for action for existing installations. Just be aware of the topic, when you are planning alarming or release tests. If you have any doubts, verify with your HDD manufacturers if they have information on this issue. What should I plan to protect my data center by an extinguishing system? As described above there is not at all any question mark behind the need of a dry extinguishing system to protect your valuable assets. Keep on going, and avoid getting other risks by not protecting your data center or using the wrong concepts. Issuer: Siemens Switzerland Ltd. Industry Sector Building Technologies Division International Headquarters COC Extinguishing I BT FS SYS EXT Gubelstrasse Zug Switzerland Contact: [email protected], [email protected] What should I do if I already installed a dry extinguishing system in my data center? We discussed the whole issue with customers, specialists and approval bodies. Nobody sees any need for immediate action. Cases where problems have been reported are quite rare, and the advantages of the protection by dry extinguishing systems by far outperform the issue of noise
9 White Paper Extinguishing Potential problems on computer hard disks with fire extinguishing systems 9 Abbreviations db EDP HDD Hz khz mbar RAID Decibel Electronic data processing Hard disk drive Hertz Kilohertz Millibar Redundant Array of Independent Disks All trademarks used are owned by Siemens or their respective owners. Siemens Switzerland Ltd. Gubelstrasse Zug, Switzerland Siemens Switzerland Ltd.2010
Data Centre alwas protected always up and running.
Data Centre alwas protected always up and running. Stefano Valdrighi - Siemens Business continuity is the critical asset to protect 609,500 Average cost per downtime 7,908 Average cost per minute The total
Disruptions to hard disk drives caused by inert gas extinguishing systems analysis and measures for the safe operation of storage systems
www.siemens.com/sinorix Silent Extinguishing Disruptions to hard disk drives caused by inert gas extinguishing systems analysis and measures for the safe operation of storage systems White paper ½ September
How intelligent must an extinguishing solution be to keep fire virtual?
How intelligent must an extinguishing solution be to keep fire virtual? Intelligent means: fire protection from Siemens. Sinorix intelligent extinguishing solutions. Answers for infrastructure. Sinorix
Maximum uptime and optimum fire safety for your data center
Maximum uptime and optimum fire safety for your data center Integrated and tailored fire safety solutions from one partner Answers for infrastructure. Complete solutions for a safe data center with a single
Maximum uptime and optimum fire safety for your data center
Maximum uptime and optimum fire safety for your data center Integrated and tailored fire safety solutions from one partner Answers for infrastructure. Complete solutions for a safe data center with a single
INERGEN Acoustics Testing Position Paper
INERGEN Acoustics Testing Position Paper INERGEN Acoustics Testing Position Paper 1 The Issue In recent years, there has been considerable confusion in the marketplace about why some data center hard
How can I protect valuable assets from fire and ensure business continuity?
How can I protect valuable assets from fire and ensure business continuity? XC10 compact panels combine fire detection and extinguishing control for comprehensive safety. Answers for infrastructure. Compact
Hydra Super-S Combo. 4-Bay RAID Storage Enclosure (3.5 SATA HDD) User Manual July 29, 2009 - v1.3
4-Bay RAID Storage Enclosure (3.5 SATA HDD) User Manual July 29, 2009 - v1.3 EN Introduction 1 Introduction 1.1 System Requirements 1.1.1 PC Requirements Minimum Intel Pentium III CPU 500MHz, 128MB RAM
Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230
Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec
Alarm and Detection/Suppression
Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent
Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection
Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect
CO 2. fire extinguishing systems
fire extinguishing systems Extinguishing technique is a colourless, odourless and electrical non-conductive gas. In systems the is mixed with a special identifiable odour. The extinguishing effect of is
Taurus - RAID. Dual-Bay Storage Enclosure for 3.5 Serial ATA Hard Drives. User Manual
Dual-Bay Storage Enclosure for 3.5 Serial ATA Hard Drives User Manual v1.0 August 23, 2007 EN Table of Contents CHAPTER 1 - INTRODUCTION 1 CHAPTER 3 - SYSTEM SET UP 9 ICON KEY 1 THE TAURUS RAID 1 AVAILABLE
For Data Center and Control Room Applications
For Data Center and Control Room Applications Nearly zero wetting No costly clean up or equipment replacement Sustainable design Quick system recharge, minimal downtime No need for assurance of tight room
Taurus Super-S3 LCM. Dual-Bay RAID Storage Enclosure for two 3.5-inch Serial ATA Hard Drives. User Manual March 31, 2014 v1.2 www.akitio.
Dual-Bay RAID Storage Enclosure for two 3.5-inch Serial ATA Hard Drives User Manual March 31, 2014 v1.2 www.akitio.com EN Table of Contents Table of Contents 1 Introduction... 1 1.1 Technical Specifications...
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
BRANCH SOLUTION. Automatic fire extinguishing systems for paint spraying plants. Safe for certain.
BRANCH SOLUTION Automatic fire extinguishing systems for paint spraying plants Safe for certain. ISK IDENTIFYING With the extreme high degree of automation in painting technology, the risk of fire has
How To Set Up A Hard Drive With A Harddrive With A 2Gb Hard Drive (I386) And 2Gb Drive (Amd64) On A Hardrive (I219) (Iee) (Amd66) (Ai219
1 Package Contents Device User manual Power adapter Power cord USB 2.0 Cable FireWire 800 Cable (IEEE1394.B) esata cable 2 Front View of the Device A Drive eject button B LED indicator C Front door panel
BMW Multi Tool User Manual
X-Horse Electronics Co., Ltd. Table of Contents 1. Safety Precautions and Warnings... 3 2. General Information... 4 3. Hardware Overview... 5 3.1. Tool Description... 5 3.2. Specifications... 6 3.3. System
HP Notebook Hard Drives & Solid State Drives. Identifying, Preventing, Diagnosing and Recovering from Drive Failures. Care and Maintenance Measures
HP Notebook Hard Drives & Solid State Drives Identifying, Preventing, Diagnosing and Recovering from Drive Failures Care and Maintenance Measures Technical White Paper Table of contents Identifying, Preventing,
For Data Center and Control Room Applications
For Data Center and Control Room Applications Nearly zero wetting No costly clean up or equipment replacement Sustainable design Quick system recharge, minimal downtime No need for assurance of tight room
FUSION R400 RAID USB 3.0
FUSION R400 RAID USB 3.0 1U Rackmount 4-Drive Hardware RAID 5 SATA Storage System with USB 3.0 Interface User s Guide For Windows Contents 1 Fusion R400 RAID USB 3.0 Features 1 2 Drive Installation and
melbourne//australia data center specifications internet + intellectual property + intelligence tel: +61 2 9948 8888 fax: +61 2 9948 1111
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Melbourne,. We can colocate standard rack-mountable servers or other
Manual IB-3620 Series
IB-RD3620SU3 1 IB-3620U3 CONTENT 1. Introduction... 3 1.1 General Information... 3 2. Hardware IB-3620 Series... 4 2.1 LED Indication / Button Front Panel... 4 2.2 Rear View... 5 3. HDD Installation...
Data center solutions from Siemens. For the factories of the 21 st century. siemens.com/datacenters
Data center solutions from Siemens For the factories of the 21 st century siemens.com/datacenters We face the challenges for the factories of the 21 st century Based on our vast experience, we offer a
Fire protection in archives and storage vaults
Fire protection in archives and storage vaults Protection of people and cultural assets Archives and storage vaults, in which documents, manuscripts, books or paintings are stored, are risk areas that
Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS
Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS Guardian Fire Safety Solutions FIRE RISK CONTROL IN WELDING FUME EXTRACTION SYSTEMS DO YOU CONTROL THE RISK OF FIRE AT
Basic Fundamentals Of Safety Instrumented Systems
September 2005 DVC6000 SIS Training Course 1 Basic Fundamentals Of Safety Instrumented Systems Overview Definitions of basic terms Basics of safety and layers of protection Basics of Safety Instrumented
2» 10» 18» 26» PD3 34 00 42»
» STARDOM Safe Capsule Series User Manual... 2» STARDOM Safe Capsule Serie Bedienungsanleitung... 10» Série STARDOM Safe Capsule Manuel de l utilisateur... 18 26 PD3500 34» Manual de usuario de STARDOM
Dismantling or replacement by the user. Connection to an alternate power source. Malfunction due to natural disasters (fire, flood, tsunami, etc.
Preface Thank you for purchasing the Samsung DVR storage. This is a user instruction manual for the SVS-5R. The user installing and/or operating this item needs to be aware of this manual and any other
Guardian MAXimus ASSEMBLY MANUAL & USER GUIDE
Guardian MAXimus ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported Drives 1.2 PACKAGE
Growth Solutions for Data Storage
1 A NEW NAS Experience a white paper Growth Solutions for Data Storage Meeting the Needs Now and in the Future for Small Business May 2009 Table of Contents 2 Introduction 3 Vertical Expansion 4 Horizontal
is605 Dual-Bay Storage Enclosure for 3.5 Serial ATA Hard Drives FW400 + FW800 + USB2.0 Combo External RAID 0, 1 Subsystem User Manual
is605 Dual-Bay Storage Enclosure for 3.5 Serial ATA Hard Drives FW400 + FW800 + USB2.0 Combo External RAID 0, 1 Subsystem User Manual (English/Deutsch/ 中 文 ) v1.0 August 23, 2007 Table of Contents CHAPTER
Restaurant & café guide
'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers
Class A - Wood, paper, cloth, trash, plastics Solid combustible materials that are not metals. (Class A fires generally leave an Ash.
Not all fires are the same, and they are classified according to the type of fuel that is burning. If you use the wrong type of fire extinguisher on the wrong class of fire, you can, in fact, make matters
USB 3.0* Radio Frequency Interference Impact on 2.4 GHz Wireless Devices
USB 3.0* Radio Frequency Interference Impact on 2.4 GHz Wireless Devices White Paper April 2012 Document: 327216-001 INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE,
Fire Protection Options for Data Centres
Fire Protection Options for Data Centres Mark L. Robin, PhD DuPont Chemicals & Fluoroproducts [email protected] Introduction Modern data centres are characterized by spaces filled with ever-increasing
Ultrasound Condition Monitoring
Ultrasound Condition Monitoring Whitepaper Alan Bandes UE Systems, Inc. Abstract: Instruments based on airborne/structure borne ultrasound technology offer many opportunities for reducing energy waste
Your Data Security Guardian. SafeTANK GR5630-WSB3+ User Manual. v.1.0 (Oct, 2012) www.raidon.com.tw
SafeTANK GR5630-WSB3+ User Manual v..0 (Oct, 202) Introduction Thank you for purchasing RAIDON products. This manual will introduce the GR5630-WSB3+. Before using your GR5630-WSB3+, please read this manual
WASTE Application Form - Dublin Waste to Energy SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE
SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE Describe the existing or proposed measures, including emergency procedures, to minimise the impact on the environment of an accidental emission or spillage.
RocketStor SMART RAID
RocketStor SMART RAID User Guide v1.0 1 Copyright HighPoint Technologies Inc., 1995-2012. All rights reserved. OS X and Macintosh are registered trademarks of Apple Corporation. All other trademarks and
Traditionally, a typical SAN topology uses fibre channel switch wiring while a typical NAS topology uses TCP/IP protocol over common networking
Network Storage for Business Continuity and Disaster Recovery and Home Media White Paper Abstract Network storage is a complex IT discipline that includes a multitude of concepts and technologies, like
SoftRAID 5 QUICK START GUIDE. for OWC ThunderBay
SoftRAID 5 QUICK START GUIDE for OWC ThunderBay TABLE OF CONTENTS INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.2 FEATURES 1.3 ABOUT THIS MANUAL SYSTEM SETUP...2 2.1 GETTING STARTED 2.2 INITIALIZING,
Hydra esata. 4-Bay RAID Storage Enclosure. User Manual January 16, 2009 - v1.0
4-Bay RAID Storage Enclosure User Manual January 16, 2009 - v1.0 EN Table of Contents 1 Introduction... 1 1.1 System Requirements... 1 1.1.1 PC Requirements... 1 1.1.2 Mac Requirements... 1 1.1.3 Supported
USB 2.0 VGA ADAPTER USER MANUAL
USB 2.0 VGA ADAPTER USER MANUAL CONTENTS INTRODUCTION... 3 FEATURES... 3 SYSTEM REQUIREMENTS... 3 PACKAGE CONTENTS... 3 SUPPORTED COMMON DISPLAY RESOLUTION... 4 TECHNICAL SPECIFICATIONS... 4 INSTALLATION
OWC Mercury Elite Pro Dual ASSEMBLY MANUAL & USER GUIDE
OWC Mercury Elite Pro Dual ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported Drives 1.2
Mechanical Systems Competency 1.20
Competency 1.20 Mechanical systems personnel shall demonstrate a working level knowledge of the safety and health fundamentals of mechanical systems and/or components. 1. Supporting Knowledge and Skills
Fire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered
singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
Remote PC Guide Series - Volume 2b
Document Version: 2013-09-06 R720 This guide provides hardware model-specific guidance in server configuration, with BIOS and RAID configuration instructions for the Dell R720. This guide is part of a
What guarantees optimal business continuity for our clean room?
What guarantees optimal business continuity for our clean room? You can rely on our fire safety solutions to provide optimum security for your employees and to ensure maximum business continuity. Answers
Guide to SATA Hard Disks Installation and RAID Configuration
Guide to SATA Hard Disks Installation and RAID Configuration 1. Guide to SATA Hard Disks Installation...2 1.1 Serial ATA (SATA) Hard Disks Installation...2 2. Guide to RAID Configurations...3 2.1 Introduction
On-Site Risk Management Audit Checklist for Program Level 3 Process
On-Site Risk Management Audit Checklist for Program Level 3 Process Auditor name: Date: I. Facility Information: Facility name: Facility location: County: Contact name: RMP Facility I.D. Phone Number:
XL-RAID-SATA2-USB. User Manual. v.1.2 (January, 2010)
XL-RAID-SATA2-USB User Manual v.1.2 (January, 2010) With regard to this manual Thank you for using the product of Xtendlan Technology Inc. This manual will introduce XTENDLAN XL-RAID-SATA2-USB. Before
Version: 1.0 Last Edited: 2005-10-27. Guideline
Process hazard and risk Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:[email protected] -1- Summary This report will try
STERILIZERS, LABORATORY DRYING OVENS
TS9026 TS9053 TS9135 TS9430 TS 9000 SERIES: STERILIZERS, LABORATORY DRYING OVENS Series TS9000 consists of four different cabinets available in sizes from 26 litres to 430 litres. Interior housing and
Safety Requirements Specification Guideline
Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:[email protected] -1- Summary Safety Requirement
Watermist fire suppression systems for commercial low hazard occupancies
Watermist fire suppression systems for commercial low hazard occupancies Watermist fire protection systems are fire suppression systems that have emerged as an alternative fire safety solution for specific
ngenieros Ingenieros Asociados De Control S.L.
ngenieros sociados de ontrol 1 Company founded in 1985 to serve commercial and technical assistance in the fields of instrumentation, control and installation for all types of industries. We offer top
Remote PC Guide Series - Volume 2a
Document Version: 2013-03-04 This guide provides hardware model-specific guidance in server configuration, with BIOS and RAID configuration instructions for the Dell R710. This guide is part of a multi-volume
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust / 2 / / 3 / Trust in Tyco Tyco s AquaMist Systems Tyco Fire Protection Products helps to keep people, property and the environment
Data Center Infrastructure & Managed Services Outline
Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists
BEP FD-2 CONTOUR MATRIX FUME DETECTOR
BEP FD-2 CONTOUR MATRIX FUME DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING GAS SENSORS...3 4 FEATURES...4 5 SPECIFICATION...4 6
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
Risk Guidance Note 03. Management of In-Rack Automatic Sprinklers (IRAS)
Risk Guidance Note 03 Management of In-Rack Automatic Sprinklers (IRAS) Overview In-rack automatic sprinklers (IRAS) are often a fundamental part of the fire protection solution for racked storage areas.
Liberty Mutual Insurance RISK ENGINEERING PROCEDURE. REP 07 Incident Planning For external use
Liberty Mutual Insurance RISK ENGINEERING PROCEDURE REP 07 Incident Planning For external use Risk Engineering Procedure Incident Planning CONTENTS Page PURPOSE... 3 BACKGROUND... 4 INCIDENT PLANNING PREPARATION...
2-3 SAS/SATA II HDD Canister USER S MANUAL XC-23D1-SA10-0-R. Document number: MAN-00076-A
2-3 SAS/SATA II HDD Canister XC-23D1-SA10-0-R USER S MANUAL Document number: MAN-00076-A ii Preface Important Information Warranty Our product is warranted against defects in materials and workmanship
Greater Manchester Fire and Rescue Service
Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY
How To Use A Sata Dsa Hard Disk Storage System
EXTERNAL RAID STORAGE OF HDDS INSTRUCTION MANUAL CAUTION RISK OF ELECTRIC SHOCK CAUTION TO REDUCE THE RISK OF ELECTRIC SHOCK, DO NOT OPEN COVER. NO USER SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED
QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
Guide to SATA Hard Disks Installation and RAID Configuration
Guide to SATA Hard Disks Installation and RAID Configuration 1. Guide to SATA Hard Disks Installation... 2 1.1 Serial ATA (SATA) Hard Disks Installation... 2 2. Guide to RAID Configurations... 3 2.1 Introduction
600-GD & 600-GDL 600 SERIES GAS DETECTOR
600-GD & 600-GDL 600 SERIES GAS DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS This page has been deliberately left blank. Page 1 Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days
Advanced Knowledge and Understanding of Industrial Data Storage
Dec. 3 rd 2013 Advanced Knowledge and Understanding of Industrial Data Storage By Jesse Chuang, Senior Software Manager, Advantech With the popularity of computers and networks, most enterprises and organizations
Internal Drive Mounted Dual SATA Hard Drive RAID Adapter
Internal Drive Mounted Dual SATA Hard Drive RAID Adapter S322SAT3R *actual product may vary from photos DE: Bedienungsanleitung - de.startech.com FR: Guide de l'utilisateur - fr.startech.com ES: Guía del
Ultrasonic Gas Leak Detection
Ultrasonic Gas Leak Detection What is it and How Does it Work? Because every life has a purpose... Ultrasonic Gas Leak Detection Introduction Ultrasonic gas leak detection (UGLD) is a comparatively recent
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
About Your NetBotz 4-20mA Sensor Pod
Thank you for purchasing this NetBotz 4-20mA Sensor Pod. Each 4-20mA Sensor Pod enables you to connect up to four 4-20mA sensors to your NetBotz 420 or NetBotz 500 appliance. Hundreds of 4-20mA sensors
NEC ESMPRO Manager RAID System Management Guide for VMware ESXi 5 or later
NEC ESMPRO Manager RAID System Management Guide for VMware ESXi 5 or later 856-127900-613-G 7th Edition Jun. 2015 Copyright NEC Corporation 2015. Trademarks NEC EXPRESSBUILDER is trademarks of NEC Corporation.
Chlorine Gas Detection System Operation & Maintenance
Chlorine Gas Detection System Operation & Maintenance Maynard King K&D Pratt Instrumentation 2011 Clean and Safe Drinking Water Workshop Chlorine Gas Detector Operation, Maintenance, Checks 1. Why you
Version : 1.1. SR2760-2S-S2 User Manual. SOHORAID Series
Version : 1.1 SR2760-2S-S2 User Manual SOHORAID Series Forewords About this manual Thank you for using products from Raidon Technology Inc. This manual will introduce the STARDOM SR2760-2S-S2 product.
EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
Compliance Schedules and Building Warrant of Fitness
Compliance Schedules and Building Warrant of Fitness Purpose of this guidance information The purpose of this guidance information is to help building owners and managers of commercial, industrial or communal
SAGEON SITE MONITOR (SSM) Application Note AN103-4012-00
SAGEON SITE MONITOR (SSM) Application Note AN103-4012-00 AN 103-4012-00, Issue 2a sageon_sm-an.pdf www.unipowerco.com SALES: +1-800-440-3504 HEAD OFFICE: +1-954-346-2442 EUROPE: +44 (0)1903 768200 SAGEON
How To Use An Esata External Hard Drive Enclosure (I386) With A Usb 2.0 And Usb 2/1.1 Hard Drive (I219) On A 2.5\" Hard Drive On A Mini Hard Drive Or An Ip
HDD external enclosure for data-storage mobility with USB 2.0 and esata interface USER Manual English AKASA Company notices The information contained in this document is subject to change without notice.
AN1991. Audio decibel level detector with meter driver
Rev. 2.1 20 March 2015 Application note Document information Info Keywords Abstract Content SA604A, LM358, RSSI, cellular radio The SA604A can provide a logarithmic response proportional to the input signal
Fire Protection of Data Centres
Fire Protection of Data Centres With SEM-SAFE High-Pressure Water Mist System Danfoss Semco A/S Total Solution Provider of Certified Fixed Fire Fighting Systems Need a fire fighting system that: Allows
USER S MANUAL. www.vantecusa.com
USER S MANUAL www.vantecusa.com Package Contents: Dual 3.5 RAID Enclosure w/fan USB 3.0 & esata Interface 1 NexStar MX 2 USB 3.0 Cable 3 esata Cable 4 Power Adapter 5 User s Manual 6 Enclosure Stand 7
This leaflet provides information on
This leaflet provides information on the fire and explosion hazards in the use of oxygen. It is for anyone who uses oxygen gas in cylinders. HSE8(rev2) Hazards from oxygen Oxygen gas in cylinders is used
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Gambling with your fire security?
Gambling with your fire security? Service Agreement for Fire Safety Building Technologies 11 No need to take risks Fire safety is elementary. Nobody doubts this. However, some people believe that a well-designed
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
Document Details. 247Time Backup & Disaster Recovery Plan. Author: Document Tracking. Page 1 of 12
Document Details Title: Author: 247Time Backup & Disaster Recovery Plan Document Tracking Page 1 of 12 TABLE OF CONTENTS 1 INTRODUCTION... 3 1.1 OVERVIEW... 3 1.2 DEFINED REQUIREMENT... 3 2 DISASTER OVERVIEW...
Take care with oxygen Fire and explosion hazards in the use of oxygen
Fire and explosion hazards in the use of oxygen This leaflet provides information on the fire and explosion hazards in the use of oxygen. It is for anyone who uses oxygen gas in cylinders. Hazards from
HISTOLOGY LABORATORY EMERGENCY PROCEDURES
HISTOLOGY LABORATORY EMERGENCY PROCEDURES CONTENTS 1 Chain of command...3 2 Disaster plan...3 2.1 Announcement 2.2 Pathology departmental duties 2.3 Reference 3 Evacuation...4 3.1 Meeting place 3.2 Evacuation
Dual/Quad 3.5 SATA to USB 3.0 & esata External Hard Drive RAID/Non-RAID Enclosure w/fan. User s Manual
Dual/Quad 3.5 SATA to USB 3.0 & esata External Hard Drive RAID/Non-RAID Enclosure w/fan User s Manual Package Contents: NextStar HX4/HX4R NextStar HX2R 1 2 1 2 3 4 3 4 5 6 5 6 7 1 NexStar HX4R/HX4 2 USB