DCREG INTERFACE VIA DEVICENET



Similar documents
Install the DeviceNet Module using the following procedure:

DeviceNet Communication Manual

GE Power Controls FIELDBUS APPENDIX PROFIBUS DP. Doc. No.: ASTAT Plus PB_Appendix-v0

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

How to make a diagnostic on TeSysT to start the network?

G3 Series PROFIBUS DP Technical Manual

Modular I/O System Analog and Digital Interface Modules

Termination Resistors:

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April SFC132089M0201 1

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

Combi switchbox with integrated 3/2 way pilot valve

Allen-Bradley/Rockwell

ABB Drives. Protocol Manual - Modbus/TCP Ethernet Adapter Module FENA-01

2011, The McGraw-Hill Companies, Inc. Chapter 3

Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: Data sheet GIOD.1 V_3.0

Contents. Document information

MEMOBUS/Modbus Communications

Original instructions. PLUTO Gateway. User Manual. PROFIBUS GATE-P1/P2 DeviceNet GATE-D1/D2 CANopen GATE-C1/C2 Ethernet GATE-E1/E2

DeviceNet Communications handbook

PLUTO Safety-PLC. Manual Absolute Encoders

DeviceNet Master Module(EH-RMD)/ Slave Controller(EH-IOCD)/ Discrete I/O slave unit (RDX16D,RDY16TP,RDY16R) APPLICATION MANUAL

CMC-DN01 DeviceNet Slave Communication Card Operation Manual

AN : Using Wago CANOpen IO

User Manual Revision English

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

DeviceNet Motor Control

ZC-24DO CANopen I/O Module: 24 Digital Outputs

Accessories. Remote Annunciator Module RAM7 RAM7: Remote Annunciator Module. Quick reference. v. 1.0_in

Nemo 96HD/HD+ MODBUS

PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN. User Manual. Document version ( )

Using the AnyBus -X Gateway to Communicate between a DVT camera and a Profibus Master

RPDO 1 TPDO 1 TPDO 5 TPDO 6 TPDO 7 TPDO 8

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

ABB Drives. User s Manual HTL Encoder Interface FEN-31

Soft-Starter SSW-06 V1.6X - Profibus DP, DeviceNet and EtherNet/IP

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

Impulse G+/VG+ Series 3, 24 VDC Interface Card Terminal Designations

Disturbance Recoder SPCR 8C27. Product Guide

IO-DIM6 6-Channel, Digital to Analogue Converters

Intelligent RS-485 I/O expansion unit: RU-87Pn Series

Product Information. Gateway For Connecting EnDat Encoders to PROFIBUS-DP

1 Application Description Objective Goals... 3

ABB RTU560A Series CMU & Modules

PCM Encoding and Decoding:

NC-12 Modbus Application

Data Sheet. Adaptive Design ltd. Arduino Dual L6470 Stepper Motor Shield V th November L6470 Stepper Motor Shield

E/P Regulator (DeviceNet TM type) ITV1000/2000/3000/2090-DE* Series

Installation and Start-up Guide. CS 31 Adapter Module NCSA-01

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

User Manual Revision English

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

Honeywell. Installation and User Manual. Modbus protocol. for Variable Frequency Drives

Contents. : AEOS Blue cabling and technical aspects. NEDAP N.V. IDEAS Information Bulletin No: H032. Date : 12 January 2016

Application/Connection Examples

How To Monitor A Photovoltaic Plant Remotely

FN2001-A1 Network module (SAFEDLINK) Mounting Installation

L5354 ControlNet Communications Interface

Non-Isolated Analog Voltage/Current Output module IC695ALG704 provides four configurable voltage or current output channels. Isolated +24 VDC Power

C441 series communication modules Accessories for electronic overload relays and soft starters. Monitoring and control made simple

DeviceNet Bus Software Help for Programming an Allen Bradley Control System

CPU systron S S S 250c. systron S S S 250c. CPUs to the process modules. Stand-alone PLC

Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP. 1 Application Description Objective Goals...

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

MBP_MSTR: Modbus Plus Master 12

Manual. VE.Bus to NMEA 2000 interface

Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION

Contents. VLT AutomationDrive EtherNet/IP

Accessing EtherNet/IP Network Variables in a WAGO with a ControlLogix PLC Application note

Pluto Gateway Siemens S7 Integration Manual

User Manual Revision English

User Manual for CH-PFC76810

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers

NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter

ABB i-bus KNX Fan Coil Controller FC/S 1.1

I.S. 1 remote I/O system Redundant coupling via PROFIBUS DP

Using the WAGO PROFINET Coupler as Remote I/O with a Siemens S7 PLC

User Manual Revision English

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Features, Benefits, and Operation

Part Number Description Packages available

M-series Virtual I/O Module 2

PCAN-MicroMod Universal I/O Module with CAN Interface. User Manual. Document version ( )

CMC-PD01 PROFIBUS DP Slave Communication Card Operation Manual

User Manual Revision English

Practical steps for a successful. PROFIBUS Project. Presented by Dr. Xiu Ji Manchester Metropolitan University

T O K I S T A R L I G H T I N G I N S T R U C T I O N M A N U A L LC-1CH-MULTI Dimmer Module

Softstarters. Type PSE Fieldbus communication DeviceNet for PSE fw rev SFC132066M0201 November SFC132066M0201 1

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

VLT 6000 HVAC. Contents

BL compact multiprotocol station for Industrial Ethernet SSI interface BLCEN-1M12MT-1SSI

Operation and Installation Manual

Installation manual. Generator Paralleling Controller GPC multi-line C

INTRODUCTION FEATURES OF THE ICM

WIND Power Technology: IMD Integrated Motor Drive

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

WIDE SCREEN ON-BOARD MONITOR

1115 4G SERIES GOVERNOR ma ANALOGUE DIGITAL SPEED SETTING

Transcription:

16B0231B1 INTERFACE VIA DEVICENET Update 27/09/06 R.00 Version D4.02 English This manual is an integral and essential part of the product. Carefully read the instructions contained herein as they provide important hints for use and maintenance safety. This product shall be used only for the purposes it is aimed at. Any other use is to be considered as improper and dangerous. The manufacturer is not responsible for any possible damage caused by improper, erroneous and irrational applications. Elettronica Santerno reserve the right to make any technical changes to this manual without prior notice. Any misprint or spelling mistake will be edited in the new versions of this manual. Elettronica Santerno is responsible for the information contained in the original version of the Italian manual. The information contained herein is Elettronica Santerno s property and cannot be reproduced. Elettronica Santerno enforces its rights on the drawings and catalogues according to the law. Elettronica Santerno S.p.A. Via G. Di Vittorio, 3 40020 Casalfiumanese (BO) Italy Phone +39 0542 668611 Fax +39 0542 668622 After-Sales Service Phone +39 0542 668610 Fax +39 0542 668623 Sales Office Phone +39 0542 668611 Fax +39 0542 668600

16B0231B1 INDEX INDEX...2 1.1 EDS File...3 2 DEVICENET FIELDBUS COMMUNICATIONS BOARD...4 2.1 Main Features...4 2.2 Devicenet Fieldbus Terminals...5 2.3 Board Configuration...5 2.4 Connection to the Fieldbus...6 2.5 Indications...8 2.5.1 Front LEDs...8 2.5.2 LED on the Control Board...8 3 PARAMETER EXCHANGE...9 3.1 From Master to...9 3.2 From to Master...9 3.3 Alarm A028 Communication Interrupted...11 2/11

16B0231B1 1 COMMUNICATION FEATURES This manual describes how to interface a (slave) converter with an intelligent outside control unit (master) via Devicenet. In order to create this interface, an optional module must be installed on the (see Module description). The converter thus becomes a slave node from which a Devicenet master can read and on which it can write. The will never start a communication towards other nodes, but will only answer incoming commands. Via Devicenet you can: read the parameters mentioned in the following From Master to write the parameters mentioned in the following From to Master 1.1 EDS File Each device in a Devicenet network is associated with an Electronic Data Sheet (EDS), containing all the information needed about the device. This file is used by the network configuration program during configuration of the network. Contact Elettronica Santerno directly to get the most recent version of the EDS file. 3/11

16B0231B1 2 DEVICENET FIELDBUS COMMUNICATIONS BOARD The Devicenet communications board allows to interface a with an external control unit through a communications interface using a CAN protocol of the Devicenet 2.0 type. The baud rate and the MAC ID can be set through the on-board dip-switches. Max. 512 bytes for input/output data are available; some of them are used for the interfacing with the. 2.1 Main Features - Baud Rate: 125, 250, 500 kbits/s - DIP switch for baud rate and MAC ID selection - Optically isolated Devicenet interface - Max. 512 bytes for input & output data - Max. 2048 bytes for input & output data through mailbox - Devicenet Specification version: Vol 1: 2.0, Vol 2: 2.0 - Configuration test version: A-12 Figure 1: Devicenet Fieldbus communications board 4/11

16B0231B1 2.2 Devicenet Fieldbus Terminals The Devicenet Fieldbus communications board is provided with a removable, screwable terminal board (pitch 5.08). The bus interface circuitry has an external supply of 24VDC ±10%, as prescribed from the CAN Devicenet specifications. Terminal arrangement as stated in the table: N. Name Description 1 V- Negative voltage for bus supply 2 CAN_L CAN_L bus line 3 SHIELD Cable shielding 4 CAN_H CAN_H bus line 5 V+ Positive voltage for bus supply 2.3 Board Configuration The on-board dip-switches allow to set the baud rate and the MAC ID identifying the device in the Devicenet network. Dip-switches 1 and 2 allow to set the baud rate, that must be the same for all the related devices. The Devicenet standard allows three baud rates: 125, 250 and 500 kbits/s. Possible settings are the following: Baudrate Setting of sw.1 & sw.2 125 kbits/s sw.1=off sw.2=off 250 kbits/s sw.1=off sw.2=on 500 kbits/s sw.1=on sw.2=off The MAC ID can be set between 0 and 63 by entering the configuration of the binary number for six dipswitches, from sw.3 to sw.8. The most significant bit (MSB) is set through sw.3, while the least significant bit (LSB) is set through sw.8. Some possible settings are shown in the table below: MAC ID sw.3 (MSB) sw.4 sw.5 sw.6 sw.7 sw.8 (LSB) 0 OFF OFF OFF OFF OFF OFF 1 OFF OFF OFF OFF OFF ON 2 OFF OFF OFF OFF ON OFF 3 OFF OFF OFF OFF ON ON.............. 62 ON ON ON ON ON OFF 63 ON ON ON ON ON ON If multiple devices are connected to the same bus, different MAC IDs are to be set. 5/11

16B0231B1 2.4 Connection to the Fieldbus The wiring quality is fundamental for the best reliability of the bus operation. The higher the baud rates, the shortest the bus lengths allowed. Reliability is strongly affected by the type of wiring and the wire topology. The Devicenet standard allows four types of wires based on the type of related devices. It also allows to connect signal dispatching nodes, line terminators and supply couplers. Two types of lines are defined: the trunk line and the drop lines. Figure xx illustrates the topology of a typical Devicenet trunk line. Figure 2: Outline of the topology of a Devicenet trunk line The equipped with a Devicenet interface board is typically connected through a drop line consisting of a 5-conductor shielded cable. The Devicenet standard defines three shielded cables based on their diameter: THICK, MID, and THIN cables. The maximum electric length between two Devicenet devices depends on the baud rate and the type of cable being used. The table below shows the maximum lengths that are recommended based on these variables. The FLAT cable can be used for the main trunk line if drop lines are connected through a system that does not require welding. Baud Rate Max. length with FLAT Max. length with Max. length with MID Max. length with THIN cable THICK cable cable cable 125 kbits/s 420m 500m 300m 100m 250 kbits/s 200m 250m 250m 100m 500 kbits/s 75m 100m 100m 100m 6/11

16B0231B1 NOTE NOTE NOTE Each Devicenet trunk line must meet some geometric requirements and must provide two terminator nodes and at least one supply node, because devices can be totally or partially powered via the bus. The type of the cable being used also determines the max. supply current available for the bus devices. For a more comprehensive overview of the Devicenet standard, go to ODVA s home page (http://www.odva.org). In particular, you can refer to the Planning and Installation Manual - DevicenetTM Cable System document at http://www.odva.org/10_2/cable_manual/cable_guide/cable_guide_print.pdf In case of failures or disturbance in the Devicenet communications, please fill in the Devicenet Baseline & Test Report form in the Appendix C of the Planning and Installation Manual before contacting the After-sales service. 7/11

16B0231B1 2.5 Indications The module is provided with four LEDs installed on its front part and with one LED assembled on the control board which is used for debugging operations. 2.5.1 FRONT LEDS Figure 3: Indications LEDs The LED functions are described in the table below: LED State Description 1. Reserved Reserved for future use Off Off Not powered / Not online 2. Green, steady Link OK, On line, Connected Network Status Green, flashing On line, Not connected Red, steady Critical link failure Red, flashing Connection timeout Off No power to device 3. Green, steady Device operational Module Status Green, flashing Data size bigger than configured Red, steady Unrecoverable fault Red, flashing Minor fault 4. Reserved Reserved for future use 2.5.2 LED ON THE CONTROL BOARD The LED located on the control board is a Watchdog LED indicating the state of the module according to the table below: Colour Frequency Description Red Unspecified internal error, or module operating in bootloader mode. 1 Hz RAM fault 2 Hz ASIC or FLASH fault 4 Hz DPRAM fault Green 2 Hz Module not initialized 1 Hz Module initialized and operating 8/11

16B0231B1 3 PARAMETER EXCHANGE The following table shows the parameters of the exchanged via Devicenet. In each of the following are listed: 1) the number and the name of the parameter, 2) its meaning, 3) its range, 4) its unit of measure (shown on the display), 5) the ratio between the value inside the (exchanged via Devicenet) and the physical value represented (as shown on the display). NOTE: unless otherwise specified, each parameter is exchanged as integer with sign at 16 bit (between 32768 and +32767). For further information on parameter configuration, refer to the "OPERATION MANUAL 15P0059B3 2 4 R.05 Software Vers. D4.01... 3.1 From Master to 1) Name 2) Meaning 3) Range M016 FBRref M019 AnOut1 M020 AnOut2 M022 MDO Speed / voltage reference from Devicenet Analog output 1 on terminal 8 Analog output 2 on terminal 10 Digital output state 4) Unit of measure 5) Ratio -100 +100 % 100 / 3FFFh -10 +10 V 10 / FFFh -10 +10 V 10 / FFFh 00000xxxb 11111xxxb Note A) P050 Ilim1A First current limit bridge A 0 300 % 1 P051 Ilim1B First current limit bridge B 0 300 % 1 not used M031 FBDigIn Digital input state from Devicenet 00000000b 11111111b Note B) 3.2 From to Master 1) Name 2) Meaning 3) Range 4) Unit of measure 5) Ratio temp Note C) M001 nfdbk Speed / voltage feedback 100 +100 % 100 / 3FFFh M004 Iarm Armature current 1.5DriveSize A DriveSize / +1.5DriveSize Note D) 2400 M006 Varm Armature voltage 1000 +1000 V 1 M010 AnIn1 Auxiliary analog input 1 at terminals 11 and 13 100 +100 % 100 / 3FFFh M011 AnIn2 Auxiliary analog input 2 at terminal 17 100 +100 % 100 / 3FFFh M012 AnIn3 Auxiliary analog input 3 at terminal 19 100 +100 % 100 / 3FFFh M026 EFreq Encoder frequency 102.4 +102.4 khz 10 / 3FFFh 9/11

16B0231B1 Note A) Bit 3 MDO5 Bit 4 MDO1 Bit 5 MDO2 Bit 6 MDO3 Bit 7 MDO4 Note B) Bit 0 ENABLE Bit 1 START Bit 2 MDI1 Bit 3 MDI2 Bit 4 MDI3 Bit 5 MDI4 Bit 6 MDI5 Bit 7 MDI6 Note C) The two 8-bit variables AlarmNumber and Led are mapped inside the variable temp. Its meaning is the following: high part Led low part AlarmNumber AlarmNumber has the following meaning: Drive OK if AlarmNumber = 0; Alarm = AlarmNumber if AlarmNumber 33; Warning = AlarmNumber-33 if AlarmNumber > 33. Led indicates the state of the LEDs on the remotable keyboard with the following map: Bit 0 RUN Bit 1 FORWARD Bit 2 LOC SEQ Bit 3 BRAKE Bit 4 REF Bit 5 REVERSE Bit 6 LOC REM Bit 7 LIMIT Note D) DriveSize identifies the size of the armature circuit of within the range 10 3500 A, as can be seen on the starting page of the remotable keyboard. 10/11

16B0231B1 3.3 Alarm A028 Communication Interrupted This alarm will trip if the does not receive any valid message via Devicenet within the timeout which can be set using parameter C143 A028Delay. This alarm can be inhibited using parameter C159 A028Inhibit. 11/11