Wet Bulb Temperature and Its Impact on Building Performance



Similar documents
Optimization of Water - Cooled Chiller Cooling Tower Combinations

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

HVAC Systems: Overview

Analysis of data centre cooling energy efficiency

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

*At the AHRI Standard flow rate of 3 gpm/ton, using today s efficient chillers, the ΔT is 9.3 F rather than the 10 F often assumed.

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Defining Quality. Building Comfort. Precision. Air Conditioning

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

Hines Property Management, NYC

Commissioning - Construction Documents (Page 1 of 6)

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

Evaporative Cooling for Residential and Light-Commercial

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Creating Efficient HVAC Systems

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

By Tom Brooke PE, CEM

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Cooling Efficiency Summary of 60-Day Notice - First Steps

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

White Paper #10. Energy Efficiency in Computer Data Centers

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

Benefits. Air-Cooled Systems

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle

Heating, Ventilation & Air Conditioning Equipment

Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX

AIR CONDITIONING TECHNOLOGY

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

State of the Art Energy Efficient Data Centre Air Conditioning

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

How do I measure the amount of water vapor in the air?

Chilled Water HVAC Systems

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Heating, Ventilation & Air Conditioning Equipment

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

3/29/2012 INTRODUCTION HVAC BASICS

Heat Recovery In Retail Refrigeration

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

The HVAC Service Assistant

How to Build a Data Centre Cooling Budget. Ian Cathcart

Temperature and Humidity

District Cooling Plant : Refrigeration Plant Simulation

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

HVAC Repair and Maintenance Strategies by Ron Prager

High Altitude HVAC. Silvertip Integrated Engineering Consultants

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

The Different Types of Air Conditioning Equipment for IT Environments

Chapter 3.4: HVAC & Refrigeration System

Tips and Tricks for Estimating Energy Savings. Celeste Cizik, P.E. Project Manager E M C Engineers, Inc.

Modular Chiller Plants for data centers. Downtime isn t acceptable

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

Guide to Minimizing Compressor-based Cooling in Data Centers

How To Improve Energy Efficiency Through Raising Inlet Temperatures

Agenda. Part I: Introduction to OptimumHVAC. Part II: Initial Energy Savings Analysis for MCO Main Terminal. Part III: Case Studies & Conclusion

National Grid Your Partner in Energy Solutions

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Evaporative Cooling System for Aquacultural Production 1

GAS TURBINE INLET AIR CHILLING FOR LNG

Economizer Modes of Data Center Cooling Systems

EnergyPro Building Energy Analysis. Assisted Living Building

The Development of a Frost-Less Heat Pump

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

Role of Economizers in Dedicated Outdoor Air Systems

85 F 80 F 50% 75 F 70 F 73.0/ F 10% Figure 1

Maintenance for Energy Efficiency

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Tim Facius Baltimore Aircoil

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

How To Design A Refrigeration System

Optimizing Design & Control Of Chilled Water Plants Part 5: Optimized Control Sequences

HVAC and REFRIGERATION

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Using Time-of-Day Scheduling To Save Energy

ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.


Hospital Application Guide. Cost-effective climate control for hospitals

Transcription:

Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1

What is Wet Bulb Temperature? Wet bulb temperature is an indication of the amount of moisture contained within the air. Wet bulb temperature differs from the temperature you feel when you go outside. The temperature you feel is called Dry Bulb temperature, and is independent of the moisture content of the air. Wet bulb temperature is the temperature you feel when water evaporates from the skin and can be measured by wrapping the bulb of a thermometer in a wet cloth. If you swing the thermometer quickly the resulting evaporation will drive the thermometer towards the wet bulb temperature. Unless the air is fully saturated (in other words, relative humidity is 100%), the web bulb temperature will be less than the ambient dry bulb temperature. 2 Since wet bulb is a measure of moisture levels within the air, the larger the differential between dry bulb and wet bulb temperatures the drier the air feels. For instance, take a look at the following example: Dry-Bulb Temperature Wet-Bulb Temperature Relative Humidity Day 1 80 F 70 F 61% Day 2 80 F 63 F 39% In the above example, both days have the same ambient dry bulb temperature, however Day 2 has a lower wet bulb and will therefore feel like a more pleasant day.

Wet Bulb Can be Used to Determine Other Physical Properties of Air By measuring the wet bulb and dry bulb temperatures, other physical properties of air, such as the relative humidity and the dew point temperature, can be determined. One means of determining the physical properties of air is by charting the known values on a psychrometric chart and interpolating the other values. 3

Wet Bulb Temperature How Does Wet Bulb Temperature Affect HVAC Systems? As we just learned, wet bulb temperature is the minimum temperature that can be attained by the evaporation of water. As a result, the wet bulb temperature is the lowest temperature that can be supplied by a cooling tower or an evaporative cooler. Cooling tower design supply temperatures are based on the worst case wet bulb temperatures for a particular region. The wet bulb temperature sets the cooling tower s lowest supply temperature limit. Cooling Tower Return: 95 F Cooling Tower Wet Bulb Temperature: 78 F Cooling Tower Supply: 85 F 4 The difference between the cooling tower return and the cooling tower supply temperatures is called the range temperature. Cooling tower range temperature is typically between 8 F - 15 F. The larger the cooling tower range temperature, the less pumping energy is required to move the cooling tower water through the HVAC system. The difference between the cooling tower supply temperature and the wet bulb temperature is called the approach temperature. Approach temperature is typically between 5 F - 10 F in the mid-atlantic region and can be higher in dry climates. As cooling tower approach temperature decreases, colder water is supplied to the HVAC system. The advantages of colder cooling tower supply temperature will be discussed in the next section.

Utilizing Wet Bulb to Increase Energy Efficiency Wet bulb temperature is typically at or above design conditions less than 1% of the year, so there is a significant opportunity to reduce cooling tower supply temperature throughout the year. This is accomplished by utilizing a control logic in the Building Management System (BMS) that varies the cooling tower supply temperature with the outside air wet bulb temperature. A common approach to cooling tower operation is to have two modes of operation; normal operation where the cooling tower supplies the design temperature to the mechanical HVAC equipment, and economizer operation where the cooling tower supplies the chilled water temperature that the HVAC system would typically supply. During economizer operation, the cooling tower supply temperature will typically range between 40 F - 50 F based on outdoor conditions. With the use of BMS controls a third operation can implemented when the cooling tower operation is in normal mode to allow the cooling tower supply temperature set point to vary (or reset) based on the wet bulb temperature. HVAC energy efficiency can typically increase upwards of 1%-2% for every degree that cooling tower supply temperature is reduced. The following graph is one example of the energy efficiency (KW/ton) of a centrifugal chiller at various entering condenser water temperatures at both 100% load and 60% load. 5 TRANE Engineers Newsletter: Vol. 25/No. 1

As indicated in the above graph, the KW/ton of the chiller decreases as the entering condenser water temperature decreases. This results in the chiller requiring less power (KW) to produce one ton of cooling, thereby increasing energy efficiency. The following is a list of several system types that would be potential candidates for condenser water supply reset strategies: Central chiller plant with centrifugal or double effect absorption chillers Floor by floor self-contained units Water cooled rooftop units Economizer Cooling When the ambient wet bulb temperature is low enough, cooling towers can produce chilled water without using mechanical cooling. Water side economizer saves energy by turning off the large compressors in the chillers and self-contained units within the building and providing chilled water straight to the units from the cooling tower. A common configuration for water side economizer is to provide cooling tower water to a plate and frame heat exchanger, which then provides cooling to the HVAC system. 6 All buildings that utilize cooling towers to reject heat are candidates for water side economizer.

Case Study: Economizer Cooling and Improving Building Performance Economizer cooling has been proven to significantly reduce building energy consumption and improve HVAC system efficiencies. For this case study we ll analyze one building where the building engineer was able to utilize economizer cooling during the morning and early afternoon hours, but had to use mechanical cooling later in the afternoon. Economizer Cooling Mechanical Cooling 7 Between 4am-1pm the average wet bulb temperature was 53 F, which allowed the economizer system to provide chilled water for free cooling. As the day progressed the chilled water temperature requirements changed due to the internal heat gains and between 1:00pm and 2:00pm the chiller was required to provide mechanical cooling to the building. The chiller activation is evident in the graph above by the large spike in electricity consumption. The electricity demand during peak economizer hours (6:00am-1:00pm) was reduced by approximately 200 KW, when compared to the 2pm to 5pm profile. This resulted in energy savings of approximately 1,400 KWh during the economizer hours. Economizer savings for this particular example were only realized during a portion of the day due to fact that this was a moderate day in mid-fall. During late fall through early spring, the building will operate almost exclusively in economizer mode. Therefore, potential savings for the building over the course of an entire year can be significant. Economizer savings for this particular example were only realized during a portion of the day due to fact that this was a moderate day in mid-fall. During late fall through early spring, the building will operate almost exclusively in economizer mode. Therefore, potential savings for the building over the course of an entire year can be significant.

Case Study: Diagnosing System Performance Issues In order to develop an optimized system performance strategy, AtSite energy managers developed a performance verification plan with the facility manger to establish a baseline of current system performance. After several weeks of diligently tracking wet bulb, dry bulb, cooling tower supply and cooling tower return temperatures the facility manger provided AtSite with the system performance results: Approach Range Two things were immediately noticed by AtSite engineers. First, the approach temperature is between 3 F-4 F consistently throughout the temperature readings. Second, the range temperature is between 15 F-18 F. These temperatures differed from the approach and range indicated on the construction documents (9 F and 8 F, respectively). The low approach and high range temperatures are indicative of a potential flow problem within the cooling tower system. 8 Based on this analysis, a cooling tower technician performed a detailed inspection of the cooling tower system and determined that the flow was restricted through the heat exchanger serving the closed loop heat pump system. Low flow through a heat exchanger can cause substantial losses in energy efficiency and impact system performance. Low velocity through a heat exchanger causes laminar flow which results in reduced heat transfer effectiveness and the build up of scale within the heat exchanger tubes. Low flow also causes the cooling tower fans to work harder to remove the heat from the condenser loop. In other words, instead of varying to meet the actual load the fans must operate at or near full capacity to satisfy cooling loads throughout all modes of operation. In addition to the issues cased by low flow, a blockage in the heat exchanger results in additional head losses through the system which causes the cooling tower pumps to work harder to produce flow. At the direction of the building owner, the technician was able to clean the heat exchanger to mitigate the flow issues and restore system performance. By diligently tracking wet bulb temperature and comparing actual system performance, AtSite engineers and the facility manager were able to diagnose and rectify an issue with the building HVAC system that was adversely impacting building energy performance. Without this process, the issue may have continued unabated until the problem reached critical failure and building systems went offline. By addressing the issue prior to system failure, AtSite engineers and energy managers improved building performance and protected valuable building assets from additional damage which may have shortened useful life.