2015 International Building Code



Similar documents
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003

A Code Review for Emergency Generators and Indoor Use of Portable Generators

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Fire and Smoke Dampers: Best Practice Design Tips. An AMCA International White Paper. July 2015

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

SECTION 903 AUTOMATIC SPRINKLER SYSTEMS

MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES

Type IIB, Type IIIB (Unprotected Construction) Story Comparison (w/ NFPA 13 Sprinklers)

Requirements for Hydrogen Storage and Use

Indiana Building Rehabilitation Standard

CHAPTER 9 FIRE PROTECTION SYSTEMS

Overview of Hotel Fire Safety Requirements

PROJECT SUMMARY. Scope of work details: (If phased construction, please see plan submittal guidelines.)

Fire Alarm Systems Requirements by Occupancy Type

Executive Summary Inclusion of Current Firewall Requirements in NBCC

Code Requirements for Existing Buildings

Disaster Recovery Plan (DRP) / Business Continuity Plan (BCP)

City of Riverside Building & Safety Division Phone: (951)

FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC CALIFORNIA BUILDING CODE 199

FIRE-RESISTANCE-RATED CONSTRUCTION

Disaster Ready. By: Katie Tucker, Sales Representative, Rolyn Companies, Inc

FIRE-RESISTANCE-RATED CONSTRUCTION

Fire Safety Risk Assessment Checklist for Residential Care Premises

NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02

Development of Seismic-induced Fire Risk Assessment Method for a Building

Earthquakes and Data Centers

2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS

Errata has been identified as follows:

FIRE AND SMOKE PROTECTION FEATURES

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, , ]

HOW METAL BUILDING INSURANCE COSTS COMPARE TO OTHER BUILDING TYPES

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

HURRICANE DISASTER PREPARATION CHECKLIST AND BUSINESS CONTINUITY PLAN

Fire Barriers & Fire Stopping

BUILDING CODE MODIFICATIONS FOR ENHANCED RESILIENCY

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

Building Code Clarifications - 7. Fire Resistance

PART 4: INSURANCE IMPLICATIONS

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

Wood use in Type I and II (noncombustible) construction

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

Designing for Fire Protection

General Fire Code Requirements Within Commercial Tenant Spaces

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST

Long-Term Disaster Recovery Top 10 Action Items. Association of Bay Area Governments April 2010

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET

CHILD CARE CENTER INFORMATION SHEET

2012 IBC & 2012 NFPA 101 Significant Means of Egress Changes. Questions Design Occupant Load Means of Egress Capacity Determination

Anchorage All-Hazard Mitigation Plan October 2004

A study of the nature of fire risks in tall buildings

Health Care Facilities

Classroom Door Security & Locking Hardware

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS

Errata NFPA 1. Fire Code Edition

REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS

Prepared For San Francisco Community College District 33 Gough Street San Francisco, California Prepared By

Chapter 3: Use and Occupancy Classification

Florida Advanced Building Code Course# FLBC11

ENGINEERING-BASED EARTHQUAKE RISK MANAGEMENT

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS

FIRE SAFETY INSPECTION REPORT

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

MAIB SAFETY BULLETIN 1/2006. Fire on board the Bermuda registered cruise ship. Star Princess

Building Code Effectiveness Grading: In Brief. What? Why? When? And What Do I Do?

- 5 - Table1. Maximum Compartment Volumes

TELECOMMUNICATION SYSTEM HAZARD MITIGATION STRATEGIC PLANNING

Wyoming State Capitol Building Restoration and Modernization

NFPA SELECT SIGNIFICANT CHANGES

Understanding Sage CRM Cloud

Additional Guidance. for application to. HM Government Guide to Fire Safety Risk Assessment Residential Care Premises

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)

February 2014 Alberta Fire Code Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities

Earthquakes: Risk & Insurance Issues

Business Impact Analysis (BIA) and Risk Mitigation

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015

FIRE AND SMOKE PROTECTION FEATURES

Resources FEMA CURRICULUM. FEMA Mitigation Curriculum MITIGATION TRAINING. Resident Courses

HOW TO EVALUATE BUILDINGS AND DETERMINE RETROFIT COSTS

Development Services City of Lawrence, KS

Fire Risk Assessment Safety Checklist

ADMINISTRATIVE SERVICES MANUAL

Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.

Barre City City-wide Policy and Program Options

How To Build A Two Hour Firewall In Calgary


CHAPTER 6 CONSTRUCTION TYPES

How to Prepare Your Business for an Emergency

Healthcare Engineering. Code Summary Report

An inventory of hazardous materials used in your workplace will prove useful.

2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i

Critical Facility Round Table

WORKING P A P E R. Planning the Safety of Healthcare Structures CHARLES MEADE WR-309. October 2005

A Guide to Hazard Identification and Risk Assessment for Public Health Units. Public Health Emergency Preparedness Protocol

Transcription:

Public Comment E97-15 LOVELL-B: Proponent : Vickie Lovell, InterCode Incorporated, representing Fire Safe North America (vickie@intercodeinc.com) requests Approve as Modified by this Public Comment. Modify as Follows: 2015 International Building Code 1017.2 Limitations. Exit access travel distance shall not exceed the values given in Table 1017.2 except where limited by Section 1017.2.3. 1017.2.3 Groups A, B, E and R decrease. InSprinklered buildings in Groups A, B, E and R occupancies, assigned to Risk Categories III andcategory IV in Table 1604.5 and of Types IIB, IIIB and VB construction, shall be limited to the travel distances in Table 1017.2 for nonsprinklered buildings without sprinkler systems where such buildings are any of the following: 1. Assigned aseismic Design Category F or Seismic Design Category C or DD where the building is assigned to Risk Category IV in Table 1613.3.5(1)accordance with 1613.3.5. 2. Located in a special flood hazard area defined by this code and established in accordance with Section 1612.3. 3. Located in a windborne-debris region of hurricane-prone regionareas based on Figure 1609.3(2). Exception: Buildings that have an automated sprinkler system installed in accordance with NFPA 13, are provided with an uninterruptable water and power supply, and the fire pumps are protected against interrupton of service in accordance with Section 913. Commenter's Reason: The increased fire resistivity required by this proposal is intended to apply ONLY to buildings that are ALL of the following: Classified in the highest risk category. Located in the highest risk, disaster-prone regions for floods, hurricanes and seismic activity. Type IIB, IIIB or VB construction. It excludes sprinklered buildings that have emergency backup systems for water and power in those regions. Although the cause is debated, naturally-occurring and man-made disasters are increasing in number and severity in the United States and around the world. That fact is undisputed. The resilience of communities and the individual buildings within those communities is becoming of vital importance. A National Institute of Building Sciences Publication (May, 2014) entitled "Moving Forward: Findings and Recommendations", states that "while a long history of building codes has laid the foundation for addressing the impacts of natural and man-made hazards, changes in the frequency and severity of events have brought new challenges challenges requiring the engagement and support of policymakers. While building codes serve as the minimum requirements for life-safety in the building stock, basic life-safety protections do not fully address building performance requirements to achieve resilience." Mitigation includes, among other things, fortifying buildings so that they are less likely to be severely damaged or completely destroyed during or immediately after a disaster. It is the key to recovery after a disaster. Mitigation allows individuals and communities to lessen post-disaster disruption and rebuild more quickly. States and cities have started implementing more stringent requirements in specific geographic areas they have designated as higher-risk. The purpose of this series of code changes proposed by Fire Safe North America is to encourage the debate in the code development process to identify what constitutes resilient buildings, and begin to identify issues that will become the basis for "new minimum requirements" for increased building resiliency. Responding to the challenge of mitigating damage and resilient buildings is an admittedly complex topic. Fire Safe North America proposals are intended to reduce the total reliance of a community and its firefighters on automatic sprinkler systems in disaster-prone areas of the country where the water supply and/or power are likely to be interrupted, or are likely to have water supply system operational issues. The proposals, if approved, will fortify the building code requirements for the most vulnerable buildings to fire - Type IIB, IIIB, and VB construction, which are also classified as Risk Category IV in Table 1604.5, and in high-risk, disaster prone regions. The proposals modify the following code requirements in such buildings: 1. Reduce allowable area limits. 2. Protect the path of egress by limiting travel distances. 3. Protect the path of egress by protecting corridors. 4. Require higher fire resistance ratings for occupancy separations. 5. Require higher fire resistance ratings for building elements. These proposals are intended to be conservative so as to promote community resiliency and disaster mitigation by protecting essential buildings with both sprinkler protection AND fire resistance rated compartmentation. These proposals may be fairly considered to be the proverbial "belt and suspenders" approach, requiring both sprinkler protection and increased fire resistance rated compartmentation in specific buildings in high risk areas for disasters. Historically, the code has been written using the general assumption that automatic sprinklers will operate satisfactorily and there will be suitable power for such building operations. Code users design and build assuming that firefighters will be able to respond at their normal efficiencies. In some parts of the country, buildings impacted by disasters may remain without reliable water and/or power for a considerable period of time, well after the occurrence of the disaster. History has shown that increased incidents of fires after a disaster can be more destructive to life and property than the disaster itself. Total reliance on an uninterrupted power and water supply may not

be an acceptable risk. It may also be an unacceptable risk to assume that firefighters will be able to respond at their normal efficiencies. For example, more than 15% of the U.S. population lives in potential major earthquake areas. 41 states and territories have moderate to high risk. There is a real likelihood of power and water supplies being interrupted following a major seismic event, along with the potential for multiple simultaneous structure fires and also building-to-building fire spread. On October 17, 1989, a 7.1 earthquake in Santa Cruz Mountains was responsible for 26 fires in San Francisco, 60 miles from epicenter. There were 67 documented breaks in water mains which effectively eliminated water pressure in the area. On January 19, 1994, a 6.8 earthquake centered in Northridge, CA. There were approximately 100 fire ignitions, 30 to 50 of those were considered significant. The water supply systems in the area were damaged causing low pressure in water distribution. On January 17, 1995, a 6.8 (approx.) earthquake near Kobe, Japan caused 90 fires to start within minutes. 85 spread to adjacent buildings and 10 approached or reached conflagration status. 1,700 water line breaks occurred within a couple of hours. There were 7,000 buildings destroyed by fire alone. In 1997, the Red River flooded Grand Forks, North Dakota, causing $3.7 billion in flood losses, and displaced thousands of families and businesses. Similar data of increased fire incidents are available in other flood and hurricane-prone areas. Undoubtedly, this will increase the cost of construction in these specific buildings. However, a recent FEMA's 2010 report "Mitigation's Value to Society" statement described how mitigation is an investment that needs to be made. A recent study by the NIBS Multihazard Mitigation Council (MMC) identified that each dollar spent on mitigation saves an average of $4.00 in disaster recovery. Links: http://www.dhses.ny.gov/oem/mitigation/documents/mitigations-value-to-society.pdf The two-volume NIBS MMC study report is available for free download at: http://www.nibs.org/index.php/mmc/projects/nhms Cost Impact: Will increase the cost of construction This code change proposal will increase the cost of construction of some building types.

Public Comment E105-15 LOVELL-B: Proponent : Vickie Lovell, InterCode Incorporated, representing Fire Safe North America (vickie@intercodeinc.com) requests Approve as Modified by this Public Comment. Modify as Follows: 2015 International Building Code 1020.1 Construction. Corridors shall be fire-resistance rated in accordance with Table 1020.1. The corridor walls required to be fire-resistance rated shall comply with Section 708 for fire partitions,. In addition, corridors in buildings of Types IIB, IIIB, and VB construction and assigned Risk Categories III and IV in Table 1604.5, other than Group I, shall have a fire resistance rating of not less than 1 hour where such buildings are any of the following: 1. Assigned a Seismic Design Category C or D in Table 1613.3.5(1). 1. Located in a flood hazard area established in accordance withapplicable, Section 1612.31020.1.1. 2. Located in a hurricane-prone regions. Exceptions: 2.1. A fire-resistance rating is not required for corridors in an occupancy in Group E where each room that is used for instruction has not less than one door opening directly to the exterior and rooms for assembly purposes have not less than one-half of the required means of egress doors opening directly to the exterior. Exterior doors specified in this exception are required to be at ground level. 2.2. A fire-resistance rating is not required for corridors contained within a dwelling unit or sleeping unit in an occupancy in Groups I-1 and R. 2.3. A fire-resistance rating is not required for corridors in open parking garages. 2.4. A fire-resistance rating is not required for corridors in an occupancy in Group B that is a space requiring only a single means of egress complying with Section 1006.2. 2.5. Corridors adjacent to the exterior walls of buildings shall be permitted to have unprotected openings on unrated exterior walls where unrated walls are permitted by Table 602 and unprotected openings are permitted by Table 705.8. 1020.1.1 Corridors in sprinklered buildings. Corridors in sprinklered buildings of Types IIB, IIIB and VB construction assigned to Risk Category IV in Table 1604.5, other than Group I, shall have a fire-resistance rating of not less than 1 hour where such buildings are any of the following: 1. Seismic Design Category F or Seismic Design Category D where the building is assigned to Risk Category IV in accordance with 1613.3.5. 2. Located in a special flood hazard area defined by this code and established in accordance with Section 1612.3. 3. Located in a windborne-debris region of hurricane-prone areas based on Figure 1609.3(2). Exception: Corridors in buildings that have an automatic sprinkler system installed in accordance with NFPA 13, are provided with an uninterruptable water and power supply, and the fire pumps are protected against interruption of service in accordance with Section 913. Commenter's Reason: The increased fire resistivity required by this proposal is intended to apply ONLY to buildings that are ALL of the following: Classified in the highest risk category. Located in the highest risk, disaster-prone regions for floods, hurricanes and seismic activity. Type IIB, IIIB or VB construction. It excludes sprinklered buildings that have emergency backup systems for water and power in those regions. Although the cause is debated, naturally-occurring and man-made disasters are increasing in number and severity in the United States and around the world. That fact is undisputed. The resilience of communities and the individual buildings within those communities is becoming of vital importance. A National Institute of Building Sciences Publication (May, 2014) entitled "Moving Forward: Findings and Recommendations", states that "while a long history of building codes has laid the foundation for addressing the impacts of natural and man-made hazards, changes in

the frequency and severity of events have brought new challenges challenges requiring the engagement and support of policymakers. While building codes serve as the minimum requirements for life-safety in the building stock, basic life-safety protections do not fully address building performance requirements to achieve resilience." Mitigation includes, among other things, fortifying buildings so that they are less likely to be severely damaged or completely destroyed during or immediately after a disaster. It is the key to recovery after a disaster. Mitigation allows individuals and communities to lessen post-disaster disruption and rebuild more quickly. States and cities have started implementing more stringent requirements in specific geographic areas they have designated as higher-risk. The purpose of this series of code changes proposed by Fire Safe North America is to encourage the debate in the code development process to identify what constitutes resilient buildings, and begin to identify issues that will become the basis for "new minimum requirements" for increased building resiliency. Responding to the challenge of mitigating damage and resilient buildings is an admittedly complex topic. Fire Safe North America proposals are intended to reduce the total reliance of a community and its firefighters on automatic sprinkler systems in disaster-prone areas of the country where the water supply and/or power are likely to be interrupted, or are likely to have water supply system operational issues. The proposals, if approved, will fortify the building code requirements for the most vulnerable buildings to fire - Type IIB, IIIB, and VB construction, which are also classified as Risk Category IV in Table 1604.5, and in high-risk, disaster prone regions. The proposals modify the following code requirements in such buildings: 1. Reduce allowable area limits. 2. Protect the path of egress by limiting travel distances. 3. Protect the path of egress by protecting corridors. 4. Require higher fire resistance ratings for occupancy separations. 5. Require higher fire resistance ratings for building elements. These proposals are intended to be conservative so as to promote community resiliency and disaster mitigation by protecting essential buildings with both sprinkler protection AND fire resistance rated compartmentation. These proposals may be fairly considered to be the proverbial "belt and suspenders" approach, requiring both sprinkler protection and increased fire resistance rated compartmentation in specific buildings in high risk areas for disasters. Historically, the code has been written using the general assumption that automatic sprinklers will operate satisfactorily and there will be suitable power for such building operations. Code users design and build assuming that firefighters will be able to respond at their normal efficiencies. In some parts of the country, buildings impacted by disasters may remain without reliable water and/or power for a considerable period of time, well after the occurrence of the disaster. History has shown that increased incidents of fires after a disaster can be more destructive to life and property than the disaster itself. Total reliance on an uninterrupted power and water supply may not be an acceptable risk. It may also be an unacceptable risk to assume that firefighters will be able to respond at their normal efficiencies. For example, more than 15% of the U.S. population lives in potential major earthquake areas. 41 states and territories have moderate to high risk. There is a real likelihood of power and water supplies being interrupted following a major seismic event, along with the potential for multiple simultaneous structure fires and also building-to-building fire spread. On October 17, 1989, a 7.1 earthquake in Santa Cruz Mountains was responsible for 26 fires in San Francisco, 60 miles from epicenter. There were 67 documented breaks in water mains which effectively eliminated water pressure in the area. On January 19, 1994, a 6.8 earthquake centered in Northridge, CA. There were approximately 100 fire ignitions, 30 to 50 of those were considered significant. The water supply systems in the area were damaged causing low pressure in water distribution. On January 17, 1995, a 6.8 (approx.) earthquake near Kobe, Japan caused 90 fires to start within minutes. 85 spread to adjacent buildings and 10 approached or reached conflagration status. 1,700 water line breaks occurred within a couple of hours. There were 7,000 buildings destroyed by fire alone. In 1997, the Red River flooded Grand Forks, North Dakota, causing $3.7 billion in flood losses, and displaced thousands of families and businesses. Similar data of increased fire incidents are available in other flood and hurricane-prone areas. Undoubtedly, this will increase the cost of construction in these specific buildings. However, a recent FEMA's 2010 report "Mitigation's Value to Society" statement described how mitigation is an investment that needs to be made. A recent study by the NIBS Multihazard Mitigation Council (MMC) identified that each dollar spent on mitigation saves an average of $4.00 in disaster recovery. Links: http://www.dhses.ny.gov/oem/mitigation/documents/mitigations-value-to-society.pdf The two-volume NIBS MMC study report is available for free download at: http://www.nibs.org/index.php/mmc/projects/nhms Cost Impact: Will increase the cost of construction This code change proposal will increase the cost of construction of some building types.

Public Comment G140-15 LOVELL-C: Proponent : Vickie Lovell, InterCode Incorporated, representing Fire Safe North America (vickie@intercodeinc.com) requests Approve as Modified by this Public Comment. Modify as Follows: 2015 International Building Code 506.1.4 Allowable area for buildings in disaster prone regions. ForThe maximum allowable area for buildings assigned to Risk Category IV that are more than one story in height above grade plane thatand are of construction Types IIB, IIIB and VB, the maximum allowable area shall not be greater than the area permitted for non-sprinklered (NS) buildings in accordance with Table 506.2, adjusted for any frontage increase in accordance with 506.3, and where such buildings are any of the following: 1. Assigned toseismic Design Category F, or Seismic Design Category C or DD where the building is assigned to Risk Category IV in Table 1613.3.5(1)accordance with 1613.3.5. 2. Located in a special flood hazard area defined by this code and established in accordance with Section 1612.3. 3. Located in a windborne-debris region of hurricane-prone regionregions based on Figure 1609.3(2) for Risk Category IV buildings. Exception: Buildings that have an automatic sprinkler system installed in accordance with NFPA 13, are provided with an uninteruptable water and power supply, and the fire pumps are protected against interruption of service in accordance with Section 913. Commenter's Reason: The area limitation is intended to apply ONLY to buildings that are all of the following: Classified as the highest risk. Located in the highest risk, disaster-prone regions for floods, hurricanes, and seismic activity. Types IIB, IIIB and VB construction. It excludes sprinklered buildings that have emergency backup systems for water and power in those regions. The purpose of this code change is to reduce the total reliance of a community and its firefighters on sprinkler systems in disaster-prone areas of the country where the water supply and/or power may be interrupted, or are likely to have municipal water system operation issues. This proposal is a very conservative proposal to promote community resiliency by limiting the footprint of multi-story buildings that have no vertical fire compartmentation to that which would normally be allowed for non-sprinklered buildings. The Type IIB, IIIB and VB buildings may have a fully involved fire in a very short amount of tim in the event that water supplies for sprinklers are reduced or impaired after a natural catastrophe. Such water supply interruptions are not uncommon after natural disasters. For non-rated multistory buildings, meaning buildings that have no fire resistance rated floors, fire may spread freely and quickly from story to story. Limiting the per-floor area of Type IIB, IIIB, and VB buildings is intended to result in protecting buildings in areas at high risk for natural catastrophes, the most essential combustible buildings, and facilities with both sprinkler protection and increased fire resistance rated vertical compartmentation. This proposal may be fairly considered to be the proverbial "belt and suspenders" approach. If one were to fail, the other protection method would provide an added layer of protection that would serve to prevent a life safety disaster. The 2012 IBC Sections 504.2 and 506.3 had specific allowable increases that were permitted when automatic sprinkler systems were installed. Those allowances have been incorporated into Tables 504.3 and 504.4 as S1 and SM. Such allowable area increases permitted by the code assumed that power and water supply will be readily available and reliable for the successful operation of fire suppression systems. This is especially true for combustible construction such as Types IIB, IIIB and VB, and also for non-combustible construction without any vertical compartmentation. For some parts of the country where buildings impacted by a natural disaster may remain without reliable water and or power for a considerable period of time, that general assumption may not be an acceptable risk. It may also be an unacceptable risk to assume that firefighters will be able to respond at their normal efficiencies. Responding to the challenge of mitigating damage from natural disasters, California has more stringent requirements on buildings they have designated as "high-risk". But more than 15% of the U.S. popluation lives in potential major earthquake areas; 41 states and territories have moderate to high risk. There is a real likelihood of power and water supplies being interrupted following a major seismic event, along with the potential for multiple simultaneous structure fires and also uncontrollable building-to-building fire spread. On October 17, 1989, a 7.1 earthquake in the Santa Cruz Mountains was responsible for 26 fires in San Francisco, 60 miles from epicenter. There were 67 documented breaks in water mains which effectively eliminated water pressure in the area. On January 19, 1994, a 6.8 earthquake centered in Northridge, CA. There were approximately 100 fire ignitions, 30 to 50 of those were considered significant. The main cause of fire was largely due to natural gas leaks. Additionally, the water supply systems in the area were damaged causing low pressure in water distribution. On January 17, 1995, a 6.8 (approx.) earthquake near Kobe, Japan caused 90 fires to start within minutes; 85 spread to adjacent buildings and 10 approached or reached conflagration status. 1,700 water line breaks occurred within a couple of hours. There were 7,000 buildings destroyed by fire alone. Similar data of increased fire incidents are available in hurricane and flood prone regions. History has shown that increased incidents of fires after a disaster can be more destructive to life and property than the disaster itself. This change is limited in its application to multi-story buildings without any vertical fire compartmentation in the higher risk, disasterprone regions defined by the code. There may be some types of combustible materials of these buildings that should appropriately be exempted from this area limitation. Cost Impact: Will increase the cost of construction This code change proposal will increase the cost of construction for some building types.

Public Comment G152-15 LOVELL-D: Proponent : Vickie Lovell, InterCode Incorporated, representing Fire Safe North America (vickie@intercodeinc.com) requests Approve as Modified by this Public Comment. Modify as Follows: 2015 International Building Code 508.4.4.2 Fire-resistance ratings. The fire-resistance ratings in Table 508.4 shall not be permitted to be reduced to less than 2 hours in sprinklered buildings of construction Types IIB, IIIB and VB in Risk Categories III andcategory IV identified in Table 1604.5 where such buildings are any of the following: 1. Assigned toseismic Design Category F or Seismic Design Category C or DD where the building is assigned to Risk Catergory IV in Table 1613.3.5(1)accordance with 1613.3.5. 2. Located in a special flood hazard area defined by this code and established in accordance with Section 1612.3. 3. Located in athe windborne-debris region of hurricane-prone regionareas based on Figure 1609.3(2). Exception: Buildings that have an automatic sprinkler system installed in accordance with NFPA 13, are provided with an uninterruptable water and power supply, and the fire pumps are protected against interruption of service in accordance with Section 913. Commenter's Reason: The increased fire resistivity required by this proposal is intended to apply ONLY to buildings that are ALL of the following: Classified in the highest risk category. Located in the highest risk, disaster-prone regions for floods, hurricanes and seismic activity. Type IIB, IIIB or VB construction. It excludes sprinklered buildings that have emergency backup systems for water and power in those regions. Although the cause is debated, naturally-occurring and man-made disasters are increasing in number and severity in the United States and around the world. That fact is undisputed. The resilience of communities and the individual buildings within those communities is becoming of vital importance. A National Institute of Building Sciences Publication (May, 2014) entitled "Moving Forward: Findings and Recommendations", states that "while a long history of building codes has laid the foundation for addressing the impacts of natural and man-made hazards, changes in the frequency and severity of events have brought new challenges challenges requiring the engagement and support of policymakers. While building codes serve as the minimum requirements for life-safety in the building stock, basic life-safety protections do not fully address building performance requirements to achieve resilience." Mitigation includes, among other things, fortifying buildings so that they are less likely to be severely damaged or completely destroyed during or immediately after a disaster. It is the key to recovery after a disaster. Mitigation allows individuals and communities to lessen post-disaster disruption and rebuild more quickly. States and cities have started implementing more stringent requirements in specific geographic areas they have designated as higher-risk. The purpose of this series of code changes proposed by Fire Safe North America is to encourage the debate in the code development process to identify what constitutes resilient buildings, and begin to identify issues that will become the basis for "new minimum requirements" for increased building resiliency. Responding to the challenge of mitigating damage and resilient buildings is an admittedly complex topic. Fire Safe North America proposals are intended to reduce the total reliance of a community and its firefighters on automatic sprinkler systems in disaster-prone areas of the country where the water supply and/or power are likely to be interrupted, or are likely to have water supply system operational issues. The proposals, if approved, will fortify the building code requirements for the most vulnerable buildings to fire - Type IIB, IIIB, and VB construction, which are also classified as Risk Category IV in Table 1604.5, and in high-risk, disaster prone regions. The proposals modify the following code requirements in such buildings: 1. Reduce allowable area limits. 2. Protect the path of egress by limiting travel distances. 3. Protect the path of egress by protecting corridors. 4. Require higher fire resistance ratings for occupancy separations. 5. Require higher fire resistance ratings for building elements. These proposals are intended to be conservative so as to promote community resiliency and disaster mitigation by protecting essential buildings with both sprinkler protection AND fire resistance rated compartmentation. These proposals may be fairly considered to be the proverbial "belt and suspenders" approach, requiring both sprinkler protection and increased fire resistance rated compartmentation in specific buildings in high risk areas for disasters. Historically, the code has been written using the general assumption that automatic sprinklers will operate satisfactorily and there will be suitable power for such building operations. Code users design and build assuming that firefighters will be able to respond at their normal efficiencies. In some parts of the country, buildings impacted by disasters may remain without reliable water and/or power for a considerable period of time, well after the occurrence of the disaster. History has shown that increased incidents of fires after a disaster can be more destructive to life and property than the disaster itself. Total reliance on an uninterrupted power and water supply may not be an acceptable risk. It may also be an unacceptable risk to assume that firefighters will be able to respond at their normal efficiencies. For example, more than 15% of the U.S. population lives in potential major earthquake areas. 41 states and territories have moderate to high risk. There is a real likelihood of power and water supplies being interrupted following a major seismic event, along with the potential for multiple simultaneous structure fires and also building-to-building fire spread. On October 17, 1989, a 7.1 earthquake in Santa Cruz Mountains was responsible for 26 fires in San Francisco, 60 miles from epicenter. There were 67 documented breaks in water mains which effectively eliminated water pressure in the area. On January 19, 1994, a 6.8 earthquake centered in Northridge, CA. There were

approximately 100 fire ignitions, 30 to 50 of those were considered significant. The water supply systems in the area were damaged causing low pressure in water distribution. On January 17, 1995, a 6.8 (approx.) earthquake near Kobe, Japan caused 90 fires to start within minutes. 85 spread to adjacent buildings and 10 approached or reached conflagration status. 1,700 water line breaks occurred within a couple of hours. There were 7,000 buildings destroyed by fire alone. In 1997, the Red River flooded Grand Forks, North Dakota, causing $3.7 billion in flood losses, and displaced thousands of families and businesses. Similar data of increased fire incidents are available in other flood and hurricane-prone areas. Undoubtedly, this will increase the cost of construction in these specific buildings. However, a recent FEMA's 2010 report "Mitigation's Value to Society" statement described how mitigation is an investment that needs to be made. A recent study by the NIBS Multihazard Mitigation Council (MMC) identified that each dollar spent on mitigation saves an average of $4.00 in disaster recovery. Links: http://www.dhses.ny.gov/oem/mitigation/documents/mitigations-value-to-society.pdf The two-volume NIBS MMC study report is available for free download at: http://www.nibs.org/index.php/mmc/projects/nhms Cost Impact: Will increase the cost of construction This code change proposal will increase the cost of construction of some building types.

Public Comment G171-15 LOVELL-C: Proponent : Vickie Lovell, InterCode Incorporated, representing Fire Safe North America (vickie@intercodeinc.com) requests Approve as Modified by this Public Comment. Modify as Follows: 2015 International Building Code 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602, except where limited by 602.1.2. Where required to have a fireresistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection of openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. 602.1.1 Fire-resistance ratings The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602. Where required to have a fire resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection of openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. 602.1.2 Building elements in disaster-prone areas. The building elements in multi-story, sprinklered buidings of construction Types IIB, IIIB and VB assigned to Risk Category IV identified in Table 1604.5 shall have a fireresistance rating of not less than 1 hour where such buildings are any of the following: 1. Seismic Design Category F or Seismic Design Category D where the building is assigned to Risk Category IV in accordance with 1613.3.5. 2. Located in a special flood hazard area defined by this code and established in accordance with Section 1612.3. 3. Located in the windborne-debris region of hurricane-prone areas based on Figure 1609.3(2). Exception: Buildings that have an automatic sprinkler system installed in accordance with NFPA 13, are provided with an uninterruptable water and power supply, and the fire pumps are protected against interruption of service in accordance with Section 913. Commenter's Reason: The increased fire resistivity required by this proposal is intended to apply ONLY to buildings that are ALL of the following: Classified in the highest risk category. Located in the highest risk, disaster-prone regions for floods, hurricanes and seismic activity. Type IIB, IIIB or VB construction. It excludes sprinklered buildings that have emergency backup systems for water and power in those regions. Although the cause is debated, naturally-occurring and man-made disasters are increasing in number and severity in the United States and around the world. That fact is undisputed. The resilience of communities and the individual buildings within those communities is becoming of vital importance. A National Institute of Building Sciences Publication (May, 2014) entitled "Moving Forward: Findings and Recommendations", states that "while a long history of building codes has laid the foundation for addressing the impacts of natural and man-made hazards, changes in the frequency and severity of events have brought new challenges challenges requiring the engagement and support of policymakers. While building codes serve as the minimum requirements for life-safety in the building stock, basic life-safety protections do not fully address building performance requirements to achieve resilience." Mitigation includes, among other things, fortifying buildings so that they are less likely to be severely damaged or completely destroyed during or immediately after a disaster. It is the key to recovery after a disaster. Mitigation allows individuals and communities to lessen post-disaster disruption and rebuild more quickly. States and cities have started implementing more stringent requirements in specific geographic areas they have designated as higher-risk. The purpose of this series of code changes proposed by Fire Safe North America is to encourage the debate in the code development process to identify what constitutes resilient buildings, and begin to identify issues that will become the basis for "new minimum requirements" for increased building resiliency. Responding to the challenge of mitigating damage and resilient buildings is an admittedly complex topic. Fire Safe North America proposals are intended to reduce the total reliance of a community and its firefighters on automatic sprinkler systems in disaster-prone areas of the country where the water supply and/or power are likely to be interrupted, or are likely to have water supply system operational issues. The proposals, if approved, will fortify the building code requirements for the most vulnerable buildings to fire - Type IIB, IIIB, and VB construction, which are also classified as Risk Category IV in Table 1604.5, and in high-risk, disaster prone regions. The proposals modify the following code requirements in such buildings: 1. Reduce allowable area limits. 2. Protect the path of egress by limiting travel distances.

3. Protect the path of egress by protecting corridors. 4. Require higher fire resistance ratings for occupancy separations. 5. Require higher fire resistance ratings for building elements. These proposals are intended to be conservative so as to promote community resiliency and disaster mitigation by protecting essential buildings with both sprinkler protection AND fire resistance rated compartmentation. These proposals may be fairly considered to be the proverbial "belt and suspenders" approach, requiring both sprinkler protection and increased fire resistance rated compartmentation in specific buildings in high risk areas for disasters. Historically, the code has been written using the general assumption that automatic sprinklers will operate satisfactorily and there will be suitable power for such building operations. Code users design and build assuming that firefighters will be able to respond at their normal efficiencies. In some parts of the country, buildings impacted by disasters may remain without reliable water and/or power for a considerable period of time, well after the occurrence of the disaster. History has shown that increased incidents of fires after a disaster can be more destructive to life and property than the disaster itself. Total reliance on an uninterrupted power and water supply may not be an acceptable risk. It may also be an unacceptable risk to assume that firefighters will be able to respond at their normal efficiencies. For example, more than 15% of the U.S. population lives in potential major earthquake areas. 41 states and territories have moderate to high risk. There is a real likelihood of power and water supplies being interrupted following a major seismic event, along with the potential for multiple simultaneous structure fires and also building-to-building fire spread. On October 17, 1989, a 7.1 earthquake in Santa Cruz Mountains was responsible for 26 fires in San Francisco, 60 miles from epicenter. There were 67 documented breaks in water mains which effectively eliminated water pressure in the area. On January 19, 1994, a 6.8 earthquake centered in Northridge, CA. There were approximately 100 fire ignitions, 30 to 50 of those were considered significant. The water supply systems in the area were damaged causing low pressure in water distribution. On January 17, 1995, a 6.8 (approx.) earthquake near Kobe, Japan caused 90 fires to start within minutes. 85 spread to adjacent buildings and 10 approached or reached conflagration status. 1,700 water line breaks occurred within a couple of hours. There were 7,000 buildings destroyed by fire alone. In 1997, the Red River flooded Grand Forks, North Dakota, causing $3.7 billion in flood losses, and displaced thousands of families and businesses. Similar data of increased fire incidents are available in other flood and hurricane-prone areas. Undoubtedly, this will increase the cost of construction in these specific buildings. However, a recent FEMA's 2010 report "Mitigation's Value to Society" statement described how mitigation is an investment that needs to be made. A recent study by the NIBS Multihazard Mitigation Council (MMC) identified that each dollar spent on mitigation saves an average of $4.00 in disaster recovery. Links: http://www.dhses.ny.gov/oem/mitigation/documents/mitigations-value-to-society.pdf The two-volume NIBS MMC study report is available for free download at: http://www.nibs.org/index.php/mmc/projects/nhms Cost Impact: Will increase the cost of construction This code change proposal will increase the cost of construction of some building types.