1 Critical Facility Round Table October 16, 2003 San Francisco Seismic Risk for Data Centers David Bonneville Senior Principal Degenkolb Engineers San Francisco, California
2 Presentation Outline Seismic Risk Code Requirements Data Center Components Issues and Solutions Data Center Buildings
3 Seismic Risk A Function of: Seismic Hazard and Building Performance
4 Bay Area 30-year Probabilities
5 USGS Seismic Hazard Map
6 Seismic Performance Buildings Northridge Earthquake
7 ST RISK % Damage vs. MMI
8 Intensity vs. Peak Ground Acceleration
9 Seismic Performance Data Centers Seattle Earthquake
10 Equipment Damage vs. MMI FROM ATC Loss to Nonstructural Items (%) VI VII VIII IX X XI XII MMI Electrical Equip. Mechanical Equip. Hi-Tech & Lab Equip. Office Equip.
11 Equipment Anchorage
12 Code Requirements 1. Pre 1997 UBC Including all editions of BOCA and SBC 2. Post a UBC 2b IBC, 2003 IBC 2003 NFPA ASCE - 7
13 Code Requirements 1994 UBC Lateral Force On Nonstructural Components F = p ZC p I p W p Where: F p = Equivalent static horizontal design force Z = Seismic Zone Coefficient C p = Coefficient (Generally 0.75 for equipment) I p = Importance Factor (1.0, 1.25 or 1.5) W p = Weight of the Item
14 Code Requirements 1997 UBC Lateral Force On Nonstructural Components Where: a p = Component Amplification Factor (rigid or flexible structure) (varies from 1.0 to 2.5) = Seismic Coefficient (dep. on Zone and Soil Type) C a I p R p a C p a p x Fp = ( 1+ 3 ) R p = Importance Factor = Component Response Modification Factor (ductility of support anchorage) h x /h r = height in building where equipment is located divided by total height of building I h h r W p
15 Code Related Issues Roof Level 1994 UBC 1997 UBC Near Fault Shallow Anchors Grade Level Lateral Forces on Nonstructural Components 1994 UBC vs UBC
16 Shallow Anchors Shallow Anchors are those with and embedment length to diameter ratio of less than 8.
17 Installation Related Issues Inadequate Anchorage No Anchorage
18 Data Center Components Server Racks Other Equipment AC and UPS Access Floors Ceiling and Fire Sprinklers Emergency Generators
19 Servers Seattle Earthquake
20 Seismic Anchorage of Servers
21 Anchorage Solution
22 Anchorage Solution Anchor servers to prevent sliding and overturning Brace access floor to prevent lateral collapse
23 Rack Design Issues Standard Rack Seismic Rack
24 Rack Design Issues Anchorage of seismic rack to floor.
25 Alternative Solution Rack Isolation
26 Alternative Solution - Rack Isolation Single isolator Isolator allows floor to move underneath equipment. Forces on equipment above are greatly reduced WORKSAFE TECHNOLOGIES
27 Alternative Solution - Rack Isolation 100% Amplitude WORKSAFE TECHNOLOGIES
28 Alternative Solution - Rack Isolation 141% Amplitude WORKSAFE TECHNOLOGIES
29 Other Equipment on Raised Floor UPS Equipment Approach is similar to server racks.
30 Heavy Equipment AC Units
31 Heavy Equipment Anchorage
32 Emergency Power Anchorage of emergency generator
33 Access Floors
34 Access Floors
35 Bracing of Access Floors Access floors must be braced or pedestals designed to cantilever. Mass to include floor system and weight of equipment (normally 25% of floor LL.) Need mechanical attachment to base slab, glue alone IS NOT acceptable.
36 Bracing of Access Floors Standard pedestals are not adequate for high seismic areas
37 Heavy Duty Pedestals and Stringers Critical Facility Round Table Seismic Risk for Data Centers October 16, 2003
38 Design Anchorage Detail: Access Floor
39 Access Floor Bracing Installation Problems
40 Access Floor Bracing Installation Problems
41 Ceilings and Fire Sprinklers Northridge Earthquake 1994
42 Ceilings and Fire Sprinklers
43 Pipe Bracing
44 Pipe Bracing NOTE: NFPA 13 editions prior to 1999 may not be adequate in high seismic areas. Acceptable Bracing NFPA-13 Detail
45 Building
46 Seismic Design Forces with Time Lateral Force (% g) Low-Rise Shear Wall Building in Zone Pre Present
47 Relative Costs Bricks and Mortar Cost / Square Foot $1,500 $1,000 $500 Relative Structural Cost 22% 15% 7% 6% 5% $0 Building Type Office Hospital Data Center Pharm Mfg. Chip Fab Structural Exterior Arch. Interiors MEP
48 Relative Costs Fully Equipped Cost / Square Foot $10,000 $8,000 $6,000 $4,000 $2,000 Building Type $0 Relative Structural Cost 15% 7% 1% Office Hospital Data Center 3% Pharm Mfg. 1% Chip Fab Structural Exterior Arch. Interiors MEP Soft Costs FF&E
49 Seismic Performance Levels Operational Immediate Occupancy Life Safe 1997 UBC Near Collapse Collapse
50 Seismic Upgrade Solution with BRBF s
51 Seismic Upgrade BRBF s
52 Seismic Upgrade Solution with BRBF s
53 Damper Solution 4-5 Link Structure Viscous Dampers
54 Damper Solution 4-5 Link Structure Viscous Dampers
55 Base Isolation Seismic Isolation provides major economic advantages: Protection of occupants, contents, structure Dramatic reduction in damage n minimal business disruption Lead- Rubber Seismic Isolator Seismically Isolated Structure
56 Base Isolation Base Isolator During Testing USGS
57 Base Isolation AboveNet Building New Isolator Under Existing Building
58 Conclusions 1. Data Centers are subject to severe damage and loss of operations in moderate (frequent) earthquakes. 2. Code requirements related to equipment anchorage have recently changed significantly. 3. Equipment bracing (even for critical equipment) is often nonexistent or second-rate. 4. Access floors are critical to data center performance and most are not intended for use in high seismic areas. 5. Seismic upgrades can generally be undertaken without severe disruption of the data center.
59 Questions? David Bonneville - Senior Principal dbonne@degenkolb.com Degenkolb Engineers 225 Bush Street, Suite 1000 San Francisco, CA Phone: Fax: San Francisco. Los Angeles. Portland. Oakland. San Diego. Seattle
Earthquakes and Data Centers
7x24 Exchange Fall Symposium September 11, 2013 Hilton Bellevue Andrew W. Taylor, Ph.D., S.E., FACI Earthquake Hazards 2 September 11, 2013 1 Cascadia Earthquake Sources Figure Credit: Craig Weaver, Pacific
More informationPrepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103. Prepared By
Project Structural Conditions Survey and Seismic Vulnerability Assessment For SFCC Civic Center Campus 750 Eddy Street San Francisco, California 94109 Prepared For San Francisco Community College District
More informationSTRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA
STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA College of Marin c/o Swinerton Management & Consulting P.O. Box 144003 835 College Avenue, Building MS-3 Kentfield, California
More informationRetrofitting in the Central US: A Federal Perspective
Retrofitting in the Central US: A Federal Perspective 2012 National Earthquake Conference Michael Mahoney FEMA, Building Science Branch National Earthquake Hazards Reduction Program (NEHRP) NEHRP was formed
More informationKCC Event Brief: 2014 La Habra Earthquake
KAREN CLARK & COMPANY KCC Event Brief: 2014 La Habra Earthquake June 2014 2 COPLEY PLACE BOSTON, MA 02116 T: 617.423.2800 F: 617.423.2808 Overview On Friday, March 28, 2014 at 9:09pm, a magnitude 5.1 earthquake
More informationWhat is Seismic Retrofitting?
What is Seismic Retrofitting? SEISMIC RETROFITTING A Seismic Retrofit provides existing structures with more resistance to seismic activity due to earthquakes. In buildings, this process typically includes
More informationASSESSMENT AND RETROFITTING OF EXISTING RC BUILDINGS IN VIETNAM IN TERMS OF EARTHQUAKE RESISTANCES
GEM-SEA Workshop on Seismic Vulnerability of Buildings Nanyang Technological University, Singapore 1 st July 2013 ASSESSMENT AND RETROFITTING OF EXISTING RC BUILDINGS IN VIETNAM IN TERMS OF EARTHQUAKE
More informationExpected Performance Rating System
Expected Performance Rating System In researching seismic rating systems to determine how to best classify the facilities within the Portland Public School system, we searched out what was used by other
More informationRehabilitation of a 1985 Steel Moment- Frame Building
Rehabilitation of a 1985 Steel Moment- Frame Building Gregg Haskell, a) M.EERI A 1985 steel moment frame is seismically upgraded using passive energy dissipation, without adding stiffness to the system.
More informationG. Michele Calvi IUSS Pavia
CONVEGNO SISMA ED ELEMENTI NON STRUTTURALI Approcci, Stati Limite e Verifiche Prestazionali Bologna 24 ottobre 2014 PROGETTO DI ELEMENTI NON STRUTTURALI SOGGETTI AD AZIONI SISMICHE G. Michele Calvi IUSS
More informationEARTHQUAKE DESIGN OF BUILDINGS
GAP.2.0.9 A Publication of Global Asset Protection Services LLC EARTHQUAKE DESIGN OF BUILDINGS INTRODUCTION Buildings in many areas of the world are susceptible to damage from moderate to severe earthquakes.
More informationAN ANALYSIS OF FIRE SPRINKLER SYSTEM FAILURES DURING THE NORTHRIDGE EARTHQUAKE AND COMPARISON WITH THE SEISMIC DESIGN STANDARD FOR THESE SYSTEMS
13 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 2004 Paper No. 2136 AN ANALYSIS OF FIRE SPRINKLER SYSTEM FAILURES DURING THE NORTHRIDGE EARTHQUAKE AND COMPARISON WITH
More informationTHE DESIGN OF BUILDING SERVICES FOR EARTHQUAKE RESISTANCE
THE DESIGN OF BUILDING SERVICES FOR EARTHQUAKE RESISTANCE Graeme J BEATTIE 1 SUMMARY The design of seismic restraints for building services equipment is often a matter that is overlooked because there
More informationCommercial Building Valuation Report
INSURED University of Houston - Victoria Effective Date: Expiration Date: Cost as of: 09/2010 BUILDING 1 217 - University Center 77901 Location Adjustments Climatic Region: High Wind Region: Seismic Zone:
More informationPage & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
More informationChapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE
Chapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE To satisfy the performance goals of the NEHRP Recommended Seismic Provisions, a number of characteristics are important to the
More informationArticle 5: Building Regulations
Article 5: Building Regulations Division 37: Additional Building Regulations for Archaic Materials and Methods of Construction (Added Additional Building Regulations for Archaic Materials and Methods of
More informationCommercial Building Valuation Report
INSURED State Office of Risk Management Effective Date: 300 W 15th Street Expiration Date: Austin, TX 78701 Cost as of: 12/2013 BUILDING 1 Athletics/PCI - 206 3302 N. Ben Wilson Victoria, TX 77901 Location
More informationAT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:
More informationSchneps, Leila; Colmez, Coralie. Math on Trial : How Numbers Get Used and Abused in the Courtroom. New York, NY, USA: Basic Books, 2013. p i.
New York, NY, USA: Basic Books, 2013. p i. http://site.ebrary.com/lib/mcgill/doc?id=10665296&ppg=2 New York, NY, USA: Basic Books, 2013. p ii. http://site.ebrary.com/lib/mcgill/doc?id=10665296&ppg=3 New
More informationStructural Retrofitting For Earthquake Resistance
Structural Retrofitting For Earthquake Resistance Ruben Boroschek WHO Disaster Mitigation in Health Facilities University of Chile rborosch@ing.uchile.cl www.hospitalseguro.cl The following paper is part
More informationAT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA
More informationSEISMIC TESTING OF NON-STRUCTURAL COMPONENTS AND ASSESSMENT OF THE PRESCRIBED RESPONSE SPECTRUM
NCEE Tenth U.S. National Conference on Earthquake Engineering Frontiers of Earthquake Engineering July -5, Anchorage, Alaska SEISMIC TESTING OF NON-STRUCTURAL COMPONENTS AND ASSESSMENT OF THE PRESCRIBED
More informationHOW TO EVALUATE BUILDINGS AND DETERMINE RETROFIT COSTS
David Bell PJHM Architects, Inc. Young Nam Daniel Traub Thornton Tomasetti how to evaluate buildings and determine retrofit costs HOW TO EVALUATE BUILDINGS AND DETERMINE RETROFIT COSTS Presented by: David
More informationGUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS
INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC 91.1301, 93.690 Effective: 01-01-2014 DOCUMENT NO.: P/GI 2014-027 Revised: 11-07-2014 Previously Issued As: P/GI 2011-027 GUIDELINES
More informationKey Considerations for Selecting Server Cabinets for Seismic Areas
Key Considerations for Selecting Server Cabinets for Seismic Areas Protect Up to 1500 of Critical Network Equipment without Sacrificing Flexibility Planning a data center in a seismically active area requires
More informationAT&T Internet Data Center Site Specification New York III (Secaucus, NJ)
AT&T Internet Data Center Site Specification New York III (Secaucus, NJ) Site Biography Market Area: New York City, New Jersey, Upstate NY and Lower Connecticut Location: Secaucus, NJ 07094 Address: 15
More informationCH. 2 LOADS ON BUILDINGS
CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends
More informationAT&T Internet Data Center Site Specification Dallas Area (Allen, Tx)
AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx) Site Biography Market Area: Dallas and Fort Worth Areas of Texas Location: Allen, Tx 75013 Address: 900 Ventura Drive CLLI, POP, NPA/NXX
More informationPrestressed Storage Tanks
Prestressed Storage Tanks Mike Harper Regional Manager mike.harper@dntanks.com / 714 767 1313 Kevin Peacock Regional Manager kevin.peacock@dntanks.com / 949 698 2740 DN Tanks overview Construction Procedures
More informationfib Bulletin 39, Seismic bridge design and retrofit structural solutions: Colour figures
fib Bulletin 39, Seismic bridge design and retrofit structural solutions: Colour figures As a service to readers of fib Bulletin 39, which was printed in black & white, figures that were available as colour
More information6 RETROFITTING POST & PIER HOUSES
Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This
More informationHow To Visit An Internet Data Center
AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina
More informationSEISMIC ANALYSIS AND RETROFITTING OF R.C.C STRUCTURE
International Journal of Advanced Research in Biology Engineering Science and Technology (IJARBEST) Vol., Issue, April 1 SEISMIC ANALYSIS AND RETROFITTING OF R.C.C STRUCTURE M.R.NAVANEETHA KRISHNAN 1,
More informationEARTHQUAKE MAGNITUDE
EARTHQUAKE MAGNITUDE Earliest measure of earthquake size Dimensionless number measured various ways, including M L local magnitude m b body wave magnitude M s surface wave magnitude M w moment magnitude
More informationEconomic Benefit Cost Analysis: CoreFirst vs. Standard Retrofit
Economic Benefit Cost Analysis: CoreFirst vs. Standard Retrofit Kleinhenz & Associates 2602 Berkshire Road Cleveland, Ohio 44106 www.kleinhenzassociates.com June 2014 Introduction CoreFirst, llc. (CoreFirst)
More informationSEISMIC RETROFITTING OF STRUCTURES
SEISMIC RETROFITTING OF STRUCTURES RANJITH DISSANAYAKE DEPT. OF CIVIL ENGINEERING, FACULTY OF ENGINEERING, UNIVERSITY OF PERADENIYA, SRI LANKA ABSTRACT Many existing reinforced concrete structures in present
More informationPersonal Information. Professional Education
Jose Antonio Flores Ruiz Structural Engineer Personal Information Telephone + (52) 1 322 108 41 12 e mail Place of birth Toluca, Mexico Date of birth October 6th 1978 Marital Status Married Nationality
More informationGUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS
INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC 91.1301, 93.690 Effective: 01-01-2014 DOCUMENT NO.: P/GI 2014-027 Revised: 12-16-2015 Previously Issued As: P/GI 2011-027 GUIDELINES
More informationUntopped Precast Concrete Diaphragms in High-Seismic Applications. Ned M. Cleland, Ph.D., P.E. President Blue Ridge Design, Inc. Winchester, Virginia
Untopped Precast Concrete Diaphragms in High-Seismic Applications Ned M. Cleland, Ph.D., P.E. President Blue Ridge Design, Inc. Winchester, Virginia S. K. Ghosh, Ph.D. President S. K. Ghosh Associates,
More informationUNIVERSITY OF CALIFORNIA, SAN DIEGO
UNIVERSITY OF CALIFORNIA, SAN DIEGO UCSD BERKELEY DAVIS IRVINE LOS ANGELES MERCED RIVERSIDE SAN DIEGO SAN FRANCISCO SANTA BARBARA SANTA CRUZ UNIVERSITY CENTERS - 0076 PHONE: (858) 822-4987 9500 GILMAN
More informationPolicy on Repair and Renovation Funding
Policy on Repair and Renovation Funding I. POLICY STATEMENT Auburn University s (the University s) Policy on Repair and Renovation Funding provides guidance and direction regarding the use of Repair and
More informationCOMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
More informationSeismic Retrofit of Existing Buildings: Innovative Alternatives
Seismic Retrofit of Existing Buildings: Innovative Alternatives Moe Cheung and Simon Foo Public Works & Government Services Canada Hull, Quebec, Canada Jacques Granadino Public Works & Government Services
More informationSeismic Analysis and Design of Steel Liquid Storage Tanks
Vol. 1, 005 CSA Academic Perspective 0 Seismic Analysis and Design of Steel Liquid Storage Tanks Lisa Yunxia Wang California State Polytechnic University Pomona ABSTRACT Practicing engineers face many
More informationFoundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training
Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline
More informationDESIGN CRITERIA. Determination of earthquake demand. Building importance level. Component categories SEISMICALLY RESILIENT NON-STRUCTURAL ELEMENTS
FACT SHEET 2 NZS 4219:2009 Seismic performance of engineering systems in buildings requires the arrangement and layout of engineering systems within a building to allow for earthquake actions. NZS 4219:2009
More informationFive reasons buildings fail in an earthquake and how to avoid them
Five reasons buildings fail in an earthquake and how to avoid them by Jeff White, AIA Published in Healthcare Design magazine There s a saying among seismologists: Earthquakes don t kill people. Buildings
More informationSEISMIC APPROACH DESIGN COMPARISON BETWEEN
IABSE ANNUAL MEETING, LONDON, 19 TH SEPTEMBER 2011 SEISMIC APPROACH DESIGN COMPARISON BETWEEN IBC AND ITALIAN DM2008 Ing. Luca Zanaica Senior Structural Engineer Ing. Francesco Caobianco Senior Structural
More informationCode Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
More informationChapter 3 FOUNDATIONS AND FOUNDATION WALLS
Chapter 3 FOUNDATIONS AND FOUNDATION WALLS This chapter discusses foundations and foundation walls constructed using the two most common foundation materials concrete and masonry. Although the IRC permits
More informationAFTER THE BIG ONE, WILL CRITICAL COUNTY SERVICES SURVIVE?
AFTER THE BIG ONE, WILL CRITICAL COUNTY SERVICES SURVIVE? SUMMARY There is a 67% probability that Southern California will be hit by a magnitude 6.7 or larger earthquake in the next 30 years according
More informationSECTION 8 Industrial Facilities Field Investigation
SECTION 8 Industrial Facilities Field Investigation Types of Data to Be Collected and Recorded Warehouses, manufacturing facilities, energy-producing facilities, and factories should be inspected for performance
More informationProtecting data centers from seismic activity Understanding enclosure standards is critical to protecting equipment
Protecting data centers from seismic activity Understanding enclosure standards is critical to protecting equipment Author: Joel Young, engineer at Crenlo Abstract In the event of an earthquake, the type
More informationMethods for Seismic Retrofitting of Structures
Methods for Seismic Retrofitting of Structures Retrofitting of existing structures with insufficient seismic resistance accounts for a major portion of the total cost of hazard mitigation. Thus, it is
More informationRisk Management Series. Engineering Guideline for Incremental Seismic Rehabilitation FEMA P-420 / May 2009 FEMA
Risk Management Series Engineering Guideline for Incremental Seismic Rehabilitation FEMA P-420 / May 2009 FEMA Cover Photo: Courtesy of University of California, Berkeley. Steel Braced Frames were added
More informationSeismic Assessment of Engineering Systems in Hospitals A Challenge for Operational Continuity
Seismic Assessment of Engineering Systems in Hospitals A Challenge for Operational Continuity S.R. Uma GNS Science, Lower Hutt. G.J. Beattie Building Research Association of New Zealand, Porirua. 2010
More informationMiss S. S. Nibhorkar 1 1 M. E (Structure) Scholar,
Volume, Special Issue, ICSTSD Behaviour of Steel Bracing as a Global Retrofitting Technique Miss S. S. Nibhorkar M. E (Structure) Scholar, Civil Engineering Department, G. H. Raisoni College of Engineering
More informationAPPLICATION OF EARTHQUAKE ENGINEERING INFORMATION IN HOSPITAL EMERGENCY RESPONSE AND RECOVERY
Workshop on Seismic Design and Retrofitting of Hospitals in Seismic Areas, October 21-22, 1999. APPLICATION OF EARTHQUAKE ENGINEERING INFORMATION IN HOSPITAL EMERGENCY RESPONSE AND RECOVERY Robert Reitherman
More informationEffect of Container Height on Base Shear of Elevated Water Tank
Effect of Container Height on Base Shear of Elevated Water Tank Rupachandra J. Aware 1, Dr. Vageesha S. Mathada 2 Shri Vitthal Education & Research Institute College of Engineering, Pandharpur, Maharashtra,
More informationDevelopment of Seismic-induced Fire Risk Assessment Method for a Building
Development of Seismic-induced Fire Risk Assessment Method for a Building AI SEKIZAWA National Research Institute of Fire and Disaster 3-14-1, Nakahara, Mitaka, Tokyo 181-8633, Japan sekizawa@fri.go.jp
More informationCertification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
More informationVibration Isolation in Data Centers
Vibration Isolation in Data Centers Vibrations in Data Centers Vibrations in Data Centers can be produced by nearby construction works, heavy traffic, railways or even the own cooling units inside or next
More informationREVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
More informationASCE 41-13: Seismic Evaluation and Retrofit Rehabilitation of Existing Buildings
SEAOC 2012 CONVENTION PROCEEDINGS ASCE 41-13: Seismic Evaluation and Retrofit Rehabilitation of Existing Buildings Robert Pekelnicky, SE Degenkolb Engineers San Francisco, CA Chris Poland, SE, NAE Degenkolb
More informationComparison of the Structural Provisions in the International Existing Building Code 2012 versus the Rhode Island State Rehabilitation Code
August 3, 2012 Existing Building Code 2012 versus the Rhode Island State By: Structural Engineers Association of Rhode Island, Building Code Committee Introduction At the request of the Building Code Standards
More informationThe Fundamentals of Seismic Compliance and Heating, Ventilation and Air-Conditioning Systems (HVAC)
Carrier Engineering Newsletter Volume 1, Issue 2 The Fundamentals of Seismic Compliance and Heating, Ventilation and Air-Conditioning Systems (HVAC) Earthquakes are a real problem and not just in California
More informationNeuStar Ultra Services Physical Security Overview
NeuStar Ultra Services Physical Security Overview Mission-critical network operations must have the highest standards of quality, security and reliability. NeuStar Ultra Services currently locates its
More informationChapter 7 Earthquake Hazards Practice Exam and Study Guide
Chapter 7 Earthquake Hazards Practice Exam and Study Guide 1. Select from the following list, all of the factors that affect the intensity of ground shaking. a. The magnitude of the earthquake b. Rather
More informationMAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND
More informationRepair of Earthquake-Damaged Masonry Fireplace Chimneys SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY
Repair of Earthquake-Damaged Masonry Fireplace Chimneys SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY Purpose and Intended Audience The August 24, 2014 South Napa Earthquake has again served as a reminder that
More informationClark County Fire Prevention
Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF
More informationAPPLICATION OF EARTHQUAKE ENGINEERING INFORMATION IN HOSPITAL EMERGENCY RESPONSE AND RECOVERY
APPLICATION OF EARTHQUAKE ENGINEERING INFORMATION IN HOSPITAL EMERGENCY RESPONSE AND RECOVERY Robert Reitherman 1 1. Consortium of Universities for Research in Earthquake Engineering 1301 South 46 th Street,
More informationSUBJECT CAN: 2-108. Temporary Systems, Utilities and Equipment. Effective: 4/09/2013. CODE SECTION 2010 California Building Code (CBC)
Facilities Development Division Office of Statewide Health Planning and Development 400 R Street, Suite 200 Sacramento, CA 95811 (916) 440-8300 700 N. Alameda Street, Suite 2-500 Los Angeles, CA 90012
More informationTHE DOW CHEMICAL COMPANY Issued: August 1, 2008 200 LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN 48674 (989) 638-8655 www.dowbuildingmaterials.
ICC EVALUATION SERVICE, INC. EvaluateP InformP Protect Los Angeles Business/Regional OfficeP 5360 Workman Mill RoadP Whittier, CA 90601 (562) 699-0543 phonep (562) 695-4694 fax DIVISION: Section: 6 WOOD
More informationBolting: Attachment Of The Mudsill To The Foundation
Bolting: Attachment Of The Mudsill To The Foundation If the mudsill of a house (the pink area in the illustration at right) is not bolted, the lateral loads (back and forth motions) of an earthquake can
More informationDESIGN DRIFT REQUIREMENTS FOR LONG-PERIOD STRUCTURES
13 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 2004 Paper No. 3292 DESIGN DRIFT REQUIREMENTS FOR LONG-PERIOD STRUCTURES Gary R. Searer 1 and Sigmund A. Freeman 2 SUMMARY
More information#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the
More informationSEISMIC ENGINEERING GUIDELINES
SEISMIC ENGINEERING GUIDELINES STANFORD UNIVERSITY Land, Buildings and Real Estate (LBRE) 3145 Porter Drive (MC 8442) Building F Los Trancos Creek Palo Alto, CA 94304 July 20, 2011 (Annotated February
More informationSEISMIC EVALUATION OF HOSPITAL PIPING SYSTEMS
13 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 2004 Paper No. 1081 SEISMIC EVALUATION OF HOSPITAL PIPING SYSTEMS Elliott GOODWIN 1, Emmanuel MARAGAKIS 2, Ahmad ITANI
More information1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona
for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety
More informationNational Clearinghouse for Educational Facilities. 2 Adapted from California s Department of Emergency Services
Earthquakes and Schools 2008 Earthquakes are low-probability, high-consequence events. Though they may occur only once in the life of a school, they can have devastating, irreversible consequences. Moderate
More information4B-2. 2. The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.
Shear Walls Buildings that use shear walls as the lateral force-resisting system can be designed to provide a safe, serviceable, and economical solution for wind and earthquake resistance. Shear walls
More informationSEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:
SEISMIC DESIGN Various building codes consider the following categories for the analysis and design for earthquake loading: 1. Seismic Performance Category (SPC), varies from A to E, depending on how the
More informationCecil Courts BE 1047 EQ2 Detailed Engineering Evaluation Quantitative Assessment Report
Christchurch City Council Cecil Courts BE 1047 EQ2 Detailed Engineering Evaluation Quantitative Assessment Report Christchurch City Council Cecil Courts Quantitative Assessment Report 16 Cecil Place and
More informationChapter. Earthquake Damage: Types, Process, Categories
3 Chapter Earthquake Damage: Types, Process, Categories Earthquakes leave behind a trail of damage and destruction. People s lives are affected by the loss of loved ones, destruction of property, economic
More information2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS
2006 IBC BUILDING CODE CHECKLIST FOR COMMERCIAL PROJECTS IBC CODE DESIGN CHECKLIST (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Transfer the resulting data on the building plans Life Safety & Building
More informationDesign and Construction of Cantilevered Reinforced Concrete Structures
Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-68 Design and Construction of Cantilevered Reinforced Concrete Structures
More informationPROJECT SUMMARY. Scope of work details: (If phased construction, please see plan submittal guidelines.)
APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL FIRE RESTORATION PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of
More informationData Center Due Diligence List
Data Center Due Diligence List Name and address of site facility Date constructed Building owner/date purchased by current owner Name of previous owner Adjacent Property Descriptions North South East West
More informationCornell University LADWP SHORT COURSE & WORKSHOP
CASE STUDY: LIFELINE RESILIENCE- LOS ANGELES DEPARTMENT OF WATER & POWER Tom O Rourke Cornell University 1200 km2 Los Angeles N 200 km 40 km Los Angeles Department of Water and Power (LADWP) Serves 4.0
More informationSpecification for Structures to be Built in Disaster Areas
Ministry of Public Works and Settlement Government of Republic of Turkey Specification for Structures to be Built in Disaster Areas PART III - EARTHQUAKE DISASTER PREVENTION (Chapter 5 through Chapter
More informationBUILDING OCCUPANCY RESUMPTION PROGRAM
BUILDING OCCUPANCY RESUMPTION PROGRAM Revised JANUARY 2011 CITY AND COUNTY OF SAN FRANCISCO DEPARTMENT OF BUILDING INSPECTION EMERGENCY OPERATIONS PLAN For any questions regarding this program, please
More informationFacilities Development Division. The Building Department for California s Hospitals
OSHPD Special Seismic Certification Preapproval (OSP) Preapproval of Special Seismic Certification by OSHPD is a voluntary program for Equipment Manufacturers! Facilities Development Division The Building
More informationDesign Development Quality Management Phase Checklist Project Phase Checklist Series
Best Practices Design Checklist Project Phase Checklist Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA
More informationDollars, deaths, and downtime: understand your building's seismic risk and how to evaluate it
Dollars, deaths, and downtime: understand your building's seismic risk and how to evaluate it SEAOSC Strengthening Our Cities Summit 5 Nov 2015, Los Angeles, CA Keith Porter, PE PhD University of Colorado
More information780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL EXISTING BUILDING CODE 2009
780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL EXISTING BUILDING CODE 2009 CHAPTER 34: EXISTING STRUCTURES 3401.1 Replace as follows: 3401.1 Scope. Chapter 34 of the International Building Code
More informationNCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
More information