Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a



Similar documents
Harmonics in your electrical system

Product Data Bulletin

Considering the effects of UPS operation with leading power factor loads

Power System Harmonics

Introduction. Harmonics and IEEE 519 Page 1 of 19

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

How To Understand The Electrical Power Supply Of A Power Supply System

Mitigating data center harmonics

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC

Specifying a Variable Frequency Drive s

GUIDE FOR TESTING POWER TRANSFORMERS

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL

Standards of Power Quality with reference to the Code of Practice for Energy Efficiency of Electrical Installations

Analysis of AC-DC Converter Based on Power Factor and THD

VOLTAGE REGULATOR AND PARALLEL OPERATION

MGE Galaxy /200/250/300/400/500 kva Power efficiency for business continuity

Investigation of Power Quality In Health Care Facility

The Different Types of UPS Systems

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

Survey of Harmonics Measurements in Electrical Distribution Systems

New Control Strategy To Improve Power Quality Using A Hybrid Power Filter

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

7. Reactive energy compensation

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

Application Guide. Power Factor Correction (PFC) Basics

Positive Feedback and Oscillators

98% Efficient Single-Stage AC/DC Converter Topologies

How To Improve Power Quality

Chapter 4. LLC Resonant Converter

Power supply output voltages are dropping with each

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

FREQUENCY CONTROLLED AC MOTOR DRIVE

Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

Transformers. Special transformers Reactors products

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

HIGH FREQUENCY TRANSFORMER WITH TRANSFORMER SWITCHOVER

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

Low Voltage Products

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Educational solutions. MV/LV power grid design and operation laboratory

Discover the power of e-learning! The Quick Guide to AC Variable Frequency

The Different Types of UPS Systems

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

The front end of the receiver performs the frequency translation, channel selection and amplification of the signal.

Neutral Currents in Three Phase Wye Systems

Opportunity of Energy Saving in electrical path is lesser as compared to other areas

Power Quality Standards for Electric Service

The design and performance of Static Var Compensators for particle accelerators

Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage

AC-Synchronous Generator

Relationship between large subject matter areas

IRON-CORE REACTORS FOR DETUNING POWER CAPACITORS IN MEDIUM AND LOW VOLTAGE NETWORKS

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

The Different Types of UPS Systems

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.

RIELLO ELETTRONICA. Master HP

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

2012 San Francisco Colloquium

Line Reactors and AC Drives

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

EET272 Worksheet Week 9

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Capacitors for A.C. motor applications

Three phase circuits

Gergely György BALÁZS. Controlling of Four-Quadrant Converters Especially in Electric Vehicles

Understanding Power Impedance Supply for Optimum Decoupling

Medium-voltage Transformers

Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM. Technical Note No. 7 August 2003

NO-BREAK KS 7e. Concentrated Energy kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

Paralleling Power Sources Which Share a Common Neutral

Electrical Essentials for HVAC&R Engineers. Wednesday, October 7

3-Phase Synchronous PWM Controller IC Provides an Integrated Solution for Intel VRM 9.0 Design Guidelines

POWER FACTOR CORRECTION

Data center power dynamics within the settings of regional power grid

Design and Simulation of Soft Switched Converter Fed DC Servo Drive

Modeling Grid Connection for Solar and Wind Energy

Control Strategy for Three Phase Shunt Active Power Filter with Minimum Current Measurements

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

AN105. Introduction: The Nature of VCRs. Resistance Properties of FETs

Power Supplies. 1.0 Power Supply Basics. Module

INTERNATIONAL STANDARD

Transcription:

Harmonics and transformers Harmonic component filter

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics are generated by non-linear loads, which are more and more frequently found in today s networks. These loads include frequency changers, constant current regulators, induction furnaces, UPSs, energy-saving lighting, discharge lamps, etc. There are several basic methods of reducing the impact of harmonics, including: - placing polluting loads on the upstream network, - grouping polluting loads together, - separating energy sources, - using transformers with specifically designed vector groups, - fitting equipment with inductances, - using an appropriate earthing system. These current and voltage harmonics can put transformers under significant stress, and may even damage them. Solutions proposed by Schneider Electric Schneider Electric proposes 2 solutions to this phenomenon, depending on the type and magnitude of the harmonics encountered. The two solutions may be combined if necessary: - oversizing the transformer at the design stage, - installing filtering systems to protect equipment. Oversizing the transformer Transformers must be oversized thermally to compensate for the additional specific losses caused by harmonic currents. Harmonisation documents HD 428 and HD538 recommend power reduction coefficients for oil-immersed distribution transformers and dry-type transformers in networks polluted by current harmonics. These coefficients are calculated according to the rates and orders of the current harmonics encountered. - 2 / 7 -

The following graph, taken from a draft of the IEEE 519 Application Guide (1996), shows the recommended derating rate for a transformer supplying electronic loads: Electronic load Recommended derating rate for a transformer supplying electronic loads. For example: 40% derating if the transformer supplies 40% of electronic loads. Standard UTE C15-112 suggests a transformer derating factor based on the type of harmonic current encountered: Typical values: «Rectangular» current (spectrum in 1/h(*)): k = 0.86 Frequency converter type current (THD 50%): k = 0.80 (*) in fact, as is the case with all rectifiers (three-phase rectifiers, induction furnaces, etc.) the current signal closely resembles a rectangle. Standard ANSI C57.110 recommends a derating factor known as the «K factor», which is obtained as follows: The K-factor, which is more restrictive, is widely used in North America. In the following example, a «K-factor» of 13 is obtained: H-order harmonic Harmonic current I h (%) 5 30 7 20 11 14 13 11 17 8 19 7 23 5 Note that a transformer sized according to this «K-factor» will be 30 to 60% more expensive depending on its rated capacity, which may vary from 15 to 500kVA. Oversizing is only possible if the harmonic pollution level is established and given to the manufacturer before the transformer is designed. - 3 / 7 -

As a guideline, for a Special Losses ratio of 10% compared with Ohmic Losses, the derating factor of power as a function of the factor Kn, to allow for harmonics, is given in the table below: Value of factor K K4 K9 K13 K20 K30 K40 K50 Derating factor 0,886 0,761 0,692 0,606 0,524 0,469 0,428 Do not forget that there is another preventive solution that can feasibly be used with transformers: it consists in using transformers with special vector groups, which effectively do away with some harmonic orders. Hence: a "Dyd" vector group stops 5 th and 7 th order harmonics, a "Dy" vector group stops 3 rd order harmonics (the harmonics circulate in each phase and return via the neutral point of the transformer). a "Dz" vector group stops 5 th order harmonics, which return via the magnetic core. A "Dyd" transformer prevents 5th and 7 th order harmonics from spreading to the upstream network. Filtering harmonics In applications using power electronic components and UPSs, 2 phases of the alternative network are, from a dielectric point of view, very briefly short-circuited at each switchover. As a result, the MV and LV waveforms are distorted, harmonics appear at the switching points, and the dv/dt values at these points are very high. The presence of these voltage harmonics at the switching points puts the transformer under significant dielectric stress. These recurring switching points (with an oscillation frequency of approximately 10 khz) may lead to premature ageing of the transformer, or to internal resonance if the natural frequencies of the transformer windings are in line with the oscillations of the switching points. If the preventive measures mentioned in the introduction above prove inadequate, the polluted equipment should be fitted with a filtering mechanism. Three types of filter can be used, depending on the type of application originally causing the harmonics: - the passive filter, - the active filter, - the hybrid filter. - 4 / 7 -

The passive filter: Typical applications: - industrial installations containing a number of harmonic component generators, the overall power of which exceeds 200 kva (speed changers, UPSs, rectifiers, etc.), - installations requiring reactive energy compensation, - reduction of the voltage distortion rate to protect sensitive receivers, - reduction of the current distortion rate to prevent overloads. Operating principle: A loop circuit (LC) is tuned to each harmonic frequency and, at the same time, to the harmonic component generator. This branch circuit absorbs the harmonics and prevents them from circulating in the power supply. Harmonic component generator Filter Linear load Passive filter operating principle The passive filter is usually tuned to a harmonic order similar to that which needs to be eliminated. Several branches of filters can be used at the same time if the distortion rate needs to be significantly reduced over several orders. The active filter: Typical applications: - tertiary installations containing a number of harmonic component generators, the overall power of which does not exceed 200 kva (speed changers, UPSs, office equipment, etc.), - reduction of the current distortion rate to prevent overloads. - 5 / 7 -

Operating principle: The active filter consists of a power electronics system, which is installed in series with or parallel to the non-linear load. Its purpose is to compensate for either the stress caused by harmonics, or the harmonic currents generated by the load. The figure below shows an example of an active filter compensating for the harmonic current: i har = - i act Active compens. Harmonic component generator Linear load The active filter injects anti-phase harmonics into the load supply to cancel existing harmonics. As a result, the loop current is sinusoidal. The hybrid filter: Typical applications: - industrial installations containing a number of harmonic component generators, the overall power of which exceeds 200 kva (speed changers, UPSs, rectifiers, etc.), - installations requiring reactive energy compensation, - reduction of the voltage distortion rate to protect sensitive receivers, - reduction of the current distortion rate to prevent overloads, - compliance with strict harmonic emission requirements. Operating principle: The above two types of filter can be combined in the same equipment to produce a hybrid filter: see figure below.. This new filtering solution has all the advantages of existing solutions, and is appropriate for a wide range of powers and performance levels. - 6 / 7 -

Active comp. Harmonic component generator Hybrid filter operating principle Hybrid filter Linear load Filter selection criteria and guidelines: - The passive filter both compensates for reactive energy and has significant current filtering capacity. The equipment in which the filter is installed must be sufficiently stable, with very little load fluctuation. If the reactive power supply is significant, the passive filter should be turned off during low load periods. Existing compensation batteries should be taken into consideration when studying the possibility of installing a passive filter, as they may subsequently have to be removed. - The active filter filters harmonics over a wide frequency band. It is suitable for all loads. However, its harmonic power is limited. - The hybrid filter combines the best attributes of both passive and active filters. These criteria can be used to establish filter selection guidelines, according to the application in question: Application type Passive filter Active filter hybrid filter Office building (computing, air conditioning, lighting, lifts) Paper, cardboard, plastics industries (conveyor systems, coilers, uncoilers) Water treatment industry (pumping, agitating) Handling (lifting, elevators) Key: - Totally suitable - Totally suitable technically, but not cost- effective - Satisfactory Whichever solution you choose, you should discuss your choice carefully with your Schneider Electric representative before ordering any equipment, to avoid potentially disastrous on-site complications. - 7 / 7 -